Critical Power
SG Series 10-40 kW
ales Presentation
ecember 2013
1
2012 General Electric Company
Product Range
UPS SG Series 10 kVA PurePulse
10kW
UPS SG Series 15 kVA PurePulse
15kW
UPS SG Series 20kVA PurePulse
20kW
UPS SG Series 30kVA PurePulse
30kW
UPS SG Series 40kVA PurePulse
40kW
CE Marked, 3x380/400/415V In & Out,
50/60Hz
Page 2
GE Critical Power
SG 10-40 kVA Presentation 2013
1
UPS Configuration
Double conversion technology
Designed for Mission Critical Applications
True On-Line Double Conversion
VFI technology
Voltage and Frequency
Independent
Inverter output transformer for
load galvanic separation
Bypass
supply
Rectifier
Rectifie
r
supply
SG CE classification: VFI SSS 111
VFI Voltage & Frequency Independent
Frequency Converter operation
available
SS
Static bypass
Inverter
AC
DC
Load
AC
DC
Battery bank
Class 1
Output voltage THD < 8% for all loads
THDv < 2% linear loads
THDv < 3% non-linear loads
111 Class 1 performance
Exceeding Class 1
Best in Class dynamic response:
+/- 3% at load step: 0-100%-0
+/- 2% at load step: 0-50%-0
SG Series
Page 4
GE Critical Power
SG 10-40 kVA Presentation 2013
UPS configuration
Double conversion with inverter output isolation transformer
Q2
MANUAL BYPASS
SSM
K6
CB4
RECTIFIER
INVERTER
Q1
K7
LOADS
INPUT MAINS
AUTOMATIC BYPASS
INVERTER
TRANSFORMER
CB3
BATTERY
Double conversion (VFI) technology with output isolation transformer
Automatic bypass for overloads, short circuit and UPS disturbances
conditions
Manual bypass for UPS maintenance operations without load
interruption
Protection safety devices integrated
Page 5
GE Critical Power
- back feed protection K6 standard
SG 10-40 kVA Presentation 2013
Backfeed protection
IEC 62040-1 : For fixed installation UPS, backfeed protection may be
provided internally or externally to the UPS in the a.c. input line
Standard feature inside UPS
cabinet
No additional cost required
No addition installation required
Backfeed contactor
static bypass
Fully compliant with IEC 62040-1
Compliance to UPS installation
safety requirements
Safer operating condition
Safer operation for end users
and
service engineers
Input
mains
Rectifier
Inverter
DC
AC
DC
Load
AC
Battery bank
preventing feedback to the mains
from the inverter in case of mains
failure and a fault in the bypass
circuit
Page 6
GE Critical Power
SG 10-40 kVA Presentation 2013
UPS configuration
dvantages - Output Isolation Transformer
No DC component in output (galvanic isolation by
transformer)
Transformer less UPS DC components are controlled
electronically
Lower DC voltage less number of batteries per string
(30-32 blocks)
Less cost for same type of batteries and back up time
Better
short circuit capability in battery mode (bypass not available)
Transformer less UPS More battery blocks, connections
Transformer based UPS 2.7 X Nominal current Ph-Ph
etc
- 4 X Nominal current Ph-N / G
Transformer less UPS 2.2 X Nominal current
No neutral current back to the mains in case of unbalanced load in
Double conversion mode
Better management of unbalanced load.
