DW PowerStudplusSD2-TP-CAEN DDS1

The document provides detailed specifications and installation instructions for the Power-Stud+ SD2 anchor, a wedge expansion anchor designed for use in various concrete applications. It includes information on material specifications, general applications, installation requirements, and compliance with relevant codes and standards. The document also outlines the anchor's features, benefits, and performance data to ensure proper use and installation.

Uploaded by

Dillon
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
11 views10 pages

DW PowerStudplusSD2-TP-CAEN DDS1

The document provides detailed specifications and installation instructions for the Power-Stud+ SD2 anchor, a wedge expansion anchor designed for use in various concrete applications. It includes information on material specifications, general applications, installation requirements, and compliance with relevant codes and standards. The document also outlines the anchor's features, benefits, and performance data to ensure proper use and installation.

Uploaded by

Dillon
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 10

General Information CANADIAN TECHNICAL PAGE SUPPLEMENT ANCHORS & FASTENERS

GENERAL INFORMATION SECTION CONTENTS


Mechanical Anchors

General Information.........................1
POWER-STUD®+ SD2 Material Specifications....................1
High Performance Wedge Expansion Anchor Installation Specifications...............2
Installation Instructions...................3
PRODUCT DESCRIPTION
Limit States Information..................5
The Power-Stud+ SD2 anchor is a fully threaded, torque-controlled, wedge expansion anchor Performance Data (ASD)..................9
which is designed for consistent performance in cracked and uncracked concrete. Suitable base
materials include normal-weight concrete, lightweight concrete and concrete over steel deck. The Ordering Information......................10
anchor is manufactured with a zinc plated carbon steel body and stainless steel expansion clip
for premium performance.
GENERAL APPLICATIONS AND USES
• Structural connections, i.e., beam and column anchorage
• Interior applications / low level corrosion environment POWER-STUD+ SD2
ASSEMBLY
• Tension zone applications, i.e., safety-related attachments
• Seismic and wind loading THREAD VERSION
• Utility supports, e.g. pipe, strut, trapeze, bracing • UNC threaded stud
• Equipment anchorage, angles, brackets and ledgers ANCHOR MATERIALS
• Barriers, guards and fencing
• Zinc plated carbon steel body with
• Mezzanines, racking and railing stainless steel expansion clip, zinc
plated carbon steel nut and washer
FEATURES AND BENEFITS
+ Consistent performance in high and low strength concrete ANCHOR SIZE RANGE (TYP.)
+ Nominal drill bit size is the same as the anchor diameter • 3/8" through 3/4" diameters
+ Anchor can be installed through standard fixture holes SUITABLE BASE MATERIALS
+ Length ID code and identifying marking stamped on head of each anchor • Normal-weight concrete
+ Anchor design allows for follow-up expansion after setting under tensile loading • Lightweight concrete
• Concrete over steel deck
APPROVALS AND LISTINGS
• Grouted-filled concrete masonry (CMU)
• International Code Council, Evaluation Service (ICC-ES), ESR-2502 and ELC-2502 for cracked and
uncracked concrete
IC REGI
• Code Compliant with the 2020/2015 NBCC and 2021 IBC/IRC, 2018 IBC/IRC, 2015 IBC/IRC, NS
ION ZO
SM

ON
NE

I
TE

and 2012 IBC/IRC

SE
CRA

E
• Tested in accordance with ACI 355.2/ASTM E488 and ICC-ES AC193 for use in structural concrete ET

QU
KE A O

N
LI
D CONC
R
FIC ATI
C

under the design provisions of ACI 318 (-19 or -14) Chapter 17 and CSA A23.3 (-19, -14, -04)
Annex D or ACI 318 Appendix D CODE LISTED CODE LISTED
• Evaluated and qualified by an accredited independent testing laboratory for recognition in ICC-ES ESR-2502 ICC-ES ELC-2502
CONCRETE CONCRETE
cracked and uncracked concrete including seismic and wind loading (Category 1 anchors)
• City of Los Angeles, LABC and LARC Supplement (within ESR-2502)
• Florida Building Code, FBC Supplement including HVHZ (within ESR-2502)
TECHNICAL GUIDE – CANADIAN SUPPLEMENT – Mechanical Anchors ©2024 DEWALT – REV. d

• FM Approvals (Factory Mutual) – see FM Approval Guide for sizes


• Underwriters Laboratory (UL Listed) – File No. EX1289 and VFXT7.EX1289, see listing for sizes
GUIDE SPECIFICATIONS
CSI Divisions: 03 16 00 - Concrete Anchors, 04 05 19.16 - Masonry Anchors and
05 05 09 - Post-Installed Concrete Anchors. Expansion anchors shall be Power-Stud+ SD2
as supplied by DEWALT, Towson, MD. Anchors shall be installed in accordance with published
instructions and the Authority Having Jurisdiction.
MATERIAL SPECIFICATIONS
Anchor component Specification
Anchor Body Medium carbon steel
Hex nut Carbon steel, ASTM A563, Grade A
Carbon Steel, ASTM F844; meets dimensional requirements of
Washer ANSI B18.22.2. Type A Plain
Expansion wedge (clip) 316 Stainless Steel
Zinc plating according to ASTM B633, SC1 Type III (Fe/Zn 5)
Plating (anchor body, nut and washer) Minimum plating requirements for Mild Service Condition.
See Tension Design Information table for yield and ultimate strengths of the anchor body.

