Assignment N Pholoba Re 2
Assignment N Pholoba Re 2
Design Report
By
Nkosinathi Pholoba
Mentored By
1|Page
Abstract
This report was undertaken upon the commissioning of a new 6 storey lecture
building by the Tshwane University of Technology for the Mbombela Campus.
The primary focus of this report is to provide Tshwane University of Technology with
the minimum structural masonry element requirements for the proposed 6 storey
lecture building. The structural masonry recommendations that are given in this
report are based on results obtained from the structural masonry design that was
undertaken for reinforced and unreinforced masonry structural elements.
This report aims to also provide a guide for the structural design of masonry
elements in buildings similar to the 6 storey lecture building commissioned by the
Tshwane University of Technology.
2|Page
Table of Content
4. Introduction Page 25
5. Results Page 27
6. Discussion Page 38
7. Conclusion Page 41
8. Recommendations Page 42
9. References Page 43
Appendices
3|Page
1. List of Tables
Table 2 of SABS 0160-1 - Partial factors for action for the ultimate limit states
Table 4 of SABS 0160-1 - Intensities of nominal imposed floor loads for occupancies
other than industrial buildings and storage
Table 5 of SABS 0160-1 - Variation of characteristic wind speed with terrain, height
and class of structure
Table 6 of SABS 0160-1 - External Pressure coefficient C pe for the walls of
rectangular clad buldings
Table 3a of SABS 0164 - 1 - Characteristics compressive strength masonry f k,
constructed with normal bricks
Table 3b of SABS 10164 - 1 - Characteristics compressive strength masonry f k,
constructed with hollow and solid bricks
Table 4 of SABS 10164 - Characteristic flexural strength of masonry fk, MPa
Table 5 of SABS 10164 - 1 - Partial safety for materials
Table 6 of SABS 10164 - 1 - Stiffness coefficients for wall stiffened by piers
Table 7 of SABS 10164 - 2 - Spacing of ties
Table 8 of SABS 10164 - 1 - Capacity reduction factor
Table 9 of SABS 10164 - 2 - Characteristic strength of wall ties used as wall
supports
Table 10 of SABS 10164 - 1 - Bending moment coefficients for laterally loaded
panels
Table 17 of SABS 10164 - 2 - Classifications of exposure conditions
Table E.4 - SABS 10164 - 2 - Requirements of full vertical ties
Table 13 - SABS 10164 - 2 - Effective height of walls and columns
Table 18 - SABS 10164 - 2 - Minimum concrete cover for carbon reinforcement
Table 11 - SABS 10164 - 2 - Limiting ratio (span to effective depth) for laterally
loaded walls
Table 12 - SABS 10164 - 2 - Limiting ratio (span to effective depth) for beams
Table E.2 - SABS 10164 - 2 - Detailed accidental damage recommendations
Table E.3 - SABS 10164 - 2 - Requirements of full peripheral, internal, columns or
wall ties
4|Page
List of tables in design report
Table 5.4.3 Combined bending and axial loading for walls D, E and F
Table 5.4.4 Combined bending and axial loading for walls D, E and F
5|Page
6|Page
7|Page
8|Page
9|Page
10 | P a g e
11 | P a g e
12 | P a g e
13 | P a g e
14 | P a g e
15 | P a g e
16 | P a g e
17 | P a g e
18 | P a g e
19 | P a g e
20 | P a g e
2. List of Figures
21 | P a g e
3. List of Symbols
22 | P a g e
α Bending moment coefficient
K Stiffness coefficient
kr Correction factor
MR Moment of resistance
Mu Design moment
Q Design load
µ Orthogonal Ratio
23 | P a g e
V Regional wind speed
SR Slenderness ratio
4. Introduction
24 | P a g e
The Tshwane University of Technology has commissioned the design of a 6 storey
lecture building, the information below regarding the lecture building was made
available by the client and the Architects:
25 | P a g e
In order to facilitate a design the following assumptions have been made:
The thickness for the roof and floor slabs, staircase landings and waists be
200 mm thick and will be made from 2% reinforced concrete.
