Boq Electrical Amcc

The document outlines the Bill of Quantities (BOQ) for the electrical system of a 5000kVA substation project in Chittagong, detailing the equipment, specifications, and quantities required for installation and commissioning. It includes sections on high-tension switchgear, low-tension switchgear, power factor improvement plants, and a distribution transformer, along with their respective technical specifications. Additionally, it mentions installation accessories and safety measures necessary for the project.

Uploaded by

Avijit Sarkar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
10 views14 pages

Boq Electrical Amcc

The document outlines the Bill of Quantities (BOQ) for the electrical system of a 5000kVA substation project in Chittagong, detailing the equipment, specifications, and quantities required for installation and commissioning. It includes sections on high-tension switchgear, low-tension switchgear, power factor improvement plants, and a distribution transformer, along with their respective technical specifications. Additionally, it mentions installation accessories and safety measures necessary for the project.

Uploaded by

Avijit Sarkar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 14

Client:

Project: AMCC
Location: Chittagong
Date: 03.06.2025 AMCC
Title: BOQ - Electrical System (Substation)
Rev No. :

Rv. Date:

Schedule for Supply, installation, load sunction and commissioning of 5000kVA Sub-station
Rate
Sl. Items Unit Qty Amount (BDT)
(BDT)

A: 5000KVA Substation equipments


1.00 HT Switchgear With VCB. (Fixed Type) sets 1

VCB:

11 KV H.T Switch Gear with VCB. Fixed Type –


1 No. 630A, 11 KV, breaking current 25KA (3 sec.),
making current 65KA, 50/60Hz, TP Fixed Type Vacuum
Circuit Breaker with motor operated mechanism with
closing solenoid shunt releases, auxiliary contacts
5NO+5NC and limit switch (1NO+1NC) for indication
“Closing spring charged” mechanical on/off/trip indicator.

Voltage Transformer:

3 Nos. - 11 KV, cast resin insulated, single pole, potential


transformer (PT) having ratio 11000/110V (open delta connection)
burden 100VA, class 0.5 for Metering & Protection.

Current Transformer:
3 Nos. - Cast resin insulated, 11KV dry type double core current
transformer (CT) having ratio 100/5/5A, for metering & protection.

1st core : 10VA, class 0.5 for metering.

2nd core : 15VA, class 10P10 for protection

Protection Relay:

1 No. - Triple pole, induction type microprocessor operated IDMT


relay with adjustable minimum time setting for over current, short
circuit & earth fault protection.

Meter & Switches:


1 Set- Voltmeter having scale 0-15KV with 3- way selector switch.

1 Set- Ammeter having scale 0-60A with 3-way selector switch.

Miniature Circuit Breaker:


1 No- MCB 6A, 3P, 10KA, 415V AC for PT secondary protection.
1 No- MCB 6A, 2P 10KA, 415V AC for control circuit protection.
Aux. Relay, Timer And Indicating Light:
3 Nos.- Auxiliary Relay 110V DC

1 No- Solid state Timer Relay 110V DC

8 Nos. - R.Y.B Phase indications, CB On/Off, IDMT Trip, Pressure Trip


& Temperature Trip Indicating Light.

Miscellaneous:
1 No- Anti condensation heater.

1 No- Thermostat 250V AC

1
Rate
Sl. Items Unit Qty Amount (BDT)
(BDT)
1 No- Neutral Link-VT Protection

3 Nos.- Capacitive Voltage Measuring Socket

1 No- Capacitive Voltage Measuring Terminal.

1 No- Temperature Alarms & Tripping Circuits.

1 No- Set of 630A main Bus bar.

HT Cable (Approximate):
As per site
HT Cable XLPE (3CX1X300mm2) (Pole To PDB Metering
1.01 Mtr. 100 measureme
Panel)
nt
HT Cable XLPE (3CX1X300mm2) (PDB Metering Panel To
1.02 Mtr. 25
Transformer HT Bushing)

2.00 8000A LT Switchgear: set 1


14/16 SWG Sheet steel fabricated Floor mounting, tropical zed
design, indoor type for 3 Phase, 4 Wire, 50/60 Hz, 380/415V AC
system 8000A LT Panel with ATS, with necessary Full Dust &
Vermin Proof powder coated painting and shall be supplied
completely with 150mm X 12mm X 3=5400mm2 X
2A=10800A TPN & 125mm X 12mm X 2A=3000A E
Electrolytic hard down copper bus bars of suitable size and
properly insulated arrange to withstand & short current of 50KA
for 1 sec.

