0% found this document useful (0 votes)
19 views103 pages

Infinity M and HC - Ig

The installation guide for the Infinity M1 (NE-M) power systems provides detailed instructions for equipment setup, including safety precautions, installation procedures, and troubleshooting tips. It covers various system configurations, components, and connections necessary for proper installation and operation. The document also includes contact information for technical support and references to additional resources.

Uploaded by

Humberto Riveros
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
19 views103 pages

Infinity M and HC - Ig

The installation guide for the Infinity M1 (NE-M) power systems provides detailed instructions for equipment setup, including safety precautions, installation procedures, and troubleshooting tips. It covers various system configurations, components, and connections necessary for proper installation and operation. The document also includes contact information for technical support and references to additional resources.

Uploaded by

Humberto Riveros
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 103

INSTALLATION GUIDE

H5692448 power systems


Infinity M1 (NE-M)
High capacity with horizontal distribution

13 U System 22U System


Initial Frame Supplemental Frame

22U System with Supplemental Frame


and Galaxy Millennium II Controller

NOTE: NE-M systems with left and right vertical distribution use installation guide document CC848815325.

This equipment is not suitable for use in location where children are likely to be present.
Equipment intended only for use in a restricted access area.

Service and Assistance - +1 972 244-9288 [email protected]


© 2023 OmniOn Company. All rights reserved omnionpower.com

1
Trademark of OmniOn Company

Page 1

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
INSTALLATION GUIDE

H5692448 power systems


Infinity M1 (NE-M)
High capacity with horizontal distribution

Table of Contents
Table of Figures ................................................................................................................................................................................. 4
Table of Tables ................................................................................................................................................................................... 6
Introduction ........................................................................................................................................................................................ 7
Reference Documents..........................................................................................................................................................................................................7
Contact Information...............................................................................................................................................................................................................7
Product Description ......................................................................................................................................................................... 8
Components................................................................................................................................................................................................................................11
Installation ........................................................................................................................................................................................... 18
Preparation...................................................................................................................................................................................................................................18
Safety ..........................................................................................................................................................................................................................18
Installation Tools ........................................................................................................................................................................................................18
Equipment Identification ....................................................................................................................................................................................18
Anchor Frame.............................................................................................................................................................................................................................19
Floor Mounted Frame ............................................................................................................................................................................................19
Battery or Battery Stand Mounted Frame ...............................................................................................................................................20
Sub-frame Mounted Systems: ..........................................................................................................................................................................20
Ground Frame ............................................................................................................................................................................................................................21
Floor Mounted Frame ............................................................................................................................................................................................21
Battery or Battery Stand Mounted Frame ...............................................................................................................................................21
Connect Central Office Ground (COG) ......................................................................................................................................................................22
Connect Supplemental Frame .......................................................................................................................................................................................22
Connect Interframe Bus Bars ...........................................................................................................................................................................23
Connect Interframe Secondary Voltage Cables ...................................................................................................................................25
Connect Interframe Signal Cables.................................................................................................................................................................27
Set Supplemental Frame ID on BIC 10 .......................................................................................................................................................30
Install PV/AC Partition Kit – NE-M Eco systems only .......................................................................................................................................30
Connect Input Power ............................................................................................................................................................................................................33
Install Battery Trays ................................................................................................................................................................................................................36
Install Batteries ..........................................................................................................................................................................................................................37
Tray Mounted Batteries.........................................................................................................................................................................................37
External Batteries ......................................................................................................................................................................................................38
Connect Batteries ....................................................................................................................................................................................................................39
Connect Tray Mounted Batteries ...................................................................................................................................................................39
Connect External Batteries.................................................................................................................................................................................44
Connect Battery Probes .......................................................................................................................................................................................45