1
ANCHORS & FASTENERS Installation Specifications

INSTALLATION SPECIFICATIONS

Mechanical Anchors
Power-Stud+ SD2 Anchor Installation Table
Anchor Property/ Nominal Anchor Size
Notation Units
Setting Information 3/8" 1/2" 5/8" 3/4"
mm 9.5 12.7 15.9 19.1
Outside diameter of anchor da (in.) (0.375) (0.500) (0.625) (0.750)
Minimum diameter of hole clearance mm 11.1 14.3 17.5 20.6
dh
in fixture (in.) (7/16) (9/16) (11/16) (13/16)
3/8
Nominal drill bit diameter dbit in. 1/2 ANSI 5/8 ANSI 3/4 ANSI
ANSI
Minimum nominal embedment depth2 hnom mm 60 64 83 98 124 114 146
Effective embedment hef mm 51 51 83 83 108 95 127
Minimum concrete member thickness hmin mm 102 114 152 146 146 146 165 203 178 254
Critical edge distance cac mm 165 203 254 203 400 254 305 305
Minimum edge distance cmin mm 64 102 70 102 70 108 108 127 114
Minimum spacing distance smin mm 89 152 152 102 152 108 108 152 152
Minimum hole depth ho mm 67 70 102 108 133 127 159
Minimum overall anchor length3 ℓanch mm 76 95 114 121 152 159 178
Installation torque Tinst N-m 27 54 81 149
Torque wrench / socket size - in. 9/16 3/4 15/16 1-1/8
Nut height - in. 21/64 7/16 35/64 4-1/64
For SI: 1 inch = 25.4 mm, 1 ft-lbf = 1.356 N-m.
1. The information presented in this table is to be used in conjunction with the design criteria of CSA A23.3 (-19, -14, -04) Annex D, as applicable.
2. The embedment depth, hnom, is measured from the outside surface of the concrete member to the embedded end of the anchor prior to tightening.
3. The listed minimum overall anchor length is based on anchor sizes commercially available at the time of publication compared with the requirements to achievethe minimum nominal
embedment depth and possible fixture attachment.

Anchor Setting Information for Installation on the Top of Concrete-Filled Steel Deck Assemblies3,4
Anchor Property/ Nominal Anchor Size (inch)
Notation Units
Setting Information 3/8" 1/2"
Nominal drill bit diameter (ANSI) dbit in. 3/8 ANSI 1/2 ANSI
mm 60 64
Minimum nominal embedment depth1 hnom (in.) (2-3/8) (2-1/2)
mm 51 51
Effective embedment hef (in.) (2.00) (2.00)
mm 64 64
Minimum concrete member thickness2 hmin,deck (in.) (2-1/2) (2-1/2)
Critical edge distance for topside of concrete- mm 203 229
filled steel deck assemblies with minimum cac,deck,top (in.) (8) (9)
topping thickness (uncracked concrete only)
mm 102 70 102 203
Minimum edge distance cmin,deck,top (in.) (4) (2-3/4) (4) (8)
mm 89 152 203 102
Minimum spacing distance smin,deck,top (in.) (3-1/2) (6) (8) (4)
mm 64 64
Minimum hole depth ho (in.) (2-1/2) (2-1/2)

TECHNICAL GUIDE – CANADIAN SUPPLEMENT – Mechanical Anchors ©2024 DEWALT – REV. d


N-m 27 54
Installation torque Tinst (ft.-lb.) (20) (40)
Torque wrench socket size - in. 9/16 3/4
Nut height - in. 21/64 7/16
Washer O.D. - in. 13/16 1-1/16
For SI: 1 inch = 25.4 mm, 1 ft-lbf = 1.356 N-m.
1. The embedment depth, hnom, is measured from the outside surface of the concrete member to the embedded end of the anchor prior to tightening.
2. The anchors may be installed in the topside of concrete-filled steel deck floor and roof assemblies provided the concrete thickness above the upper flute meets the minimum thicknesses
specified in this table. Minimum concrete member thickness refers to the concrete thickness above the upper flute (topping thickness). See Installation Detail D.
3. For all other anchor diameters and embedment depths, refer to the installation table for applicable values of hmin, cmin and smin.
4. Design capacities shall be based on calculations according to values in Tension Design Information and Shear Design Information tables.

2
Installation Instructions ANCHORS & FASTENERS
Mechanical Anchors

Power-Stud+ SD2 Anchor Detail Interpolation of Minimum Edge Distance


and Anchor Spacing

spacing s
hmin
dh t dh t cmin at s ≥
lanch
lanch
sdesign smin at c ≥
hef hef
hnom
da
da
ho ho

cdesign
edge distance c

dbit dbit This interpolation applies to the cases when two sets of minimum edge distances, cmin,
and minimum spacing distances, smin, are given for a selected anchor diameter effective
embedment depth, hef, and corresponding minimum member thickness, hmin.
Before After
Head Marking Power-Stud+ SD2 Anchor Assembly

Legend
Letter Code = Length Identification Mark
‘+’ Symbol = Strength Design Compliant Anchor
Number Code 2 = Carbon Steel Body and Stainless Steel Hex Nut Washer UNC Thread Stud Collar Expansion Mandrel
Expansion Clip Wedge Clip

Length Identification
Mark A B C D E F G H I J K L M N O P
From 1-1/2" 2" 2-1/2" 3" 3-1/2" 4" 4-1/2" 5" 5-1/2" 6" 6-1/2" 7" 7-1/2" 8" 8-1/2" 9"
Up to but not 2" 2-1/2" 3" 3-1/2" 4" 4-1/2" 5" 5-1/2" 6" 6-1/2" 7" 7-1/2" 8" 8-1/2" 9" 9-1/2"
including
Length identification mark indicates overall length of anchor.

INSTALLATION INSTRUCTIONS
Installation Instructions for Power-Stud+ SD2
TECHNICAL GUIDE – CANADIAN SUPPLEMENT – Mechanical Anchors ©2024 DEWALT – REV. d

Step 1 Step 2 Step 3 Step 4


Using the proper drill bit size, drill a hole Remove dust and debris from the hole Position the washer on the anchor and Tighten the anchor with a torque wrench
into the base material to the required during drilling, (e.g. dust extractor, hollow thread on the nut. If installing through by applying the required installation
depth. The tolerances of the drill bit used bit) or following drilling (e.g. suction, a fixture, drive the anchor through the torque, Tinst.
should meet the requirements of ANSI forced air) to extract loose particles fixture into the hole. Be sure the anchor
Standard B212.15. created by drilling. is driven to the minimum required
embedment depth, hnom.