Equipments within the panel board:


Incoming:
Air Circuit Breaker (ACB) (Fixed Type),- Motorized with
microprocessor based multi-function protective device with
Motor operating mechanism & stored energy feature, with UVT
& Key Lock auxiliary contact 4No+4Nc with LED Display.

Breaking Capacity: 85KA, 3P, 400V, AC


LT Panel BUSBAR (PHASE)-150X12X3 (Double BUSBAR)-
10800 A
LT Panel BUSBAR (NEUTRAL)-150X12X3 (Double BUSBAR)-10800 A
LT Panel BUSBAR (EARTHING)-125X12X2 (Single BUSBAR)-5400 A
Push Button Switch (Start & Stop)
Type: AR22FOR-10G/01R
Digital Voltmeter with Selector
Model No. DVM360-240V
Features:
Built-in selector switch, Auxiliary supply : 198~265 VAC
Easy to read,14.2 mm digit display, VA Rating : 3 VA
Input frequency : 50 Hz
Maximum input voltage : 500 Vrms
DIN size casing.
Digital Ammeter with Selector
Model No. DAM 3000 (5000/5A)
Features:
Built-in selector switch, Auxiliary supply : 198~265 VAC
Easy to read,14.2 mm digit display, VA Rating : 3 VA
Input frequency : 50 Hz
Maximum input : 6 A continuous
Ammeter CT ratio: 5000/5A, Class :1.0
DIN size casing.
Current Transformer (Ratio: 8000/5A)
Indication Lamp (X-mer. type)
Type: DR22DOL-Q4G/Y/R
Control Fuse with carrier
Industrial Relay
Type: SH4 (2NO+2NC)
Super Timer with base
Type: MS4S A-AP,0.5-60s,100-240V AC
Auto/Manual selector switch
Type: AR22PR-311B

2
Rate
Sl. Items Unit Qty Amount (BDT)
(BDT)
Incoming For PFI:

Air Circuit Breaker (Fixed Type), -Motorized with


microprocessor based multi-function protective device with
Motor operating mechanism & stored energy feature, with
auxiliary contact 4No+4Nc, with LED Digital Display.

Outgoing For BBT:


Air Circuit Breaker (Fixed Type),- Motorized with
microprocessor based multi-function protective device with
Motor operating mechanism & stored energy feature, with
auxiliary contact 4No+4Nc with LED Display.

Type: BT3-4000P/3 4000E, 8000A, 3P, 440V, 50/60HZ

Thermal Adjustable Setting Range-1600-8000A


Breaking Capacity: 85KA, 3P, 400V, AC
Outgoing For DB (Utility):
Adjustable Moulded Case Circuit Breaker with thermal &
Magnetic standard protection tripping unit.
Type: E250 SJ -3P (MCCB), 250A, 25KA, 400V AC.
Adjustable Setting Range:160-250A
Outgoing For Spare:
Adjustable Moulded Case Circuit Breaker with thermal &
Magnetic standard protection tripping unit.
Type: E250 SJ -3P (MCCB), 250A, 25KA, 400V AC.
Adjustable Setting Range:160-250A
Outgoing For Fire System:
Adjustable Moulded Case Circuit Breaker with thermal &
Magnetic standard protection tripping unit.
Type: S160 SCJ-3P (MCCB), 88A, 25KA, 400V AC.
Adjustable Setting Range:63-100A
Outgoing For Spare:
Adjustable Moulded Case Circuit Breaker with thermal &
Magnetic standard protection tripping unit.
Type: S160 SCJ-3P (MCCB), 100A, 25KA, 400V AC.
Adjustable Setting Range:63-100A
Cooling Fan with Dust net 6”
2.01 Wiring cable, cable socket &other accessories
2.03 Enclosure (Adequate Size.)-Powder Coated.
2.04 Working Charge
Others will be as per attached Technical Specification
Sheet
3.00 3000 KVAR AUTO/ MANUAL PFI PLANT set 1
14/16 SWG Sheet steel fabricated Floor mounting, tropical zed
design, indoor type for 3 Phase, 4 Wire, 50/60 Hz, 380/415V AC
system 3000kVAR PFI Panel, with necessary Full Dust &
Vermin Proof powder coated painting and shall be supplied
completely with 125mm X 12mm X 2=3000mm2 X 2A=
6000A TPN+ 50% E Electrolytic hard down copper bus bars of
suitable size and properly insulated arrange to withstand &
short current of 50KA for 1 sec.

