ST-UK33 Series UPS
3/3 Transfermer-less IGBT based
UPS from 10 to 200 KVA
Parformance,compactness
and reliability
ST-UK33 the new transformer-less UPS from SATRON Power Solutions.
Best in class system for its compact footprint,the system also provides high efficiency
(> 95.6 % in double conversion and up to 98% in Eco Mode).
ST-UK33 is flexible in its configurations and benefits of a wide range of options.
This makes it an ideal power protection for small and medium sized critical applications
where power consumption, available space and reliability are key parameters.
The combination of high-level performance, with integrated battery solutions,
or (as an alternative), the inbuilt galvanic isolation, the compact footprint and
the wide range of options, make ST-UK33 the best solution for the power
quality of any critical load.
FEATURES • DSP, fully digital control technology.
• 3-level IGBT technology.
The UPS is based on a highly efficient • Transformer-less architecture.
transformer-less online, double conversion • AC/AC efficiency up to 95.6 % (VFI) and 98 % in VFD.
technology, ensuring the lowest OPEX • Input PF > 0.99 and THDi < 3 %.
on the market in its category. • Output PF up to unity (without derating).
Best in class for energy consumption; • Up to 8 units in parallel connection.
the system has a very low Total • Static and maintenance bypass switches included.
Cost of Ownership (TCO). • Back-feed protection included.
• Cold start (battery start) function.
• Touch screen display.
• Compact foot-print, with integrated batteries up to 40 kVA
BENEFITS GREEN POWER
• Easy installation, operation and maintenance: • High efficiency in online mode
all models have front access, for easy maintenance (≥95.6%) reduces heat dissipation
or inspection. and limits power consumption costs.
• Maximized savings in terms of footprint (m2), • Efficiency>98% in ECO mode gives
power installed (kVA), electrical system (cabling significant cost reduction.
and protection devices), security (MTTR and MTBF)
and power management (kW and cost).
• Easy upgradeable architecture with reduced CAPEX
and optimized OPEX.
• ST-UK33 offers a low input THDi and almost unity
input PF, even when a low percentage of load is applied.
( no additional power-consuming filter.)
• Wide range of options such as a load synchronization
tool, top cable entry, up to IP41 protection degree,
battery temperature probes
as well as all connectivitydevices (SNMP, Modbus, RS232).
• Touch screen display: all the main parameters of the UPS
are always under control.
FLEXIBLE DESIGN INTELLIGENT MANAGEMENT
• Common battery bank sharing in parallel system. • Fault Trace Management (FTM) for convenient
• Flexible battery configuration improves service ability. failure analysis (waveform record)
• High power density design with compact size, • Intelligent battery management system prolongs
120kW only cover 0.3825 m2. battery service life
• Smart generator management. • HMI enables more setting and status showing
• Self-aging test function without load enables onsite • Key components pre-alarm function
commission.
• Easy onsite parallel modification.
• Built-in battery quantity: 30-72 pcs configurable.
MODEL ST-UK33-10 ST-UK33-20 ST-UK33-30 ST-UK33-40 ST-UK33-50 ST-UK33-60
Power Ratings ( KW ) 10 20 30 40 50 60
UPS INPUT
Input Voltage 380/400/415 VAC , 3 Ph + N + G
Voltage range without battery mode -25% / +20%
Frequency ( Auto Selection ) 40 ~ 70 HZ (auto-sensing )
Power Factor ≥ 0.99
THDi < 3% ( with full linear load )
UPS OUTPUT
Output Voltage L-N 220/230/240 ±1% , L-L 380/400/415 ±1%
Frequency ( Hz ) 50/60 Hz ± 0.1 ( Battery Mode )
Slew Rate ( HZ / S ) 0.5 to 5 ( adjustable )
Power Factor 1
THDv THD < 1% ( Linear Load ) , < 4% ( Nonlinear Load )
Voltage Waveform Pure Sine Wave
Transfer Time 0
Efficiency ( AC/AC VFI mode ) > 93% > 93.3% > 94.5%
Efficiency ( AC/AC VFD mode ) > 98%
Overload 115 % for 60 Min. , 130 % for 10 Min. , 150 % for 1 Min , > 150 % 200 ms
Crest Factor 3:1
Short Circuit Response Short circuit proof ( 1.8 x In for 180 ms ) , if continuous UPS will shutdown
BATTERY
Type Sealed Lead Acid maintenance - free .