The roof slab will be finished with 10 mm Screed on the top and a 10 mm
cement sand plaster at the bottom.
The floor slabs will be finished with a 10 mm granolithic screed on top and a
10 mm plaster underneath
The load bearing walls and balustrade will be 190 mm thick collar joint walls
constructed from solid concrete masonry bricks that are 190x90x90 mm in
size and will be finished with a 10 mm plaster on both sides.
Because a considerable amount of people with gather in the building strict
control measures must be enforced. As such γ m will be taken as 2.9 as the
supplier to be selected to supply the masonry blocks must operates a
quality control scheme and do quality checks on the work produced, a
suitably qualified QA/QC is to be appointed onsite to ensure that work is
carried out according to specifications.
γ c will be taken as 1 because the building will be used by a considerable
amount of people
All walls and their respective return/intersecting walls will be built
simultaneously and will be built into each other.
The loads will be evenly distributed between the columns and walls, it is also
assumed that the slab has sufficient stiffness in areas where excessive
deflection will want to form.
The water tanks will be centrally placed on the roof and the load will be
computed in terms on the overall area of the roof but the load will be
distributed over the surface area of the roof.
26 | P a g e
5. Results
In order to maintain order the buildings masonry wall will be allocated as illustrated in
figure 2
27 | P a g e
5.1. Wall A
Type of Quantity
Load
Dn 139 kN/m
Ln 26 kN/m
Fn 0.22 kN/m
Wn 0.602 kN/m²
Table 5.1.1 nominal loads on walls A
From the nominal loads in table 5.1.1 an ultimate axial load (Q) was calculated to be
209kN/m
Standard parameters that governed the design for compression of wall A have been
summarized in the table bellow
Parameters Result
hef 2100mm
tef 190mm
SR 11
ex 0.167t
β 0.73
γm 2.9
fk req 4.37MPa
Table 5.1.2. Axial compression design parameters for wall A
Based on the results in table 5.1.2 it was decided that a brick with a 14MPa nominal
compressive strength and class II mortar (fk = 5.1 MPa) be used for wall A.
Parameters Results
Q 182 kN/m
Required Capacity 0.802kN/m²
qlat 12.15kN/m²
ha / t 15
Table 5.1.3 Combined bending and axial loading for wall A
Based on the results in table 5.1.3 it was concluded that wall A has adequate lateral
strength and slenderness requirements are adhered to.
28 | P a g e
5.2. Wall B and G
From the nominal loads in table 5.2.1 an ultimate axial load (Q) was calculated to be
209kN/m
Standard parameters that governed the design for compression of wall B and G have
been summarized in the table bellow
Parameters Result
lef 1807.5mm
tef 235.6mm
SR 7.67
ex 0.167t
β 0.73
γm 2.9
Aspect ratio 2.05
fk req 4.37MPa
Table 5.2.2 Design parameters for wall B and G
Based on the results in table 5.2.2 it was decided that a brick with a 14MPa nominal
compressive strength in class II mortar (fk = 5.1 MPa) be used for walls B and G
29 | P a g e
5.3. Wall C
The full design of wall C can be found in appendix C. The loading for wall C was
assessed under cases, namely case 1 and case 2 which have different tributary
areas as noted in figures 5.3.1 and 5.3.2 below.
From the nominal loads in table 5.3.1 an ultimate axial load (Q) was calculated to be
209kN/m for case 1 and 240kN/m for case 2
Standard parameters that governed the design for compression of wall C have been
summarized in the table bellow
Based on the results in table 5.3.2 it was decided that a brick with a 14MPa nominal
compressive strength in class II mortar (f k = 5.1 MPa) can be used for case 1 and a
brick with a 35MPa nominal compressive strength in class II mortar (fk = 9.3 MPa)
can be used for case 2.
30 | P a g e
5.4. Walls D, E, and F
The full design of walls D, E and F can be found in appendix D. Please take note of
the following:
Wall E is not carrying and axial loads other than its self-weight (including
finishes) but for uniformity it will be designed the same way as wall D which in
addition to its self-weight it is also supporting the staircase.
