XQ1475 Spec Sheet

The Cat® XQ1475G Rental Generator Set provides a continuous power output of 1475 kW with switchable 50/60 Hz capabilities, featuring a Cat G3516C gas engine and advanced monitoring systems. It is designed for efficiency and compliance with global emissions standards, offering extensive support and maintenance options. The generator set is housed in a sound-attenuated container, ensuring ease of transport and operation in various environments.

Uploaded by

Johnny R.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
104 views10 pages

XQ1475 Spec Sheet

The Cat® XQ1475G Rental Generator Set provides a continuous power output of 1475 kW with switchable 50/60 Hz capabilities, featuring a Cat G3516C gas engine and advanced monitoring systems. It is designed for efficiency and compliance with global emissions standards, offering extensive support and maintenance options. The generator set is housed in a sound-attenuated container, ensuring ease of transport and operation in various environments.

Uploaded by

Johnny R.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 10

Cat® XQ1475G Rental Generator Set

Continuous 1475 kW
50/60 Hz Switchable
North America

Image shown may not reflect actual configuration

Specifications
Continuous Speed
Frequency Voltage
kW (kVA) rpm
50 Hz 400/230V 1475 (1844) 1500
60 Hz 480/240V 1475 (1844) 1800

Cat® G3516C Gas Engine Metric Imperial (English)


Number of Cylinders V16
Bore 170 mm 6.7 in
Stroke 190 mm 7.5 in
Displacement 69 L 4,210 in3
Aspiration Turbocharged Separate Circuit Aftercooled
Compression Ratio 11.3:1
Aftercooler Inlet 54⁰C 129⁰F
Jacket Water Outlet 98⁰C 208.4⁰F
Exhaust Manifold Dry
Engine rpm 1500/1800
Fuel system Cat Low Pressure with Air Fuel Ratio Control
Fuel Pressure Range 0.206 - 0.483 Bar 3-7 PSI
Methane Number 55-100
Governor Type ADEM™ A3 Control System

LEHX0059-01 Page 1 of 10
Cat® XQ1475G Rental Generator Set

Features & Benefits


Fuel/Emissions Strategy Cat EMCP 4.2 Control Panel
• Provides engine and generator monitoring and
• Meets most worldwide emissions requirements protection
down to 1.00 g/bhp-hr NOx level without after • 3.8-inch, graphical display denotes text
treatment and expected* emissions level to alarm/event descriptions, set points, engine and
0.50 g/bhp-hr NOx level with optional catalyst generator monitoring, and is visible in all lighting
*subject to site conditions conditions
Single Source Supplier • Integration with the Cat Digital Voltage
Regulator (CDVR) provides enhanced system
• Generator set manufactured in ISO 9001:2000 performance
compliant facility • Intertie protection provided via utility grade
• Package factory designed and production Basler BE1-11i utility multi-function relay (UMR)
tested • Three-phase sensing with adjustable volts-per-
Worldwide Product Support hertz regulation
• Cat® dealers provide extensive post sale support • Provides precise control and constant voltage in
including maintenance and repair agreements the normal operating range
• Supported 100% by the Cat dealer with warranty Power Distribution and Paralleling Controls
on parts and labor • 3200A IEC rated, fixed type, 3 poles, package
mounted, electrically operated Circuit Breaker
Cat G3516C Island Mode Gas Engine Manual and automatic paralleling capability
• Compact, four-stroke-cycle gas engine provides • AGC-4 provides paralleling, load sharing, VFD
exceptional dependability, fuel economy and control, and primary generator protection
power density • Multi-mode operation (island, multi-island and
• Robust kilowatt-based air to fuel ratio control utility parallel), load sharing (multi-unit only)
system yields enhanced system performance
Sound-attenuated Container
• Designed for maximum performance on low
pressure pipeline natural gas of 3-7 psi (0.21 • Provides 9-high stack CSC rated container for
ease of transportation and protection
kg/cm² - 0.49 kg/cm²) to the container with a
• Meets 72 dB(A) at 15 meters or below per SAE
methane number range of 55-100 (contact factory
J1074 measurement procedure at continuous
for methane numbers <55)
rating
• Island mode feature improves engine’s capability • Personnel doors (2 total) on both sides of the
to handle electrical loading and unloading engine for service access, plus 1 additional
Cat SR4 Generator personnel door for general access
• Sound attenuated air intake louvers
• Designed to match the performance and output
characteristics of the Cat gas engine Asset Monitoring and Management
• Class H insulation operating at Class F • Cat Connect PLE601
temperature for extended life
Quality
• Double bearing, wye-connected, static regulated,
brushless, permanent magnet excited • Factory designed and production tested to
• Stator winding and bearing temperature assure customer satisfaction.
monitoring • Manufactured in ISO 9001:2000 certified facility
• Coastal insulation protection and anti- Reduced Environmental Impact
condensation space heaters • 110% spill containment of onboard engine fluids
• Positive crankcase fumes ventilation

