Battery Charging Tutorial
Battery Charging Tutorial
Current battery charging technology relies on microprocessors (computer chips) to recharge, using 3 stage (or 2 or 4 stage) regulated charging. These are the "smart chargers", and quality units generally are not found in discount stores. The three stages or steps in lead/acid battery charging are bulk, absorption, and float. Qualification, or equalization are sometimes considered another stage. A 2 stage unit will have bulk and float stages. It is important to use battery manufacturer's recommendations on charging procedures and voltages, or a quality microprocessor controlled charger to maintain battery capacity and service life. The "smart chargers" are profiled with contemporary charging philosophy in mind, and also take information from the battery to provide maximum charge benefit with minimum observation. Some gel cell and AGM batteries may require special settings or chargers. Our units are selected for their suitability on the battery types they specify. Gel batteries generally require a specific charge profile, and a gel specific or gel selectable or gel suitable charger is called for. The peak charging voltage for Gel batteries is 14.1 or 14.4 volts, which is lower than a wet or AGM type battery needs for a full charge. Exceeding this voltage in a Gel battery can cause bubbles in the electrolyte gel, and permanent damage. Most battery manufacturers recommend sizing the charger at about 25% of the battery capacity (ah = amp hour capacity). Thus, a 100 ah battery would take about a 25 amp charger (or less). Larger chargers may be used to decrease charge time, but may decrease battery life. Smaller chargers are fine for long term floating, e.g. a 1 or 2 amp "smart charger" can be used for battery maintenance between higher amp cycle use. Some batteries specify 10% of capacity (.1 X C) as the charge rate, and while this doesn't hurt anything, a good microprocessor charger of the appropriate charge profile should be fine up to the 25% rate. You talk to different engineers, even at the same company, you get different answers.
Equalization
Equalization is essentially a controlled over charge. Some charger manufacturers call the peak voltage the charger attains at the end of the BULK mode (absorption voltage) an equalization voltage, but technically it's not. Higher capacity wet (flooded) batteries sometimes benefit from this procedure, particularly the physically tall batteries. The electrolyte in a wet battery can stratify over time, if not cycled occasionally. In equalization, the voltage is brought up above typical peak charging voltage (to 15 to 16 volts in a 12 volt system) well into the gassing stage, and held for a fixed (but limited) period. This stirs up the chemistry in the entire battery, "equalizing" the strength of the electrolyte, and knocking off any loose sulphation that may be on the battery plates. The construction of AGM and Gel batteries all but eliminates any stratification, and most all manufacturers of this type do not recommend it (advising against it). Some manufacturers (notably Concorde) list a procedure, but voltage and time are critical to avoid battery damage.
Battery Testing
Battery testing can be done in several ways. The most popular includes measurement of specific gravity, and battery voltage. Specific gravity applies to wet cells with removable caps, giving access to the electrolyte. To measure specific gravity, buy a temperature compensating hydrometer at an auto parts store or tool supply. To measure voltage, use a digital voltmeter in the DC voltage setting. The surface charge must be removed from a freshly charged battery before testing. A 12 hour lapse after charging qualifies, or you may remove the surface charge with a load (20 amps for 3 plus minutes).
Voltage 12V 6V 12.7 6.3 12.4 6.2 12.2 6.1 12.0 6.0 11.9 6.0
Load testing is another method of testing a battery. Load testing removes amps from a battery (similar to starting an engine). Some battery companies label their battery with the amp load for testing. This number is usually 1/2 of the CCA rating. For instance, a 500 CCA battery would load test at 250 amps for 15 seconds. A load test can only be performed if the battery is at or near a full charge. Some electronic load testers apply a 100 amp load for 10 seconds, and then display battery voltage. This number is compared to a chart on the tester, based on CCA rating to determine battery condition. Sulphation of batteries starts when specific gravity falls below 1.225 or voltage measures less than 12.4 (12v Battery ) or 6.2 (6 volt battery). Sulphation can harden on the battery plates if left long enough, reducing and eventually destroying the ability of the battery to generate rated volts and amps. There are devices for removing hard sulphation, but the best practice is preventing formation by proper battery care and recharging after a discharge cycle. Sulphation is the main reason a significant portion of lead acid batteries don't attain their chemical life span.