Equipments within the panel board


50KVAR (25x2) FIXED 415V, 3 Phase, 50Hz, dry type, self-
healing compact Capacitor Bank with discharge resistor.

50KVAR (25x2) 415V, 3 Phase, 50Hz, dry type, self-healing


compact Capacitor Bank with discharge resistor.

100KVAR (25X4) 415V, 3 Phase, 50Hz, dry type, self-healing


compact Capacitor Bank with discharge resistor.
200KVAR (25X8) 415V, 3 Phase, 50Hz, dry type, self-healing
compact Capacitor Bank with discharge resistor.

3
Rate
Sl. Items Unit Qty Amount (BDT)
(BDT)
16 Stage reactive power factor control relay which perform the
switching of capacitor in automatic power connection
equipment depending on changing Reactive Power complete
with Luminescent Indicator and Digital Power Factor meter.
Model : NV-14s (144mmx144mm)– 14 Steps

80A, Magnetic contactor Type: SC-N4-2A+2B, 415V, 50Hz Coil:


220VAC suitable for 50KVAR Capacitor bank. Electrical Life
(Operation): 1.5 million/Above

180A, Magnetic contactor,


Type: SC-N8-2A+2B, 415V, 50Hz Coil: 220VAC suitable for
100KVAR Capacitor bank.
Electrical Life (Operation): 1.5 million/Above

400A, Magnetic contactor,


Type: SC-N12-2A+2B, 415V, 50Hz Coil: 220VAC suitable for
200KVAR Capacitor bank.
Electrical Life (Operation): 1.5 million/Above

100A MCCB for 50KVAR Capacitor


Molded Case Circuit Breaker (MCCB) with thermal &
Magnetic standard protection trip unit.
Current Rating:100A
Breaking Capacity:10KA
Type: BW100EAG, 3P, 415V, 50/60Hz

200A MCCB for 100KVAR Capacitor


Molded Case Circuit Breaker (MCCB) with thermal &
Magnetic standard protection trip unit.
Current Rating:200A
Breaking Capacity:18KA
Type: BW253EO/BW250EAG, 3P, 415V, 50/60Hz.

400A MCCB for 200KVAR Capacitor


Molded Case Circuit Breaker (MCCB) with thermal &
Magnetic standard protection trip unit.
Current Rating:400A
Breaking Capacity:30KA
Type: BW 400EAG, 3P, 415V, 50/60Hz.

Push button switch,


Type: AR22 FOR 10G (START) &
AR22 FOR 01R (STOP)

Signal lamp (X-mer Type) for Run indicator


Type: DR22 DOL Q4G. 220V, 50 Hz.
Auto/Manual selector switch
Type: AR22PR311B
Industrial Relay (4NO + 4NC)
Type: SH4, 10A, 220V with
Auxiliary Contact
Type: SZ- A22 (2NO + 2NC)

Modular fuse
Current transformer (4000/5A)
Cooling Fan 6’’
80mm X 10mm X 2=1600mm2 X 2A= 3200A TPN+ 50% E
Copper bus bar of adequate rating, suitable Size and Properly
Insulated
3.01 Enclosure (Adequate Size)- POWDER COATING
3.02 Cable, cable socket, cable ties and other Necessary Accessories
3.03 Working Charge
PRELIMINARIES, INSTALLATION, TESTING &
4.00 job 1
COMMISSIONING
4.01 Insurance
4.02 Protection for Worker
4.03 Installation of Substation
4.04 Installation of BBT, Tap off Box and Distribution

4
Rate
Sl. Items Unit Qty Amount (BDT)
(BDT)
4.05 Testing & Commisioning

TOTAL OF SECTION A=

B: 5000 KVA DISTRIBUTION TRANSFORMER


5.00 5000 KVA Dry Type Distribution Transformer set 1

The Transformer are designed and manufactured in accordance


with the IEC-60076 Standard. It is 3 Phase, dry type, naturally
air cooled Transformer. 3 HT & 4 LT Bushings, conservators are
arranged on tank top Cover. Transformer is also fitted with oil
level indicator, drain and filling valves, lifting lugs, rollers etc.
New Fresh dried PCB free mineral oil of high dielectric strength
will be filled in the Transformer.

