Manual - Tech - IP710-DL Installation Instructions
Manual - Tech - IP710-DL Installation Instructions
COLLECTION BY LEVITON
INSTALLATION INSTRUCTIONS WARNING: TO BE INSTALLED AND/OR USED IN ACCORDANCE WITH APPROPRIATE ELECTRICAL CODES AND REGULATIONS. WARNING: IF YOU ARE NOT SURE ABOUT ANY PART OF THESE INSTRUCTIONS, CONSULT A QUALIFIED ELECTRICIAN. WARNING: TO AVOID OVERHEATING AND POSSIBLE DAMAGE TO THIS DEVICE AND OTHER EQUIPMENT, USE ONLY WITH THE ADVANCE TRANSFORMER 120/277V
MARK VII OR OSRAM SYLVANIA QUICKTRONIC HELIOS ELECTRONIC BALLASTS FOR CONTROLLING THE SPECIFIC FLUORESCENT LAMPS.
OTHER CAUTIONS:
1. USE ONLY ONE (1) DIMMER IN A 3-WAY CIRCUIT. THE SWITCH(ES) WILL TURN THE LIGHT ON AT THE BRIGHTNESS LEVEL SELECTED AT THE DIMMER. 2. LIGHTING FIXTURE AND DIMMER MUST BE GROUNDED. 3. DISCONNECT POWER WHEN SERVICING OR CHANGING LAMPS. 4. USE THIS DEVICE ONLY WITH COPPER OR COPPER CLAD WIRE. WITH ALUMINUM WIRE USE ONLY DEVICES MARKED CO/ALR OR CU/AL. MULTI-GANG INSTALLATION: When ganging dimmers, the side sections of the mounting strap must be removed. Use pliers to carefully bend side sections back and forth until they break off (see Chart and Figure 1). MAXIMUM BULB WATTAGE: Mark VII and OSRAM Sylvania Quicktronic Helios ballast are rated in Volt-Amps (VA). The maximum number of ballast per dimmer is based on the load VA rating (see Maximum Load per Dimmer table) or 50 ballast maximum, which ever is less. The maximum bulb wattage is determined by the efficiency of the ballast. The following tables show the maximum number of ballasts that can be connected to a single dimmer for different Mark VII or OSRAM Sylvania Quicktronic Helios ballasts. FOR DIRECT LOAD APPLICATION CONFIGURATIONS (WIRING DIAGRAMS 1, 2 AND 3), REFER TO TABLE 1 AND TABLE 2 FOR BALLAST INFORMATION. NOTE: For additional switching capacity (up to 50 ballast), use dimmers in conjuction with a Leviton ODP 120/277V Power Pack.
MAXIMUM LOAD PER DIMMER FOR MULTI-GANG Two Gang 1200 VA 1500 VA More than 2 Gang 1200 VA 1500 VA
ON/OFF LED
INSTALLATION INSTRUCTIONS
DI-000-IP710-00B
FOR APPLICATIONS USING LEVITON'S ODP (WIRING DIAGRAMS 4 AND 5), ODP SWITCH RATINGS ARE AS FOLLOWS (REFER TO ODP INSTRUCTION SHEET FOR ADDITIONAL INFORMATION): ODP SWITCH RATINGS: 20 Amps for 120 and 277 VAC Ballast
TO INSTALL: 1. WARNING: TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER AT CIRCUIT BREAKER
OR FUSE AND TEST THAT POWER IS OFF BEFORE WIRING! 2. Remove existing wallplate and switch, if applicable. 3. Remove 3/4" (1.9 cm) of insulation from each circuit conductor. Make sure the ends of wires are straight.
4. Connect wires per appropriate WIRING DIAGRAM and FIGURE 3 as follows: NOTE: Common terminal of 3-Way Switch is usually labeled and/or BLACK. Twist strands of each lead tightly and, with circuit conductors, push firmly into appropriate wire connector (see chart for allowable wire connector and number of conductor combinations). Screw connectors on clockwise making sure no bare wires show below the wire connectors. Secure each connector with electrical tape. NOTE: For single pole applications, cap one BLACK lead with an appropriate size wire connector. Secure connector with electrical tape. NOTE: For long low-voltage wiring runs or where excessive electrical noise exists, shielded cable or conduit is recommended. 5. Installation may now be completed by carefully positioning all wires to provide room in outlet box for dimmer. Mount dimmer into box with mounting screws supplied. Attach Decora wallplate. 6. Restore power at circuit breaker or fuse. INSTALLATION IS COMPLETE.
Strap
5. Moving the slider up or down will automatically engage the slider control mechanism. Replace Decora wallplate. The color conversion is complete.
