7 Transformer-Protection
7 Transformer-Protection
PROTECTION
Transformer Through-Fault
Protection
limiting fuses.
larger transformers limited by the impedance
Transformer differential relays and
transformer sudden pressure relays are used
to quickly detect and isolate the failed
transformer.
Backup time overcurrent relays are used to
protect against faults that are not cleared
properly on circuits that are connected to the
transformer secondary.
Selection Criteria
The suggested criteria for the selection of protection relays or
schemes are:
Proven experience for a minimum period of three years
Relays built to IEEE switchgear standards or equivalent IEC
standards
Relays tested to IEEE C37.90, C37.90.1, C37.90.2 or to IEC
60255
Where possible, microprocessor-based relays with features
such as self checking, self-diagnostics, RMS sensing,
metering, event logging, wave capture, disturbance
recording, and with a communications port for data recovery
and setting
Relays that perform satisfactorily in the presence of
harmonics and electromagnetic (EMI) and radio frequency
(RFI) interferences
Redundancy requirements for generators, large motors, and
transformers
Availability of application literature and technical support
Fuses
are
used
extensively
to
protect
transformers rated at 69 KV and below when
long fault clearing times (seconds) are
acceptable.
Fuses that are not current limiting are not
recommended for transformer protection
Sudden pressure relays are used to complement
differential relays for internal failures in oil-filled
transformers.
Modern sudden pressure relays provide effective
transformer protection
Transformer
differential
protection
a.Consider, for example, a 75-MVA, 230-69-
inrush.
b. This can be accomplished by specifying a relay
with a higher pickup and some small time delay
(six to 12 cycles) to override high initial peaks.
c. Utilize
a harmonic restraint or harmonic
supervisory unit in conjunction with the
differential relays
d. More modern, microprocessor-based relays can
record a transformers inrush signature and use
that waveform to decide whether to restrain or
enable tripping.
230-69-KV transformer
Step 1
Determine maximum load current.
175% = 693 A
69 KV leads: 1394 A (@ 62.1 KV)
175% = 2440 A
Step 2
CT connections delta
Relay current will be 3 greater than
the current in the transformer leads.
Maximum current to relay, 230-KV
leads:
= 693 A x3 = 1200 A
Maximum current to relay, 69-KV
leads:
= 2440 A x3 = 4225 A
Step 3
a. Select CT ratios so that the relays
Step 4
a. Select relay taps at transformer full
load current.
b. 230 KV 376 A 376 A 3 600/5
= 5.427 A
c. 69 KV 1255 A 1255 A 3
2500/5 = 4.347 A
d. Use relay taps of 5.4 amps for 230KV and 4.3 amps for 69-KV relay
Step 5
a. Select
percent restraint.
Minimum operate current is 0.5
amps.
b. Check current seen by the
differential relay
c. maximum high-voltage tap and
the minimum low-voltage tap.
d. minimum high-voltage tap and
the maximum low-voltage tap.
5.4 CT
at
230 kV
4.3 CT
at
68 kV
amp
Transformer External
Fault Protection
flow of current through each
transformer lead
For Y-Y or - transformers, current
secondary of -Y transformers,
phase to- phase fault current flowing in
secondary leads is 0.866 of the three
phase value,
Typical Settings of
Protective Devices for
Power Transformers