Cognex D750 CommunicationsAndProgramming
Cognex D750 CommunicationsAndProgramming
Legal Notices
The software described in this document is furnished under license, and may be used or copied only in accordance with the terms of such license and with the inclusion of the copyright notice shown on this page. Neither the software, this document, nor any copies thereof may be provided to, or otherwise made available to, anyone other than the licensee. Title to, and ownership of, this software remains with Cognex Corporation or its licensor. Cognex Corporation assumes no responsibility for the use or reliability of its software on equipment that is not supplied by Cognex Corporation. Cognex Corporation makes no warranties, either express or implied, regarding the described software, its merchantability, non-infringement or its fitness for any particular purpose. The information in this document is subject to change without notice and should not be construed as a commitment by Cognex Corporation. Cognex Corporation is not responsible for any errors that may be present in either this document or the associated software. No part of this document may be reproduced or transmitted in any form or by any means, electronic or mechanical, for any purpose, nor transferred to any other media or language without the written permission of Cognex Corporation. Copyright 2011 Cognex Corporation. All Rights Reserved. Portions of the hardware and software provided by Cognex may be covered by one or more of the U.S. and foreign patents listed below as well as pending U.S. and foreign patents. Such pending U.S. and foreign patents issued after the date of this document are listed on Cognex web site at http://www.cognex.com/patents. VisionPro
5481712, 5495537, 5548326, 5583954, 5602937, 5640200, 5751853, 5768443, 5825913, 5850466, 5872870, 5901241, 5943441, 5978080, 5978521, 5987172, 6005978, 6039254, 6064388, 6075881, 6137893, 6141033, 6167150, 6215915, 6240208, 6324299, 6381366, 6381375, 6411734, 6421458, 6459820, 6490375, 6516092, 6563324, 6658145, 6687402, 6690842, 6697535, 6718074, 6748110, 6771808, 6804416, 6836567, 6850646, 6856698, 6920241, 6959112, 6963338, 6973207, 6975764, 6985625, 6993177, 6993192, 7006712, 7016539, 7043081, 7058225, 7065262, 7088862, 7164796, 7190834, 7242801, 7251366, 7313761, EP0713593, JP3522280, JP3927239
DataMan
5742037, 5943441, 6215915, 6236769, 6282328, 6381375, 6408109, 6457032, 6690842, 6941026, 7175090, 7181066, 7412106, 7427028, 7549582, 7604174, 7614563, 7617984, US-2005-0087601-A1, US-2006-0131418-A1, US-2006-0131419-A1, US-2006-0133757-A1, US-2007-0090193-A1, US-20070091332-A1, US-2007-0152064-A1, US-2007-0170259-A1, US-2008-0004822-A1, US-2008-0011855-A1, US-2008-0142604-A1, US-2008-0143838-A1, US2008-0158365-A1, US-2009-0090781-A1, US-2009-0108073, US-2009-0121027-A1, US-2009-0166424-A1, US-2009-0294541-A1, WO06065619A1, EP1687752
CVL
5495537, 5548326, 5583954, 5602937, 5640200, 5717785, 5751853, 5768443, 5825483, 5825913, 5850466, 5859923, 5872870, 5901241, 5943441, 5949905, 5978080, 5987172, 5995648, 6002793, 6005978, 6064388, 6067379, 6075881, 6137893, 6141033, 6157732, 6167150, 6215915, 6240208, 6240218, 6324299, 6381366, 6381375, 6408109, 6411734, 6421458, 6457032, 6459820, 6490375, 6516092, 6563324, 6658145, 6687402, 6690842, 6718074, 6748110, 6751361, 6771808, 6798925, 6804416, 6836567, 6850646, 6856698, 6920241, 6959112, 6975764, 6985625, 6993177, 6993192, 7006712, 7016539, 7043081, 7058225, 7065262, 7088862, 7164796, 7190834, 7242801, 7251366, EP0713593, JP3522280, JP3927239
VGR
5495537, 5602937, 5640200, 5768443, 5825483, 5850466, 5859923, 5949905, 5978080, 5995648, 6002793, 6005978, 6075881, 6137893, 6141033, 6157732, 6167150, 6215915, 6324299, 6381375, 6408109, 6411734, 6421458, 6457032, 6459820, 6490375, 6516092, 6563324, 6658145, 6690842, 6748110, 6751361, 6771808, 6804416, 6836567, 6850646, 6856698, 6959112, 6975764, 6985625, 6993192, 7006712, 7016539, 7043081, 7058225, 7065262, 7088862, 7164796, 7190834, 7242801, 7251366
OMNIVIEW
6215915, 6381375, 6408109, 6421458, 6457032, 6459820, 6594623, 6804416, 6959112, 7383536
SMD 4
5995648, 5850466, 6751361, 6690842, 6563324, 6490375, 5949905, 5978080, 6137893, 6167150, 6075881, 6748110, 5859923, 6411734, 6324299, 6516092, 7190834, 6658145, 6836567, 6850646, 6975764, 6985625, 6993192, 7006712, 7043081, 7058225, 7065262, 7088862, 7164796, 7251366, 6856698, 6002793, 6005978, 6771808, 6804416, 7016539, 6959112, 5602937, 7242801, 5640200, 5495537, 5768443, 5825483, 6421458, 6459820,
Legal Notices
6215915, 6381375, 6457032, 6157732, 6408109, 6141033, 6026176, 6442291, 6151406, 6396942, 6614926, 5371690, 5845007, 5943441, 6963338, 5805722, 5909504, 5933523, 5964844, 5974169, 5987172, 6078700, 6252986, 6278796, 6307210, 6408429, 6424734, 6526165, 6571006, 6639624, 6681039, 6748104, 6813377, 6853751, 6898333, 6950548, 6993177, 7139421, 5757956
Wire Bonder
5495537, 5532739, 5581632, 5602937, 5640199, 5640200, 5642158, 5676302, 5754679, 5757956, 5768443, 5825483, 5835622, 5850466, 5859923, 5861909, 5949905, 5978080, 5991436, 5995648, 6002793, 6005978, 6035066, 6061467, 6075881, 6137893, 6141033, 6157732, 6167150, 6215915, 6289492, 6324299, 6381375, 6408109, 6411734, 6421458, 6457032, 6459820, 6490375, 6516092, 6563324, 6658145, 6690842, 6748110, 6751361, 6771808, 6804416, 6836567, 6850646, 6856698, 6959112, 6975764, 6985625, 6993192, 7006712, 7016539, 7043081, 7058225, 7065262, 7088862, 7164796, 7171036, 7190834, 7242801, 7251366
Other product and company names mentioned herein are the trademarks, or registered trademarks, of their respective owners.
LASER LIGHT DO NOT STARE INTO BEAM CLASS 2 LASER PRODUCT 650 nm < 1 mW CLASSIFIED PER IEC 60825-1, Ed 2. 2007-08 AS/NZS. 2211.1:2004
Contents
About this Manual ...................................................................................................... 7 Networking ................................................................................................................ 8 Connecting your DataMan to the Network ...................................................................... 8 Direct Connection to Your Computer ............................................................................. 8 Configuring the DataMan to reside on the same subnet as the PC .................................. 8 Configuring the PC to reside on the same subnet as the DataMan ................................ 10 Connecting Your Reader across Subnets ...................................................................... 13 Troubleshooting an Ethernet Connection...................................................................... 14 Industrial Network Protocols ................................................................................... 15 EtherNet/IP ............................................................................................................. 16 DMCC ..................................................................................................................... 16 Reader Configuration Code ........................................................................................ 16 Setup Tool ............................................................................................................... 16 Getting Started ........................................................................................................ 17 Object Model............................................................................................................ 20 Attributes .............................................................................................................. 21 SoftEvents ............................................................................................................ 23 General Fault Indicator ........................................................................................... 23 Services ................................................................................................................ 23 Acquire Service ...................................................................................................... 24 SendDMCC Service ................................................................................................. 24 GetDecodeResults Service ....................................................................................... 25 GetDecodeResults Request Data Format ................................................................... 25 Acquisition Sequence .............................................................................................. 25 Decode / Result Sequence ....................................................................................... 26 Behavior of DecodeStatusRegister ............................................................................ 26 Results Buffering .................................................................................................... 27 Assembly Object .................................................................................................... 28 Input Assembly...................................................................................................... 28 Output Assembly ................................................................................................... 29 PCCC Object .......................................................................................................... 29 Rockwell ControlLogix Examples ................................................................................. 32 Implicit Messaging ................................................................................................. 32 Establishing an Implicit Messaging Connection ........................................................... 32 Accessing Implicit Messaging Connection Data ........................................................... 38 Verifying Implicit Messaging Connection Operation ..................................................... 41
Contents
Explicit Messaging .................................................................................................. 43 Issuing DMCC Commands ....................................................................................... 43 Rockwell CompactLogix Examples ............................................................................... 47 Rockwell SLC 5/05 Examples ................................................................................... 48 Setting up the PLC for Ethernet communication ......................................................... 48 Message Instruction (MSG) ..................................................................................... 49 Sending DMCC Commands from an SLC 5/05 ............................................................ 51 Message Instruction Results .................................................................................... 54 Using the Generic Ethernet/IP Profile ........................................................................ 54 Establishing a Generic Implicit Messaging Connection ................................................. 54 Accessing Generic Implicit Messaging Connection Data ............................................... 57 Examples............................................................................................................ 57 PROFINET ................................................................................................................ 59 DMCC ..................................................................................................................... 59 Reader Configuration Code ........................................................................................ 59 Setup Tool ............................................................................................................... 60 Getting Started ........................................................................................................ 60 Modules .................................................................................................................. 65 Acquisition Control Module .................................................................................... 66 Acquisition Status Module ..................................................................................... 67 Results Control Module ......................................................................................... 67 Results Status Module .......................................................................................... 68 Soft Event Control Module .................................................................................... 68 User Data Module ................................................................................................ 69 Result Data Module .............................................................................................. 70 Operation ................................................................................................................ 71 SoftEvents ............................................................................................................ 71 General Fault Indicator ........................................................................................... 71 Acquisition Sequence .............................................................................................. 72 Decode / Result Sequence ....................................................................................... 73 Behavior of DecodeStatusRegister ............................................................................ 73 Results Buffering .................................................................................................... 74 Siemens Examples .................................................................................................... 75 Symbol Table ........................................................................................................ 75 Trigger and Get Results .......................................................................................... 76 Using Soft Events ................................................................................................... 80
Contents
Executing DMCC commands .................................................................................... 82 DataMan Application Development .......................................................................... 84 DMCC Overview ....................................................................................................... 84 Command Syntax ..................................................................................................... 84 Command Header Syntax........................................................................................ 84 Header Examples ................................................................................................... 84 Command ............................................................................................................. 84 Commands ......................................................................................................... 85 Parameters ......................................................................................................... 85 Arguments .......................................................................................................... 85 Footer .................................................................................................................. 85 Reader Response ................................................................................................... 85 Examples .............................................................................................................. 86 DMCC Application Development .................................................................................. 86
Accordingly, the DataMan connected to a network can be triggered to acquire images by several methods. It can be done by the Setup Tool, it can be triggered by trigger bits or manipulating objects (industrial protocols), by external hard wired input or through DMCC command. This document provides a detailed description on how to do each.