TO OPERATE
GREEN LED will remain ON when the lights are OFF - Facilitates access to switch in the dark. Depress push-button switch to ON position - Lights will turn ON (GREEN LED will turn OFF). Move slider control lever lights will brighten or dim to level set. Depress push-button switch to OFF position - Lights will turn OFF (GREEN LED will turn ON). Lights will turn ON at set brightness level (from either switch location in a 3-way or 4-way installation).
TROUBLESHOOTING
Lights do not go to full output - Move the slider to the top and locate the trim pot, located on the back top left of the dimmer. Using a small screwdriver, adjust the high end trim until the desired output is achieved. Lights do not dim low enough - Check the ballast output with a light meter when no other sources of illumination are present, or subtract out other sources from both high and low readings. The ratio of the low reading and the high reading should be at lest 1:20 or 0.05 for the Advance Mark VII RZT Series. When taking the high end measurement, adjust the trimpot to provide maximum output. - If 100% and minimum output is not achieved, check to see that the Purple and Gray wires are not miswired in any fixtures.
For Technical Assistance Call: 1-800-824-3005 (U.S.A. Only) 1 800 405-5320 (Canada Only) www.leviton.com
DI-000-IP710-00B
DI-000-IP710-00B
9/26/02, 10:15 AM
TABLE 1
Cat. No. ISD BC, 120/277V, For use with Advance Transformer 120/277V Mark VII
Advance Mark VII Part No. RZT-I32 RZT-2S32 RZT-3S32 RZT-132 RZT-2S32 RZT-3S32 RZT-1TTS40 VZT-4S32 VZT-132 VDC-2S32-TP VZT-2S32 VZT-3S32 VZT-4S32 VZT-132 VDC-2S32-TP VZT-2S32 VZT-3S32 VZT-4S32 IZT-1T42-M2-BS@120 IZT-1T42-M2-BS@277 IZT-1T42-M2-LD@120 IZT-1T42-M2-LD@277 IZT-2Q26-M2-BS@120 IZT-2Q26-M2-BS@277 IZT-2Q26-M2-LD@120 IZT-2Q26-M2-LD@277 IZT-1T42-M2-BS@120 IZT-1T42-M2-BS@277 IZT-1T42-M2-LD@120 IZT-1T42-M2-LD@277 IZT-2T42-M3-BS@120 IZT-2T42-M3-BS@277 IZT-2T42-M3-LD@120 IZT-2T42-M3-LD@277 IZT-1T42-M2-BS@120 IZT-1T42-M2-BS@277 IZT-1T42-M2-LD@120 IZT-1T42-M2-LD@277 IZT-2T42-M3-BS@120 IZT-2T42-M3-BS@277 IZT-2T42-M3-LD@120 IZT-2T42-M3-LD@277 IZT-1T42-M2-BS@120 Lamp F25T8 F25T8 F25T8 F32T8 F32T8 F32T8 FT40W/2G11 F17T8 F25T8 F25T8 F25T8 F25T8 F25T8 F32T8 F32T8 F32T8 F32T8 F32T8 CFM26W/GX24Q CFM26W/GX24Q CFM26W/GX24Q CFM26W/GX24Q CFM26W/GX24Q CFM26W/GX24Q CFM26W/GX24Q CFM26W/GX24Q CFM32W/GX24Q CFM32W/GX24Q CFM32W/GX24Q CFM32W/GX24Q CFM32W/GX24Q CFM32W/GX24Q CFM32W/GX24Q CFM32W/GX24Q CFM42W/GX24Q CFM42W/GX24Q CFM42W/GX24Q CFM42W/GX24Q CFM42W/GX24Q CFM42W/GX24Q CFM42W/GX24Q CFM42W/GX24Q CFQ26W/G24Q Max. # Ballasts/Dimmer for Multi-gang 1500VA@ Voltage 1200VA@ 120V 277V N/A 120 47 120 120 120 120 120 120 277 277 277 277 277 277 277 277 277 277 277 120-277 120-277 120-277 120-277 120-277 120-277 120-277 120-277 120-277 120-277 120-277 120-277 120-277 120-277 120-277 120-277 120-277 120-277 120-277 120-277 120-277 120-277 120-277 120-277 120-277 23 15 35 18 12 31 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 40 N/A 40 N/A 20 N/A 20 N/A 30 N/A 30 N/A 15 N/A 15 N/A 23 N/A 23 N/A 12 N/A 12 N/A 40 N/A N/A N/A N/A N/A N/A 21 50 31 30 19 15 45 24 22 15 12 N/A 49 N/A 49 N/A 25 