LEHX0059-01 Page 2 of 10
Cat® XQ1475G Rental Generator Set

Standard Equipment
Cat® G3516C Island Mode Gas Engine Lube Oil System
• Operates on 31.5 to 47.2 MJ/Nm3 (800 to 1200 • Integral lube oil cooler, lube oil pump, oil filter,
btu/ft3) dry pipeline natural gas) filler, and dipstick and oil drain lines routed to
• Cat Gas Engine Control Module (Cat GECM) engine rail
includes electronic speed governor with hydrax • Prelube Pump, 24VDC continuous type
actuator and provides transient richening and • Includes engine-mounted oil level regulator and
turbo bypass control 114-L (30gal) oil tank for maintaining oil pan levels
• Electronic Ignition System (controlled by ECM) in extended run applications
• Individual cylinder Detonation Sensitive Timing Control Panel
(DST)
• Package mounted EMCP 4.2 provides power
• Engine installed electronic fuel metering valve
metering, protective relaying and engine and
• Hydraulic actuated throttle plate electronically
generator control and monitoring.
controlled by ECM
• Convenient service access for Cat service tools
• Jacket Water Heater, 9kW, 400/480V, 50/60 Hz,
• Integration with the Cat Digital Voltage Regulator
3-phase with isolation valves
(DVR) provides enhanced system monitoring.
Generator • Ability to view and reset diagnostics of all controls
• 826 Frame double bearing SR-4B generator, networked on J1939 datalink eliminates need for
6-lead design separate service tools for troubleshooting
• Three-phase brushless, form wound, permanent • Real-time clock allows for date and time-stamping
magnet excited of diagnostics and events
• Winding temperature detectors • True RMS AC metering, 3 phase: L-L volts, L-N
volts, Phase, Amps, Hz, ekW, kVA, kVAR, kWHr,
Air Filter % kW, PF
• Heavy duty, single element canister type air • Graphical display with positive image,
cleaner with service indicator transflective LCD, adjustable white
Cat Cooling System backlight/contrast
• Digital indication for:
• Standard cooling provides 40C (104F) ambient
- Operating hours - Coolant Temperature
capability with 500mg/Nm3 NOx at 100% - DC Volts - Oil pressure
Continuous rating before derate
- Oil Temperature - RPM
• Horizontally mounted radiator with vertical air
• Two LED status indicators (1 red, 1 amber)
discharge
• Engine cool-down timer
• Energy efficient electric drive fan
• Engine cycle crank
• Variable frequency drive (VFD) for optimal partial
load fuel consumption • Three engine control keys and status indicators
(Run/Auto/Stop)
Starting/Charging System • Lamp test and Alarm acknowledgement keys
• Dual 24V electric starting motors • Warnings/shutdowns with indicating text for:
• 24 VDC/20A battery charger with float/equalize - Low oil pressure - High Oil Temperature
modes and charging ammeter - Emergency stop - Overspeed
• Charging Alternator, 60-Amp - Overcrank - AGC-4
• Four (4) oversized maintenance-free batteries • Emergency stop pushbutton
• Display navigation keys including two shortcut
Exhaust System keys for Engine Parameters or Generator
• Critical grade, internally mounted rectangular Parameters
exhaust silencers with vertical discharge • Generator Protection features: 25, 32, 40, 46,
• 2 m high vertical discharging exhaust stack with rain 47, 50/51, 27/59, 81 O/U
cap located in radiator discharge area (optional to • Reverse compatibility for interface to legacy
mount rain cap only) power modules Quality and Product Support