Networking Networking
You can connect your DataMan via a simple Ethernet connection. You can either set the IP address and subnet mask of your DataMan manually or let them be configured automatically using DHCP.
To disconnect the reader: 1. Disconnect the reader from the PoE injector. 2. Disconnect the power cord from the PoE injector. 3. Disconnect the PoE injector from the Ethernet network.
Networking
2. In the Open field, type cmd and click OK. 3. In the command prompt window, type ipconfig and press Enter. A listing of all network adaptors on the PC is shown.
4. Record your PCs IP Address and Subnet Mask. In this example, IP Address is 169.254.135.189 Subnet Mask is 255.255.0.0.
5. Change to Advanced mode in the Setup Tools Connect to Reader pane, and use the Force Network Settings dialog to manually configure the network settings on the target DataMan. 6. Click the Force Network Settings button. The Force Network Settings dialog opens.
Networking
7. To force the network settings on your DataMan: a. b. c. NOTE The default Subnet Mask is 255.255.255.0. You can set it back to default by scanning the Reset Scanner to Factory Defaults Configuration Code. Authentication should be left blank unless Authentication has been enabled on the DataMan. Authentication is disabled by default. Enter the MAC address of the DataMan in the MAC Address field. The MAC Address of the DataMan can be found on the label of the reader. Select Use Static IP Address. Enter an IP Address and Subnet Mask that will be on the same subnet as the PC. Make sure this IP address is not yet in use (for example, test by pinging it). Example IP Address: 169.254.135.200 Subnet Mask: 255.255.0.0
Click OK. Your DataMan is configured to the network settings specified, and it reboots automatically. Your DataMan appears under the Network devices node after the address has been resolved. This can take up to 60 seconds. 8. If the device does not appear after 1 or 2 minutes, push the Refresh button on the Setup Tools Connect to Reader pane. This will force the Setup Tool to scan for DataMan devices connected to the PC or connected to the same network.
Networking
Once the IP Address and Subnet Mask of the DataMan are known, the PCs network settings can be changed. Perform the following steps to configure your PC (examples here are of Windows XP): 1. In the Start Menu, right click My Network Places, click the Properties menu option to launch Network Connections. 2. Right click on the network adaptor connected to the DataMan and select the Properties menu option.
3. Under the General tab, scroll down and select Internet Protocol (TCP/IP), and click Properties.
Networking
4. Under the General tab, select the Use the following IP address radio option and enter an IP Address and Subnet Mask that are on the same subnet as your DataMan. Click OK.
5. Click Close. The network settings of your PC will change to the new specified values. 6. Reboot the DataMan. It appears under the Network devices node on the Connect to Reader pane after the network address has been resolved. 7. If the device does not appear after 1 or 2 minutes, click the Refresh button on the Setup Tools Connect to Reader pane. The Setup Tool scans for DataMan devices connected to the PC or connected to the same network.
Networking
Connecting Your Reader across Subnets
The following options can be used to connect to the DataMan with the Setup Tool across subnets if you already know the IP Address of the DataMan. 1. In the Setup Tools Connect to Reader pane, click Add Device.
2. Enter a name and the actual IP Address of the target DataMan. The name has no effect upon the DataMan. It is only used as an identifier to list the target DataMan under the Network devices node.
3. Click OK. The name appears under the Network devices node. Double click the new node or highlight it and click the Connect button. If the device is available, you will be connected (a DataMan 200 is connected in this example).
Networking
EtherNet/IP EtherNet/IP
DataMan supports EtherNet/IP, an application level protocol based on the Common Industrial Protocol (CIP). EtherNet/IP provides an extensive range of messaging options and services for the transfer of data and I/O over Ethernet. All devices on an EtherNet/IP network present their data to the network as a series of data values called attributes. Attributes can be grouped with other related data values into sets, these are called Assemblies. By default the DataMan has the EtherNet/IP protocol disabled. The protocol can be enabled via DMCC, scanning a parameter code, or in the Setup Tool.
DMCC
The following commands can be used to enable/disable EtherNet/IP on the DataMan. The commands may be issued via RS-232 or Telnet connection. NOTE Because you have to make changes to the Telnet client provided by Windows to communicate with DataMan, it is recommended you use third party clients such as Putty.
Enable: ||>SET ETHERNET-IP.ENABLED ON ||>CONFIG.SAVE ||>REBOOT Disable: ||>SET ETHERNET-IP.ENABLED OFF ||>CONFIG.SAVE ||>REBOOT
Enable:
Disable:
Setup Tool
EtherNet/IP can be enabled/disabled by checking or unchecking the EtherNet/IP Enabled box on the Industrial Protocols tab of the advanced Network Settings pane. Make sure to save the new selection by choosing Save Settings before disconnecting from the reader. NOTE The new settings take effect only after the reader is rebooted.
EtherNet/IP
Getting Started
Preparing to use EtherNet/IP involves the following main steps: Make sure you have the Rockwell Software tool on your machine. Set up the Rockwell Software tool so that it recognizes your DataMan device. Install the DataMan Electronic Data Sheet (EDS) for the DataMan reader.
Perform the following steps to set up EtherNet/IP: 1. Verify that the Rockwell Software is on your PC. 2. Make sure you select the Add on Profile installation and the Samples installation. Add on Profile is only used with Rockwell ControlLogix or CompactLogix PLCs. 3. Install the Rockwell Add on Profiles by navigating to the following directory. NOTE Adjust the path for the specific Setup Tool version that you are using.
EtherNet/IP
5. If you have not previously installed the Rockwell AOP, now run MPSetup.exe. 6. From the Start menu, go to Programs Rockwell Software RSLinx Tools EDS Hardware Install Tool.
7. Run the ESD Install tool. NOTE If you have an existing EDS file, uninstall it first, then install the latest version of the EDS. 8. Run the Setup Tool and update the DataMan firmware. 9. Check if the firmware has been loaded into the unit by clicking in the Setup Tool View System Info.
10. In the Setup Tool, go to the Network Settings panes Industrial Protocols tab and check the EtherNet/IP Enabled checkbox.
EtherNet/IP
11. In order for the changes to take effect, you must save your settings and cycle power. In the Setup Tool menu, click System Save Settings. 12. Reboot your reader. 13. Your DataMan is visible now in the RSWHO.
If your DataMan is visible, but the icon is a question mark, repeat the ESD Installation. 14. Open one of the sample jobs and integrate your DataMan into your program using the Add on Profile. 15. Alternatively, you can add the DataMan as a Module on your network.
EtherNet/IP
Object Model
The ID Reader Object is a vendor specific object class. This means it is not part of the CIP common (public) architecture but rather an extension. It is a custom object that Cognex has added to the Ethernet/IP architecture on the DataMan device. This object models all data and functionality available in the DataMan reader. This includes triggering, status, events, errors and result data. The ID Reader Object is identified by its vender specific class code: DataMan ID Reader Object Class Code: 0x79 Objects are made up of attributes (data) and services (functionality). These can be defined at the class level (common to all instances of the class) or the instance level (unique to an individual instance). There are common attributes and services defined by the CIP specification that apply to all objects (often these are optional). Vendors may also define their own attributes and services for their vendor specific classes. The ID Reader Object attributes and services can be individually accessed via explicit messaging. Also a number of the ID Reader Object attributes are exposed in the DataMan assembly objects which allow them to be accessed as a group via implicit messaging.