3
ANCHORS & FASTENERS Installation Instructions

Mechanical Anchors
Installation Detail A: Power-Stud+ SD2 Installed in the Soffit of Concrete over Steel Deck Floor
and Roof Assemblies (see dimensional profile requirements)1
1. Anchors may be placed in the upper flute or lower flute of the steel deck
STRUCTURAL SAND-LIGHTWEIGHT CONCRETE OR NORMAL WEIGHT CONCRETE
OVER STEEL DECK (MINIMUM 3,000 PSI) profiles in accordance with installation Detail A provided the minimum
hole clearance is satisfied. Anchors in the lower flute of installation
Min. 3-1/4" 3/4" Clearance Min. Upper Flute (Valley)
Detail A profiles may be installed with a maximum 1-inch offset in either
direction from the center of the flute. The offset distance may be increased
proportionally for profiles with lower flute widths greater than those shown
provided the minimum lower flute edge distance is also satisfied.

Max. Power-Stud+
3" Anchor (Typ)
Min. 4-1/2"
(Typ) Lower Flute (Ridge)
Min. No. 20 Gauge Steel Deck Min.
1-1/4"
Flute Edge

Installation Detail B: Power-Stud+ SD2 Installed in the Soffit of Concrete Over Steel Deck Floor
and Roof Assemblies (see dimensional profile requirements)1
1. Anchors may be placed in the upper flute or lower flute of the steel deck
LIGHTWEIGHT CONCRETE OR NORMAL WEIGHT CONCRETE profiles in accordance with Detail B provided the minimum hole clearance
OVER STEEL DECK (MINIMUM 3,000 PSI)
is satisfied. Anchors in the lower flute of Detail B profiles may be installed
Min. 2"
with a maximum 15/16 -inch offset in either direction from the center of
1" Clearance Min. Upper Flute (Valley) the flute. The offset distance may be increased proportionally for profiles
with lower flute widths greater than those shown provided the minimum
lower flute edge distance is also satisfied.

Max. Power-Stud+
3" Anchor (Typ)
Min. 3-7/8" Lower Flute (Ridge)
(Typ)
No. 20 Gauge Steel Deck Min.
Min.
1" Flute Edge

Installation Detail C: Power-Stud+ SD2 Installed in the Soffit of Concrete over Steel Deck Floor
and Roof Assemblies (See Dimensional Profile Requirements)1,2
SAND-LIGHTWEIGHT CONCRETE OR NORMAL WEIGHT CONCRETE 1. Anchors may be placed in the lower flute of the steel deck profiles in
OVER STEEL DECK (MINIMUM 3,000 PSI) accordance with installation Detail C provided the minimum hole clearance
is satisfied. Anchors in the lower flute of installation Detail C profiles may be
installed with a maximum 1/8-inch offset in either direction from the center
Min. 2-1/4" 1" Clearance Min. of the flute. The offset distance may be increased proportionally for profiles
with lower flute widths greater than those shown provided the minimum
lower flute edge distance is also satisfied.
2. Anchors may be placed in the upper flute of the steel deck profiles in
accordance with installation Detail C provided the concrete thickness above
1-1/2" the upper flute is minimum 3-1/4-inch and a minimum hole clearance of
Power-Stud+
Max. Anchor (Typ) 3/4-inch is satisfied.

1-3/4"

TECHNICAL GUIDE – CANADIAN SUPPLEMENT – Mechanical Anchors ©2024 DEWALT – REV. d


Min.
Min.
3/4"

No. 20 Gauge Steel Deck Min.


Lower Flute Edge

Installation Detail D: Installation Detail for Anchors in the Top of Concrete Over Steel Deck Floor
and Roof Assemblies (see dimensional profile requirements)1,2
LIGHTWEIGHT CONCRETE OR NORMAL WEIGHT CONCRETE 1. Anchors may be placed in the top side of concrete over steel deck profiles
OVER STEEL DECK (MINIMUM 2,500 PSI) in accordance with Detail D provided the minimum concrete thickness
Power-Stud+ Anchor (Typ) above the upper flute (topping thickness) is as illustrated and the minimum
Min. 2-1/2"
Upper Flute (Valley) spacing distance and minimum edge distances are satisfied as given in
Setting Information for Installation on the Top of Concrete-Filled Steel Deck
Assemblies Table.
2. For anchors installed in the top of concrete over steel deck profiles with
concrete thickness above the upper flute (topping thickness) greater than
or equal to the minimum concrete member thicknesses specified in
Min. Installation Table for the Power-Stud+ SD2, the minimum spacing distance
1-1/2"
and minimum edge distances may be used from this table,
Min. 1-3/4" Min. 6" (Typ) as applicable.
(Typ)
Lower Flute (Ridge)
No. 20 Gauge Steel Deck Min.
Flute Edge

4
Limit states Information ANCHORS & FASTENERS

LIMIT STATES INFORMATION


Mechanical Anchors

CODE LISTED
Tension Design Information for Power-Stud+ SD2 in Concrete1,2,12 ICC-ES ESR-2502

Nominal Anchor Diameter (inch)


Design Characteristic Notation Units
3/8 1/2 5/8 3/4
Anchor category 1,2 or 3 - 1 1 1 1
STEEL STRENGTH IN TENSION4

Minimum specified yield strength (neck) fy N/mm2 662 586 586 483

Minimum specified ultimate tensile strength (neck) futa N/mm2 827 731 731 620

Effective tensile stress area (neck) Ase, N mm2 35.6 65.0 104.5 153.2

Steel strength in tension5 Nsa kN 29.5 46.5 58.2 94.4


Steel embedment material resistance factor for
reinforcement fs - 0.85
Reduction modification factor for steel strength3 R - 0.80
CONCRETE BREAKOUT STRENGTH IN TENSION9

