Ventilation Fan - List
Ventilation Fan - List
LOCATION
SERVING
S/N Description Unit Static
Tag.No
Qty Quantity
TYPE
Remarks
Pressure
CFM Inch
Note: The contractor should read the specifications thoroughly and quote the price for each item. The
BOQ should read in conjunction with specification, drawing & equipment schedule. The cost shall
include the cost of the material, transportation, taxes, duties, lifting, shifting, storing, handling,
installation, testing and commissioning.
I AXIAL FLOW FANS FOR VENTILATION SYSTEM
1 AXIAL FLOW MAIN FANS WITH VFD FOR CAR PARKING EXHAUST (NORMAL MODE EXHAUST & FRESH
AIR FANS)
Supply, installation, testing & commissioning of Heavy duty AMCA Certified Smoke Spill Axial flow fan
with MS or galvanized steel Double flanged long casing, impellers, pressure casted aluminium adjustable
pitch blades as per the specification. The fan shall be suitable to operating temperature of 250 deg.C
and fire rating shall be for 2 hours with totally enclosed class H motor with Variable speed and min IP 55
protection with direct driven motor and the air flowing from impeller to the motor for Basement
Ventilation application as per specification & as indicated in the Equipment Schedule. Motor shall be
suitable for 415±10% volts, 50 cycles/second, 3 phase AC supply. Each fan shall include all accessories,
controls, Flexible connection, vibration Isolators, harmonic filters for variable speed drive as per the
specification. Refer Equipment schedule for details.
Static pressure and Motor Rating : The Indicated static pressure and motor rating is only provisional.
Contractor to calculate static pressure based on final approved construction drawing and pressure drop
of finalized Equipment / Items and submit for review / approval to the consultants. The procurement
shall be processed only after duly verification / approval of calculation and selection from the
consultants.
Tag Numbers (Refer Equipment Schedule)
LOCATION
SERVING
S/N Description Unit Static
Tag.No
Qty Quantity
TYPE
Remarks
Pressure
CFM Inch
2 AXIAL FLOW MAIN FANS WITH OUT VFD FOR CAR PARKING EXHAUST (FIRE MODE EXHAUST & FRESH
AIR FANS)
Supply, installation, testing & commissioning of Heavy duty AMCA Certified Smoke Spill Axial flow fan
with MS or galvanized steel Double flanged long casing, impellers, pressure casted aluminium adjustable
pitch blades as per the specification. The fan shall be suitable to operating temperature of 250 deg.C
and fire rating shall be for 2 hours with totally enclosed class H motor with variable speed and min IP 55
protection with direct driven motor and the air flowing from impeller to the motor for Basement
Ventilation application as per specification & as indicated in the Equipment Schedule. Motor shall be
suitable for 415±10% volts, 50 cycles/second, 3 phase AC supply. Each fan shall include all accessories,
controls, Flexible connection, vibration Isolators, Refer Equipment schedule for details.
Static pressure and Motor Rating : The Indicated static pressure and motor rating is only provisional.
Contractor to calculate static pressure based on final approved construction drawing and pressure drop
of finalized Equipment / Items and submit for review / approval to the consultants. The procurement
shall be processed only after duly verification / approval of calculation and selection from the
consultants.
LOCATION
SERVING
S/N Description Unit Static
Tag.No
Qty Quantity
TYPE
Remarks
Pressure
CFM Inch
Supply, installation, testing & commissioning of Heavy duty AMCA certified dual speed Jet ventilation
fans long casing with Silencer as per the specification. The fan operating temperature shall be 250 deg c
3 and fire rating shall be for 2 hours with totally enclosed class H motor with dual speed direct driven
motor for Basement ventilation Normal / fire mode application as per specification & as indicated in the
Equipment Schedule. Motor shall be suitable for 415±10% volts, 50 cycles/second, 3 phase AC supply.
Size: Fan (Motor) dia shall be 315 mm Dia excluding silencer.