EtherNet/IP
DataMan Reader System
Identity Object
TCP/IP Object
Attributes
The DataMan ID Reader Object (Class Code: 0x79) has the following attributes. Attribute ID 0x9 Access Rule Set Name Data Type BOOL Description 0 = Ethernet/IP triggering is disabled 1 = Ethernet/IP triggering is enabled Acquire an image when this attribute changes from 0 to 1. Bit0: Trigger Ready Bit1: Trigger Ack Bit2: Acquiring Bit3: Missed Acquisition Bit4-7: Reserved User defined data that may be used as an input to the acquisition/decode. When true, it enables buffering of the decode results. Bit0: Decoding Bit1: Decode completed (toggle) Bit2: Results buffer overrun Bit3: Results available Bit4: Reserved Bit5: Reserved Bit6: Reserved Bit7: General fault indicator Acknowledges that the client received the decode results.
AcqTriggerEnable
0xA
Set
AcqTrigger
BOOL
0xB
Get
AcqStatusRegister
BYTE
0xC 0xD
Set Set
UserData BufferResultsEnable
0xE
Get
DecodeStatusRegister
BYTE
0xF
Set
DecodeResultsAck
BOOL
EtherNet/IP
Attribute ID Access Rule Name DecodeResults Data Type STRUCT of UINT Description The last decode results Decode results identifier. Corresponds to the TriggerID of the decoded image. Decode result summary code value Bit0: 1=Read, 0=No read Bit1: 1=Validated, 0=Not Validated Bit2: 1=Verified, 0=Not Verified Bit3: 1=Acquisition trigger overrun Bit4: 1=Acquisition buffer overrun Bit5-15: Reserved (future use) Extended result information Current number of result data bytes. Result data from last decode SoftEvents act as virtual inputs (execute action on 0 to 1 transition) Bit0: Train code Bit1: Train match string Bit2: Train focus Bit3: Train brightness Bit4: Un-Train Bit5: Reserved (future use) Bit6: Execute DMCC command Bit7: Set match string Trigger identifier. ID of the next trigger to be issued. Optional user data information Current number of user data bytes.
ResultsID
0x10
Get
ResultCode
UINT
0x12
Set
SoftEvents
BYTE
EtherNet/IP
Attribute ID Access Rule Name Data Type Description Acknowledgment of SoftEvents. Bit0: Train code ack Bit1: Train match string ack Bit2: Train focus ack Bit3: Train brightness ack Bit4: Un-Train ack Bit5: Reserved (future use) Bit6: Execute DMCC command ack Bit7: Set match string ack
0x18
Get
SoftEventAck
BYTE
SoftEvents
SoftEvents act as virtual inputs. When the value of a SoftEvent changes from 0 1 the action associated with the event will be executed. When the action completes the corresponding SoftEventAck bit will change from 1 0 to signal completion. The SoftEvent and SoftEventAck form a logical handshake. After SoftEventAck changes to 1 the original SoftEvent should be set back to 0. When that occurs SoftEventAck will automatically be set back to 0. The ExecuteDMCC and SetMatchString soft event actions require user supplied data. This data must be written to the UserData & UserDataLength area of the Input Assembly prior to invoking the soft event. Since both of these soft events depend on the UserData, only one may be invoked at a time.
SoftEvent cycle #1
SoftEvent cycle #3
Services
The ID Reader Object supports the following Common CIP services.
EtherNet/IP
Service Code 0x05 0x0E 0x10 Service Name Reset Get_Attribute_Single Set_Attribute_Single Description Resets the ID Reader object Returns the contents of the specified attribute. Modifies the specified attribute
The ID Reader Object supports the following vendor specific services. Service Code 0x32 0x34 0x35 Service Name Acquire SendDMCC GetDecodeResults Description Triggers a single acquisition Sends a DMCC command to the device Gets the content of the DecodeResults attribute
Acquire Service
The Acquire Service will cause an acquisition to be triggered (if the acquisition system is ready to acquire an image). If the acquisition could not be triggered, then the Missed Acquisition bit of the AcqStatusRegister will be set until the next successful acquisition.
SendDMCC Service
The SendDMCC Service sends a DMCC command string to the device. The request data consists of the DMCC command string that is to be sent to the reader. The reply data will contain the string result of the DMCC command. Additionally the service provides a numeric result status for the call. Most of these result codes relate to the basic success/failure of the service execution. However, the service also maps the actual DMCC status codes. This allows the PLC to interpret the service request without having to parse the actual DMCC return string. Service Return Code 0 1 4 100 101 102 103 104 Description Success No error Bad Command No Answer System too busy Unidentified error Command invalid Parameter invalid Checksum incorrect Parameter rejected/altered due to reader state DMCC Return Code 0 100 101 102 103 104
NOTE The string must be in the CIP STRING2 format (16-bit integer indicating the string length in characters followed by the actual string characters, no terminating null required).
EtherNet/IP
GetDecodeResults Service
The GetDecodeResults service reads data from the DecodeResults attribute of the ID Reader Object. This service takes parameters indicating the size (number of bytes to read) and the offset (offset into the DecodeResults attribute to begin reading). This gives the service the flexibility to be used with PLCs that have different restrictions on the amount of data allowed in an explicit message. It also allows the user to access very large codes that cannot be completely transferred with implicit messaging (assembly object).
Acquisition Sequence
DataMan can be triggered to acquire images by several methods. It can be done implicitly via the Assembly object. Or done explicitly via the ID Reader object. When using explicit messaging it can be done in a single step by accessing the Acquire Service, it can also be done by directly manipulating the ID Reader object attributes (AcqTrigger and AcqStatusRegister) and finally it can be done via DMCC command. The ID Reader attributes will be discussed here but these same values can be accessed via the assembly objects. On startup the AcqTriggerEnable attribute will be False. It must be set to True to enable triggering. When the device is ready to accept triggers, the Trigger Ready bit in the AcqStatusRegister will be set to True. While the AcqStatusRegister Trigger Ready bit is True, each time the ID Reader object sees the AcqTrigger attribute change from 0 to 1, it will initiate an image acquisition. When setting this via the assembly objects, the attribute should be held in the new state until that same state value is seen in the Trigger Ack bit of the AcqStatusRegister (this is a necessary handshake to guarantee that the change is seen by the ID Reader object). During an acquisition, the Trigger Ready bit in the AcqStatusRegister will be cleared and the Acquiring bit will be set to True. When the acquisition is completed, the Acquiring bit will be cleared. The Trigger Ready bit will again be set True once the device is ready to begin a new image acquisition. If results buffering is enabled, the device will allow overlapped acquisition and decoding operations. Trigger Ready will be set high after acquisition is complete but while decoding is still in process. This can be used to achieve faster overall trigger rates. If result buffering is not enabled, the Trigger Ready bit will remain low until both the acquisition and decode operations have completed. As a special case, an acquisition can be cancelled by clearing the Trigger signal before the read operation has completed. This allows for the cancellation of reads in Presentation and Manual mode if no code is in the field of view. To ensure that a read is not unintentionally cancelled, it is advised that the PLC hold the Trigger signal True until both TriggerAck and ResultsAvailable are True (or DecodeComplete toggles state).
EtherNet/IP
2 1
1
3
2
2
1
M
2 2
3
M
1 1 1
Acquisition #1
2 2
3 3
3 3
M
Acquisition #2
Missed Acq
Acquisition #3
Client DataMan
To force a reset of the trigger mechanism set the AcqTriggerEnable attribute to False, until the AcqStatusRegister is 0. Then, AcqTriggerEnable can be set to True to re-enable acquisition.
Behavior of DecodeStatusRegister
Bit 1 2 Bit Name Decoding Decode Complete Results if Buffering Disabled Set when decoding an image. Toggled on completion of an image decode. Results if Buffering Enabled Set when decoding an image. Toggled on completion of an image decode. Set when decode results could not be queued because the client failed to acknowledge a previous result. Cleared when the decode result is successfully queued.
EtherNet/IP
Bit Bit Name Results if Buffering Disabled Set when new results are placed in the DecodeResults attribute. Stays set until the results are acknowledged by setting DecodeResultsAck to true. Results if Buffering Enabled Set when new results are placed in the DecodeResults attribute. Stays set until the results are acknowledged by setting DecodeResultsAck to true.
Results Available
Trigger Ready Trigger Trigger Ack Acquiring Decoding Decode Cmplt Results Avail Results Ack
1 1 1 1 1 1 1 1
2 2
1 1
2 2 1
2 2 2
2 1 1
22 2
2
2t
Read #2
h t p : / / w w w . f a c e b o o k . c o m / a l b u m . p h p ? a
Results Buffering
There is an option to enable a queue for decode results. If enabled this allows a finite number of decode result data to queue up until the client (PLC) has time to read them. This is useful to smooth out data flow if the client (PLC) slows down for short periods of time. Also, if result buffering is enabled the device will allow overlapped acquisition and decode operations. Depending on the application this can be used to achieve faster over all trigger rates. See Acquisition Sequence description above for further detail. In general, if reads are occurring faster than results can be sent out the primary difference between buffering or not buffering is determining which results get discarded. If buffering is not enabled the most recent results are kept and the earlier result (which was not read by the PLC fast enough) is lost. Essentially the more recent result will simply over write the earlier result. If buffering is enabled (and the queue becomes full) the most recent results are discarded until room becomes available in the results queue.