SPECIFICATION OF 5000 KVA TRANSFORMER


Standard : IEC-60076
Rated Capacity : 5000 KVA
Rated Voltage at No Load : 11000/415/240 V
Rated Frequency : 50Hz
No. of Phase : Three
Cooling Type : ONAN
Vector Group : DYn-11
Installation : Indoor/ Out door
Tap Change : Off Load, Manual Type
Rated Tapings : +2.5%, 0 ,-2.5% ,-5%,-7.5% of rated KV
Impedance : 6%
No Load Loss :6500Watt
Load Loss at 750C :38000Watt
Ambient Temperature : 400C
Temperature Rise:
In Oil : 600C
In Winding : 650C
BIL (For HV) : 75KV

5.01 12.7 mm Solid Copper for Frame Earthing (X-Former)


5.02 12.7 mm Solid Copper for Body Earthing(X-Former)
5.03 12.7 mm Solid Copper for Neutral Earthing(X-Former)
5.05 Transformer Room Fencing
5.06 Transformer Base (Civil Work)
LT Cable NYY=(10X4X1C-800mm2)(TPN)
5X1C-800mm2 for ECC.
5.08 OR 8000 A Portable Busbar(TPN) (Tx to LT)

TOTAL OF SECTION B=

C: INSTALLATION ACCESSORIES AND DOWN THING EARTHING


6.0 11 KV DROP-OUT FUSE set 1

Technical specification of 11KV Drop-out Fuse:


Rated Voltage (Nominal) : 11 KV
Rated Maximum Voltage : 15 KV
Rated Frequency : 50 Hz
BIL : 75 KV
Rated Current RMS : 300A
Interrupting Current RMS : 10 KA
Withstand Test Voltage
Dry, 1 Min : 35 KV
Wet, 10 Sec : 30 KV

7.0 11KV LIGHTNING ARRESTOR set 1

5
Rate
Sl. Items Unit Qty Amount (BDT)
(BDT)
Technical specification of 11 KV Lightning Arrestor:
Rated Voltage (RMS) : 9 KV
Rated System Voltage : 12 KV
Rated Frequency : 50 Hz
Minimum Spark Over (RMS) :14 KV
Maximum Spark Over (RMS) :40 KV
Maximum Impulse Spark(Crest):45 KV
Withstand Test Voltage
Dry, 1 Min : 28 KV
Wet, 10 Sec : 24 KV
Discharge 33 KV (Crest) : 5 KA
Impulse Current withstand : 55 KA

8.00 Sub-Station Earthing Boring including Earth pit set 8


8.01 X-Former
8.02 LT & PFI panel
8.03 HT Switchgear Panel
8.04 PDB Metering Panel
9.0 Heat shrink kit /Termination Kits. nos 6
10.0 Cross Arm nos 1
11.0 Pole Band/ Clam set 2
12.0 PG Clamp for 11KV Conductor nos 6
13.0 PIB Tape & PVC Tape L/S -
14.0 Cable Stand nos 2
15.0 Cable tie, Cable Socket, Cable Shoe etc. L/S -
TOTAL OF SECTION C=

D: ELB PERMISSION:
Charge of approval from Bangladesh Electric
16.0 job 1
Licensing Board for PDB connection.
TOTAL OF SECTION D=

E: LOAD SANCTION
N.B.: This cost can bear by client if want.
17.0 Government demand note fee./ Bank fee kw 2400
CT, PT, HT energy meter & accessories govt.
18.0 job 1
deposit/Bank fee
19.0 Government estimation fee /Bank fee job 1
PDB load sanction purpose file formalities cost.
20.0 (Miscellaneous Cost/ Speed Money) kw 2400

21.0 HT meter, CT, PT, sanction and carrying from Dhaka job 1
22.0 CT, PT, HT meter wiring charge. job 1
23.0 Energy audit team fees L/S -
HT cable lying, Drop out fuse, Lighting Arrester,
24.0 job 1
Cross Arm fitting& Installation.
25.0 Metering Panel (PDB) nos 1