Effective embedment hef mm 51 51 83 83 108 95 127

Effectiveness factor for uncracked concrete kucr - 10 10 10 10

Effectiveness factor for cracked concrete kcr - 7 7 7 7


1.0 1.0 1.0 1.0
Modification factor for cracked and uncracked concrete6 ψ c,N - See See note 6 See note 6 See note 6
note 6
Material resistance factor for concrete fc - 0.65

Critical edge distance cac mm See note 6


Resistance modification factor for tension, concrete failure R - 1.0
modes, Condition B3
PULLOUT STRENGTH IN TENSION 9

Characteristic pullout strength, uncracked concrete See See See See See
Np,uncr kN 12.3 29.4
(217.2 MPa)7 note 8 note 8 note 8 note 8 note 8
Characteristic pullout strength, cracked concrete See See See See
Np,cr kN 9.6 19.5 35.1
(17.2 MPa)7 note 8 note 8 note 8 note 8
Material resistance factor for concrete fc - 0.65
Resistance modification factor for tension, pullout R - 1.0
strength, Condition B3
PULLOUT STRENGTH IN TENSION FOR SEISMIC APPLICATIONS9
See See See See
Characteristic pullout strength, seismic (17.2 MPa) 7,10
Np,eq kN 9.6 19.5 35.1
note 8 note 8 note 8 note 8
Material resistance factor for concrete fc - 0.65
Resistance modification factor for pullout strength, R 1.0
TECHNICAL GUIDE – CANADIAN SUPPLEMENT – Mechanical Anchors ©2024 DEWALT – REV. d

seismic, Condition B3

Uncracked concrete b kN/mm 1517 1258 998 747


Mean axial stiffness values
service load range11
Cracked concrete b kN/mm 87 100 113 126
For SI: 1 inch = 25.4 mm, 1 ft-lbf = 1.356 N-m, 1 ksi = 6.895 N/mm , 1 lbf = 0.0044 kN.
2

1. The data in this table is intended to be used with the design provisions of CSA A23.3 (-19, -14, -04) Annex D, as applicable; for anchors resisting seismic load combinations the additional
requirements CSA A23.3 (-19, -14, -04) D.4.3, as applicable, must apply
2. Installation must comply with published instructions and details.
3. All values of R for use with the load combinations of Division B, Part 4, Section 4.1.3 of the 2020 NBCC, 2015 NBCC or 2010 NBCC, CSA A23.3-19 Annex C, CSA A23.3-14 Annex C or CSA
A23.3-04 Annex C, as applicable. Condition B applies where supplementary reinforcement in conformance with CSA A23.3-19 D.5.3 (c), CSA A23.3-14 D.5.3(c) or CSA A23.3-04 D.5.4(c), as
applicable, is not provided, or where pullout or pryout strength governs. For cases where the presence of supplementary reinforcement can be verified, the strength reduction factors associated
with Condition A may be used
4. The Power-Stud+ SD2 is considered a ductile steel element in tension as defined by CSA A23.3-19 D.2, CSA A23.3-14 D.2 or CSA A23.3-04 D.2, as applicable.
5. Tabulated values for steel strength in tension are based on test results per ACI 355.2 and must be used for design in lieu of calculation.
6. For all design cases Ψc,N =1.0. The appropriate effectiveness factor for cracked concrete (kcr) or uncracked concrete (kuncr) must be used.
7. For all design cases Ψc,P =1.0. For the calculation of Ncpr, see CSA A23.3 (-19, -14, -04) D.6.3.
8. Pullout strength does not control design of indicated anchors. Do not calculate pullout strength for indicated anchor size and embedment.
9. Anchors are permitted to be used in lightweight concrete in accordance with CSA A23.3 (-19, -14, -04) D.4.
10. Tabulated values for characteristic pullout strength in tension are for seismic applications are based on test results per ACI 355.2 (Section 9.5), as referenced in CSA
11. Actual stiffness of the mean value varies considerably depending on concrete strength, loading and geometry of application.

5
ANCHORS & FASTENERS Limit states Information

Mechanical Anchors
CODE LISTED
Shear Design Information for Power-Stud+ SD2 in Concrete1,2,8 ICC-ES ESR-2502

Nominal Anchor Diameter (inch)


Design Characteristic Notation Units
3/8 1/2 5/8 3/4
Anchor category 1,2 or 3 - 1 1 1 1
STEEL STRENGTH IN SHEAR4

Minimum specified yield strength (threads) fy N/mm2 530 469 469 386

Minimum specified ultimate strength (threads) futa N/mm2 690 607 607 551

Effective tensile stress area (threads) Ase, V mm2 50.0 65.7 104.9 215.8

Steel strength in shear 5


Vsa kN 13.9 21.4 45.2 56.1
Steel embedment material resistance factor for
reinforcement fs - 0.85
Resistance modification factor for steel strength, shear3,4 R - 0.75
CONCRETE BREAKOUT STRENGTH IN SHEAR6
Load-bearing length of anchor mm 51 51 83 83 103 95 127
Nominal anchor diameter Vsa, eq mm 9.5 12.7 15.9 19.1
Steel embedment material resistance factor for
reinforcement fs - 0.65
Resistance modification factor for shear, concrete failure R - 1.0
modes, Condition B3
PRYOUT STRENGTH IN SHEAR6
Coefficient for pryout strength kcp - 1.0 1.0 2.0 2.0 2.0 2.0 2.0
(1.0 for hef < 2.5 in., 2.0 for hef ≥ 2.5 in.)
Effective embedment hef mm 51 51 83 83 108 95 127
Steel embedment material resistance factor for
reinforcement fs - 0.65
Resistance modification factor for pryout strength3 R - 1.0
STEEL STRENGTH IN SHEAR FOR SEISMIC APPLICATIONS