EtherNet/IP
Assembly Object
Assemblies are combinations of selected attributes (data items) from CIP objects with in a device. The device vendor defines assemblies according to their needs. They combine data together in useful groupings according to the requirements of the application. The designation of Input & Output assembly can be confusing. DataMan is an I/O adapter class device. The convention for adapters is that Input Assemblies produce (transmit) data for another device (i.e. DataMan PLC) and Output Assemblies consume (receive) data from another device (i.e. PLC DataMan). Essentially DataMan acts as an I/O module for another device such as a PLC. Assembly objects use implicit messaging. In the abstract they are just blocks of data which are transmitted as the raw payload of implicit messaging packets. These implicit messaging packets are produced (transmitted) repeatedly at a predefined chosen rate (100ms, 200ms, etc). DataMan readers have a single input assembly and single output assembly. These assemblies combine selected attributes (data) of the DataMan ID Reader Object into groupings that minimize network bandwidth and still allow for efficient control and processing. The data in these assemblies can also be accessed individually from the ID Reader Object. However, using the assembly objects is much more efficient. This is the reason that they are the primary means of runtime communication between a DataMan reader and a PLC.
Input Assembly
The Input assembly provides status information, process state, and decode results.
Instance 11 Byte 0 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Missed Acq Results Available Soft Event Ack 4 Soft Event Ack 3 Bit 2 Acquiring Results Buffer Overrun Soft Event Ack 2 Bit 1 Trigger Ack Bit 0 Trigger Ready
Reserved
Reserved
Decode Complete Decoding Toggle Soft Event Ack 1 Soft Event Ack 0
3-5 6
Reserved
Trigger ID (16-bit integer) 7 8 Result ID (16-bit integer) 9 10 Result Code (16-bit integer) 11 12 Result Extended (16-bit integer) 13
EtherNet/IP
Instance Byte 14 Result Data Length (16-bit integer) 15 16 499 Result Data 483 Result Data 0 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Output Assembly
The Output assembly contains control signals, software event signals, and any user data required for the trigger & decode.
Instance 21 0 Reserved Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Results Ack Soft Event 4 Soft Event 3 Bit 2 Buffer Results Enable Soft Event 2 Bit 1 Bit 0 Trigger Enable Soft Event 0
Trigger
1 2
Soft Event 7
Soft Event 6
Soft Event 5
Soft Event 1
Reserved 3 4 User Data Option (16-bit integer) 5 6 User Data Length (16-bit integer) 7 8 499 User Data 491 User Data 0
PCCC Object
DataMan has limited support for the Rockwell PCCC object. This allows legacy PLCs (PLC-5, SLC, etc) to communicate with DataMan using their native PCCC command set and explicit messaging. The PCCC object allows DataMan to look like a Rockwell PLC-5 logic controller. PCCC commands are organized to work with data tables that exist in legacy logic controllers. Each data table is an array of a give data type (BYTE, INT, FLOAT, etc). The commands are oriented to read/write one or more data items of a given data table. Items are addressed by specifying the data table and the index of the item in the table (indexes base from 0). For instance to read the 6th integer in PLC data table you would send the PCCC command to read N7:5. N specifies an integer table, 7 is the table number in the PLC (each table has a unique numeric identifier assigned when the user PLC program was created), and 5 is the index into the table (note indexes begin at 0). The PCCC object in DataMan maps the read and write requests to ID Reader assemblies (or in one special case to the DMCC service). Read commands return data from the Input
EtherNet/IP
assembly (instance 11). Write commands send data to the Output assembly (instance 21). In essence the PCCC Object gives the outward appearance of PLC-5 data tables but is actually accessing the assembly data. Currently the implementation only supports an Integer data table (N7) and an ASCII data table (A9). There is one special case of String data table (ST10:0) for DMCC. Table N7 A9 ST10 Data Type Integer (16-bit) ASCII (8-bit) String Table Size 250 elements 500 elements 1 element
The ResultCode value is located at word offset 5 (counting from 0) of the Input Assembly. To access this value you would issue the following PLC command.
Integer Table N7 Word 0 PCCC Read 1 element @ N7:5 Word 1 1 Word ... Word 5 Word 6 Word 7 ... Word n Input Assembly Word 0 Word 1 1 Word ... Word 5 Word 6 Word 7 ... Word n
PLC Command
The decode ResultData begins at byte offset 16 (counting from 0) of the Input Assembly. To read the first 4 bytes of result data you would issue the following PLC command.
ASCII Table A9 Byte 0 Word Byte 1 1 ... Byte 16 Byte 17 Byte 18 Byte 19 ... Byte n
Input Assembly Byte 0 Byte 1 ... Byte 16 Byte 17 Byte 18 Byte 19 ... Byte n
The UserData begins at word offset 4 (counting from 0) of the Output Assembly. To write 4 words of UserData you would issue the following PLC command.
EtherNet/IP
PLC Command PCCC Write 4 elements @ N7:4 Integer Table N7 Word 0 Word 1 ... Word 4 Word 5 Word 6 Word 7 Word 8 ... Word n Output Assembly Word 0 ... Word 4 Word 5 Word 6 Word 7 Word 8 ... Word n
The bit to trigger an acquisition is in byte offset 0 of the Output Assembly. To write to this byte you would issue the following PLC command.
PLC Command PCCC Write 1 element @ A9:0 ASCII Table A9 Byte 0 Word 1 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 ... Byte n Output Assembly Byte 0 Word Byte 1 1 Byte 2 Byte 3 Byte 4 Byte 5 ... Byte n
The PCCC Object supports a special case mapping of a string table element (ST10:0) to the DMCC service. Any string written to ST10:0 will be passed to the DMCC service for processing. This allows PCCC write string commands to be used to invoke DMCC commands. NOTE The string table is only one element in size. Writing to the other elements will return an error.
PLC Command PCCC Write 1 element @ ST10:0 String Table ST10 String 0 DMCC Service
EtherNet/IP
Rockwell ControlLogix Examples
Implicit Messages transmit time-critical application specific I/O data, and can be point-topoint or multicast. Explicit messages require a response from the receiving device. As a result, explicit messages are better suited for operations that occur less frequently. An instruction to send a DMCC command is an example of an explicit message.
Implicit Messaging
EtherNet/IP implicit messaging allows a DataMan readers inputs and outputs to be mapped into tags in the ControlLogix PLC. Once these connections are established the data is transferred cyclically at a user defined interval (10ms, 50ms, 100ms, etc). The figure below represents Ethernet-based I/O through EtherNet/IP:
ControlLogix
DataMan:I
ID Reader Object
DataMan:O
Acquisition Subsystem
Decode Subsystem
DMCC Subsystem
The Input Assembly and Output Assembly map various attributes (data) from the ID Reader object: The Input Assembly is the collection of DataMan reader data values sent to the PLC (PLC inputs); and the Output Assembly is the collection of data values received by the DataMan reader from the PLC (PLC outputs).
EtherNet/IP
2. From the Select Module dialog, choose your model of DataMan ID Reader from the list. NOTE This option will only be available after the DataMan Add-On Profile has been installed.
NOTE The remainder of the steps is identical regardless of which DataMan model is selected. 3. After the selection is made, the configuration dialog for the DataMan ID Reader system will be displayed. Give the module a name and enter the DataMans IP address. The default is a bidirectional (send/receive) connection consisting of control, status, and 32 bytes of result data with keying disabled. To change this default connection, select the Change button. If no change is required skip over the next step.
EtherNet/IP
4. Change the connection configuration. Selecting the Change button will bring up the Module Definition dialog. This dialog is used to alter the connection configuration. You can change: DataMan revision Electronic keying Connection type (bidirectional/receive-only) Amount of data received (from the DataMan) Amount of data sent (to the DataMan)
Electronic Keying: Defines the level of module type checking that is performed by the PLC before a connection will be established. Exact Match All of the parameters must match or the connection will be rejected. Vendor
EtherNet/IP
Product Type Catalog Number Major Revision Minor Revision
Compatible Module The following criteria must be met, or else the inserted module will reject the connection: The Module Types must match Catalog Number must match Major Revision must match The Minor Revision of the module must be equal to or greater than the one specified in the software.
Disable Keying The controller will not employ keying at all. Connection: Defines the type of data flow. Data (Bidirectional) The connection will send data (to the DataMan) and receive data (from the DataMan). Input (Results only) The connection will only receive data (from the DataMan). Generally used in situations where more than one PLC needs to receive data from the same DataMan device. Input Results from Sensor: Defines the amount of data received on the connection (from the DataMan). The minimum amount is the Status data only. The connection can be configured to also receive read result data. The amount of result data received is defined in fixed increments (16 bytes, 32 bytes, 64 bytes etc). The size should be selected to return no more than the largest code size to be read by the application. Setting the size larger wastes network bandwidth and diminishes performance.
