Voltage Surge Protection-1
Voltage Surge Protection-1
Design
ELECTRICAL SAFETY: Voltage
Surge Protection
Contents
EE
314
Overcurrent protection
Earth leakage protection
Overcurrent vs Overvoltage
protection
Standards requirements
Circuits
So far in overcurrent
EE
protection
314
Overcurrent protection
Reduce chances of fire: Causes i2Rt heat in conductors that
could lead to fire if not managed well.
Protection against electrical shock (ventricular
fibrillation): Circuit breaker/fuses work best for severe overload
(worst case being short circuit condition) when fault currents
reach over 5x rated value.
Breaker time is stipulated by all international standards (AS 3000/BS
7671) as 0.4 seconds for final sub-circuits where portable hand held
apparatus would be plugged in. and 5 seconds for other circuits.
EE
314
EE
314
Source: Philips Application Notes: Protecting LED systems in accordance with IEEE &
ANSI C62.41.2; Transient Surge Requirements; 2011
6
EE
314
Source: Philips Application Notes: Protecting LED systems in accordance with IEEE &
ANSI C62.41.2; Transient Surge Requirements; 2011
7
EE
314
Category C SPD
Standard tests
1.2/50 s
Voltage
generator
Exposure
Minimium
open-circuit
voltage
evaluation
to be applied
to SPD
Optional test
Low
The scope of these tests6kV
is limited to SPDs, in contrast
tests
3kA with all the other recommended
6kV
that may be applied to equipment other than SPDs.
10kV
10kA
6kA with a
High
Values shown for the current
are applicable for each
phase of the SPD. In contrast
test applied to equipment for the purpose of assessing its response to the surge environment,
a test applied to characterize the performance of an SPD requires that the specified current
be driven through the SPD. For the low exposure, this can be accomplished with a typical
Combination Wave generator. For the high exposure, two
separate generators, in two successive tests, must be used to apply the specified values.
For low exposure tests, if a Combination Wave generator is used instead of two separate
generators, the generator charging voltage has to be adjusted to obtain the stated current
8 2014 H.Reddy, The University of the South Pacific
amplitude.
EE
314
Source: Philips Application Notes: Protecting LED systems in accordance with IEEE &
ANSI C62.41.2; Transient Surge Requirements; 2011
9
EE
314
Source: Philips Application Notes: Protecting LED systems in accordance with IEEE &
ANSI C62.41.2; Transient Surge Requirements; 2011
10
EE
314
EE
314Parameters to consider when selecting voltage SPD
Nominal voltage should match the utility system voltage where the device is to be
installed
MCOV The Maximum Continuous Operating Voltage, this is the maximum voltage the device
can withstand before conduction (clamping) begins. It is higher than the nominal system
voltage.
Nominal Discharge Current (In) is the peak value of current, selected by the
manufacturer, through the SPD having a current waveshape of 8/20 where the SPD remains
functional after 15 surges.
VPR Voltage Protection Rating. A rating per UL 1449 Third edition, signifying the rounded
up average measured limiting voltage of an SPD when the SPD is subjected to the surge
produced by a 6 kV, 3 kA 8/20 s combination waveform generator. VPR is a clamping voltage
measurement that is rounded up to one of a standardized table of values. The standard VPR
ratings include 330, 400, 500, 600, 700, etc. As a standardized rating system, VPR allows the
direct comparison between like SPDs (i.e. same Type and Voltage).
SCCR Short Circuit Current Rating. The suitability of an SPD for use on an AC power circuit
that is capable of delivering not more than a declared rms symmetrical current at a declared
voltage during a short circuit condition. SCCR is not the same as AIC (Amp Interrupting
Capacity). SCCR is the amount of available current that the SPD can be subjected to and
safely disconnect from the power source under short circuit conditions. The amount of current
interrupted by the SPD is typically significantly less than the available current.
Enclosure rating ensures that the NEMA rating of the enclosure matches the
environmental conditions at the location where the device is to be installed.
12
EE
314
Source: Philips Application Notes: Protecting LED systems in accordance with IEEE &
ANSI C62.41.2; Transient Surge Requirements; 2011
13
EE
314
EE
314
EE
314
GDT vs MOV
MOV
GDT
Fast response
Lower ratings
Lower life cycle
EE
314
Circuit
Source: Wikipedia
17