TYPE
Remarks
mm Nm
LOCATION
SERVING
S/N Description Unit Static
Tag.No
Qty Quantity
TYPE
Remarks
Pressure
CFM Inch
Supply, installation, testing & commissioning of AMCA Certified TUBE AXIAL FANS with galvanized
steel Double flanged long casing, impellers of pressure casted aluminum adjustable pitch blades as per the
specification. The fan shall be min IP 55 protection with direct driven motor and the air flowing from
impeller to the motor for Lift lobby, Lift Well & staircase pressurization application as per specification
& as indicated in the Equipment Schedule. Motor shall be suitable for 415±10% volts, 50 cycles/second, 3
phase AC supply. Each fan shall include all accessories, controls, Flexible connection, Cowl piece with
bird mesh, vibration Isolators, necessary supports as per the specification. (Refer Equipment schedule for
details).
Static pressure and Motor Rating : The Indicated static pressure and motor rating is only provisional.
Contractor to calculate static pressure based on final approved construction drawing and pressure drop of
finalized Equipment / Items and submit for review / approval to the consultants. The procurement shall be
processed only after duly verification / approval of calculation and selection from the consultants.
High rise
GH-TF-LWP-AF- Passenger Lift
GH-TF-LWP-AF-03 - 04 Nos 2 03 - 04 well
Terrace Floor Axial 40000 1.2 Fire mode fans 1400 Yes Yes Yes Yes Yes
pressurization
GH-TF-LWP-AF- Passenger
GH-TF-LWP-AF-01 - 02 Nos 2 01 - 02 Lobby Terrace Floor Axial 50000 1.2 Fire mode fans 1600 Yes Yes Yes Yes Yes
pressurization
LOCATION
SERVING
S/N Description Unit Static
Tag.No
Qty Quantity
TYPE
Remarks
Pressure
CFM Inch
Supply, installation, testing & commissioning of AMCA Certified Smoke Spill Axial flow fan with MS or
galvanized steel Double flanged long casing, impellers, pressure casted aluminium adjustable pitch blades
as per the specification. The fan shall be suitable to operating temperature of 250 deg.C and fire rating
shall be for 2 hours with totally enclosed class H motor with single speed and min IP 54 protection with
direct driven motor and the air flowing from impeller to the motor for Smoke Exhaust application as per
specification & as indicated in the Equipment Schedule. Motor shall be suitable for 415±10% volts, 50
cycles/second, 3 phase AC supply. Each fan shall include all accessories, controls, Flexible connection,
Cowl piece with bird mesh, vibration Isolators, necessary supports as per the specification. (Refer
Equipment schedule for details.)
Static pressure and Motor Rating : The Indicated static pressure and motor rating is only provisional.
Contractor to calculate static pressure based on final approved construction drawing and pressure drop of
finalized Equipment / Items and submit for review / approval to the consultants. The procurement shall be
processed only after duly verification / approval of calculation and selection from the consultants.
Office Smoke
GH-TF-SE-AF-01 Nos 1 GH-TF-SE-AF-01
Exhaust Fans
Terrace Floor Axial 38000 1.2 Fire mode fans 1400 Yes Yes Yes Yes Yes
Supply, installation, testing & commissioning of AMCA Certified Smoke Spill Axial flow fan with MS or
galvanized steel Double flanged long casing, impellers, pressure casted aluminium adjustable pitch blades
as per the specification. The fan shall be suitable to operating temperature of 250 deg.C and fire rating
shall be for 2 hours with totally enclosed class H motor with single speed and min IP 54 protection with
direct driven motor and the air flowing from impeller to the motor for Pressurization application as per
specification & as indicated in the Equipment Schedule. Motor shall be suitable for 415±10% volts, 50
cycles/second, 3 phase AC supply. Each fan shall include all accessories, controls, Flexible connection,
Cowl piece with bird mesh, vibration Isolators, necessary supports as per the specification. (Refer
Equipment schedule for details.)
Static pressure and Motor Rating : The Indicated static pressure and motor rating is only provisional.
Contractor to calculate static pressure based on final approved construction drawing and pressure drop of
finalized Equipment / Items and submit for review / approval to the consultants. The procurement shall be
processed only after duly verification / approval of calculation and selection from the consultants.
II TOTAL VALUE
1583800
Gravi Vibration
Fan Dia Sound Acc Bird Screen Canvas
Louvers Iso
Total
Total Air
LOCATION
SERVING
S/N Description Unit Static
Tag.No
Qty Quantity
TYPE
Remarks
Pressure
CFM Inch
12278900