TOTAL OF SECTION E=

GRAND TOTAL OF ALL SECTION= -

6
Client:

Project: AMCC
Location Chittagong
:
Date: 03.06.2025 AMCC
Title: BOQ - Electrical System (Generator)
Rev No. :
Rv.
Date:
Schedule for Supply, installation, and commissioning of 3x2000kVA Generator Set

Sl. Items Unit Qty Rate (BDT) Amount (BDT)

A: Diesel Generator Set


1.00 Generator Control Module Nos 3
General Specification:

A. Shutdowns & Protections:


1.Low Oil Pressure Shutdown
2.High Engine Temperature Shutdown
3.Under / Over Voltage Warning /Shutdown
4.Over Speed / Over Frequency
5.Under Speed / Under Frequency
6.Over Crank / Fail To Start Alarm
7.Over Current Alarms

B. Monitoring & Control:


1.Manual & Automatic Modes
2.Three Phase Voltage Monitoring
3.Three Phase Current Monitoring
4.Frequency Monitoring
5.Start, Crank, Crank Rest, Warm Up Timers
6.Return & Cool Down Timers
7.Battery Under / Over Voltage Alarms
8.Exercise Scheduler

2.00 Synchronizing Control Panel Nos 1


General Specification:

Continuous Voltage Rating: 8 V to 35 V continuous


Voltage Range: 15 V to 333 V AC (L-N)
Frequency Range: 3.5 Hz to 75 Hz
Minimum Load Impedance: 1000Ω (Fully isolated)
Gain Voltage: 0 V to 10 V DC (Fully isolated)
Offset Voltage: +/- 10 V DC (Fully isolated)
Built-in AVR Control.

3.00 5000A Auto Transfer Switch (ATS) Nos 2

B: Installation Accessories
4.00 3200A TP ACB (Adj.) Nos 3
5.00 Copper Wire Lot 1
12.7 mm Solid Copper for Frame Earthing (Generator)
12.7 mm Solid Copper for Body Earthing(Generator)
12.7 mm Solid Copper for Neutral Earthing(Generator)
6.00 Earthing Boring System (Generator) Nos 9

Earthling for grounding & neutral, 100 feet depth with 4SWG CU
wire and 40mm dia GI pipe 10 feet

7.00 2A Fuse Nos 9


8.00 Indicating Lamp (RYB) (3X3) Nos 9
9.00 Digital AVO Meter Nos 3
10.00 Power Cable (Approximate) Meter 45
5000A PORTABLE BUSBAR(TPN)-FOR GENERATOR

11.00 Other accessories for wiring Lot 1


12.00 Foundation for 2000 kVA DG set (Civil Work) Job 3
13.00 Testing & Commissioning Job 1

TOTAL AMOUNT=
Client:
Project: AMCC
Location
: Cumilla
Date: 03.06.2025 AMCC
Title: BOQ - Electrical System (Internal Electrification)
Rev No. :
Rv.
Date:
Schedule for Supply, installation, and commissioning of internal electrical system
Rate
Sl. Items Unit Qty Amount (BDT)
(BDT)

A: INTERNAL ELECTRICAL ESTIMATED BOQ

1.00 Round Ceiling Light with Holder nos 750

2.00 Concealed Type Panel Light with Holder nos 820

3.00 Mirror Light with Holder nos 50

4.00 LED Tube Light with Holder nos 50

5.00 Squire Type Surface Panel Light nos 120

6.00 Wall Light with Holder nos 60

7.00 Ceiling Mounted Light with Holder nos 40

8.00 Wall Washer Light nos 70

9.00 SCONCE LIGHT IP65 STAR LAMP nos 15


10.00 CF- CEILING FAN nos 30
11.00 CFR- CEILING FAN DIMMER nos 30
12.00 GARDEN LIGHT nos
13.00 12" EXF- EXHAUST FAN POINTS SINGLE PHASE nos 90
14.00 SECURITY BOUNDARY LIGHT (30 W) POINTS nos
3PIN-13A SOCKET AT SKIRTING LEVEL OR 10" HEIGHT
15.00 nos 480
FROM FINISHED FLOOR