Output Data to Sensor: Defines the amount of data transmitted on the connection (to the DataMan). The minimum amount is the Control data only. The connection can be configured to also send user data. The amount of user data sent is defined in fixed increments (16 bytes, 32 bytes, 64 bytes etc).
EtherNet/IP
5. The final step is configuring the connection rate. The rate at which data is transmitted/received is defined as the Requested Packet Interval (RPI). The RPI defines how frequently the data is transmitted/received over the connection. To optimize network performance this rate should be set no lower than absolutely required by a given application. In general it should be set no lower than the expected maximum read rate of the user application. Setting it lower wastes bandwidth and does not improve processing performance. 6. Select the Connection tab of the New Module dialog to set the rate.
7. After adding the module to ControlLogix, the I/O tree should appear as follows:
EtherNet/IP
8. When the DataMan module is added to the I/O tree RSLogix 5000 creates tags that map to the DataMan reader Input and Output Data (i.e. the Input & Output Assembly Objects in the DataMan Reader). These tags can be found under the Controller Tags node of the project tree. NOTE The base name of these tags is the name you gave to the DataMan Module that you added to the I/O Configuration in the earlier steps.
EtherNet/IP
The tags are organized in two groups: Status and Control. The Status group represents all the data being received (from the DataMan). The Control group represents all the data being sent (to the DataMan). These tags are the symbolic representation of the DataMan Assembly Object contents. The PLC ladder is written to access these tag values. By monitoring or changing these tag values the PLC ladder is actually monitoring and changing the DataMan Assembly Object contents. NOTE There is a time delay between the DataMan and these PLC tag values (base on the configured RPI). All PLC ladder must be written to take that time delay into account.
TriggerReady: Indicates when the DataMan reader can accept a new trigger. This tag is True when the Control tag TriggerEnable has been set and the sensor is not currently acquiring an image.
EtherNet/IP
TriggerAck: Indicates when the DataMan reader has been triggered (i.e. the Control tag Trigger has been set to True). This tag will stay set until the Trigger tag is cleared. Acquiring: Indicates when the DataMan reader is currently acquiring an image; either by setting the Trigger bit or by an external trigger. MissedAcq: Indicates when the DataMan reader misses an acquisition trigger; cleared when the next successful acquisition occurs. Decoding: Indicates when the DataMan reader is decoding an acquired image. DecodeCompleted: Tag value is toggled (10 or 01) on the completion of a decode. ResultsBufferOverrun: Indicates when the DataMan reader has discarded a set of decode results because the results queue is full. Cleared when the next set of results are successfully queued. ResultsAvailable: Indicates when a set of decode results are available (i.e. the ResultID, ResultCode, ResultLength and ResultsData tags contain valid data). GeneralFault: Indicates when a fault has occurred (i.e. Soft event SetMatchString or ExecuteDMCC error has occurred). TrainCodeAck: Indicates that the soft event TrainCode has completed. TrainMatchStringAck: Indicates that the soft event TrainMatchString has completed. TrainFocusAck: Indicates that the soft event TrainFocus has completed. TrainBrightnessAck: Indicates that the soft event TrainBrightness has completed. UnTrainAck: Indicates that the soft event UnTrain has completed. ExecuteDmccAck: Indicates that the soft event ExecuteDMCC has completed. SetMatchStringAck: Indicates that the soft event SetMatchString has completed. TriggerID: Value of the next trigger to be issued. Used to match triggers issued with corresponding result data received later. ResultID: The value of TriggerID when the trigger that generated these results was issued. Used to match TriggerIDs with result data. ResultCode: Indicates success/failure of this set of results. Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bits 5-15 ,1=read 0=no read ,1=validated 0=not validated (or validation not in use) ,1=verified 0=not verified (or verification not in use) ,1=acquisition trigger overrun ,1=acquisition buffer overflow (not the same as result buffer overflow). ,reserved (future use)
ResultExtended: Currently unused. ResultLength: Number of bytes of result data contained in the ResultData tag. ResultData: Decode result data.
EtherNet/IP
A description of the Control tag group follows. This is the data sent from the ControlLogix to the DataMan reader.
TriggerEnable: Setting this tag enables Ethernet/IP triggering. Clearing this field disables the Ethernet/IP triggering. Trigger: Setting this tag triggers an acquisition when the following conditions are met: The TriggerEnable tag is set. No acquisition/decode is currently in progress. The device is ready to trigger.
ResultsBufferEnable: When set, the decode results will be queued. Results are pulled from the queue (made available) each time the current results are acknowledged. until acknowledged by the PLC. The Decode ID, Decode Result and Decode ResultsData fields are held constant until the DecodeResultsAck field has acknowledged them and been set. The DataMan reader will respond to the acknowledgement by clearing the ResultsValid bit. Once the DecodeResultsAck field is cleared the next set of decode results will be posted. ResultsAck: The ResultsAck tag is used to acknowledge that the PLC has read the latest results. When ResultsAck is set, the ResultsAvailable tag will be cleared. If results buffering is enabled the next set of results will be made available when the ResultsAck tag is again cleared. TrainCode: Changing this tag from 0 to 1 will cause the train code operation to be invoked. TrainMatchString: Changing this tag from 0 to 1 will cause the train match string operation to be invoked. TrainFocus: Changing this tag from 0 to 1 will cause the train focus operation to be invoked.
EtherNet/IP
TrainBrightness: Changing this tag from 0 to 1 will cause the train brightness operation to be invoked. Untrain: Changing this tag from 0 to 1 will cause the un-train operation to be invoked. ExecuteDMCC: Changing this tag from 0 to 1 will cause the DMCC operation to be invoked. A valid DMCC command string must be written to UserData prior to invoking this soft event. SetMatchString: Changing this tag from 0 to 1 will cause the set match string operation to be invoked. The match string data must be written to UserData prior to invoking this soft event. UserDataOption: Currently unused. UserDataLength: Number of bytes of user data contained in the UserData tag. UserData: This data is sent to the DataMan reader to support acquisition and/or decode.
To verify the correct, 2-way transfer of I/O data, in RSLogix, go to the controller tags and change the state of the TriggerEnable bit from 0 to 1:
EtherNet/IP
3. The TriggerReady tag changes to 1. 4. Triggering is now enabled. Whenever the Trigger tag is changed from 0 to 1, the DataMan reader will acquire an image. Note that the current TriggerID value is 1. The results of the next trigger to be issued should come back with a corresponding ResultID of 1. 5. After the acquisition/decode has completed, the DecodeCompleted tag will toggle and the ResultsAvailable tag will go to 1. In the example shown here a successful read has occurred (ResultCode bit 0 = 1) and the read has returned 16 bytes of data (ResultLength=16). The data can be found in the ResultData tag.
EtherNet/IP
Explicit Messaging
Unlike implicit messaging, explicit messages are sent to a specific device and that device always responds with a reply to that message. As a result, explicit messages are better suited for operations that occur infrequently. Explicit messages can be used to read and write the attributes (data) of the ID Reader Object. They may also be used for acquiring images, sending DMCC commands and retrieving result data.
EtherNet/IP
Boolean flag used to initiate the command. String containing the DMCC command to execute. String receiving the DMCC command results Temp buffer holding the data to send via the MSG instruction. Temp buffer holding the data received via the MSG instruction. Boolean flag used to indicate that a message is in process. Data structure required by the Logix MSG instruction.
2. Add the following two rungs to the MainRoutine of your ControlLogix project:
EtherNet/IP
3. Edit the MSG instruction. Configure it for CIP Generic, service 0x34 SendDMCC, class 0x79 ID Reader Object and instance 1. Set the source to Message_Data and the destination to Message_Result.
4. On the MSG instruction Communication tab, browse for and select the DataMan which you added to the project I/O Configuration tree. This tells Logix where to send the explicit message.
EtherNet/IP
Place a DMCC command in the DMCC_Command_String tag. For example ||>GET TRIGGER.TYPE$r$l. Note the $r$l at the end of the string. This is how Logix represents a CRLF. Toggle the Send_DMCC_Command tag to 1. When the Send_DMCC_Command tag goes back to 0 execution is complete. The DMCC command results will be found in DMCC_Result_String.
EtherNet/IP
Rockwell CompactLogix Examples
CompactLogix differs very little from ControlLogix in terms of programming. The ControlLogix examples apply to equally to CompactLogix systems. There is only a slight difference in adding the DataMan device in the project I/O tree. The I/O Configuration tree in a CompactLogix project looks a bit different from a ControlLogix project. Regarding the Ethernet connection, the difference is that the Ethernet logic module is actually embedded in the CompactLogix processor module. It is displayed in the I/O Configuration tree as if it were a separate module on the backplane. This module is also configured exactly like a ControlLogix Ethernet module. The DataMan module is added in the same way for CompactLogix as for ControlLogix. Right-click on the Ethernet node in the I/O Configuration tree and select New Module.
From the Select Module dialog, choose your model of DataMan ID Reader from the list.
After the selection is made, the configuration dialog for the DataMan ID Reader system will be displayed. From this point on configuration and programming are done exactly as shown in the ControlLogix section above.