Wall F is not exposed to any wind loading but for uniformity it will be designed
the same was as wall D, furthermore wall F will be subject to a dynamic load
arising from the movement of elevator in the lift shaft as such it if
recommended that dynamic load consultants be consulted with regards to the
suitability of the wall.
The ultimate reaction loads as a result of the staircase are R A = RA = 30kN and the
ultimate self-weight load (Q) is 117kN/m
Standard parameters that governed the design for compression of walls D, E and F
have been summarized in the table bellow
Parameters Result
hef 2100mm
tef 190mm
SR 11
ex 0.05t
β 0.949
γm 2.9
fk req 1.88MPa
Table 5.4.2 Axial compression design parameters for walls D, E and F
Based on the results in table 5.4.2 it was decided that a brick with a 7MPa nominal
compressive strength and a class II mortar (f k = 3.2 MPa) be used for wall D, E and
F.
31 | P a g e
Design for concentrated axial loading (unreinforced)
Parameters Results
Q 30 kN/m
Bearing type 1
fk 3.1MPa
Bearing resistance 444kN/m
hef 2100mm
tef 190mm
SR 11
ex 0.167t
β 0.73
γm 2.9
Q at 0.4h 137kN/m
Bearing resistance at 0.4h 161 kN/m
Q at h=2800mm 60kN/m
Bearing resistance at h=2800mm 161kN/m
Table 5.4.3 Combined bending and axial loading for walls D, E and F
Based on the results in table 5.4.3 it was concluded that a brick with a 7MPa nominal
compressive strength in class II mortar (fk = 3.1 MPa) is adequate for concentrated
loading
Parameters Results
Height x length 9.8x10⁶mm²
1500tef 54.15 x10⁶mm²
50tef 9500mm
Design wind load 0.803kN/m²
fkx par 0.3MPa
fkx perp 0.9MPa
µ 0.4
Aspect ratio h/l 0.8
α 0.033
Mu perp 0.326kNm/m
Mu par 0.13kNm/m
MR perp 1.867kNm/m
MR par 0.821kNm/m
Shear at each support 1.28kN/m
Vu 0.004MPa
fv 0.171MPa
Vh 0.069MPa
Table 5.4.4 Combined bending and axial loading for walls D, E and F
Based on the results in table 5.4.4 it was concluded that walls D,E and F is adequate
for combined axial load and bending.
32 | P a g e
5.5. Wall H
The full design of wall H can be found in appendix E. The loading for wall H was
assessed under cases, namely case 1 and case 2 which have different tributary
areas as noted in figures 5.5.1 and 5.5.2 below.
From the nominal loads in table 5.6.1 an ultimate axial load (Q) was calculated to be
290kN/m for case 1 and 192kN/m for case 2
Standard parameters that governed the design for compression of wall H have been
summarized in the table bellow
Based on the results in table 5.6.2 it was decided that a brick with a 49MPa nominal
compressive strength in class II mortar (fk = 12.0 MPa) can be used for case 1 and a
33 | P a g e
brick with a 28MPa nominal compressive strength in class II mortar (fk = 8.0 MPa)
can be used for case 2.
Based on the information in the two table above it was decided to design all the
lintels in the building based on the nominal loading on the roof (table 5.7.1) because
they are higher and the following was calculated:
It was decided to use the same bricks specified in the design for walls B and G which
will be supporting the lintel. Standard parameters that governed the design of
brickwork lintels have been summarized in the table bellow
Parameters Result
fk 5.1MPa
d 395mm
γ mm 2.3
γ ms 1.15
fy 485MPa
As 39mm²
Z 394mm
MR 6.15 kN.m
V 0.14MPa
γ
fbs / mb 1.07MPa
Table 5.6.3 Design parameters for brickwork lintel
From the results in table 5.7.3 it was decided to used 2 Y5 diameter hard drawn
prestraightend wire placed in the mortar.
34 | P a g e
5.7. Reinforced design
Walls A, B, C and G
These walls were exposed to the same load and the same material will be used for
all of them as calculated above only the design for wall A will be done and the results
will be replicated for the other walls.