LEHX0059-01 Page 3 of 10
Cat® XQ1475G Rental Generator Set

Standard Equipment

Container Distribution System


• 40' ISO high cube container, 9-high stack CSC • 3500:5 rated Current Transformers with
certified secondary wired to shorting terminal strip
• Sound attenuated 72 dB(A) @ 15 m (50 ft) protection
• Four (4) sound attenuated air intake louvers and • Three phase, plus full rated neutral, bus bars are
3 lockable personnel doors with panic release tin-plated copper with NEMA standard hole
• Interior walls and ceilings insulated with 100 mm pattern for connection of customer load cables
of acoustic paneling and generator cables
• Floor of container is undercoated for corrosion • Bus bars are sized for full load capacity of the
protection generator set at 0.8 power factor
• Side bus bar access door, external access load • Includes ground bus, tin-plated copper, for
connection bus bars connection to the generator frame ground and
• Shore power connection via distribution block field ground cable.
connections for jacket water heater, battery • 50/60 Hz Transformer distributes utility voltage or
charger, generator customer supplied line voltage, which is electable
• Six (6) compact LED type internal DC lights with via onboard switch, for the Power Module AC
timers located at each personnel door auxiliaries
• 3” ANSI flange customer fuel connection with • Provides 240/120 VAC for all module accessories
cover to prevent vandalism except Jacket water heater (400/480V)
• Energized-to-run (ETR) shutoff valve (double • Includes controls to de-energize jacket water
solenoid, low/high pressure switch, CSA/FM heaters and generator space heater when the
approved) engine is running
• Cat Brand fuel filter, wall mounted and gas Protective Relaying
pressure regulator
• Generator protective features
• Vibration isolators, stainless steel fastening
o 25 sync-check ( AGC-4)
hardware and hinges
o 32 rev. power (EMCP 4.2 and AGC-4)
• External drain access to standard fluids
o 40 loss of excitation (Cat DVR and AGC-4
• One 4.5 kg (10 lb) carbon dioxide fire
impedance based)
extinguisher
o 50/51 Inst. and time overcurrent (GCB trip unit
• LH and RH engine service panels integrated
and AGC-4)
into container side walls
o 47 Negative Voltage Sequence (AGC-4)
• 110% spill containment system for on-board
o 46 Negative Sequence Current (AGC-4)
engine fluids
o 27/59 phase under/over voltage (EMCP 4.2
• One (1) duplex service receptacle
and AGC-4)
o 81O/U under/over frequency (EMCP 4.2 and
AGC-4)
• Package mounted AGC-4 controls provides auto
paralleling, CAN-bus, Ethernet communications,
PWM and Analog outputs, and legacy analog load
sharing (real and reactive)
• AGC-4 main display/ AOP secondary display

LEHX0059-01 Page 4 of 10
Cat® XQ1475G Rental Generator Set

Standard Equipment

Modes of Operation Utility Multi-Functional Relay


• Provides for single unit stand-alone operation, • Intertie protection provided via utility grade Basler
island mode paralleling and load sharing with • BE1-11i
other power modules, and single unit-to-utility • Provides the following utility/intertie enabled
mode paralleling for base load control (with open • protections:
transition between paralleling modes) o 25 (sync-check, utility mode)
• Island mode paralleling features: o 27 (under voltage, 2 stage)
o AGC-4 control allows single unit to connect o 32 (rev. power)
o to a dead bus o 40Z (loss of excitation, impedance based)*
o Auto synchronization (voltage & phase o 47 (neg. sequence over voltage)
o matching) o 51 (phase, time over current)
o Load sharing (kW) analog signal (like units & o 51N (neutral, over current)
legacy compatible) o 59 (over voltage, 2 stage)
o Load sharing (kVAR) analog signal (like units
o 81U (under frequency, 2 stage)
only)
o 81O (over frequency)
• Utility mode paralleling features:
o Auto synchronization (voltage & phase o 60FL (fuse loss, ‘major alarm’ LED - no trip)
o matching) o Modbus interface via 485 serial connection
o Base-load control (selectable: programmable o Real or Reactive Load High Demand, ‘minor
set-point or potentiometer adjust) o alarm’ LED - no trip, requires site-specific
o Soft load/unload (programmable, shared setpoint values programmed
setpoint)
o Power Factor control (programmable Optional Equipment
setpoint)
Trailer
Power Factor Control Circuitry
• Three axle with Anti-lock brake system
• Manual raise/lower voltage adjust capability and
VAR/power factor control circuitry, all via AGC-4, • Ladders, handrails, internal storage provisions
for maintaining constant generator power factor • Goodyear G314 295/75R225 Load Range G
while paralleled with utility
• Includes RFI suppression, exciter limiter and
exciter diode monitoring