EtherNet/IP
Rockwell SLC 5/05 Examples
This section outlines a PCCC (PC3) Communications configuration between a DataMan reader and the PLC. This example uses the Allen-Bradley SLC5/05 and Rockwell 500 software.
2. The Allen-Bradley SLC has 2 channels available for configuration: Channel 1 (Ethernet); and Channel 0 (DF1 Full Duplex - serial). Click on the Chan. 1 - System tab. 3. Configure Channel 1 (Ethernet) as necessary. Consult with a network administrator for proper settings.
EtherNet/IP
Type: Peer-To-Peer. This cannot be modified. Read/Write: Select the function you want to perform on a DataMan reader. Read retrieves data from the DataMan; Write sends data to the DataMan. Target Device: Choose PLC5 to talk to a DataMan reader. This tells the SLC which communication protocol to use. The DataMan reader acts much like a ControlLogix controller (see Rockwell document 13862). Local/Remote: Choose Local to indicate that the DataMan reader is on the same network as the SLC; Remote tells the SLC that you will be communicating to a DataMan on another network. For remote communication, you must direct the message through another device acting as a gateway to that secondary network. Typically, this could be an Allen-Bradley ControlLogix controller. (Refer to Rockwell documentation on how to address devices on other networks through a gateway.) Control Block: This is a temporary integer file that the MSG instruction uses to store data (i.e., IP address, message type, etc.). This is typically not the user data to be sent. Control Block Length: This is automatically computed by the MSG instruction.
EtherNet/IP
Setup Screen: Selecting Setup Screen will open the Message Instruction Setup dialog.
The following setup parameters can be configured within an MSG Instruction Setup screen.
This Controller section: Communication Command: Should be the same command (READ/WRITE) that was chosen on the first screen (as seen in MSG Instruction screen). Data Table Address: This is the location of the data file on the SLC where data will be written to (READ) or sent from (WRITE) (as seen in MSG Instruction screen). In this instance, 'F8:0', 'F' indicates the float file, '8' indicates the file number 8, and '0' indicates the offset into that file (in this case, start at the 0th element). The figure below shows an example of the Float Table accessed from the RSLogix 500 main screen.
Size in Elements: This is the number of elements (or individual data) to send. In this example, two elements are being sent (3.14 and 78.87). Channel: Depends on the configuration of the SLC. In the SLC, Channel 1 is the Ethernet port.
Target Device section: Message Timeout: Choose an appropriate length of time in which the DataMan reader will be able to respond. If the DataMan does not respond within this length of time, the MSG instruction will error out. This parameter cannot be changed from this screen. Message Timeout is determined by the parameters entered in the Channel 1 setup dialog.
EtherNet/IP
Data Table Address: This is the location on the DataMan reader where data will be read or written to. In this instance, 'N7:1', 'N' indicates that the data is of type integer (16-bit); '7' is ignored by the DataMan (data is always being written to the Output Assembly, and read from the Input Assembly); and the '1' is the element offset from the start of the target buffer. For example: If the message were a READ, 'N7:2' would instruct to read the 3rd integer (the ':2' indicates the 3rd element, due to the SLC's 0-based index) from the Input Assembly (because a READ gets data from the DataMan's Input Assembly). If the message were a WRITE, 'N7:12' would indicate to write a (16-bit) integer value to the 13 integer location of the Output Assembly. NOTE The ST10:0 destination address is a special case used for sending DMCC commands to a DataMan reader. Any string sent to ST10:0 will be interpreted as a DMCC command. Local/Remote: Set to Local or Remote, depending on the application. MultiHop: This setting is dependent on the information previously entered. For successful In-Sight communication, this should YES at this time.
EtherNet/IP
4. Add a new Message (MSG) instruction to your ladder logic and configure it as shown in the following example:
EtherNet/IP
Parameter ST10:0 1 1
Description First element from the String Table (ST) created above Always set to 1. PCCC MSG only allows 1 string (therefore 1 command) to be sent at a time. Set this to the Ethernet channel of your controller.
Parameter
Description
(From channel configuration dialog) ST10:0 This is the destination address. For DMCC commands, this will always be ST10:0
6. Click the MultiHop tab and configure it as required (i.e. set IP address of DataMan). 7. When everything is configured, close the MSG window. 8. Save your ladder logic, download it to the controller, then go online and set the controller in RUN mode. 9. Trigger the message to send it to the DataMan reader.
EtherNet/IP
Message Instruction Results
The Enable (EN) bit of the message instruction will be set to 1 when the input to the instruction is set high. The Done (DN) bit will be set to 1 when DataMan has replied that the DMCC command was received and executed with success. If the Error bit (ER) is enabled (set to 1), there has been a problem with the message instruction. If an error occurs, click the Setup Screen for the MSG instruction. The Error Code will be shown at the bottom of the window.
EtherNet/IP
3. From the Select Module dialog, choose the Allen-Bradley Generic Ethernet Module.
4. After the selection is made, the configuration dialog for the Generic Ethernet Module will be displayed. Configure the following: Give the module a name. Enter your DataMans IP address. Set the Comm Format to Data INT. This tells the module to treat the data as an array of 16-bit integers. Input Assembly: Set instance 11. Set the size to the amount of Input Assembly data you want the PLC to receive. Basic Status data requires 8 integers. The amount beyond that will be the actual decode result data. In the example below the size is set to 24 (8 for status + 16 for result data). This connection will receive the status info plus 32 bytes of result data. Output Assembly: Set instance 21. Set the size to 4 integers. This size is sufficient to send all required Control data to the DataMan. Configuration Assembly: Set instance 1. Set size to zero (no used).
EtherNet/IP
5. The final step is configuring the connection rate. The rate at which data is transmitted/received is defined as the Requested Packet Interval (RPI). The RPI defines how frequently the data is transmitted/received over the connection. To optimize network performance this rate should be set no lower than absolutely required by a given application. In no case should it be set to lower than the median scan rate of the PLC ladder program. Setting it lower wastes bandwidth and does not improve processing performance.
6. After adding the generic module to ControlLogix, the I/O tree should appear as follows.
EtherNet/IP
7. When the Generic Module is added to the I/O tree RSLogix 5000 creates tags that map to the DataMan reader Input and Output Data (i.e. the Input & Output Assembly Objects in the DataMan Reader). These tags can be found under the Controller Tags node of the project tree. NOTE The base name of these tags is the name you gave to the Generic Module that you added to the I/O Configuration earlier.
The tags are organized in three groups: Config MyDM200:C, Input MyDM200:I, and Output MyDM200:O. You can ignore the Config tags (no used). The Input tags represent all the data being received (from the DataMan). The Ouput tags represent all the data being sent (to the DataMan). These tags are the data table representation of the DataMan Assembly Object contents. The PLC ladder is written to access these tag values. By monitoring or changing these tag values the PLC ladder is actually monitoring and changing the DataMan Assembly Object contents. NOTE There is a time delay between the DataMan and these PLC tag values (based on the configured RPI). All PLC ladder must be written to take that time delay into account.
EtherNet/IP
Input Assembly ResultLength: Word 7 of the Input Assembly. From the Input tag array for the DataMan select word 7.
Output Assembly Trigger: Bit 1 of word 0 of the OutputAssembly. From the Output tag array for the DataMan select bit 1 of word 0.
PROFINET PROFINET
PROFINET is an application-level protocol used in industrial automation applications. This protocol uses standard Ethernet hardware and software to exchange I/O data, alarms, and diagnostics. DataMan supports PROFINET I/O. This is one of the 2 views contained in the PROFINET communication standard. PROFINET I/O performs cyclic data transfers to exchange data with Programmable Logic Controllers (PLCs) over Ethernet. The second view in the standard, PROFINET CBA (Component Based Automation), is not supported. A deliberate effort has been made to make the DataMan PROFINET communication model closely match the Cognex In-Sight family. Customers with In-Sight experience should find working with DataMan familiar and comfortable. By default, the DataMan has the PROFINET protocol disabled. The protocol can be enabled via DMCC, scanning a parameter code or in the Setup Tool.
DMCC
The following commands can be used to enable/disable PROFINET. The commands can be issued via RS-232 or Telnet connection. NOTE Because you have to make changes to the Telnet client provided by Windows to communicate with DataMan, it is recommended you use third party clients such as Putty.
Enable: ||>SET PROFINET.ENABLED ON ||>CONFIG.SAVE ||>REBOOT Disable: ||>SET PROFINET.ENABLED OFF ||>CONFIG.SAVE ||>REBOOT
Enable:
Disable:
PROFINET
Setup Tool
The PROFINET protocol can be enabled/disabled by checking or unchecking the PROFINET Enabled box on the Industrial Protocols tab of the advanced Network Settings pane. Make sure to save the new selection by choosing Save Settings before disconnecting from the reader. NOTE You must reboot your reader for the new settings to take effect.
Getting Started
Preparing to use PROFINET involves the following main steps: Make sure you have the Siemens Step 7 programming software (SIMATIC) installed. Set up the Siemens Software tool so that it recognizes your DataMan device. Install the Generic Station Description (GSD) file.