Steel strength in shear, seismic7 Vsa,eq kN 11.0 21.4 30.1 35.9


Steel embedment material resistance factor for
reinforcement fs - 0.85
Resistance modification factor for steel strength, shear, R - 0.75
seismic3
For SI: 1 inch = 25.4 mm, 1 ft-lbf = 1.356 N-m, 1 ksi = 6.895 N/mm , 1 lbf = 0.0044 kN.
2

1. The data in this table is intended to be used with the design provisions of CSA A23.3 (-19,-14, -04) Annex D, as applicable; for anchors resisting seismic load combinations the additional
requirements CSA A23.3 (-19, -14, -04) D.4.3, as applicable, must apply..
2. Installation must comply with published instructions and details.
3. All values of R for use with the load combinations of Division B, Part 4, Section 4.1.3 of the 2020 NBCC, 2015 NBCC or 2010 NBCC, CSA A23.3-19 Annex C, CSA A23.3-14 Annex C or CSA
A23.3-04 Annex C, as applicable. Condition B applies where supplementary reinforcement in conformance with CSA A23.3-19 D.5.3 (c), CSA A23.3-14 D.5.3(c) or CSA A23.3-04 D.5.4(c), as
applicable, is not provided, or where pullout or pryout strength governs. For cases where the presence of supplementary reinforcement can be verified, the strength reduction factors
associated with Condition A may be used.

TECHNICAL GUIDE – CANADIAN SUPPLEMENT – Mechanical Anchors ©2024 DEWALT – REV. d


4. The Power-Stud+ SD2 is considered a ductile steel element as defined by CSA A23.3-19 D.2, CSA A23.3-14 D.2 or CSA A23.3-04 D.2, as applicable.
5. Tabulated values for steel strength in shear are based on test results per ACI 355.2, Section 9.4 and must be used for design. These tabulated values are lower than calculated results using
equation D.31 in CSA A23.3-19 or CSA A23.3-14.
6. Anchors are permitted to be used in lightweight concrete in accordance with CSA A23.3 (-19, -14, -04) D.4.6.
7. Tabulated values for steel strength in shear are for seismic applications and based on test results in accordance with ACI 355.2 (Section 9.6), as referenced in CSA A23.3- Section D.4.3.4.

6
Limit states Information ANCHORS & FASTENERS
Mechanical Anchors

Tension and Shear Design Data for Power-Stud+ SD2 Anchors CODE LISTED
ICC-ES ESR-2502
in the Soffit of Concrete-Filled Steel Deck Assemblies1,2,7
Nominal Anchor Size (inch)
Design Characteristics Notation Units
0.375 0.5 0.625 0.75
Anchor Category 1, 2 or 3 - 1 1 1 1
mm 60 64 83 98 124 114
Minimum Nominal Embedment Depth hnom (in.) (2-3/8) (2-1/2) (3-3/4) (3-7/8) (4-7/8) (4-1/2)
mm 51 51 83 83 108 95
Effective Embedment hef (in.) (2.00) (2.00) (3.25) (3.25) (4.25) (3.75)
mm 67 70 102 108 133 27
Minimum Hole Depth ho (in.) (2-5/8) (2-3/4) (4) (4-1/4) (5-1/4) (5)
PULLOUT STRENGTH IN TENSION FOR ANCHORS IN SOFFIT OF SAND LIGHTWEIGHT AND NORMAL-WEIGHT CONCRETE OVER STEEL DECK1
According to Characteristic pullout strength, kN 8.3 9.2 17.5 20.8 32.8 21.8
Np,deck,uncr
Detail A uncracked concrete over steel deck2 (lbf) (1,855) (2,065) (3,930) (4,665) (7,365) (4,900)
4-1/2-inch-wide Characteristic pullout strength, Np,deck,cr kN 6.4 6.5 11.6 14.7 23.2 15.4
deck flute cracked concrete over steel deck2,3 (Np,deck,eq) (lbf) (1,445) (1,465) (2,600) (3,305) (5,215) (3,470)
According to Characteristic pullout strength, kN 9.9 12.4 24.9 19.9 32.3 Not
Np,deck,uncr
Detail B uncracked concrete over steel deck2 (lbf) (2,235) (2,785) (5,600) (4,480) (7,265) Applicable
3-7/8-inch-wide Characteristic pullout strength, Np,deck,cr kN 7.8 8.8 16.4 14.1 22.9 Not
deck flute cracked concrete over steel deck2,3 (Np,deck,eq) (lbf) (1,745) (1,975) (3,695) (3,175) (5,145) Applicable
According to Characteristic pullout strength, kN 7.1 9.0 Not Not Not Not
Np,deck,uncr
Detail C uncracked concrete over steel deck2 (lbf) (1,600) (2,025) Applicable Applicable Applicable Applicable
1-3/4-inch-wide Characteristic pullout strength, Np,deck,cr kN 5.6 6.4 Not Not Not Not
deck flute cracked concrete over steel deck2,3 (Np,deck,eq) (lbf) (1,250) (1,435) Applicable Applicable Applicable Applicable
Reduction factor for pullout strength6 φ - 0.65
STEEL STRENGTH IN SHEAR FOR ANCHORS IN SOFFIT OF SAND-LIGHTWEIGHT AND NORMAL WEIGHT CONCRETE OVER STEEL DECK4,5
According to Steel strength in shear, lbf 2,170 3,815 5,040 4,015 6,670 4,325
Vsa,deck
Detail A concrete over steel deck (kN) (9.7) (17.0) (22.4) (17.9) (29.7) (19.2)
4-1/2-inch-wide Steel strength in shear, seismic, lbf 1,715 3,815 5,040 2,675 4,445 2,820
deck flute Vsa,deck,eq
concrete over steel deck (kN) (7.6) (17.0) (22.4) (11.9) (19.8) (12.5)
According to Steel strength in shear, lbf 3,040 2,675 4,930 Not Not Not
Vsa,deck
Detail B concrete over steel deck (kN) (13.5) (11.9) (21.9) Applicable Applicable Applicable
3-7/8-inch-wide Steel strength in shear, seismic, lbf 2,400 2,675 4,930 Not Not Not
deck flute Vsa,deck,eq
concrete over steel deck (kN) (10.6) (11.9) (21.9) Applicable Applicable Applicable
According to Steel strength in shear, lbf 2,170 2,880 Not Not Not Not
Vsa,deck
Detail C concrete over steel deck (kN) (9.7) (12.8) Applicable Applicable Applicable Applicable
1-3/4-inch-wide Steel strength in shear, seismic, lbf 1,715 2,880 Not Not Not Not
deck flute Vsa,deck,eq
concrete over steel deck (kN) (7.6) (12.8) Applicable Applicable Applicable Applicable
Reduction factor for steel strength in shear,
concrete over steel deck6 φ - 0.65