Voltage ( VDC ) ±180~±240 (can be selected from +15cells~+20cells, default is +16 cells)
Charger Current ( A ) Max. 10 20
Charging time h ( to 90 % ) 5
Battery Management Exhaustive discharge protection / Protection against excess load Automatic battery test
(daily, weekly, monthly)
COMMUNICATION
Communication Interface RS232+USB (RS485, Dry contact and SNMP optional)
3 LED’s with traffic light display, detailed indication via LCD display (acoustic/visual)
User interface / failure indication (alarms: at mains failure, overload, battery charging, battery replacement,
fan fault data logger – with clear text display incl. Date and time history)
PROTECTION / ALARM
Protection Low battery, overload, short-circuit and over temperature
Alarms Low battery, abnormal AC input, UPS failure
GENERAL DATA
Audible Noise dB ( 1 m distance ) < 65
Operation Temperature ºC -5 to 40
Relative Humidity 0 to 95% No Condensation
Operation Altitude Up to 1000 m @ nominal load
Dimension ( WxDxH ) mm 320x840x1030 320x840x1400 450x840x967
Weight ( Kg ) with/without batteries 240/120 250/120 350/120 370/120 160
MODEL ST-UK33-80 ST-UK33-100 ST-UK33-120 ST-UK33-160 ST-UK33-200
Power Ratings ( KW ) 80 100 120 160 200
UPS INPUT
Input Voltage 380/400/415 VAC , 3 Ph + N + G
Voltage range without battery mode -25% / +20%
Frequency ( Auto Selection ) 40 ~ 70 HZ (auto-sensing )
Power Factor ≥ 0.99
THDi < 3% ( with full linear load )
UPS OUTPUT
Output Voltage L-N 220/230/240 ±1% , L-L 380/400/415 ±1%
Frequency ( Hz ) 50/60 Hz ± 0.1 ( Battery Mode )
Slew Rate ( HZ / S ) 0.5 to 5 ( adjustable )
Power Factor 1
THDv THD < 1% ( Linear Load ) , < 4% ( Nonlinear Load )
Voltage Waveform Pure Sine Wave
Transfer Time 0
Efficiency ( AC/AC VFI mode ) > 94.8% > 95.6% > 94.5% > 95.3%
Efficiency ( AC/AC VFD mode ) > 98%
Overload 115 % for 60 Min. , 130 % for 10 Min. , 150 % for 1 Min , > 150 % 200 ms
Crest Factor 3:1
Short Circuit Response Short circuit proof ( 1.8 x IN for 180 ms ) , if continuous UPS will shutdown
BATTERY
Type Sealed Lead Acid maintenance - free.
Voltage ( VDC ) ±180~±240 480 (400-522 )settable
Battery Size ( internal ) NA
Charger Current ( A ) Max. 20 30 40 50
Charging time ( to 90 % ) 5h
Battery Management Exhaustive discharge
protection
/ Protection
against
excess
load Automatic
battery test (daily, weekly, monthly)
COMMUNICATION
Communication Interface RS232+USB (RS485, Dry contact and SNMP optional)
3 LED’s with traffic light display, detailed indication via LCD display (acoustic/visual)
User interface / failure indication (alarms: at mains failure, overload, battery charging, battery replacement,
fan fault data logger – with clear text display incl. Date and time history)
PROTECTION / ALARM
Protection Low battery, overload, short-circuit and over temperature
Alarms Low battery, abnormal AC input, UPS failure
GENERAL DATA
Audible Noise ( 1 m distance ) < 65
Operation Temperature -5 to 40 ºC
Relative Humidity 0 to 95% No Condensation
Operation Altitude Up to 1000 m @ nominal load
Dimension ( WxDxH ) mm 450x840x1400 600x9001600
Weight ( Kg ) with/without batteries 210 242 320 350
STARON Power Solutions
Approach your local SATRON Power Solutions
representative for further support.
Contact details can be found on:
www.satronpower.com