Section A: - Q 4400021172 1-2434056.03 NJN419 342108 SA B

The document contains detailed engineering drawings and specifications for a 500MVA power transformer installation, including dimensions, materials, and construction notes. It emphasizes the importance of following approved samples and includes various details regarding waterproofing and structural elements. All dimensions are provided in metric units, and specific references to other sheets and details are made throughout the document.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
34 views1 page

Section A: - Q 4400021172 1-2434056.03 NJN419 342108 SA B

The document contains detailed engineering drawings and specifications for a 500MVA power transformer installation, including dimensions, materials, and construction notes. It emphasizes the importance of following approved samples and includes various details regarding waterproofing and structural elements. All dimensions are provided in metric units, and specific references to other sheets and details are made throughout the document.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.

B 03 of 05
NJN419 SA-342108 Q 4400021172 1-2434056.03
NOTES
REV. NO. SHEET NO. DRAWING NUMBER PLANT NO. INDEX JOB ORDER NO. CONTRACT NO. 1. ALL DIMENSIONS ARE IN MILLIMETERS AND ELEVATIONS ARE IN
METERS UNLESS OTHERWISE NOTED.

2. FOR OTHER NOTES REFER SHEET-01.

| OF 500MVA
700
POWER RANSFORMER
EL. +8.980 12340

300
EL. +8.680

8980
FOR DETAILS REFER TO PRE-CAST
PLAN & SECTION & DETAILS 250 850 1720 2700 2400 2700 2320 850 250

FIRE WALL
DRAWING NO. SA-342146

600 GRAVEL GRAVEL GRAVEL GRAVEL SEE DETAIL-03


SEE DETAIL-03 SHEET-05
EL. -0.300 EL. -0.300

100
NON SHRINK GROUT EL.(+) 0.000 SHEET-05 EL.(+) 0.000 EL.(+) 0.000
(TOG) (TOG)
(TOC) (TOC) (TOC) EL.(+) 0.000 (TOC)
(MIN.)

(MIN.)

(MIN.)
300

300

300
FGL FGL FGL

{16@200 C/C 24-{16 {16@200 C/C


2 COATS OF {12@150 C/C GRAPHIC SCALE:
{10@200 {12@150 C/C {12@150 {10@200
COAL TAR EPOXY C/C
0 0.1 0.5 1m
{12@150 C/C C/C {12@150 C/C
1000

1000
167 {12@150
{10@200

2310

2310
{12@150 C/C {12@150 C/C SCALE : 1 : 10
(1X2){200MM PVC PIPE @ -1.000M & C/C
{12@150 C/C
-1.400M COS TO TOA {12@150 C/C

1820

1820
{12@150 C/C 24-{16
TWO(2) LAYERS OF 4mm
400

400
{10@200 C/C TWO(2) LAYERS OF 4mm
THK. WATERPROOFING {12@150 C/C GRAPHIC SCALE:
THK. WATERPROOFING
MEMBRANE WITH 15mm THK. OIL LEVEL 0 0.5 1 1.5 2 2.5m
{10@200 C/C MEMBRANE WITH 15mm THK.
PROTECTION BOARD
-1.870 MAX. PROTECTION BOARD
(TYP.) AS PER APPROVED SCALE : 1 : 25
(TYP.) AS PER APPROVED
SAMPLE (TYP.)

440
SAMPLE (TYP.)

400

400
{10@200 C/C {16@150 C/C
48-{25 {16@150 C/C
EL. -2.200 (TOC) MAX.
GRAPHIC SCALE:
{12@150 C/C {10@200 C/C EL. -2.310 (TOC) MIN.
0 0.5 1 2 3 4 5m

