XQ1475 Spec Sheet
XQ1475 Spec Sheet
Continuous 1475 kW
50/60 Hz Switchable
North America
Specifications
Continuous Speed
Frequency Voltage
kW (kVA) rpm
50 Hz 400/230V 1475 (1844) 1500
60 Hz 480/240V 1475 (1844) 1800
LEHX0059-01 Page 1 of 10
Cat® XQ1475G Rental Generator Set
LEHX0059-01 Page 2 of 10
Cat® XQ1475G Rental Generator Set
Standard Equipment
Cat® G3516C Island Mode Gas Engine Lube Oil System
• Operates on 31.5 to 47.2 MJ/Nm3 (800 to 1200 • Integral lube oil cooler, lube oil pump, oil filter,
btu/ft3) dry pipeline natural gas) filler, and dipstick and oil drain lines routed to
• Cat Gas Engine Control Module (Cat GECM) engine rail
includes electronic speed governor with hydrax • Prelube Pump, 24VDC continuous type
actuator and provides transient richening and • Includes engine-mounted oil level regulator and
turbo bypass control 114-L (30gal) oil tank for maintaining oil pan levels
• Electronic Ignition System (controlled by ECM) in extended run applications
• Individual cylinder Detonation Sensitive Timing Control Panel
(DST)
• Package mounted EMCP 4.2 provides power
• Engine installed electronic fuel metering valve
metering, protective relaying and engine and
• Hydraulic actuated throttle plate electronically
generator control and monitoring.
controlled by ECM
• Convenient service access for Cat service tools
• Jacket Water Heater, 9kW, 400/480V, 50/60 Hz,
• Integration with the Cat Digital Voltage Regulator
3-phase with isolation valves
(DVR) provides enhanced system monitoring.
Generator • Ability to view and reset diagnostics of all controls
• 826 Frame double bearing SR-4B generator, networked on J1939 datalink eliminates need for
6-lead design separate service tools for troubleshooting
• Three-phase brushless, form wound, permanent • Real-time clock allows for date and time-stamping
magnet excited of diagnostics and events
• Winding temperature detectors • True RMS AC metering, 3 phase: L-L volts, L-N
volts, Phase, Amps, Hz, ekW, kVA, kVAR, kWHr,
Air Filter % kW, PF
• Heavy duty, single element canister type air • Graphical display with positive image,
cleaner with service indicator transflective LCD, adjustable white
Cat Cooling System backlight/contrast
• Digital indication for:
• Standard cooling provides 40C (104F) ambient
- Operating hours - Coolant Temperature
capability with 500mg/Nm3 NOx at 100% - DC Volts - Oil pressure
Continuous rating before derate
- Oil Temperature - RPM
• Horizontally mounted radiator with vertical air
• Two LED status indicators (1 red, 1 amber)
discharge
• Engine cool-down timer
• Energy efficient electric drive fan
• Engine cycle crank
• Variable frequency drive (VFD) for optimal partial
load fuel consumption • Three engine control keys and status indicators
(Run/Auto/Stop)
Starting/Charging System • Lamp test and Alarm acknowledgement keys
• Dual 24V electric starting motors • Warnings/shutdowns with indicating text for:
• 24 VDC/20A battery charger with float/equalize - Low oil pressure - High Oil Temperature
modes and charging ammeter - Emergency stop - Overspeed
• Charging Alternator, 60-Amp - Overcrank - AGC-4
• Four (4) oversized maintenance-free batteries • Emergency stop pushbutton
• Display navigation keys including two shortcut
Exhaust System keys for Engine Parameters or Generator
• Critical grade, internally mounted rectangular Parameters
exhaust silencers with vertical discharge • Generator Protection features: 25, 32, 40, 46,
• 2 m high vertical discharging exhaust stack with rain 47, 50/51, 27/59, 81 O/U