Parameters Result
Design Load 209 kN/m
hef 2100mm
tef 190mm
SR 11
ex 0.167t
β 0.73
γm 2.9
fk req 5.1MPa
Q (without reinforcement) 244 kN/m
As (for Y6 bars) 141.5mm²
Q (with reinforcements) 341 kN/m
Table 5.7.1. Reinforced design parameters for wall A
From the results in table 5.8.1 it can be seen that the addition on reinforcements will
increase the load resistance capacity by 97 kN/m as such the a weaker brick can be
used (say fk = 3.1MPa in class II mortar) together with the reinforcements which will
give an overall load resistance of 220 kN/m
35 | P a g e
Wall H
These walls were exposed to the same load and the same material will be used for
all of them as calculated above only the design for wall A will be done and the results
will be replicated for the other walls.
Parameters Result
Design Load 290 kN/m
hef 2100mm
tef 190mm
SR 11
ex 0.3t
β 0.44
γm 2.9
fk req 12.0MPa
Q (without reinforcement) 345 kN/m
As (for Y6 bars) 141.5mm²
Q (with reinforcements) 456 kN/m
Table 5.7.2. Reinforced design parameters for wall H
From the results in table 5.8.2 it can be seen that the addition on reinforcements will
increase the load resistance capacity by 110 kN/m as such the a weaker brick can
be used (say fk = 9.3MPa in class II mortar) together with the reinforcements which
will give an overall load resistance of 358 kN/m
From table 5.8.1 above the ultimate self-weight load (Q) was calculated to be
12kN/m
36 | P a g e
Design for axial compression for self-weight only (Unreinforced)
Standard parameters that governed the design for compression of the balustrade
Wall have been summarized in the table bellow
Parameters Result
hef 1750mm
tef 190mm
SR 9.21
ex 0.05t
β 0.99
γm 2.9
fk req 0.19MPa
Table 5.8.2 Axial compression design parameters for Balustrade Wall
Based on the results in table 5.8.2 it was decided that a brick with a 3.5MPa nominal
compressive strength and a class II mortar (f k = 2.0 MPa) be used for the balustrade
wall
Parameters Results
Height x length 6.13x10⁶mm²
1350tef 48.74 x10⁶mm²
50tef 9500mm
Design wind load 0.803kN/m²
fkx par 0.3MPa
fkx perp 0.9MPa
µ 0.36
Aspect ratio h/l 0.5
α 0.063
Mu perp 0.62kNm/m
Mu par 0.22kNm/m
MR perp 1.87kNm/m
MR par 0.749kNm/m
Shear along vertical supports 0.308kN/m
Shear at base 0.35kN/m
Vu 0.004MPa
fv 0.16MPa
Vh 0.07MPa
Table 5.8.3 Combined bending and axial loading for Balustrade Wall
Based on the results in table 5.8.3 it was concluded that the balustrade Wall is
adequate for combined axial load and bending.
37 | P a g e
6. Discussion
Wall A
Wall A was designed for axial compression which warranted the use of a brick with a
minimums nominal compression strength of 14MPa in class II mortar, the result was
found to be adequate on the basis of the load it will be supporting.
Wall A is also precompressed and is exposed to a lateral wind load as such on that
basis it was also checked for combined bending and axial loading and it was found
that the wall has sufficient lateral resistance.
A reinforced design was also carried out on wall A and it was found that the strength
of the wall is increased by 40% with the addition of Y6 bars in the mortar, as such
the wall will exhibit an increased tensile and compression strength increase which
will further minimise the risk of failure. The only disadvantage with adding
reinforcements is that the will be cost escalations as a result
Wall B and G
Walls B and G are internal walls as such they were designed for axial compression
alone which warranted the use of a brick with a minimum compressive strength of
14MPa in class II mortar.
Wall G will further be exposed to a dynamic load due to the movement of the
elevator in the lift shaft as such further checks on the adequacy of the wall will have
to be done by the dynamic consultants.
