C&I Part of SC
C&I Part of SC
super critical
The boiler remains in an over fired condition (total fuel 5% above steam
flow) 50 seconds after a turbine trip or fast cutback.
Separator
Flash
Tank
WW C
ECO
HWL
To Condenser
C
Deaerator
HPH
C
BFP
26 October 2017 PMI Revision 00 7
START-UP
If the water system of the boiler is empty (economizer,
furnace walls, separators), then the system is filled with
approximately 10% TMCR feed water flow.
26 October 2017 8
START-UP
The water system is considered full when:
The separator water level remains stable for two(2)
minutes
and
The WR valve is fully opened and ZR valve is
>15% open for two(2) minutes.
Start BCP and open the UG valve to establish minimum water wall flow
at 30% TMCR.
As the pressure is raised, first the WR and then the ZR valves will open
when
separator water level increases due to boiler water swell. As pressure
further
increases, the WR and ZR valves will start to close as the water level
decreases.
26 October 2017 10
START-UP contd
The steam temperature at the separator inlet will reach a
stable superheated
condition at app. 30% TMCR, causing the level in the
separator to decrease and
eventually disappear. The boiler is now in once-through
mode (dry mode). The
BCP (Boiler Circulating Pump) will be stopped automatically.
Control action:
The boiler circulating pump is started following the start
of a turbine-driven feed water pump and the final clean-up
cycle. This pump circulates feed water from the evaporator
outlet back to the economizer inlet.
Located at the outlet of this pump is the UG valve which
controls economizer inlet flow during the start-up phase of
operation. Demand for this recirculation control valve is
established based on measured economizer inlet flow
compared to a minimum boiler flow set point.
The primary objective is to keep the final superheat spray water control
valves in their desired operating range.
Control objective:
Control final superheat steam temperature.
Control action:
The master controller for each valve acts on the
corresponding final steam outlet temperature as
compared to a load dependent set point.
The slave controller positions the final spray valve
(subject to saturation limit) in response to the master
output (with over/under firing feedforward) as compared
to the associated spray station outlet temperature.