1. For all design cases Ψc,P = 1.0. For concrete compressive strength greater than 20.68 MPa [3,000 psi], Npn=(pullout strength value from table) * (specified concrete compressive
strength/20.68)n. For all anchors n=1/2 with exception of the 3/8-inch-diameter anchor size, where n=1/3.
2. Values for Np,deck are for sand-lightweight concrete (f'c, min = 3,000 psi) and additional lightweight concrete reduction factors need not be applied. In addition, evaluation for the concrete breakout
capacity in accordance with ACI 318-19 17.6.2, ACI 318-14 17.4.2 or ACI 318 D.5.2 and CSA A23.3 (-19, -14, -04) Annex D, as applicable, is not required for anchors installed in the deck
soffit (flute).
3. Values for Np,deck,cr are applicable for seismic loading.
4. Shear loads for anchors installed through steel deck into concrete may be applied in any direction.
TECHNICAL GUIDE – CANADIAN SUPPLEMENT – Mechanical Anchors ©2024 DEWALT – REV. d

5. Values for Vsa,deck and Vsa,deck,eq are for sand-lightweight concrete (f'c, min = 20.68 MPa [3,000 psi]) and additional lightweight concrete reduction factors need not be applied. In addition,
evaluation for the concrete breakout capacity in accordance with ACI 318-19 17.7.2, ACI 318-14 17.5.2 or ACI 318 D.6.2 and CSA A23.3 (-19, -14, -04) Annex D, as applicable and the
pryout capacity in accordance with ACI 318-19 17.7.3, ACI 318-14 17.5.3 or ACI 318-11 D.6.3 and CSA A23.3 (-19, -14, -04) Annex D, as applicable, is not required for anchors installed in
the deck soffit (flute).
6. All values of φ were determined from the load combinations of IBC Section 1605.2, ACI 318 (-19 or -14) Section 5.3 or ACI 318-11 Section 9.2 and CSA A23.3 (-19, -14, -04) Annex D,
as applicable. If the load combinations of ACI 318-11 Appendix C are used, then the appropriate value of φ must be determined in accordance with ACI 318-11 D.4.4.
7. Anchors shall have an axial spacing along the flute soffit equal to the greater of 3hef or 1.5 times the flute width.

7
ANCHORS & FASTENERS Limit states Information

Mechanical Anchors
Tension and Shear Design Strengths for Power-Stud+ SD2 in Cracked Concrete1,2,3,4,5,6
Minimum Concrete Compressive Strength
Nominal Nominal f'c = 17.2 Mpa f'c = 20.7 Mpa f'c = 27.6 Mpa f'c = 41.4 Mpa f'c = 55.2 Mpa
Anchor Embed.
Diameter hnom Nr Vr Nr Vr Nr Vr Nr Vr Nr Vr
(in.) (mm.) Tension Shear Tension Shear Tension Shear Tension Shear Tension Shear
(kN) (kN) (kN) (kN) (kN) (kN) (kN) (kN) (kN) (kN)
3/8 60 6.2 6.9 6.6 7.5 7.3 8.7 8.4 8.9 9.2 8.9
64 6.9 6.9 7.5 7.5 8.7 8.7 10.7 10.7 12.3 12.3
1/2
95 12.7 13.6 13.9 13.6 16.0 13.6 19.7 13.6 22.7 13.6
98 14.3 17.4 15.7 19.1 18.1 22.0 22.1 27.0 25.6 28.8
5/8
124 21.2 28.8 23.2 28.8 26.8 28.8 32.9 28.8 37.9 28.8
114 17.5 31.3 19.2 34.3 22.1 35.8 27.1 35.8 31.3 35.8
3/4
143 22.8 35.8 25.0 35.8 28.9 35.8 35.4 35.8 40.8 35.8
■ - Anchor Pullout/Pryout Strength Controls ■ - Concrete Breakout Strength Controls ■ - Steel Strength Controls

Tension and Shear Design Strengths for Power-Stud+ SD2 in Uncracked Concrete1,2,3,4,5,6
Minimum Concrete Compressive Strength
Nominal Nominal f'c = 17.2 Mpa f'c = 20.7 Mpa f'c = 27.6 Mpa f'c = 41.4 Mpa f'c = 55.2 Mpa
Anchor Embed.
Diameter hnom Nr Vr Nr Vr Nr Vr Nr Vr Nr Vr
(in.) (mm.) Tension Shear Tension Shear Tension Shear Tension Shear Tension Shear
(kN) (kN) (kN) (kN) (kN) (kN) (kN) (kN) (kN) (kN)
3/8 60 8.0 8.9 8.8 8.9 10.1 8.9 12.4 8.9 14.3 8.9
64 9.8 9.8 10.8 10.8 12.4 12.4 15.2 13.6 17.6 13.6
1/2
95 19.1 13.6 20.9 13.6 24.2 13.6 29.6 13.6 31.6 13.6
86 20.4 24.4 22.4 26.7 25.8 28.8 31.6 28.8 36.5 28.8
5/8
117 30.3 28.8 33.2 28.8 38.3 28.8 39.6 28.8 39.6 28.8
102 25.0 35.8 27.4 35.8 31.6 35.8 38.7 35.8 44.7 35.8
3/4
143 38.6 35.8 42.3 35.8 48.9 35.8 59.9 35.8 64.2 35.8
■ - Anchor Pullout/Pryout Strength Controls ■ - Concrete Breakout Strength Controls ■ - Steel Strength Controls

