Lecture 13 Basic Protection System Updated
Lecture 13 Basic Protection System Updated
❑ However, If the short circuit fault persists on a power system for an extended
period, the following problems may occur:
1. Damage to the equipment that is in the vicinity of the fault due to heavy
currents, unbalanced currents, or low voltages produced by the short circuit.
❑ They receive input from sensors and compare with the Set Value (Trip Value)
then provide output and isolate electrical equipment from the system.
Attributes of Protective Relays
❑ The principal function of protective relaying is to cause the
prompt removal from service of any element of the power system
when it starts to operate in an abnormal manner or interfere with
the effective operation of the rest of the system.
❑ Fast
❑ Reliable
❑ Selective
❑ Simple
❑ Cheap
Zone of Protection
❑ Consider the figure below. The closed dashed lines indicate the five zones of protection
in which this power system is divided.
❑ Each zone contains one or more power system components in addition to two CBs.
❑ Each CB is included in two neighbouring zones of protection.
❑ The boundary of each zone defines a portion of the power system such that for a fault
anywhere withing that zone the protection system responsible for that zone takes active
to isolate everything within that zone from the rest of the system.
Zone of Protection
❑ The CBs help define the boundaries of the zone of protection.
❑ The neighbouring zones always overlap. This overlap is necessary, since without it a
small part of the system which falls between the neighbouring zones, however small it
may be, would be left without protection. By overlapping neighbouring zones, no part
of the power system is left without protection.
❑ Reach: Area of responsibility of the protection system is known as reach.
Measuring Equipment--Transducers
Transducers
Two transducers:
1. Current transformer (CT)
2. Potential transformer (PT)
Burden on Transducer
❑ The load on CTs and PTs are commonly known as their burden. The term burden
usually means the impedance connected to the transformer secondary winding.
For example, a transformer delivering 5 A to a resistive burden of 0.1 Ohm may also
be said to have a burden of 2.5 voltampere at 5 Ampere.
Current transformer (CT)
Current transformer (CT)
❑ Consider Fig. 1.3 which represent a schematic of a CT.
❑ The primary winding of a CT usually consists of a single turn, in Fig. 1.3, by a
straight line marked a & b.
❑ This single turn is obtained by threading the primary conductor through one or
more toroidal steel core. See working principle.
Transformer
—primary winding at the system voltage
1. Magnitude relays
2. Directional relays
4. Differential relays
5. Pilot relays.
Ratio relays (Distance or Impedance Relay)
❑ So, Z plotted in the complex plane under normal system conditions will lie
outside the circle of radius |Zr| and consequently the CB will not trip.
❑ Under fault conditions, Z will be inside the circle of |Zr|, the CB will trip.
Differential Relays:
❑ Consider the zone of protection of one phase of a generator winding in Fig. 1.6.
❑ Two current transformers having the same turns ratios are placed at the boundaries
of the zone of protection (two for each phase of a three-phase unit).
𝐼1 − 𝐼2 = 0
𝐼1 − 𝐼2 = 𝐼𝑓
SF6 CB
Introduction to Circuit Breakers (CB)
❖ The automatic control employs relays and operates only under fault conditions.
Introduction to Circuit Breakers (CB)
Operating Principle of CB
❑ Under normal operating conditions, these contacts remain closed and will not
open automatically until and unless the system becomes faulty. Of course, the
contacts can be opened manually or by remote control whenever desired.
❑ When a fault occurs on any part of the system, the trip coils of the circuit
breaker get energized and the moving contacts are pulled apart by some
mechanism, thus opening the circuit.
Introduction to Circuit Breakers (CB)
Operating Principle of CB
❑ When the contacts of a circuit breaker are separated under fault conditions, an
arc is struck between them. The current is thus able to continue until the
discharge ceases.
❑ The production of arc not only delays the current interruption process, but it
also generates enormous heat which may cause damage to the system or to the
circuit breaker itself.
❑ Therefore, the main problem in a circuit breaker is to extinguish the arc within
the shortest possible time so that heat generated by it may not reach a
dangerous value.
Introduction to Circuit Breakers (CB)
Classification of CB
Based on medium used for arc extinction, CBs are classified as:
1. Oil circuit breakers which employ some insulating oil (e.g., transformer
oil) for arc extinction.
❑ When a fault occurs, there is considerable asymmetry in the fault current due to the
presence of a d.c. component.
❑ The d.c. component dies away rapidly, a typical decrement factor being 0·8 per cycle.
❖ Thus, if I is the rated breaking current in amperes and V is the rated service line
voltage in volts, then for a 3-phase circuit,
Introduction to Circuit Breakers (CB)
Ratings of CBs Making capacity
❑ The peak value of current (including d.c. component) during the first cycle of
current wave after the closure of circuit breaker is known as making capacity
❑ It may be noted that the definition is concerned with the first cycle of current
wave on closing the circuit breaker. This is because the maximum value of fault
current possibly occurs in the first cycle only when maximum asymmetry occurs
in any phase of the breaker.
❑ The short-time rating of a circuit breaker depends upon its ability to withstand
❑ The oil circuit breakers have a specified limit of 3 seconds when the ratio of
symmetrical breaking current to the rated normal current does not exceed 40.
However, if this ratio is more than 40, then the specified limit is 1 second.