A Zig-Zag transformer will share an unbalanced load on the three inverter
bridges
Transformer less UPS inverter legs may see unbalanced load ( different
leg operates at different load % - Components stress level are different)
improves battery lifetime through less ripple
Page 7
GE Critical Power
Better management of non linear load (low level harmonics
are
SG 10-40
kVAshortPresentation 2013
circuited)
2
Input performance
IGBT technology for clean input
Pure Pulse configuration for highest input performances
Constant behavior at all loads
Negligible harmonics contents at full
and
partial loads
Benefit on input mains
Saving in the sizing of upfront
equipment's
e.g. GenSet, cablings, circuit breakers,
No disturbances to nearby equipment
Saving cost due to additional filters
Total Input Harmonic Distortion
5%
4%
THDi
UPS input performances
Total Current Harmonic Distortion
THDi=2% @ 100% load and 5% @ 50%
load
UPS input power factor: 0.99
PurePulse technology for IGBT
rectifier
3%
2%
1%
0%
0%
20%
40%
60%
Load
80%
100%
Page 9
GE Critical Power
SG 10-40 kVA Presentation 2013
Input rectifier performances
Wide input window to preserve battery autonomy and lifetime
Input window
Soft start
Rectifier can be activated gradually,
controlling the input current
Preventing instable situation for
GenSet
Avoids false trip of upfront
protection devices
Sequential softstart for parallel UPS
+10%
Input
frequency
Wide input voltage and frequency
windows
Limited use of battery
Preserve battery autonomy for real
input mains failures
Increase battery lifetime
50 Hz
10%
-15%
400V
Input
voltage
+15%
Soft start
UPS input current
UPS 1
2
100%
UPS
0%
time
Page 10
GE Critical Power
SG 10-40 kVA Presentation 2013
Perfect integration with GenSet
No GenSet oversizing required
GenSet integration
Compatible with GenSet design
Saving GenSet size
(suggested GenSet vs. UPS ratio ~ 1.1)
Reducing GenSet installation space
Saving GenSet investment
GenSet system integration
GenSet integration via Customer
Interface (dedicated auxiliary contact)
Programmable functions based on
GenSet working condition (Gen on/off)
Page 11
GE Critical Power
SG 10-40 kVA Presentation 2013
3
Output performance
Highest UPS output power capability
Capability to supply Inductive, Resistive and Capacitive loads
Full range power capability
Designed to supply real power for
any type of application
- inductive loads
- resistive loads
- capacitive loads
I.e. SG-CE 20kVA load capabilities:
Inductive load PF=0.9 18 kW / 20 kVA
Resistive load PF=1
20 kW / 20 kVA
Capacitive load PF=0.9 18 kW / 20 kVA
No over-sizing required to supply
resistive and capacitive loads
Suitable for modern power supply
application with unit or capacitive
power factor (e.g. new servers
generation), crest factor up to 3:1
Page 13
GE Critical Power
SG 10-40 kVA Presentation 2013
No output voltage distortion
Best in class inoutput dynamic stiffness
No output voltage distortion with
linear and non-linear loads
Voltage distortion
- linear loads:
THDv <2%
- non-linear loads: THDv < 3%
Enhanced customer productivity
Improved quality of application,
reducing
stress for loads
supplied
Increased uptime and MTBF of
customer
Reduced service intervention
Output voltage with linear + nonlinear load
output voltage
curren
t
Output voltage with non-linear
load
output voltage
curren
t
Page 14
GE Critical Power
SG 10-40 kVA Presentation 2013
Output Dynamic Stiffness
Best in class inoutput dynamic stiffness
Best in class in output voltage
variation with load steps:
Static
:<+
1%
Dynamic at load steps 0-50-0% : < +
2%
Dynamic at load steps 0-100-0% : < +
3%
Enhanced customer unit productivity
Improved quality of application
(i.e. medical images)
Capability to supply critical loads with
high and fast loads steps (pulsating
loads)
Increased uptime and MTBF of customer
Reduced service intervention
Medical scanner - dynamic current
absorbtion
1
ms
Voltage variation at 0100% load
step
load step 0-100%
output voltage
Page 15
GE Critical Power
SG 10-40 kVA Presentation 2013
High Efficiency at all loads
Reduced customer operation costs and cost saving in air conditioning
design
High efficiency performances
High efficiency > 92% at full and
partial loads for real benefit in
operating conditions
Energy cost saving
Reduced cost of customer equipment
operation at all loads
Air conditioning cost saving