1- Tabular values are provided for illustration and are applicable for single anchors installed in normal-weight concrete with minimum slab thickness, ha = hmin, and with
the following conditions:
- ca1 is greater than or equal to the critical edge distance, cac (table values based on ca1 = cac).
- ca2 is greater than or equal to 1.5 times ca1.
2- Calculations were performed following methodology in CSA A23.3 (-19,-14,-04), Annex D. The load level corresponding to the failure mode listed (e.g. For tension:
steel, concrete breakout and pullout; For shear: steel, concrete breakout and pryout). Furthermore, the capacities for concrete breakout strength in tension and pryout
in shear are calculated using the effective embedment values, hef, for the selected anchors as noted in the design information tables. Please also reference the
installation specifications for more information.
3- Material Resistance factors (ø) are in accorance with CSA A23.3 (-19,-14,-04) Annex D, Sections 8.4.2 and 8.4.3. Mondification Factors (R) are in accordance with
CSA A23.3 (-19,-14,-04) Annex D, Section D.5.3 Condition B; it is assumed that supplementary reinforcement not present. Material resistance factors for steel
strength are taken as 0.85 for tension and shear; Modification factors are taken as 0.80 for Tension and 0.75 for Shear; values correspond to ductile steel elements.

TECHNICAL GUIDE – CANADIAN SUPPLEMENT – Mechanical Anchors ©2024 DEWALT – REV. d


4- Tabular values are permitted for short-term static loads only, seismic loading is not considered with these tables.
5- For designs that include combined tension and shear, the interaction of tension and shear loads must be calculated in accordance with CSA A23.3 (-19,-14,-04) Annex
D, Section D.8.
6- Interpolation is not permitted to be used with the tabular values. For intermediate base material compressive strengths, please see CSA A23.3 Annex D and information
contained in this product supplement. For other design conditions including seismic considerations please see CSA A23.3 Annex D.

8
Performance Data (ASD) ANCHORS & FASTENERS

PERFORMANCE DATA (ASD)


Mechanical Anchors

Converted Allowable Loads for Power-Stud+ SD2 in Cracked Concrete1,2


Minimum Concrete Compressive Strength
Nominal Nominal f'c = 17.2 Mpa f'c = 20.7 Mpa f'c = 27.6 Mpa f'c = 41.4 Mpa f'c = 55.2 Mpa
Anchor Embed.
Size hnom Tallowable,ASD Vallowable,ASD Tallowable,ASD Vallowable,ASD Tallowable,ASD Vallowable,ASD Tallowable,ASD Vallowable,ASD Tallowable,ASD Vallowable,ASD
(in.) (mm) Tension Shear Tension Shear Tension Shear Tension Shear Tension Shear
(kN) (kN) (kN) (kN) (kN) (kN) (kN) (kN) (kN) (kN)

3/8 60 4.5 4.9 4.7 5.4 5.2 6.2 6.0 6.3 6.6 6.3
64 4.9 4.9 5.4 5.4 6.2 6.2 7.6 7.6 8.8 8.8
1/2
95 9.1 9.7 9.9 9.7 11.5 9.7 14.1 9.7 16.2 9.7
98 10.2 12.4 11.2 13.6 12.9 15.7 15.8 19.3 18.3 20.6
5/8
124 15.1 20.6 16.6 20.6 19.2 20.6 23.5 20.6 27.1 20.6
114 12.5 22.4 13.7 24.5 15.8 25.5 19.4 25.5 22.4 25.5
3/4
143 16.3 25.5 17.9 25.5 20.6 25.5 25.3 25.5 29.2 25.5
1. Allowable load values are calculated using a conversion factor, α, from the Factored Resistances and conditions shown on the previous page.
2. Tabulated allowable load values assume 50% dead load and 50% live load, with controlling load combination 1.2D + 1.6L. Calculated weighted average for the conversion factor
α : 1.2(0.5) + 1.6(0.5) = 1.4.

Converted Allowable Loads for Power-Stud+ SD2 in Uncracked Concrete1,2


Minimum Concrete Compressive Strength
Nominal Nominal
Anchor Embed. f'c = 17.2 Mpa f'c = 20.7 Mpa f'c = 27.6 Mpa f'c = 41.4 Mpa f'c = 55.2 Mpa
Size hnom
(in.) (mm) Tallowable,ASD Vallowable,ASD Tallowable,ASD Vallowable,ASD Tallowable,ASD Vallowable,ASD Tallowable,ASD Vallowable,ASD Tallowable,ASD Vallowable,ASD
Tension Shear Tension Shear Tension Shear Tension Shear Tension Shear
(kN) (kN) (kN) (kN) (kN) (kN) (kN) (kN) (kN) (kN)

3/8 60 5.7 6.3 6.3 6.3 7.2 6.3 8.9 6.3 10.2 6.3
64 7.0 7.0 7.7 7.7 8.9 8.9 10.9 9.7 12.6 9.7
1/2
95 13.7 9.7 15.0 9.7 17.3 9.7 21.2 9.7 22.6 9.7
98 14.6 17.4 16.0 19.1 18.4 20.6 22.6 20.6 26.1 20.6
5/8
124 21.6 20.6 23.7 20.6 27.4 20.6 28.3 20.6 28.3 20.6
114 17.9 25.5 19.6 25.5 22.6 25.5 27.7 25.5 31.9 25.5
3/4
143 27.9 25.5 30.2 25.5 34.9 25.5 42.8 25.5 45.9 25.5
1. Allowable load values are calculated using a conversion factor, α, from the Factored Resistances and conditions shown on the previous page.
2. Tabulated allowable load values assume 50% dead load and 50% live load, with controlling load combination 1.2D + 1.6L. Calculated weighted average for the conversion factor
α : 1.2(0.5) + 1.6(0.5) = 1.4.