SEE DETAIL-04 EL. -2.710 (BOC) SCALE : 1 : 50


EL. -2.80 TOF SHEET-05
300

300 300 300 SEE DETAIL-04


EL. -3.10 BOF {16@150 C/C {16@150 C/C SHEET-05
TYP TYP TYP LEGEND
250 400 900 895 750 1950 750 1650 750 1950 750 1495 900 400 250
TOFW - TOP OF FIRE WALL TOF - TOP OF FOUNDATION
1047 14040
{12@150 C/C SEE DETAIL-02 THK. - THICK
BOF - BOTTOM OF FOUNDATION
SHEET-05 SH. - SHEET
CONSTRUCTION SEE DETAIL-01 TYP. - TYPICAL
1500 1500 1500
JOINT WITH APPROVED
A SECTION {10 CHAIR BAR AS PER
EL. - ELEVATION
B - REVISION CLOUD
SITE REQUIREMENT (TYP.) SHEET-05
4500
BONDING AGENT SH-02 SCALE 1:30 | - CENTERLINE
(1X2){200MM PVC PIPE @ -1.000M TOC - TOP OF CONCRETE
& -1.400M COS TO TOA | OF 500MVA
TOC - TOP OF CONCRETE
POWER RANSFORMER
12340 TOP - TOP OF PEDESTAL

TOG - TOP OF GRITTING


EL. +8.680
FGL - FINISH GROUND LEVEL

MAX. - MAXIMUM

MIN. - MINIMUM

C/C - CENTER TO CENTER

250 600 3970 2600 800 800 1650 2520 600 250 | - CENTER LINE
80MM THICK NON RC - REINFORCEMENT CEMENT CONCRETE
4-M36 GRAVEL
SHRINK GROUT 1500
ANCHOR BOLT 700 SEE DETAIL-03
{10@200 C/C
SEE DETAIL-03 AS PER VENDOR
EL. -0.300 EL. -0.080 EL. -0.300 SHEET-05 GRAPHIC SCALE:
RAIL GAUGE
100

100
SHEET-05 (TOP) EL.(+) 0.000 EL.(+) 0.000
GRAVEL (TOG) B {10@200 C/C (TOG) 0 0.5 1 2 3m
(TOC) (TOC) EL.(+) 0.000 (TOC)
(MIN.)

(MIN.)
300

300
SCALE : 1 : 30

FGL FGL

REFERENCE DRAWINGS

1150
1300
{16@200 C/C {16@200 C/C DRAWING TITLE DRAWING NO.
24-{16 24-{16
34-{16
{12@150 C/C {12@150 C/C {12@150 C/C DRAWING CONTROL SHEET (NEW) SE-0339800
(1) {200MM PVC
2310

2310
{10@200 {10@200 SLEEVES @-0.850M SCOPE OF WORK AND TECHNICAL SPECIFICATION PTS-23SN382
(2x1) {200MM PVC SLEEVES

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO.
{12@150 C/C {10@200 {12@150 C/C COS TO TOA (TYP) {12@150 C/C
C/C C/C
1820

1820
C/C @ -1.300M COS TO TOA
SITE TOPOGRAPHY LAYOUT SA-0339801

400
(TYP)
TWO (02) LAYERS OF 4mm THK.
WATERPROOFING MEMBRANE 15mm THK. OIL LEVEL OVERALL ELECTRICAL LAYOUT PLAN SA- 0340176
TWO(2) LAYERS OF 4mm THK.
PROTECTION MEMBRANE AS PER -1.870 MAX. WATERPROOFING MEMBRANE WITH 15mm
APPROVED SAMPLE SITE GRADING PLAN AND SECTIONS SA- 342223
THK. PROTECTION BOARD (TYP.) AS PER
{10@200 C/C
440

250 300 300 APPROVED SAMPLE (TYP.)


LAYOUT PLAN & SECTIONS - ELECTRICAL CABLE DUCTBANKS / TRENCHES SA- 340218
400

{16@150 C/C {16@150 C/C


{10@200 C/C
EL. -2.200 (TOC) MAX.
EL. -2.310 (TOC) MIN.
SEE DETAIL-04
SHEET-05 EL. -2.710 (BOC)

300 300 300 SEE DETAIL-04


{16@150 C/C {16@150 C/C SHEET-05
TYP TYP TYP
250 4120 900 71 1079 3600 200 900 2670 250
DRAWING/DOCUMENT ISSUED FOR
EL.(+)0.000
14040 (TOC) BASE DESIGN

APPROVAL

{10 CHAIR BAR AS PER (2x2) {200MM PVC SLEEVES @-1.00M & -1.400M COS TO CONSTRUCTION B SECTION SEE DETAIL-01
3-{16
INFORMATION ONLY