16.00 3PIN-15A SOCKET AT 7’-6’’ HEIGHT FROM FINISHED FLOOR nos 90

17.00 2PIN-10A SOCKET AT 54" HEIGHT FROM FINISHED FLOOR nos 180
18.00 CENTRIFUGAL PUMP POWER SOCKET BOARD WITH MOTOR nos 4

SUBMERSIBLE WATER PUMP WITH PUMP POWER SOCKET


19.00 nos 1
BOARD

20.00 SUMP PUMP POWER SOCKET BOARD WITH MOTOR nos 6


21.00 WTP PUMP POWER SOCKET BOARD WITH MOTOR nos 1
22.00 ETP PUMP POWER SOCKET BOARD WITH MOTOR nos 1

CENTRAL GEYSER PUMP POWER SOCKET BOARD WITH


23.00 nos 1
MOTOR

24.00 1 GANG MK STEEL BOX nos 150


25.00 2 GANG MK STEEL BOX nos 200
26.00 3 GANG MK STEEL BOX nos 170
27.00 4 GANG MK STEEL BOX nos 220
28.00 1 GANG SWITCH BOARD nos 150
29.00 2 GANG SWITCH BOARD nos 200
30.00 3 GANG SWITCH BOARD nos 170
31.00 4 GANG SWITCH BOARD nos 220
32.00 NETWORK SOCKET nos 150
33.00 ANTENNA SOCKET nos 40
34.00 TELEPHONE OUTLET nos 150
35.00 INTERCOM OUTLET nos 100

B: DISTRIBUTION BOARD (SDB/MDB/EMDB/ DB-UTLITY/FDB)

MDB- MAIN DISTRIBUTION BOARD (INCLUDING


nos 2
ACCESSORIES)

36.00
Accessories: Heat Shrink Bus Bar, Bus Bar Supporter, SS
Nutbolt, Seal Tube, Powder Coat Paint, Digital AVO-meter,
100/5V C.T for Bus Bar, Cooling Fan, SS Lock,
Ebonite/Transparent Sheet for Busbar, Indicating Lamp,
36.00 SDB Box 18SWG GP Sheet, Rubber Gland for door & Rubber
Cascaded, Wall Mounted attached with Angle.
Type-1: 24+24 way TP&N (4 pcs)
Dimension: 52" x 36" x 8" (H x W x D)

FDB- FLOOR DISTRIBUTION BOARD (INCLUDING


nos 6
ACCESSORIES)
Accessories: Heat Shrink Bus Bar, Bus Bar Supporter, SS
Nutbolt, Seal Tube, Powder Coat Paint, Digital AVO-meter,
100/5V C.T for Bus Bar, Cooling Fan, SS Lock,
Ebonite/Transparent Sheet for Busbar, Indicating Lamp,
SDB Box 18SWG GP Sheet, Rubber Gland for door & Rubber
Cascaded, Wall Mounted attached with Angle.
Type-1: 24+24 way TP&N (4 pcs)
37.00
Dimension: 52" x 36" x 8" (H x W x D)
Type-2: 12+12 way TP&N (2pcs)
Dimension: 44" x 36" x 8" (H x W x D)
Type-3: 8+8 way TP&N (1pcs)
Dimension: 38" x 32" x 8" (H x W x D)
Type-4: 10+10 way TP&N (1pcs)
Dimension: 44" x 36" x 8" (H x W x D)

SDB-SUB DISTRIBUTION BOARD (INCLUDING


nos 49
ACCESSORIES)
Accessories: Heat Shrink Bus Bar, Bus Bar Supporter, SS
Nutbolt, Seal Tube, Powder Coat Paint, Digital AVO-meter,
100/5V C.T for Bus Bar, SS Lock, Ebonite/Transparent Sheet
for Busbar, Indicating Lamp, SDB Box 18SWG GP Sheet,
Rubber Gland for door & Rubber Cascaded.
38.00 Type-1 (15 pcs): 12" x 18" x5" (H x W x D)
BUS BAR SIZE(LXWXT)
8’’X0.75’’X3mm.
Type-2 (8 pcs) : 18" x 30" x 8" (H x W x D)
BUS BAR SIZE 14’’X1.25’’X4mm