Reducing size and cost of air condition
system
Reducing consumption and related
operating cost
Higher backup time
Page 16
GE Critical Power
SG 10-40 kVA Presentation 2013
Superior Battery Management
Safe and protected battery management to preserve investment and UPS
reliability
Charging voltage = f (battery temperature)
2.36
2.33
Volt per cell
Flexible applications
Different battery technologies
applicable: PB sealed (VRLA) - PB
vented NiCd
Wide autonomy range: few minutes
... hours
2.30
2.27
2.24
2.21
2.18
0
User friendly information
Prediction of true back-up time,
based on load status
Alarm for stop operation to
prevent
any unknown shut-down
Monitoring and control
Battery test (programmable or
manual) ; preserve UPS system
reliability
Battery earth fault detection; safer
operation
for service engineer &
end user
10
15
20
25
30
35
40
Battery tem perature [C]
Voltage temperature compensation
Page 17
GE Critical Power
SG 10-40 kVA Presentation 2013
4
Improved serviceability
High Reliability
Improved diagnostic, High Reliability
SG Series Improved diagnostic, High
reliability
Front access (including battery)
Wave form capture capability
Fan failure detection
AC Capacitor health monitoring
Component life time counters
Dedicated supply path for bypass logic
Regulated power supply
Page 19
GE Critical Power
SG 10-40 kVA Presentation 2013
Improved diagnostic, High Reliability
SG Series Improved diagnostic, High
reliability
Robust RPA communication (Manchester
coded)
Simplified design through reduction of
PCBA & connections
Output filter capacitors PCBA mounted,
easy to replace
Input & battery circuit breaker instead of
contactor
Robust rectifier control with input mains
diagnostic
Page 20
GE Critical Power
SG 10-40 kVA Presentation 2013
New FLEX DSP board
Improved diagnostic capabilities
Extended modularity
Enhanced connectivity
Black box -> Waveform Capture
capability improved diagnostic
Higher computing capability ->
more ability to manage data
New digital communication
3X bandwidth
Faster connectivity -> up to
10x with connectivity devices
hardware upgrade
Waveform capture
Improved reliability
Dedicated supply for bypass logic
Dedicated supply for connectivity
channels
Redundant logic for emergency bypass
activation
Main-board integrated RPA control: RPA
board contains only interface hardware
More robust RPA communication
(Manchester coded)
Common platform
Page 21
GE Critical Power
SG 10-40 kVA Presentation 2013
New FLEX DSP board: the black-box Option
Waveform capture, diagnostic and trend analysis
Simultaneous acquisition of 32 channels
Sampling frequency up to 10kHz
Smart trigger capability with up to 16 indipendent trigger
sources to record only specific events with pre/post trigger
data acquisition
Buffer depth of 1000 samples per channel: each event is
recorded for 100ms @ s.f. 10kHz
8 buffers to record up to 8 events without losing older
events can be extended with external USB mass storage
devices
WAVEFORMS
Inverter voltages
Bypass voltages
Input mains voltages
Output voltages:
Output current Phases:
Input capacitors Cin voltages:
Inverter primary current:
Input current:
IDC current:
Battery current:
Bypass current:
UDC
Communication status RPA
Auxiliary status
SSM status
Fuses status
Phase error slave master.
Page 22
GE Critical Power
SG 10-40 kVA Presentation 2013
EMC - Immunity
Immunity
SG-CE products design exceed IEC 62040-2 C3 level
for immunity, i.e. can withstand possible disturbances
and noise without affecting standard working
conditions
IEC 62040-2 C2 SG Series 10kVA
Immunity
SG-CE
immunity level
IEC requirements
ESD
8kV (air)
4kV (contact)
8kV (air)
4kV (contact)
Surge
2kV line to line
4kV line to earth
1kV line to line
2kV line to earth
Burst
4kV @5kHz
2kV @5kHz
RF common mode (1kHz)
10V
10V
Page 23
GE Critical Power
SG 10-40 kVA Presentation 2013
Redundant Parallel Architecture
True redundancy with no single point of failure
Modular design
Future system expansion
Saving investment
Input mains
rectifier
bypass
rectifier
bypass
True redundancy
No single point of failure
Decentralized bypass
Distributed parallel management
system
Redundancy loss alarm
Increased system reliability
Safe and reliable power supply for
mission critical applications
Increase productivity
True redundancy with no single
point of failure
AC
AC
DC
battery
DC
battery
DC
DC
AC
AC
critical load