B CONSTRUCTION
TOA (TYP) + (1) {110MM PVC SLEEVES @-1.00M COS TO JOINT WITH APPROVED
SITE REQUIREMENT (TYP.) SH-02 SCALE 1:30 SHEET-05 DATE
15.06.2025
BY
M.M
TOA + (1) {200MM PVC SLEEVES @-1.400M COS TO TOA BONDING AGENT

500
(TYP)
{10@200 C/C

22860 3-{16 AS-BUILT BY Al Gihaz Contracting Company. DATE

700 4840 700 4840 700 4840 700 4840 700 B 15.06.25 DAR FOR SITE REFERENCE D.A A.M M.M

EL. +8.980
A 29.05.25 DAR FOR SITE REFERENCE D.A R.I M.M
300
FOR DETAILS REFER TO FOR DETAILS REFER TO
PRE-CAST PLAN & SECTION & DETAILS PRE-CAST PLAN & SECTION & DETAILS 02 04.05.25 DAR REVISED AS PER SEC COMMENTS M.E R.I M.M
GROUND BEAM/GB-01
DRAWING NO. SA-342146 DRAWING NO. SA-342146
TYPICAL REINFORCEMENT DETAIL 01 18.02.25 DAR REVISED AS PER SEC COMMENTS M.E R.I A.B

SCALE 1:10
8980

REV. DATE BY CHKD. CERT. APPD.


DESCRIPTION
NO.

NON DRAWING COMPLETION CERTIFICATE (DCC):


NON NON NON NON
SHRINK 250mm THK. PRE-CAST SOLID 250mm THK. PRE-CAST SOLID
SHRINK SHRINK SHRINK SHRINK
GROUT FIRE WALL PANEL FIRE WALL PANEL 1500
250mm THK. PRE-CAST SOLID GROUT GROUT 250mm THK. PRE-CAST SOLID GROUT GROUT
(MIN.)

(MIN.)
48-{25
300

300
FIRE WALL PANEL FIRE WALL PANEL
EL.(+) 0.000 750 EL.(+) 0.000
(TOC) (TOC)

FGL GB-01 GB-01 GB-01 GB-01 FGL


(300X500) (300X500) (300X500) (300X500)

X
{10@200 C/C {10@200 C/C 00 {10@200 C/C {10@200 C/C {10@200 C/C
R 10
A.I M.A AS SHOWN
-

1500
DRAWN BY CHECKED BY SCALE:
48-{25 48-{25 48-{25 48-{25 48-{25
2800

DETAIL-02 DATE STARTED


-
DATE COMPLETED
SHEET-05 (2X2){200MM PVC PIPE
00
10 @ -1.000M & -1.400M OPR'G. DEPT. ENG. DEPT.
R
COS TO TOA
{12@150 C/C
THIS DRAWING IS NOT TO BE USED FOR APPROVAL/CERTIFICATION INFORMATION
2 COATS OF 2 COATS OF 2 COATS OF 2 COATS OF CERTIFIED
COAL TAR EPOXY {12@150 C/C COAL TAR EPOXY COAL TAR EPOXY COAL TAR EPOXY CONSTRUCTION OR FOR ORDERING
EL. -2.800 TOF EL. -2.800 TOF
300

300

MATERIAL UNTIL CERTIFIED AND DATED BY


DDC NO. REV. NO.
DATE

EL. -3.100 BOF EL. -3.100 BOF


7-{10 @ 200 C/C
LAYOUT AND DETAILS OF POWER
{12@150 C/C {12@150 C/C X SECTION
450 1500 4040 1500 4040 1500 4040 1500 4040 1500 450
TRANSFORMER FOUNDATION (500MVA)
24560 - SCALE 1:25
CONSTRUCTION OF A NEW SUBSTATION FOR NAJRAN-PV 380/132KV BSP
DETAIL-02
NAJRAN SAUDI ARABIA
B' SECTION SHEET-05
CONTRACT NO. JOB ORDER NO. INDEX PLANT NO. DRAWING NUMBER SHEET NO. REV. NO.

SH-02 SCALE 1:50


4400021172 1-2434056.03 Q NJN419 SA-342108 03 of 05 B