A reinforced design was also carried out on walls B and G and it was found that the
strength of the wall is increased by 40% with the addition of Y6 bars in the mortar, as
such the wall will exhibit an increased tensile and compression strength increase
which will further minimise the risk of failure. The only disadvantage with adding
reinforcements is that the will be cost escalations as a result
It is advisable that the material recommended for wall C also be used in the
construction for wall G. The walls will be built into each other as such it is advisable
be to standardise the material for both walls to reduce the implications of improper
construction.
38 | P a g e
Wall C
Wall C is an internal wall as such is only exposed to an axial load which formed the
basis of the design. The wall was designed under two load cases; case 1 where the
wall is not supporting the restroom and case 2 where the load for the rest room is
evenly shared with wall H.
A reinforced design was also carried out on wall C and it was found that the strength
of the wall is increased by 40% with the addition of Y6 bars in the mortar, as such
the wall will exhibit an increased tensile and compression strength increase which
will further minimise the risk of failure. The only disadvantage with adding
reinforcements is that the will be cost escalations as a result
Walls D, E and F
These wall were designed for axial compressing due to self-weight and a
concentrated point load due to the staircase reactions, this warranted the use of a
brick with a minimum compressive strength of 7MPa in class II mortar.
The walls were checked against lateral wind load and were found to be sufficient.
Due to the fact that the building and there will be a considerable amount of people it
is advisable to increase the strength of the wall to 14MPa in class II mortar and the
wall be reinforced with Y5 bars in the mortar to further increase resistance and
further minimise the risk of failure.
Wall H
Wall H is an internal wall as such is only exposed to an axial load which formed the
basis of the design. The wall was designed under two load cases; case 1 where the
wall is not supporting the restroom and case 2 where the load for the rest room is
evenly shared with wall C.
39 | P a g e
Because case 1 yielded as higher ultimate load it warranted a stronger brick to be
used. The material required for case 2 is reduced because the ultimate load from
case 1 was less by 33%.
A reinforced design was also carried out on wall H and it was found that the strength
of the wall is increased by 32% with the addition of Y6 bars in the mortar, as such
the wall will exhibit an increased tensile and compression strength increase which
will further minimise the risk of failure. The only disadvantage with adding
reinforcements is that the will be cost escalations as a result.
Lintel
The building called for the inclusion of a lintel to span between wall B and G and will
support the floor and roof slabs also spanning between walls B and G. Through load
computation it was found that the nominal loads from the roof slab were higher than
those from the flor slabs as such the lintels were designed to using the nominal loads
from the roof slabs.
Because the lintels will be built into walls B and G for uniformity sake it was decided
to use the same material as specified in the designs for walls B and G (14MPa brick
in class II mortar) and it was decided that 2 Y5 diameter hard drawn prestraightened
wire placed in the mortar.
Balustrade wall
The Balustrade wall was designed for axial compression due to self-weight and it
was found that required a brick with a minimum compressive strength of 3.5MPa in
class II mortar. Due to the fact that it is only supporting its-self axial the material
strength requirements are not high.
The wall was also checked against the lateral wind load and was found to be
sufficient provided that full control joints be placed at 3500mm intervals.
It is advisable to increase the strength of the material due to the nature of the
building and the results of failure as such a brick with 14MPa compressive strength
can be used and the wall be reinforced with Y5 bars in the mortar to further increase
resistance.
40 | P a g e
7. Conclusion
41 | P a g e
8. Recommendations
It is further recommended that the results from load case 2 be adopted for wall C and
the results for load case 2 be adopted for wall H
42 | P a g e
9. References
CROFTS, FS. & LANE, JW. 2011. Structural concrete masonry. 1st ed. Midrand:
Concrete Manufactures Association.
43 | P a g e
APPENDIX A
44 | P a g e
APPENDIX B
45 | P a g e
APPENDIX C
46 | P a g e
APPENDIX D
47 | P a g e
APPENDIX E
48 | P a g e
APPENDIX F
49 | P a g e
APPENDIX G
50 | P a g e
APPENDIX H
51 | P a g e
APPENDIX I
52 | P a g e