Standard Equipment Numbers Used in Schematic Drawings
Standard Equipment Numbers Used in Schematic Drawings
62 63 64 67 68 74 75 76 77 79 80 81 83 85 86 87 88 89 95 96 97
Time delay on operating relay e.g. PDR. Liquid or gas pressure relay e.g. 63AR, 63GA. Instantaneous Earth fault relay. IDMTL Directional over current & E/F relay. Blocking relay. Alarm relay. P.T. Selection relay / Position changing mechanism. D.C. Over current relay. Phase angle out of step relay Reclosing relay. D.C. Supervision relay e.g. 80B1, 80B2 etc. Frequency relay. Automatic selective control or transfer relay. Carrier or pilot wire receive relay. Master Trip & lockout relay. Differential relay. Auxiliary motor or Generator e.g. Compressor. Motorized Isolator. Trip circuit supervision relay. Bus Bar trip relay. Fuse fail relay.
SYMBOLS
DESCRIPTION
SYMBOLS
DESCRIPTION
MAKE CONTACT
BREAK CONTACT
MAKE CONTACT WITH BLOWN OUT MAGNET MAKE CONTACT HAND RESET
SYMBOLS
DESCRIPTION
SYMBOLS
DESCRIPTION
CONTROL SWITCH
CHANGE OVER CONTACT HAND RESEST CHANGE OVER CONTACT DELAYED DROP OFF
FLAG INDICATOR
SYMBOLS
DESCRIPTION
SYMBOLS
DESCRIPTION
SYMBOLS
DESCRIPTION
SYMBOLS
DESCRIPTION
FUSE
HEATER
LINK
HEATER SWITCH
TEST BLOCK-MPG
POWER SOCKET
RESISTOR
THERMOSTAT
STABILIZING RESISTOR
SYMBOLS
DESCRIPTION
SYMBOLS
DESCRIPTION
ELECTRIC HOOTER/BUZZER
INDICATING LAMP
NO CONTACT
SEMAPHORE INDICATOR
NC CONTACT
ELECTRIC BELL
PUSH BUTTON
Symbol S is used in C.T. ckt for C.T. secondary wiring from C.T. secondary box to C.T. Marshalling box e.g. R-1S1, R-1S2, Y-2S2, B-3S1 etc. Symbol T is sometimes used for trip ckt e.g. K-3AT, K-3BT, etc. Symbol U is used for equipment spare auxiliary contacts e.g. U1, U2, U11, U12 etc. Symbol R-Y-B are used for phases & phase sequence in C.T. ckt, P.T. ckt as well as A.C. ckt.
Purpose of Auxiliary Contacts:The Auxiliary contacts are used for following purposes:Auxiliary contacts are the replica of main contacts. To use breaker contacts for various purposes, Auxiliary contacts are used. Auxiliary contacts are used for indication purposes. Auxiliary contacts are used for protection of CC & TC. Sometimes Auxiliary contacts are used for alarm. Auxiliary contacts are used for PDR Circuit. Auxiliary contacts are used for TCS Circuit. Auxiliary contacts are used for various interlocks.
Multiplication of Auxiliary contacts:In some equipment, only one or two Auxiliary contacts remain available but in scheme, we require more contacts. So, to get more contacts, we multiply one contact by using Auxiliary relay. Sometimes we require a number of contacts of one equipment as interlocks in C & R panel. It is not economical to bring a number of contacts through cables. So we multiply only one contact in C & R panel by using Auxiliary relay. By using contact multiplication method, the problem of voltage drop from control room to switch yard and from switch yard to control room, can be avoided.