UTILITY DB- DISTRIBUTION BOARD (INCLUDING


39.00 nos 1
ACCESSORIES)
40.00 DB-DISTRIBUTION BOARD FOR FIRE SAFETY SYSTEM nos 1
41.00 DB-DISTRIBUTION BOARD FOR EMERGENCY SYSTEM nos 1
42.00 ELEVATION & BOUNDARY LIGHTING CONTROL PANEL nos 1
LOW VOLTAGE JUNCTION BOARD (INCLUDING
ACCESSORIES)
43.00 nos 16
DB SIZE (LXWXD)(20’’X18’’X6’’)
BUS BAR SIZE(L X W X T) 12"X0.75’’X3mm

C: POWER CABLE & BBT


44.00 BYA 1CX1X1.5 mm2 RED CABLE meter 15000
45.00 BYA 1CX1X1.5 mm2 BLACK CABLE meter 15000
46.00 BYA 1CX1X2.5 mm2 RED CABLE meter 12000
47.00 BYA 1CX1X2.5 mm2 BLACK CABLE meter 12000
48.00 BYA 1CX1X4 mm2 RED CABLE meter 600
49.00 BYA 1CX1X4 mm2 BLACK CABLE meter 600
50.00 BYA 1CX1X4 mm2 BLUE CABLE meter 600
51.00 BYA 1CX1X4 mm2 YELLOW CABLE meter 600
52.00 BYA 1CX1X4 mm2 GREEN ECC CABLE meter 600
53.00 BYA 1CX1X6 mm2 RED CABLE meter 2500
54.00 BYA 1CX1X6 mm2 BLACK CABLE meter 2500
55.00 BYA 1CX1X6 mm2 BLUE CABLE meter 2500
56.00 BYA 1CX1X6 mm2 YELLOW CABLE meter 2500
57.00 BYA 1CX1X6 mm2 GREEN ECC CABLE meter 2500
58.00 BYA 1CX1X10 mm2 RED CABLE meter 2200
59.00 BYA 1CX1X10 mm2 BLACK CABLE meter 2200
60.00 BYA 1CX1X10 mm2 BLUE CABLE meter 2200
61.00 BYA 1CX1X10 mm2 YELLOW CABLE meter 2200
62.00 BYA 1CX1X10 mm2 GREEN ECC CABLE meter 2200
63.00 NYY 1CX1X 16 mm2 (TPN) meter 1400
64.00 NYY 1CX1X 16 mm2 (ECC) meter 1400
65.00 NYY 1CX1X 25 mm2 (TPN) meter 500
66.00 NYY 1CX1X 16 mm2 (ECC) meter 500
67.00 NYY 1CX1X 35 mm2 (TPN) meter 450
68.00 NYY 1CX1X 16 mm2 (ECC) meter 450
69.00 NYY 1CX2X4X 50 mm2 (TPN) meter 400
70.00 NYY 1CX1X 50 mm2 (TPN) meter 400
71.00 NYY 1CX1X 50 mm2 (TPN) meter 400
72.00 NYY 1CX1X 25 mm2 (ECC) meter 400
73.00 NYY 1CX4X2X 70 mm2 (TPN) meter 900
74.00 NYY 1CX1X 70 mm2 (TPN) meter 900
75.00 NYY 1CX1X 70 mm2 (TPN) meter 900
76.00 NYY 1CX1X 35 mm2 (ECC) meter 900
77.00 NYY 1CX4X2X 95 mm2 (TPN) meter 300
78.00 NYY 1CX1X 95 mm2 (TPN) meter 300
79.00 NYY 1CX1X 95 mm2 (TPN) meter 300
80.00 NYY 1CX1X 50 mm2 (ECC) meter 300
81.00 NYY 1CX4X3X 300 mm2 (TPN) meter 50
82.00 NYY 1CX2X 185 mm2 (ECC) meter 50
83.00 Busbar Tracking (BBT)
84.00 8000A meter 30
85.00 4000A meter 230
86.00 Tap of Box
87.00 4000A Each 12
88.00 1000A Each 1
89.00 1250A Each 1
90.00 350A Each 1
91.00 400A Each 2
92.00 OTHER ACCESSORIES Job