LEHX0059-01 Page 5 of 10
Cat® XQ1475G Rental Generator Set

Technical Data*

Cat Generator
Frame size 826
Pitch 2/3
No. of poles 4
Insulation Class H
Excitation Static regulated brushless PM excited
Constructions Double bearing, close coupled
Enclosure Drip proof IP22
Temperature rise 105⁰C (221⁰F)
Alignment Pilot shaft
Overspeed capability – % of rated 125% of rated
Voltage regulator 3-phase sensing with volts-per-hertz
Less than ± 0.5% voltage gain
Voltage regulation Adjustable to compensate for engine speed droop and
line loss
Wave form deviation Less than 3% deviation
Telephone Influence Factor (TIF) Less than 50
Harmonic Distortion (THD) Less than 5%

Units 50 Hz 60 Hz
Power Rating kW (kVA) 1475 (1844)
Performance Specification EM0765 EM0754
Lubricating System
Lube Oil Refill Volume with filter change for L (gal) 416 (110)
standard sump
Fuel System
Fuel consumption (ISO 3046/1)
100% Load
Max VFD (50kW) MJ/ekW-hr 9.62 10.34
Min VFD (3kW) MJ/ekW-hr 9.35 10.05
75% Load
Max VFD (50kW) MJ/ekW-hr 9.92 10.74
MJ/ekW-hr 9.57 10.39
Min VFD (3kW)
50% Load
MJ/ekW-hr 10.59 11.86
Max VFD (50kW) 9.97
MJ/ekW-hr 11.14
Min VFD (3kW)

Altitude Capability
At 25° C (77° F) ambient, above sea level m (ft) 1500 (4921)

LEHX0059-01 Page 6 of 10
Cat® XQ1475G Rental Generator Set

Technical Data (continued)

Units 50 Hz 60 Hz
Cooling System
Package ambient capability ° C (° F) 40 (104)
Jacket water temperature (maximum outlet) ° C (° F) 99 (210)
System coolant capacity L (gal) 770 (203)
System required airflow m3/min (ft³/min) 2,604 (91,959)

Exhaust System
Combustion air inlet flow rate m3/min (ft³/min) 116 (4,907) 111 (3,920)
Exhaust stack gas temperature ° C (° F) 467 (877) 492 (918)
Exhaust gas flow rate Nm3/min 113 118

Sound Performance**
Noise rating @ 15 m (49 feet) dB(A) 72

Emissions at 100% Load


Nox (as NO2) g/bhp-hr 1.00 1.00
CO g/bhp-hr 2.03 2.74
VOC (NMNEHC) g/bhp-hr 0.51 0.47
HCHO g/bhp-hr 0.53 0.56
Exhaust O2 % (dry) 10.0 10.0

Expected1 emissions with


optional catalyst at 100% Load
Performance Specification EM0766 EM0758
Nox (as NO2) g/bhp-hr 0.51 0.50
CO g/bhp-hr 1.03 1.22
VOC (NMNE) g/bhp-hr 0.32 0.32
HCHO g/bhp-hr 0.38 0.41
Exhaust O2 % (dry) 10.2 10.3

* Materials and specifications are subject to change without notice. Reference SRR GR-3500-158-02 For Max VFD Power and
SRR GR-3500-157-02 for Min VFD Power Data at 50 Hz. Reference SRR GR-3500-136-00 For Max VFD Power and SRR
GR-3500-137-00 for Min VFD Power Data at 60 Hz. 60 Hz emissions data pending factory testing results.
** per SAE J1074.
1 use of 0.5 g/bhp-hr performance number with Catalyst, Emissions subject to site conditions.

Dimensions and Weights


Weight with Lube oil and
Length Width Height
Model Coolant
mm (in) mm (in) mm (in)
kg (lb)
XQ1475G without Trailer 12,192 (480) 2,438 (96) 2,896 (114) 31,920 (70,372)

XQ1475G with Trailer 12,192 (480) 2,438 (96) 2,896 (114) 36,003 (79,372)

LEHX0059-01 Page 7 of 10
Cat® XQ1475G Rental Generator Set

Methane Number Operation Guidelines**


Fuel Usage Guidelines

Cat Methane Number 30 35 40 45 50 55 60 65 70 75 80 85 to 100

Ignition Timing Contact Factory 24 24 25 27 27 28 28

Deration Factor Contact Factory 0.90 0.91 0.93 1.00 1.00 1.00 1.00

**This table shows the derate factor required for a given fuel. Note that deration occurs as the methane number decreases. Methane number is a scale to
measure detonation characteristics of various fuels. The methane number of a fuel is determined by using the Cat Methane Number Calculation program.
Contact factory for operation with methane numbers below 55.

