08-SA27 Capacitance Level Switch Operation Manual
08-SA27 Capacitance Level Switch Operation Manual
※ When there are materials or mixtures with multiple characteristics such as high/low dielectric and
conductive haracteristics simultaneously (for example; silica sand in the glass industry, etc), it must be SPECIAL CONDITIONS FOR SAFE USE OF PRODUCTS
tested on the site first, to etermine whether the sensor is suitable or not. If there still exists measuring 1.The user should contact the manufacturer directly if detailed information regarding the product is
problems, we suggest using our uning Fork Level Switch (SC) or Rotary Paddle Level Switch (SE). required.
2.If the product sensor bar is made of or coated with non-metallic materials, specific measures should
PANEL FUNCTION
be taken to prevent the danger of static electrical explosion.
70
60
50 40
30 SIGNAL 1. The safety parameters of the electrostatic capacitance level T6/T85℃ -20~+80
10
+
SENSIT VIT Y - No. High
T4/T135℃ -20~+130
● Power supply : maximum voltage Um : 250V
H L
Temperature Type
COARSE TIM E DELAY
NO C OM NC
AC100~240V
N L ● Supply voltage / Contact rating : T3/T200℃ -20~+195
clockwise to set up delay time. After delay time is set, when probe contacts with material, LED is
Connecting A B
turned on but the relay or PNP/NPN output will not be generated immediately until delay time is up.
Pipe 25mm M ax.
Delay time function is applicable for liquid tanks with agitator, or solid tanks which the medium will α
SA2 7A SA2 7F
300mm
300mm
200
N O C OM N C 0V 24V 0V O/P 0V 24V 0V O/P 0V 24V 0V
300mm 20
Load Load
24 Vdc 24Vdc
24Vdc
Fuse Fuse Fuse
*Fuse:400mA *Fuse:400mA
For top mounting, angle of repose It's recommended to install the When multiple switches are
SA2 7B SA2 7C SA2 7E must be considered when installation. switch away from material inlet to installed, keep at least 300mm
SA27 UL Type SA27 Wire Probe Model must be avoid damage. If switch must be distance for each switch.
installed min. 300mm from tank wall. installed near inlet area, a
SA27 Plate Model is applicable for protective cover must be placed
AC
100~240V
bottom mounting. 200mm on top of the switch.
NO COM NC N L NO COM N C 0V 24V
100~ 24Vdc
Fuse 240V
Fuse
SA2 7M SA2 7N
Cable entry must face down firmly Top mounting is recommended Switches with delay time function
Load
Load
24Vdc 24Vdc locked to avoid rain damage. for medium with poor flowability is recommended for tank with
Fuse
to avoid medium build up. agitator to advoid false action.
Fuse
*Fuse:400mA *Fuse:400mA
SA2 7P SA2 7Q
CALIBRATION (ROTARY KNOB)
INITIAL CALIBRATION
1. After installation with power supply, make sure no material within 300 mm around the probe.
2. Turn the "SENSITIVITY" to the "H" position (Figure 2).
3. Using flat-head screwdriver to turn "Coarse" clockwisely for adjustment until LED indicator is on.
4. Turn the knob clockwise from H position to 90% position about 1/2 circle (95% position) until LED
indicator shut off (Figure 3). Then, Initial calibration is complete. After that, please continue to next
step "SENSITIVITY ADJUSTMENT".
SENSITIVITY ADJUSTMENT
1. Make sure the "Indicator" sign does not light up, when the medium does not contact with the probe,
and vice versa, when the medium contacts or covers the probe, then the "Indicator" sign lights up.
2. Gradually, adjust the capacitance value (turn the knob clockwise to the "L" direction) until "Indicator"
light turns off.
3. Record the turning angle from "Indicator" sign lights up status to turn off status, then reset "SENSI
TIVITY ADJ" by turning the knob counterclockwise back for half of the recorded turning angle.
4. Based on the previous experience, 70% (Figure 4) adjustment position can be used to most of
mediums (Need to do INITIAL CALIBRATION first).
50 4 50 4 60 50 40
60 0 60 0
30
30 30 70
70 70
80
80
80
20
2
2
0
0
90
90
90
10
10
10
H L H L H L
Seal ring aged & failed Seal ring aged Replace seal ring
Cable entry is not firmly locked Cable entry is not firmly locked Lock the cable entry firmly
Water get into
housing Cable entry does not face down Cable entry faces up Turn the cable entry & face down
Cable wire does not connected Cable wire is connected upward
downward Connect the cable downward
Diameter of cable wire does not fit Cable wire is loose Replace cable with diameter 8mm~10mm
Sensivity Adjustment knob Position of Sensivity Adjustment Re-adjust sensivity
is activated by mistake knob is abnormal
Level up & down but False wiring of power & signal cable False wiring of power & signal cable Re-wiring according to wiring guide
switch / relay no response Circuit damaged by EMI Dry powder or high speed frictioin Replace with anti-static model
Dielectric constant of medium Continuous action when Contact your local business representative.
is too small. coarse or fine adjustment
Humidity inside tank is over limit Probe with water or dew Replace probe with coating
Level up & down but
switch on/off Probe contacts with tank wall Probe contacts with tank wall Re-install and avoid grounding
continuously
non-stop or relay Circuit damaged by EMI Dry powder or high speed frictioin Replace with anti-static model
can't be reset Continuous action when
Dielectric constant is over limit Contact your local business representative.
coarse or fine adjustment
Wiring terminals are loose Loose screw bolt Lock screw bolt firmly
Process connection is not Lock thread or flange firmly
Loose thread
firmly locked
Unstable switch signal. Short-circuit due to aging Idle loop, resistance abnormal Revise external layout
Abnormal of supply voltage Supply voltage over limit Restore power supply
Loose structure due to vibration Obvious vibration environment Replace with remote model
F i n e Te k C o . , L t d .
No.16, Tzuchiang St., Tucheng Industrial Park, New Taipei City 23678, Taiwan.
Te l: 8 8 6 -2 -2 2 6 9 6 7 8 9 F a x: 8 8 6 -2 -2 2 6 8 6 6 8 2
Em a il: in f o @ f in e -t e k. co m h t t p : / / w w w. f in e -t e k. co m 08-SA27-B11-EM,09/03/2024