Effectivenessnumber of Transfer Unit Relationships
is a function of NTU, R, and flow arrangement.
Counter flow exchanger as a
function of NTU and R.
1.The heat exchanger effectiveness
increases monotonically with
increasing values of NTU for a
specified R.
2.The exchanger effectiveness
increases with decreasing values of
R for a specified NTU.
3. For 40%, the heat capacity
rate ratio R does not have a
significant influence on the
exchanger effectiveness".
Department of Mechanical Engineering
College of Engineering, Pune (COEP)
Forerunners in Technical Education
11
4.Heat exchanger effectiveness increases with increasing NTU as
noted above in item 1, but at a diminishing rate.
5.Because of the asymptotic nature of the -NTU curves, a
significant increase in NTU and hence in the exchanger size is
required for a small increase in at high values of .
6. Alternatively, a larger increase in NTU (or the size of the
exchanger) is required to compensate for the same (or small)
amount of heat loss to the surroundings at high values of in
comparison to that for a lower exchanger.
The counter-flow exchanger has the highest exchanger effectiveness for
specified NTU and R of that for all other exchanger flow arrangements.
Alternatively, the heat transfer surface area is utilized most efficiently
for counter-flow compared to all other flow arrangements.
It should be emphasized that many industrial heat exchangers
are not counter-flow