Page 24
GE Critical Power
SG 10-40 kVA Presentation 2013
Control panel
Easy and intuitive interface
Back lit Graphic Display (LCD)
Multilanguage communication
interface:
English, German, Italian, Spanish,
French, Finnish, Polish, Portuguese,
Czech, Slovakian, Chinese, Swedish,
Russian and Dutch
Synoptic diagram indicating UPS status
Command keys and parameters setting
UPS status control LED
LED - red
Stop
Operation
LED - yellow
Alarm
LED - green
Operation
Page 25
GE Critical Power
SG 10-40 kVA Presentation 2013
Customer interface
Easy integration with Building Management System (BMS)
UPS supervision capability
1x RS232 Serial Communication Port
6 programmable potential free alarm
contacts:
- D plug
- Terminals blocks
1x Emergency Power OFF contact
1x Gen-ON Input contact
1x Control Input contact
Additional interface:
SNMP Interface Card
(10/100Mbps auto-select)
MODBUS RTU Interface (RS232 or
RS485)
Page 26
GE Critical Power
SG 10-40 kVA Presentation 2013
Installation flexibility - Product options
Product Options
Empty Battery cabinets:
Rectifier, Bypass transformer
RPA card, SNMP card, Modbus RTU
iUPSGuard (Remote monitoring)
Black box capability
24V DC Power supply
EMC filter class A (40 kVA) the 40kVA is class C2 standard as
well (adding 4x ferrites)
Customer connection kit
Page 27
GE Critical Power
SG 10-40 kVA Presentation 2013
5
Product Comparison
Product Comparison
Site pro 10-40 kVA
SG Series 10-40 kVA
Rectifier topology Thyristor based
Rectifier topology IGBT
Input power factor 0.8
Input power factor 0.99
Input THDi 30%
Input THDi 2%
Efficiency Low at part load
Filter Capacitor overhang
mounting
Robust control
Efficiency Improved by 1-1.5%
Filter Capacitor PCBA mounting
Service access Side for battery
Service access Front/Top only
Customer interface Separate card
Customer interface embedded
card
Page 29
GE Critical Power
SG 10-40 kVA Presentation 2013
Product Comparison
Site pro 10-40 kVA
Power supply not regulated AC
power
SG Series 10-40 kVA
Power supply regulated AC/DC
power
Battery disconnect Optional
Battery disconnect Standard CB3
Cooling system One blower
Cooling system Fans
No Fan failure detection
Fan failure detection
No Cooling redundancy
Partial Cooling redundancy
Enhance diagnostic capability No
Enhance diagnostic capability
Galvanic isolation
Galvanic isolation
No Capacitor monitoring
Capacitor monitoring
Page 30
GE Critical Power
SG 10-40 kVA Presentation 2013
Product Comparison
Site pro 10-40 kVA
Cable connection
SG Series 10-40 kVA
Cable kit extension available to replace
Sitepro without changing cable connections.
Page 31
GE Critical Power
SG 10-40 kVA Presentation 2013
New SG Series.... high
performances UPS
- Increased reliability
- Better short circuit
cap
Output isolation
transformer
Saving in the sizing
-Input Breaker
-Input cables
High Efficiency > 92%
Output pf 1.0
(lead to lag)
- More Output power
Clean Input < 5%
THDi
Input pf 0.99
Wide input voltage
-Inbuilt back feed
protection
Saving in the sizing
- Genset
Output V THDv
<2%
- Reduce stress on load
- Stiff bus for pulsed loads
-Enhance battery life
Low Total Cost of
Ownership
Page 32
32
GE Critical Power
SG 10-40 kVA Presentation June 2013
SG 10-40 kVA - Applications
Process industries
Large railway
organizations
Control systems
Healthcare
33
2012 General Electric Company
Page 34
GE Critical Power
SG 10-40 kVA Presentation 2013
Competitive Comparison
Technology
Power range
Input PF
Input THDi
Output PF
Efficiency
IP degree of
protection
Input/output
Back-feed
Foot Print
Serviciability
GE
SG 10-40 kVA
Socomec
Masterysy
Riello
Master MPS
Riello
Multisentry
Liebert
NXC
Tx based
10-40
0.99
< 3%
1
92%
Tx based
10-40 (up to 80)
0.99
< 3%
0.9/0.8
?
Tx based
10-800
0.92
< 5-7%
0.9
92 ?
Tx less with internal
option
10-40 (upto 120)
0.99
<3%
0.9
up to 94% ?
Tx less with internal
option
10-40
0.99
< 4%
0.9
92.5% (with Tx)
20
3/3
Standard
680 x 800 x 1450 mm
31
3/3 & 3/1
Optional
600 x 800 x 1400 mm
1000 x 835 x 1400 mm
(40kVA)
20
3/3 & 3/1
Optional
555 x 740 x 1400
Internal Batt upto
20kVA
20 (31 option)
3/3 & 3/1 (20 kVA)
Optional
440 x 850 x 1320
20
3/3 & 3/1 (20 kVA)
500 x 860 x 1240
600 x 850 x 1600 (3040 kVA)
Front access
Front and back access
Front access
Internal battery upto 40
kVA
Internal Batt upto 30kVA
Front access
Front access
Page 35
GE Critical Power
SG 10-40 kVA Presentation 2013