Perform the following steps to set up PROFINET: 1. Verify that SIMATIC is on your machine. 2. From the Windows Start menu, launch the SIMATIC Manager.
3. If you already have a project, select Cancel to skip past the New Project wizard. Otherwise, let the wizard guide you through creating a new project.
PROFINET
4. Once the Manager has opened the project, double-click on the Hardware icon to open the HW Config dialog screen. From the main menu, select OptionsInstall GSD File.
5. Browse to the location where the GSD file was installed (or the location where you saved the GSD file if it was downloaded from the web).
PROFINET
6. Select the GSD file you wish to install and follow the displayed instructions to complete the installation. NOTE There may be more than one GSD file in the list. If you are unsure which to install, choose the one with the most recent date.
7. Add your DataMan device to your project. This makes the DataMan available in the Hardware Catalog. Launch the SIMATIC Hardware Config tool. 8. In the main menu, select View Catalog. 9. The catalog is displayed. Expand the PROFINET IO tree to the Cognex ID Readers node. 10. With the left mouse button, drag the DataMan reader over and drop it on the PROFINET IO network symbol in the left pane.
PROFINET
The HW Config tool automatically maps the DataMan I/O modules into the memory space. NOTE By default, the 64 byte User Data and 64 byte Result Data Modules are inserted. There are multiple sizes available for both of these modules. To optimize performance use the module size that most closely matches the actual data requirements of your application. You can change the module simply by deleting the one in the table and inserting the appropriate sized module from the catalog. 11. Right-click on the DataMan icon and select Object Properties. 12. Give the reader a name. This must match the name of your actual DataMan reader. The name must be unique and conform to DNS naming conventions. Refer to the SIMATIC Software help for details. 13. If your DataMan reader is configured to use its own static IP, uncheck the Assign IP address via IO controller box. Otherwise if you wish the PLC to assign an IP address, select the Ethernet button and configure the appropriate address.
PROFINET
14. In the IO Cycle tab, select the appropriate cyclic update rate for your application.
15. By default, the SIMATIC software maps the User Data & Result Data Modules to offset 256. This is outside of the default process image area size of 128. That is, by default, data in these modules are inaccessible by some SFCs such as BLKMOV. As a solution, either remap the modules to lower offsets within the process image area or expand the process image area to include these modules. If you choose to expand the process image area, make the size large enough for the module size plus the default 256 offset.
PROFINET
NOTE Expanding the process image can have a performance impact on the PLC scan cycle time. If your scan time is critical, use the minimal acceptable module sizes and manually remap them down lower in the process image.
Modules
The PROFINET implementation on DataMan consists of seven I/O modules. 1. Acquisition Control Module 2. Acquisition Status Module 3. Results Control Module 4. Results Status Module 5. Soft Event Control Module 6. User Data Module 7. Result Data Module
PROFINET
Acquisition Control Module Controls image acquisition. This module consists of data sent from the PLC to the DataMan device. Slot number: 1 1 byte Description Setting this bit enables triggering via PROFINET. Clearing this bit disables triggering. Setting this bit triggers an acquisition when the following conditions are met: 1 Trigger Trigger Enable is set No acquisition is currently in progress The device is ready to trigger 27 Reserved Reserved for future use
PROFINET
Acquisition Status Module Indicates the current acquisition status. This module consists of data sent from the DataMan device to the PLC. Slot number: 2 3 bytes Description Indicates when the device is ready to accept a new trigger. Bit is True when Trigger Enable has been set and the device is ready to accept a new trigger. Indicates that the DataMan has received a new Trigger. This bit will remain True as long as the Trigger bit remains True (that is, it is interlocked with the Trigger bit). Indicates that the DataMan is currently acquiring an image. Indicates that the DataMan was unable to successfully trigger an acquisition. Bit is cleared when the next successful acquisition occurs. Reserved for future use ID value of the next trigger to be issued (16-bit integer). Used to match issued triggers with corresponding result data received later. This same value will be returned in ResultID of the result data.
Trigger Ack
2 3 47
823
Trigger ID
Results Control Module Controls the processing of result data. This module consists of data is sent from the PLC to the DataMan device. Slot number: 3 1 byte Description Enables queuing of Result Data. If enabled, the current result data will remain until acknowledged (even if new results arrive). New results are queued. The next set of results are pulled from the queue (made available in the Result Data module) each time the current results are acknowledged. The DataMan will respond to the acknowledge by clearing the Results Available bit. Once the Results Ack bit is cleared the next set of read results will be posted and Results Available will be set True. If results buffering is not enabled newly received read results will simply overwrite the content of the Result Data module.
PROFINET
Bit Name Description Bit is used to acknowledge that the PLC has successfully read the latest result data. When set True the Result Available bit will be cleared. If result buffering is enabled, the next set of result data will be pulled from the queue and Result Available will again be set True. Reserved for future use
Results Ack
27
Reserved
Results Status Module Indicates the acquisition and result status. This module consists of data sent from the DataMan device to the PLC. Slot number: 4 1 byte Description Indicates that the DataMan is decoding an acquired image. Bit is toggled on the completion of a decode operation when the new results are made available (01 or 10). Indicates that the DataMan has discarded a set of read results because the results queue is full. Cleared when the next set of results are successfully queued. Indicates that a new set of read results are available (i.e. the contents of the Result Data module are valid). Cleared when the results are acknowledged. Reserved for future use Indicates that a fault has occurred (i.e. Soft Event Set Match String or Execute DMCC error has occurred).
Decode Complete
3 46 7
Soft Event Control Module Used to initiate a Soft Event and receive acknowledgment of completion. Note, this is a bidirectional I/O module. Module data sent from the PLC initiates the Soft Event. Module data sent by the DataMan device acknowledges completion. Slot number: 5 1 byte (input) and 1 byte (output)
Data written from the PLC to DataMan: Bit 0 1 2 Name Train Code Train Match String Train Focus Description Bit transition from 01 will cause the train code operation to be invoked. Bit transition from 01 will cause the train match string operation to be invoked. Bit transition from 01 will cause the train focus operation to be invoked.
PROFINET
Bit 3 4 5 6 Name Train Brightness Untrain Reserved Execute DMCC Description Bit transition from 01 will cause the train brightness operation to be invoked. Bit transition from 01 will cause the untrain operation to be invoked. Reserved for future use Bit transition from 01 will cause the DMCC operation to be invoked. Note that a valid DMCC command string must first be placed in User Data before invoking this event. Bit transition from 01 will cause the set match string operation to be invoked. Note, match string data must first be placed in User Data before invoking this event.
Data written from the DataMan to PLC: Bit 0 1 2 3 4 5 6 7 Name Train Code Ack Train Match String Ack Train Focus Ack Train Brightness Ack Untrain Ack Reserved Execute DMCC Ack Set Match String Ack Description Indicates that the Train Code operation has completed Indicates that the Train Match String operation has completed Indicates that the Train Focus operation has completed Indicates that the Train Brightness operation has completed Indicates that the Untrain operation has completed Reserved for future use Indicates that the Execute DMCC operation has completed Indicates that the Set Match String operation has completed
User Data Module Data sent from a PLC to a DataMan to support acquisition, decode and other special operations. Currently this module is only used to support the Execute DMCC and Set Match String soft events. Note, there are actually 5 versions of the User Data module. Only one instance can be configured for use in a given application. The User Data Option and User Data Length fields are the same for each module. The User Data field varies in size based on the selected module. Choose the module which is large enough to exchange the amount of data required by your application. Slot number: 6 (16 bytes of User Data) (32 bytes of User Data) (64 bytes of User Data) 4 + 32 4 + 64
PROFINET
4 + 128 (128 bytes of User Data) 4 + 250 (250 bytes of User Data)
Byte
Name
Description Currently only used by Set Match String soft event. Specifies which code target to assign the string (16-bit Integer).
0-1
0, assign string to all targets 1, assign string to 2D codes 2, assign string to QR codes 3, assign string to 1D / stacked / postal codes
2-3
Number of bytes of valid data actually contained in the User Data field (16-bit Integer). Data sent from the PLC to the DataMan to support acquisition, decode and other special operations (array of bytes).
User Data
Result Data Module Read result data sent from a DataMan to a PLC. NOTE There are actually 5 versions of the Result Data module. Only a single instance can be configured for use in a given application. The Result ID, Result Code, Result Extended and Result Length fields are the same for each module. The Result Data field varies in size based on the selected module. Choose the module which is large enough to exchange the amount of result data required by your application. Slot number: 7 (16 bytes of Result Data) (32 bytes of Result Data) (64 bytes of Result Data) 8 + 32 8 + 64
8 + 128 (128 bytes of Result Data) 8 + 246 (246 bytes of Result Data)
Byte 0-1
Name Result ID
Description The value of the Trigger ID when the trigger that generated these results was issued. Used to match up triggers with corresponding result data (16-bit Integer).