N/A 25 N/A 38 N/A 38 N/A 20 N/A 20 N/A 30 N/A 30 N/A 15 N/A 15 N/A QT1x54/277PHO-Dim QT2x54/277PHO-Dim QT1x54/277PHO-Dim QT2x54/277PHO-Dim QT1x54/277PHO-Dim QT2x54/277PHO-Dim QT1x54/120PHO-Dim QT2x54/120PHO-Dim QT1x54/120PHO-Dim QT2x54/120PHO-Dim QT1x54/120PHO-Dim QT2x54/120PHO-Dim QTP1x32T8/277 Dim5-B QTP1x32T8/277 Dim5-B QTP1x32T8/277 Dim5-B QTP1x32T8/277 Dim5-B QTP1x32T8/277 Dim5-B QTP1x32T8/277 Dim5-B QTP1x32T8/277 Dim5-B QTP2x32T8/277 Dim5-B QTP2x32T8/277 Dim5-B QTP2x32T8/277 Dim5-B QTP3x32T8/277 Dim5-Q QTP3x32T8/277 Dim5-Q QTP3x32T8/277 Dim5-Q QTP4x32T8/277Dim10-B QTP4x32T8/277 Dim10-B QTP4x32T8/277 Dim10-B
TABLE 2
Cat. No. ISD BC, 120/277V, For use with OSRAM Sylvania Quicktronic 120/277V Helios Electronic Ballasts
OSRAM Sylvania Quicktronic Helios Part No. QTP1x32T8/120 Dim5-B QTP1x32T8/120 Dim5-B QTP1x32T8/120 Dim5-B QTP1x32T8/120 Dim5-B QTP1x32T8/120 Dim5-B QTP1x32T8/120 Dim5-B QTP1x32T8/120 Dim5-B QTP2x32T8/120 Dim5-B QTP2x32T8/120 Dim5-B QTP2x32T8/120 Dim5-B QTP3x32T8/120 Dim5-Q QTP3x32T8/120 Dim5-Q QTP3x32T8/120 Dim5-Q QTP4x32T8/120 Dim10-B QTP4x32T8/120 Dim10-B QTP4x32T8/120 Dim10-B Lamp F17T8 FBO16T8 F25T8 FBO24T8 F32T8 FBO32T8/U/6 FBO31T8/U F32T8 FBO32T8/U/6 FBO31T8/U F32T8 FBO32T8/U/6 FBO31T8/U F32T8 FBO32T8/U/6 FBO31T8/U F17T8 FBO16T8 F25T8 FBO24T8 F32T8 FBO32T8/U/6 FBO31T8/U F32T8 FBO32T8/U/6 FBO31T8/U F32T8 FBO32T8/U/6 FBO31T8/U F32T8 FBO32T8/U/6 FBO31T8/U FP54T5HO FP54T5HO FT55DL FT55DL FPC55 FPC55 FP54T5HO FP54T5HO FT55DL FT55DL FPC55 FPC55 Max. # Ballasts/Dimmer for Multi-gang 1500VA@ Voltage 1200VA@ 277V 120V N/A 120 50 120 120 120 120 120 120 120 120 120 120 120 120 120 120 120 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 277 120 120 120 120 120 120 277 277 277 277 277 277 50 43 45 37 37 38 17 17 18 12 12 13 9 9 9 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 18 9 19 10 19 10 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 50 50 50 50 45 45 45 21 21 22 15 15 16 9 9 10
3-Way Switch
3-Way Dimmer
White
Primary Side To Lamps
Neutral (White)
3-Way Switch
4-Way Switch
Dimmer
Purple Gray Black Red Black
Red 0-10 VDC Ballast Blue Yellow
Black
To Additional Ballast
Green Ground
Green Ground
White
Primary Side To Lamps
Dimmer
ODP
120V/277V
Cap off Black wire with Wire Connector
ODP
Hot (Black) To circuit #2 120V/277V
Cap off Black wire with Wire Connector
To Additional Ballast
Hot (Black)
Red Black
Black Blue
Primary Side
To Lamps
Red
Black
0-10 VDC Ballast
White
Black
0-10 VDC Ballast
White
White
Neutral (White)
Dimmer
Purple Gray Red Black White
Primary Side Red
Hot (Black)
Common Terminal (Black Screw)
To Additional Ballast
Red
Blue Yellow
Black
Black Red
Green Ground
Black
Black
Red Black
Red 0-10 VDC Ballast Blue Yellow
To Lamps
Neutral (White)
Green Ground
Neutral (White)
DI-000-IP710-00B
DI-000-IP710-00B
9/26/02, 10:15 AM
17.0
Front Panel
Cat. No.
11.0
3
FOLD SCHEME 2 1
LEVITON INSTRUCTION SHEET/MANU ON INSTRUCTION SHEET/MANUAL SPECIFICATIONS TIONS
DI-40x-IP710-00A Black
Helvetica
50 Lb. offset
Paper size: Overall size: 17" x 11" Final fold size: 2.83" x 3.66"
DOCUMENTATION DOCUMENT
Front Panel
Cat. No.
rde
N/A 07/18/02
DI-000-IP710-00B
9/26/02, 10:15 AM