0% found this document useful (0 votes)
5 views2 pages

Solis_Inverter_S5-GC(50-60)K_Datasheet_MYS_V1,5_202507

GINLONG TECHNOLOGIES CO., LTD. offers the S5-GC(50-60)K Solis Three Phase Grid-Tied Inverters, featuring high efficiency of 98.7%, multiple MPPTs, and advanced protection mechanisms including AFCI. The inverters come in two models, S5-GC50K and S5-GC60K, with specifications for input and output power, protection features, and operational conditions. Additional functionalities include intelligent monitoring, optional PID recovery, and compliance with various grid connection standards.

Uploaded by

prathlohi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
5 views2 pages

Solis_Inverter_S5-GC(50-60)K_Datasheet_MYS_V1,5_202507

GINLONG TECHNOLOGIES CO., LTD. offers the S5-GC(50-60)K Solis Three Phase Grid-Tied Inverters, featuring high efficiency of 98.7%, multiple MPPTs, and advanced protection mechanisms including AFCI. The inverters come in two models, S5-GC50K and S5-GC60K, with specifications for input and output power, protection features, and operational conditions. Additional functionalities include intelligent monitoring, optional PID recovery, and compliance with various grid connection standards.

Uploaded by

prathlohi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

GINLONG TECHNOLOGIES CO.,LTD.

S5-GC(50-60)K

Solis Three Phase Grid-Tied Inverters

Features:
• 5/6 MPPT, max. efficiency 98.7%

• Nighttime PID recovery function (optional)

• AFCI protection, proactively reduces fire risk

• Intelligent string monitoring, smart I-V curve scan

• 24-hour load consumption monitoring

• IP66, C5 Anti-Corrosion level

• Night SVG function

Models:
S5-GC50K / S5-GC60K

360º View
solisinverters.com/my

DATASHEET S5-GC(50-60)K

Models 50K 60K


Input DC
Max. input voltage 1100 V
Rated voltage 600 V
Start-up voltage 195 V
MPPT voltage range 180 - 1000 V
Max. input current 5 × 32 A 6 × 32 A
Max. short circuit current 5 × 40 A 6 × 40 A
MPPT number / Max. input strings number 5 / 10 6 / 12
Output AC
Rated output power 50 kW 60 kW
Max. apparent output power 55 kVA 66 kVA
Max. output power 55 kW 66 kW
Rated grid voltage 3/N/PE, 220 V / 380 V, 230 V / 400 V
Rated grid frequency 50 Hz / 60 Hz
Rated grid output current 76.0 A / 72.2 A 91.2 A / 86.6 A
Max. output current 83.6 A 100.3 A
Power factor > 0.99 (0.8 leading - 0.8 lagging)
THDi < 3%
Efficiency
Max. efficiency 98.7%
EU efficiency 98.3%
Protection
DC reverse-polarity protection Yes
Short circuit protection Yes
Output over current protection Yes
Surge protection DC Type II / AC Type II
Grid monitoring Yes
Anti-islanding protection Yes
Temperature protection Yes
Strings monitoring Yes
I/V Curve scanning Yes
Multi peak scan Yes
Integrated AFCI 2.0 Optional
Integrated PID recovery Optional (1)
Integrated DC switch Yes
General Data
Dimensions (W × H × D) 691 × 578 × 338 mm
Weight 53.7 kg
Topology Transformerless
Self-consumption (night) <1W
Operating ambient temperature range -25 ~ +60°C
Relative humidity 0 - 100%
Ingress protection IP66
Noise emission (typical) < 55 dB(A)
Cooling concept Intelligent fan-cooling
Max. operation altitude 4000 m
G99, VDE-AR-N 4105/VDE V 0124, EN 50549-1, VDE 0126/UTE C 15/VFR:2019, RD 1699/RD 244/UNE 206006/
Grid connection standard
UNE 206007-1, CEI 0-21, C10/11, NRS 097-2-1, EIFS 2018.2, IEC 62116, IEC 61727, IEC60068, IEC 61683, EN 50530
Safety / EMC standard IEC 62109-1/-2, IEC62116 & IEC 61000-6-1/-2/-3/-4
Features
DC connection MC4 connector
AC connection OT terminal (max. 70 mm²)
Display LCD
Communication RS485, USB, Optional: Wi-Fi, GPRS

(1) Due to the similar functional logic, when the night time PID-Recovery function is integrated, the night time var compensation function
can not be used. Also, the negative grounding option is not available for inverters with night time PID-Recovery function.