cap located in radiator discharge area (optional to • Reverse compatibility for interface to legacy
mount rain cap only) power modules Quality and Product Support
LEHX0059-01 Page 3 of 10
Cat® XQ1475G Rental Generator Set
Standard Equipment
LEHX0059-01 Page 4 of 10
Cat® XQ1475G Rental Generator Set
Standard Equipment
LEHX0059-01 Page 5 of 10
Cat® XQ1475G Rental Generator Set
Technical Data*
Cat Generator
Frame size 826
Pitch 2/3
No. of poles 4
Insulation Class H
Excitation Static regulated brushless PM excited
Constructions Double bearing, close coupled
Enclosure Drip proof IP22
Temperature rise 105⁰C (221⁰F)
Alignment Pilot shaft
Overspeed capability – % of rated 125% of rated
Voltage regulator 3-phase sensing with volts-per-hertz
Less than ± 0.5% voltage gain
Voltage regulation Adjustable to compensate for engine speed droop and
line loss
Wave form deviation Less than 3% deviation
Telephone Influence Factor (TIF) Less than 50
Harmonic Distortion (THD) Less than 5%
Units 50 Hz 60 Hz
Power Rating kW (kVA) 1475 (1844)
Performance Specification EM0765 EM0754
Lubricating System
Lube Oil Refill Volume with filter change for L (gal) 416 (110)
standard sump
Fuel System
Fuel consumption (ISO 3046/1)
100% Load
Max VFD (50kW) MJ/ekW-hr 9.62 10.34
Min VFD (3kW) MJ/ekW-hr 9.35 10.05
75% Load
Max VFD (50kW) MJ/ekW-hr 9.92 10.74
MJ/ekW-hr 9.57 10.39
Min VFD (3kW)
50% Load
MJ/ekW-hr 10.59 11.86
Max VFD (50kW) 9.97
MJ/ekW-hr 11.14
Min VFD (3kW)
Altitude Capability
At 25° C (77° F) ambient, above sea level m (ft) 1500 (4921)
LEHX0059-01 Page 6 of 10
Cat® XQ1475G Rental Generator Set
Units 50 Hz 60 Hz
Cooling System
Package ambient capability ° C (° F) 40 (104)
Jacket water temperature (maximum outlet) ° C (° F) 99 (210)
System coolant capacity L (gal) 770 (203)
System required airflow m3/min (ft³/min) 2,604 (91,959)
Exhaust System
Combustion air inlet flow rate m3/min (ft³/min) 116 (4,907) 111 (3,920)
Exhaust stack gas temperature ° C (° F) 467 (877) 492 (918)
Exhaust gas flow rate Nm3/min 113 118
Sound Performance**
Noise rating @ 15 m (49 feet) dB(A) 72
* Materials and specifications are subject to change without notice. Reference SRR GR-3500-158-02 For Max VFD Power and
SRR GR-3500-157-02 for Min VFD Power Data at 50 Hz. Reference SRR GR-3500-136-00 For Max VFD Power and SRR
GR-3500-137-00 for Min VFD Power Data at 60 Hz. 60 Hz emissions data pending factory testing results.
** per SAE J1074.
1 use of 0.5 g/bhp-hr performance number with Catalyst, Emissions subject to site conditions.
XQ1475G with Trailer 12,192 (480) 2,438 (96) 2,896 (114) 36,003 (79,372)
LEHX0059-01 Page 7 of 10
Cat® XQ1475G Rental Generator Set
Deration Factor Contact Factory 0.90 0.91 0.93 1.00 1.00 1.00 1.00
**This table shows the derate factor required for a given fuel. Note that deration occurs as the methane number decreases. Methane number is a scale to
measure detonation characteristics of various fuels. The methane number of a fuel is determined by using the Cat Methane Number Calculation program.
Contact factory for operation with methane numbers below 55.
LEHX0059-01 Page 8 of 10
Cat® XQ1475G Rental Generator Set
General Layout
LEHX0059-01 Page 9 of 10
Cat® XQ1475G Rental Generator Set
To determine the actual power available, take the lowest rating between 1. and 2. below:
1. Fuel Usage Guide Deration
2. 1-((1-Altitude/Temperature Deration) + (1-RPC))
www.Cat.com/rentalpower
©2022 Caterpillar
All rights reserved.
Materials and specifications are subject to change without notice. The International System of Units (SI)
is used in this publication.