Altitude XQ1475G 1500rpm (50 Hz) Altitude / Ambient Derate Chart


Meters Feet Switchable Cams & High Ambient Air Intake System
2,400 7,874 84.9% 66.3% 62.0% 61.2% 59.5% 57.9% 56.3% 54.7% 53.0% 42.4% 31.8% 21.2% 10.6% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0%
2,250 7,382 88.0% 71.6% 66.7% 65.8% 64.1% 62.5% 60.9% 59.2% 57.6% 46.1% 34.6% 23.0% 11.5% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0%
2,000 6,562 92.0% 79.3% 75.3% 74.4% 72.6% 70.8% 68.9% 67.1% 65.3% 52.2% 39.2% 26.1% 13.1% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0%
1,750 5,741 97.1% 85.9% 82.7% 82.1% 80.0% 78.0% 76.0% 73.9% 71.9% 68.8% 65.8% 62.7% 59.7% 56.6% 45.3% 34.0% 22.6% 11.3% 0.0%
1,500 4,921 100.0% 92.7% 89.8% 89.2% 87.3% 85.3% 83.4% 81.5% 79.5% 76.5% 73.4% 70.4% 67.3% 64.2% 56.6% 48.9% 41.3% 33.6% 26.0%
1,250 4,101 100.0% 99.1% 96.8% 96.4% 94.5% 92.7% 90.9% 89.0% 87.2% 84.3% 81.4% 78.5% 75.6% 72.7% 69.3% 65.9% 62.6% 59.2% 55.8%
1,000 3,281 100.0% 100.0% 100.0% 100.0% 100.0% 99.2% 97.8% 96.5% 95.1% 92.0% 89.0% 85.9% 82.8% 79.8% 76.3% 72.8% 69.4% 65.9% 62.4%
900 2,953 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 99.5% 98.7% 97.9% 94.8% 91.8% 88.7% 85.7% 82.6% 79.1% 75.7% 72.2% 68.7% 65.3%
800 2,625 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 97.9% 94.8% 91.8% 88.7% 85.7% 82.2% 78.7% 75.3% 71.8% 68.3%
700 2,297 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 98.9% 96.4% 93.8% 91.3% 88.7% 85.1% 81.6% 78.0% 74.4% 70.9%
600 1,969 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 99.9% 97.9% 95.8% 93.8% 91.8% 88.1% 84.4% 80.8% 77.1% 73.4%
500 1,640 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 98.9% 97.4% 95.8% 94.3% 90.9% 87.4% 83.9% 80.5% 77.0%
400 1,312 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 99.9% 98.9% 97.9% 96.9% 93.6% 90.3% 87.1% 83.8% 80.6%
300 984 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 99.9% 99.4% 96.8% 94.1% 91.5% 88.8% 86.2%
200 656 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 99.6% 99.0% 97.9% 95.8% 93.8% 91.8%
100 328 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 99.6% 99.0% 98.3% 97.6% 97.0% 96.3%
0 0 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 99.6% 99.0% 98.3% 97.6% 97.0% 96.3%
Ambient (C) 20 25 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46

Chart applicable to 1g/bhp-hr operation only.


For derates less than 50%, refer to partial load operation section in OMM.