PROFINET
Byte Name Description Indicates the success or failure of the read that produced these results (16-bit Integer). Bit 0,1=read, 0=no read 2-3 Result Code Bit 1,1=validated, 0=not validated (or validation not in use) Bit 2,1=verified, 0=not verified (or verification not in use) Bit 3,1=acquisition trigger overrun Bit 4,1=acquisition buffer overflow Bits 5-15 reserved 4-5 6-7 8 Result Extended Result Length Result Data Currently unused (16-bit Integer). Actual number of bytes of read data contained in the Result Data field (16-bit Integer). Decoded read result data (array of bytes)
Operation
SoftEvents
SoftEvents act as virtual inputs. When the value of a SoftEvent changes from 0 1 the action associated with the event will be executed. When the action completes the corresponding SoftEventAck bit will change from 0 1 to signal completion. The acknowledge bit will change back to 0 when the corresponding SoftEvent bit is set back to 0. The ExecuteDMCC and SetMatchString soft event actions require user supplied data. This data must be written to the UserData & UserDataLength area of the UserData Module prior to invoking the soft event. Since both of these soft events depend on the UserData, only one may be invoked at a time.
PROFINET
SoftEvent cycle #1
SoftEvent cycle #3
Acquisition Sequence
DataMan can be triggered to acquire images by several methods. It can be done explicitly by manipulating the Trigger bit of the Acquisition Control Module, it can be triggered by external hard wired input, and finally it can be triggered via DMCC command. Manipulating the Acquisition Control Module bits will be discussed here. On startup the Trigger Enable bit will be False. It must be set to True to enable triggering. When the device is ready to accept triggers, the Trigger Ready bit will be set to True. While the Trigger Ready bit is True, each time the reader sees the Trigger bit change from 0 to 1, it will initiate an image acquisition. The client (PLC) should hold the bit in the new state until that same state value is seen back in the Trigger Ack bit (this is a necessary handshake to guarantee that the change is seen by the reader). During an acquisition, the Trigger Ready bit will be cleared and the Acquiring bit will be set to True. When the acquisition is completed, the Acquiring bit will be cleared. The Trigger Ready bit will again be set True once the device is ready to begin a new image acquisition. If results buffering is enabled, the device will allow overlapped acquisition and decoding operations. Trigger Ready will be set high after acquisition is complete but while decoding is still in process. This can be used to achieve faster overall trigger rates. If result buffering is not enabled, the Trigger Ready bit will remain low until both the acquisition and decode operations have completed. To force a reset of the trigger mechanism set the Trigger Enable bit to False, until the Trigger Ready bit is 0. Then, Trigger Enable can be set to True to re-enable acquisition. As a special case, an acquisition can be cancelled by clearing the Trigger signal before the read operation has completed. This allows for the cancellation of reads in Presentation and Manual mode if no code is in the field of view. To ensure that a read is not unintentionally cancelled, it is advised that the PLC hold the Trigger signal True until both TriggerAck and ResultsAvailable are True (or DecodeComplete toggles state).
PROFINET
Trigger EN Trigger Ready Trigger Trigger Ack Acquiring Missed Acq Acquisition #1 Client DataMan Acquisition #2
2 1
1 1 1
3
2
M
2 2
3
M
1 1
2 2
3 3
3 3
Missed Acq
Acquisition #3
Behavior of DecodeStatusRegister
Bit 1 2 Bit Name Decoding Decode Complete Results if Buffering Disabled Set when decoding an image. Toggled on completion of an image decode. Results if Buffering Enabled Set when decoding an image. Toggled on completion of an image decode. Set when decode results could not be queued because the client failed to acknowledge a previous result. Cleared when the decode result is successfully queued.
PROFINET
Bit Bit Name Results if Buffering Disabled Set when new results are placed in the Results Module. Stays set until the results are acknowledged by setting Results Ack to true. Results if Buffering Enabled Set when new results are placed in the Results Module. Stays set until the results are acknowledged by setting Results Ack to true.
Results Available
Trigger Ready Trigger Trigger Ack Acquiring Decoding Decode Cmplt Results Avail Results Ack
1 1 1 1 1 1 1 1
2 2
1 1
2 2 1
2 2 2
2 1 1
22 2
2
2t
Read #2
h t p : / / w w w . f a c e b o o k . c o m / a l b u m . p h p ? a
Results Buffering
There is an option to enable a queue for decode results. If enabled this allows a finite number of decode result data to queue up until the client (PLC) has time to read them. This is useful to smooth out data flow if the client (PLC) slows down for short periods of time or if there are surges of read activity. Also, if result buffering is enabled the device will allow overlapped acquisition and decode operations. Depending on the application this can be used to achieve faster over all trigger rates. See Acquisition Sequence description above for further detail. In general, if reads are occurring faster than results can be sent out, the primary difference between buffering or not buffering is determining which results get discarded. If buffering is not enabled the most recent results are kept and the earlier result (which was not read by the PLC fast enough) is lost. Essentially the more recent result will simply over write the earlier result. If buffering is enabled (and the queue becomes full) the most recent results are discarded until room becomes available in the results queue.
PROFINET
Siemens Examples
This section gives some examples of using the DataMan with a Siemens S7-300 PLC. It is assumed that the reader is familiar with the S7-300 and the SIMATIC programming software.
Symbol Table
Although not required, defining symbols for the DataMan I/O module elements can be extremely helpful. It makes the code much easier to read and reduces mistakes. This sample table shows symbols defined for a typical instance of a DataMan reader. Note, DataMan I/O modules may be at different addresses in your project. Make sure to adjust your symbol definitions based on the specific offsets of the I/O modules.
PROFINET
Trigger and Get Results
Run the sample program DM200_SampleRead for the complete example program. Note, this sample can be used with any Profinet enabled DataMan reader. Perform the following steps to install the program: 1. Start the SIMATIC Manager software. 2. Close any open applications. 3. From the main menu, select File Retrieve 4. Browse to find the sample file on your PC.
5. Look for the Siemens folder and select the zip file.
PROFINET
7. The Siemens software extracts the sample archive and makes it available. 8. Reduced to the basics the process of reading and retrieving results consists of the following: 9. Define an area in your application to save read results. There are many options regarding how and where result data can be stored. For our example we define a Data Block (DB) which contains the fields of the Result Data module that we are interested in for our application.
11. Set the trigger signal and set semaphore to indicate a read is pending.
PROFINET
12. As soon as the trigger signal is acknowledged, clear the trigger signal.
13. As soon as the results are available save a copy of the result data and set the results acknowledge signal.
PROFINET
PROFINET
14. When the reader sees the result acknowledge signal clear result acknowledge, clear the read pending semaphore, and signal that the read process has completed. NOTE The reader clears Results Available as soon as it sees the PLCs Results Ack signal.
PROFINET
5. Look for the Siemens folder and select Dm200_SoftEvents.zip. 6. Select a destination directory to save the project on your PC.
7. The Siemens software extracts the sample archive and makes it available. Soft events are a means of invoking an activity by simply manipulating a single control bit. The activity for each bit is predefined (refer to the Soft Events section above for details). With the exception of Execute DMCC and Set Match String all soft events may be invoked in the same way. Execute DMCC and Set Match String require the added step of loading the User Data module with application data before invoking the event. Reduced to the basics the process of invoking a Soft Event consists of the following:
PROFINET
PROFINET
command strings that the copy function could reference by an index value. That would allow the user to pre-define all DMCC commands that are required by the application and invoke them simply by index.
The function Set User Data (FC11) simply copies the provided string to the User Data module. Refer to the example program for the actual STL code.
DMCC Overview
Depending on the DataMan reader you are using, the COM port connection can be either RS232 or USB and an Ethernet connection can be established through the Telnet protocol. By default, the DataMan reader is configured to communicate over TCP port number 23, but you can use the Setup Tool to assign a different port number as necessary.
Command Syntax
All DMCC commands are formed of a stream of ASCII printable characters with the following syntax: command-header command [arguments] footer For example: ||>trigger on\CR\LF
Header Examples
Example Description Default Header Header indicating no-checksum and ID of 123 Header indicating checksum after command and data.
Command
The command is an ASCII typable string possibly followed by data. All command names and public parameters data are case insensitive. Only a single command may be issued
Footer
The footer is a carriage return and linefeed (noted as \CR\LF or \r\n).
Reader Response
The reader will have one of several response formats. The choice of response format is configured using the SET COM.DMCC-RESPONSE command. NOTE While the reader can process a stream of DMCC commands, it is typically more robust to either wait for a response, or insert a delay between consecutive commands.
Silent: (Default) No response will be sent from the reader. Invalid commands are ignored without feedback. Command responses are sent in space delimited ASCII text without a header or footer. Extended: The reader responds with a header data footer block similar to the command format. ||checksum:command-id[status] checksum The response uses the same checksum format as the command sent to the reader. 0: no checksum 1: last byte before footer is XOR of bytes command-id The command-id sent to the reader is returned in the response header. status An integer in ASCII text format. 0: no error 1: reader initiated read-string
Examples
Command Silent Response Extended Response Description Is the DataMatrix symbology enabled? Enable the DataMatrix symbology. Trigger Command
ON
||[0]ON\r\n
no response
||[0]\r\n
namespace DataManSerialPort { public partial class Form1 : Form { System.IO.Ports.SerialPort _port; UpdateTextDelegate myDelegate; public Form1() { InitializeComponent(); myDelegate = new UpdateTextDelegate(UpdateText); }
textBoxPort buttonConnect
richTextBox1