D: PROTECTIVE CIRCUIT BREAKER


93.00 6 APMS SP MCB nos 201
94.00 10 APMS SP MCB nos 48
95.00 16 APMS SP MCB nos 138
96.00 20 APMS SP MCB nos 2
97.00 25 APMS SP MCB nos 6
98.00 50 APMS SP MCB nos 1
99.00 10 APMS TP MCCB nos 19
100.00 16 APMS TP MCCB nos 15
101.00 20 APMS TP MCCB nos 5
102.00 25 APMS TP MCCB nos 7
103.00 32 APMS TP MCCB nos 14
104.00 40 APMS TP MCCB nos 2
105.00 50 APMS TP MCCB nos 1
106.00 63 APMS TP MCCB nos 2
107.00 100APMS TP MCCB nos 1
108.00 125APMS TP MCCB nos 6
109.00 200APMS TP MCCB nos 6
110.00 250APMS TP MCCB nos 6
111.00 300APMS TP MCCB nos 5
112.00 350APMS TP MCCB nos 2
113.00 400APMS TP MCCB nos 2
114.00 500APMS TP MCCB nos 1
115.00 1250APMS TP MCCB nos 1
116.00 4000APMS TP ACB nos 2

E: ELECTRICAL FITTINGS ACCESSORIES


117.00 PVC PIPE (3/4’’) feet
118.00 PVC BEND (3/4’’) dozen
119.00 PVC SOCKET (3/4’’) dozen
120.00 PVC CLUMP (3/4’’) dozen
121.00 PVC TEE (3/4’’) dozen
122.00 CABLE LUX (2.5 RM) dozen
123.00 CABLE LUX (4 RM) dozen
124.00 CABLE LUX (6 RM) dozen
125.00 CABLE LUX ( 10 RM) dozen
126.00 CABLE LUX ( 16 RM) dozen
127.00 CABLE LUX ( 25 RM) dozen
128.00 CABLE LUX ( 35 RM) dozen

Lot
129.00 CABLE LUX ( 50 RM) dozen
130.00 CABLE LUX ( 70 RM) dozen
131.00 CABLE LUX ( 120 RM) dozen Lot
132.00 PVC PIPE (1’’) feet
133.00 PVC BEND (1’’) dozen
134.00 PVC SOCKET (1’’) dozen
135.00 PVC TEE (1’’) dozen
136.00 1’’ STAR SCREW packet
137.00 PVC TAPE (R+Y+B+B+G) nos
138.00 CABLE TRAY (8’’X4’’)-18 SWG meter
139.00 CABLE TRAY (4’’X2’’)-18 SWG meter
140.00 CABLE TRAY JOINT SOCKET nos
141.00 3’ ANGLE ROD FOR CABLE TRAY nos
142.00 ROYAL PLUG Packet
143.00 OTHER ACCESSORIES Job

F: Installation, Testing and Commissioning Lot

GRAND TOTAL OF ALL SECTION= -


Client:

Project: AMCC
Locatio Chittagong
n:
Date: 03.06.2025 AMCC
Title: BOQ - Electrical System (Lift)
Rev No.
:
Rv.
Date:
Schedule for Supply, installation, and commissioning of Lift System
Rate
Sl. Items Unit Qty Amount (BDT)
(BDT)
Supply of following lift complete with car, BMS compatible
control panel, traction machine (permanent magnet
synchronous motor), gearless, oil-free, steel suspension
ropes, safety devices, guide rails, push buttons, with other
necessaryaccessories etc. Complete including counter
weight as required. Suitable for installation & use in
tropical country like Bangladesh (considering ambient
temperature from 0ºC to 46ºC and relative humidity from
40% to 98%)

1.00 STRETCHER LIFT-1350 KG Nos 8

2.00 SERVICE LIFT- 1350 KG Nos 4

2.00 PASSENGER LIFT- 1350 KG Nos 4

Total Amount=
Client:

Project: AMCC
Locatio Chittagong
n:
Date: 03.06.2025 AMCC
Title: BOQ - Electrical System (LPS)
Rev No.
:
Rv.
Date:
Schedule for Supply, installation, and commissioning of Lightning Protection System
Rate
Sl. Items Unit Qty Amount (BDT)
(BDT)
1.00 Air Terminal-24 Inch Nos 49
2.00 Main & Down Conductor-10x3 mm Feet 1600
3.00 Ground Terminal & Inspection Pit Nos 13
4.00 Conductor Fasteners Nos 745
5.00 Loop Conductor 30 sqmm Bare Cu. Wire Feet 2000
6.00 Other Accessories Lot 1
7.00 Installation, Testing & Commissioning Job 1
Total Amount=