Altitude XQ1475G 1800rpm (60 Hz) Altitude / Ambient Derate Chart


Meters Feet Switchable Cams & High Ambient Air Intake System
2,400 7,874 84.9% 80.7% 76.8% 76.0% 74.0% 72.1% 70.1% 68.1% 66.1% 56.8% 47.4% 38.0% 28.7% 19.3% 14.8% 10.2% 5.7% 1.1% 0.0%
2,250 7,382 88.0% 83.8% 80.5% 79.8% 77.7% 75.6% 73.5% 71.4% 69.3% 66.1% 63.0% 59.8% 56.6% 53.5% 42.1% 30.7% 19.3% 7.9% 0.0%
2,000 6,562 92.0% 89.7% 86.8% 86.2% 84.0% 81.9% 79.8% 77.7% 75.6% 72.4% 69.3% 66.1% 63.0% 59.8% 47.1% 34.5% 21.8% 9.2% 0.0%
1,750 5,741 97.1% 95.0% 92.1% 91.4% 89.5% 87.6% 85.7% 83.8% 81.9% 78.8% 75.6% 72.4% 69.3% 66.1% 63.0% 59.8% 56.6% 53.5% 50.3%
1,500 4,921 100.0% 100.0% 98.2% 97.7% 95.9% 94.0% 92.1% 90.2% 88.3% 85.3% 82.4% 79.4% 76.5% 73.5% 69.9% 66.3% 62.7% 59.2% 55.6%
1,250 4,101 100.0% 100.0% 100.0% 100.0% 100.0% 99.0% 97.5% 96.1% 94.6% 91.4% 88.3% 85.1% 81.9% 78.8% 75.2% 71.6% 68.0% 64.4% 60.9%
1,000 3,281 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 97.7% 94.6% 91.4% 88.3% 85.1% 81.5% 77.9% 74.3% 70.8% 67.2%
900 2,953 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 98.6% 95.9% 93.1% 90.4% 87.6% 84.0% 80.3% 76.6% 73.0% 69.3%
800 2,625 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 99.4% 97.1% 94.8% 92.5% 90.2% 86.4% 82.7% 78.9% 75.1% 71.4%
700 2,297 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 98.2% 96.3% 94.4% 92.5% 88.8% 85.1% 81.3% 77.6% 73.9%
600 1,969 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 99.0% 97.5% 96.1% 94.6% 91.0% 87.5% 84.0% 80.4% 76.9%
500 1,640 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 99.9% 98.8% 97.7% 96.7% 93.3% 89.9% 86.6% 83.2% 79.8%
400 1,312 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 99.4% 98.8% 95.9% 93.1% 90.2% 87.3% 84.5%
300 984 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 99.6% 98.6% 96.2% 93.8% 91.5% 89.1%
200 656 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 99.6% 99.0% 98.3% 96.9% 95.2% 93.5%
100 328 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 99.6% 99.0% 98.3% 97.6% 97.0% 96.3%
0 0 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 99.6% 99.0% 98.3% 97.6% 97.0% 96.3%
Ambient (C) 20 25 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46

Chart applicable to 1g/bhp-hr operation only.


For derates less than 50%, refer to partial load operation section in OMM.

LEHX0059-01 Page 8 of 10
Cat® XQ1475G Rental Generator Set

General Layout

LEHX0059-01 Page 9 of 10
Cat® XQ1475G Rental Generator Set

Overall Package Derate Guidance


To determine the actual package rating at site conditions, one must consider, separately, limitations due to fuel characteristics
and air system limitations. The Fuel Usage Guide deration establishes fuel limitations while the Altitude/Temperature deration
factors and RPC (reference the Cat Methane Program) establish air system limitations. RPC is considered when the
Altitude/Temperature deration is less than 1.0 (100%). Under this condition, add the two factors together.
When the site conditions do not require an Altitude/Temperature derate (factor is 1.0), it is assumed the turbocharger has
sufficient capability to overcome the low fuel relative power and RPC is ignored.

To determine the actual power available, take the lowest rating between 1. and 2. below:
1. Fuel Usage Guide Deration
2. 1-((1-Altitude/Temperature Deration) + (1-RPC))

Ratings Definitions and Conditions


Continuous — Output available without varying load for an unlimited time. Continuous power is in accordance
with ISO8528, AS2789, and BS5514. Fuel stop power is in accordance with ISO03036. Natural gas ratings have
been established on natural gas with net calorific Low Heat Value (LHV) of approximately 35.6 MJ/Nm3 (905 Btu/
cu ft) and 80 Methane Number (MN). For values in excess of altitude, ambient temperature, inlet/exhaust
restriction, or different from the conditions listed, contact your local Cat dealer.

www.Cat.com/rentalpower
©2022 Caterpillar
All rights reserved.
Materials and specifications are subject to change without notice. The International System of Units (SI)
is used in this publication.
CAT, CATERPILLAR, LET’S DO THE WORK, their respective logos, "Caterpillar Corporate Yellow", the
"Power Edge" and Cat “Modern Hex” trade dress as well as corporate and product identity used herein, are
LEHX0059-01 (01/22) trademarks of Caterpillar and may not be used without permission.