Ultimate and Allowable Load Capacities for Power-Stud+ SD2 in Grouted Filled Concrete Masonry1,2,3
Minimum Masonry Compressive Strength,
TECHNICAL GUIDE – CANADIAN SUPPLEMENT – Mechanical Anchors ©2024 DEWALT – REV. d

Installation f’m = 1,500 psi (10.4 MPa)


Nominal Minimum
Torque Ulimate Allowable Ulimate Allowable Minimum End
Anchor Embedment Installation Distance (Typ)
Tinst Load Load Load Load
Size Depth Location3
ft.-lb. Tension Tension Shear Shear
in. (mm)
(N-m) lbs. lbs. lbs. lbs. Minimum
Edge Distance
(kN) (kN) (kN) (kN) (Typ)

Wall Face or End


20 2-1/2 1,670 335 2,075 415 Grout Filled
CMU (Typ)
3/8 Min. 2-1/2" Edge and
(27) (51) (7.4) (1.5) (9.2) (1.8)
End Distances Mortar Joint

Wall Face or End Wall Face


2-1/2 2,295 460 1,310 260
Min. 3" Edge and Permissible Anchor Locations
(51) (10.2) (2.0) (5.8) (1.2)
40 End Distances (Un-hatched Area)
1/2 (54) Top of Wall
3-3/4 3,320 665 1,140 230
Min. 1-3/4" Edge and
(95) (14.8) (3.0) (5.1) (1.0)
4" End Distances
1. Tabulated load values are for anchors installed in minimum 6-inch wide, minimum Grade N, Type II, lightweight, medium-weight or normal-weight concrete masonry units conforming to ASTM
C90. Mortar must be Type N, S or M. Masonry compressive strength must be at the specified minimum at the time of installation.
2. Allowable load capacities listed are calculated using and applied safety factor of 5.0. Consideration of safety factors of 10 or higher may be necessary depending upon the application such as
life safety.
3. Anchor installations into grouted masonry walls are limited to one per masonry cell. The tabulated values are for anchors installed at a minimum of 16 anchor diameters on center for 100
percent capacity.

9
ANCHORS & FASTENERS Ordering Information

ORDERING INFORMATION

Mechanical Anchors
Power-Stud+ SD2 (Carbon Steel Body with Stainless Steel Expansion Clip)
Approx. Suggested ANSI Carbide Drill Bit Cat. No.
Pack Carton
Cat. No. Anchor Size Thread Full Head Hollow Bit Hollow Bit
Qty. Qty. SDS-Plus SDS-Max
Length SDS-Plus SDS-Plus SDS-Max
7413SD2-PWR 3/8" x 3" 1-3/4" 50 300 DW5527 DW5427 - - -
7414SD2-PWR 3/8" x 3-1/2" 2-1/4" 50 300 DW5527 DW5427 - - -
7415SD2-PWR 3/8" x 3-3/4" 2-1/2" 50 300 DW5527 DW5427 - - -
7416SD2-PWR 3/8" x 5" 3-3/4" 50 300 DW55300 DW5429 - - -
7422SD2-PWR 1/2" x 3-3/4" 2-1/8" 50 200 DW5537 DW5437 DW5803 DWA54012 -
7423SD2-PWR 1/2" x 4-1/2" 2-7/8" 50 200 DW5539 DW5438 DW5803 DWA54012 -
7424SD2-PWR 1/2" x 5-1/2" 3-7/8" 50 150 DW5539 DW5438 DW5803 DWA54012 -
7426SD2-PWR 1/2" x 7" 5-3/8" 25 100 DW5539 DW5438 DW5803 DWA54012 -
7427SD2-PWR 1/2" x 8-1/2" 6-7/8" 25 100 DW5539 DW5439 DW5804 DWA54012 -
7435SD2-PWR 5/8" x 4-3/4" 2-7/8" 25 100 - DW5446 DW5806 DWA54058 DWA58058
7433SD2-PWR 5/8" x 5" 3-1/8" 25 50 - DW5446 DW5806 DWA54058 DWA58001
7434SD2-PWR 5/8" x 6" 4-1/8" 25 75 - DW5446 DW5806 DWA54058 DWA58001
7436SD2-PWR 5/8" x 7" 5-1/8" 25 75 - DW5447 DW5806 DWA54058 DWA58001
7438SD2-PWR 5/8" x 8-1/2" 6-5/8" 25 75 - DW5447 DW5809 DWA54058 DWA58001
7442SD2-PWR 3/4" x 5-1/2" 3-1/4" 20 60 - DW5453 DW5810 DWA54074 DWA58034
7444SD2-PWR 3/4" x 6-1/4" 4" 20 60 - DW5455 DW5810 DWA54074 DWA58034
7446SD2-PWR 3/4" x 7" 4-3/4" 20 60 - DW5455 DW5810 DWA54074 DWA58034
7448SD2-PWR 3/4" x 8-1/2" 6-1/4" 10 40 - DW5455 DW5812 DWA54074 DWA58034
The published size includes the diameter and the overall length of the anchor.
Allow for fixture thickness (as applicable) plus one anchor diameter for the nut and washer thickness when selecting a length.
All anchors are packaged with nuts and washers.
Hollow drill bits must be used with a dust extraction vacuum (e.g. Cat. No. DW012).

TECHNICAL GUIDE – CANADIAN SUPPLEMENT – Mechanical Anchors ©2024 DEWALT – REV. d

10