Page 2

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Verify Battery Bus Voltage and Polarity ....................................................................................................................................................................45
Connect Load Wiring.............................................................................................................................................................................................................45
Verify Installation ......................................................................................................................................................................................................................54
Install Controller ........................................................................................................................................................................................................................55
Install Pulsar Plus ......................................................................................................................................................................................................55
Install Millennium II..................................................................................................................................................................................................61
Install BSM6 Modem ...............................................................................................................................................................................................65
Install Optional Controller Peripherals ........................................................................................................................................................65
Install Rectifiers/Converters ..............................................................................................................................................................................................65
Install Rectifiers ..........................................................................................................................................................................................................67
Verify Rectifier Positions .......................................................................................................................................................................................68
Install Converters .......................................................................................................................................................................................................69
Install Battery Voltage Temp (VT)-Probes ................................................................................................................................................................69
Install Aux Display (NE830A) Alarm Cable (Optional)......................................................................................................................................69
Configure Controller – Minimum ..................................................................................................................................................................................70
Configure Pulsar Controller ................................................................................................................................................................................70
Configure Millennium II Controller ...............................................................................................................................................................72
Acceptance Testing .......................................................................................................................................................................... 75
Troubleshooting ................................................................................................................................................................................ 79
System .............................................................................................................................................................................................................................................79
Rectifiers/Converters .............................................................................................................................................................................................................86
Voltage Temp (VT)-Probes..................................................................................................................................................................................................87
Specifications and Application ..................................................................................................................................................... 88
Millennium II Alarm & Control Signals .......................................................................................................................................................................89
Fuse Alarm Major (FAJ) - BSL-63 .....................................................................................................................................................................92
Fuse Alarm Minor (FAN) - BSL-65 ...................................................................................................................................................................92
Open String Alarm (OS) - BSL-72 ....................................................................................................................................................................92
Aux Major (AMJ) - BSL-64.....................................................................................................................................................................................92
Aux Minor (AMN) - BSL-66 ...................................................................................................................................................................................92
Low Voltage Disconnect Active (LVD1) - BSL-84 ..................................................................................................................................92
Low Voltage Disconnect Active (LVD2/LVD2R) - BSL-61/62...........................................................................................................92
External Boost Option (TFLT/TBST/PBT) - BSL-67-69 ........................................................................................................................92
Rectifier Hold OFF on Engine Option (RO/ROR) - BSL-77-78 .....................................................................................................93
Rectifier External Sequence Option (TR1-TR4) - BSL-73/79/85/80............................................................................................93
Safety .................................................................................................................................................................................................... 94
Déclarations de sécurité ................................................................................................................................................................. 95
Precautions ......................................................................................................................................................................................... 96
Précautions ......................................................................................................................................................................................... 97
Special Installation Notes ............................................................................................................................................................... 98
Revision History ................................................................................................................................................................................. 102

Page 3

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Table of Figures
Figure 1 Block Diagram ...............................................................................................................................................................................................................10
Figure 2 NE-M Components ....................................................................................................................................................................................................11
Figure 3 Pulsar Front Panel ......................................................................................................................................................................................................12
Figure 4 Millennium II Controller Front Panel .............................................................................................................................................................12
Figure 5 NE830 Display ...............................................................................................................................................................................................................13
Figure 6 Rectifier and Converter Type Badge .............................................................................................................................................................13
Figure 7 Power Input Panel......................................................................................................................................................................................................15
Figure 8 Battery Stand .................................................................................................................................................................................................................15
Figure 9 DC Distribution 4 Bullet Panels ........................................................................................................................................................................16
Figure 10 DC Distribution – Bolt In Panel with return bar ...................................................................................................................................16
Figure 11 NE-M System – 22U ...................................................................................................................................................................................................16
Figure 12a New Shunt Bus Arrangements (Series 1:3) ............................................................................................................................................17
Figure 12b Old Shunt Bus Arrangements ......................................................................................................................................................................17
Figure 13 Frame Mount Footprint ........................................................................................................................................................................................19
Figure 14 Battery Stand Mount .............................................................................................................................................................................................20
Figure 15 Mount Sub Frame .....................................................................................................................................................................................................20
Figure 16 Ground Frame .............................................................................................................................................................................................................21
Figure 17 Ground Short Frame ...............................................................................................................................................................................................21
Figure 18 CO Ground Landing ................................................................................................................................................................................................22
Figure 19 Supplemental Frame..............................................................................................................................................................................................22
Figure 20 New Interframe Bus Bars ...................................................................................................................................................................................23
Figure 21 L635L Dual Voltage Panel Location ..............................................................................................................................................................25
Figure 22 Secondary Voltage Bus ........................................................................................................................................................................................25
Figure 23 Interframe Cables .....................................................................................................................................................................................................27
Figure 24 Breaker Panel Alarm Connections ...............................................................................................................................................................28
Figure 25 RPM Connections .....................................................................................................................................................................................................29
Figure 26 Set Frame ID on BIC 10 .........................................................................................................................................................................................30
Figure 27 Eco Input Panel .........................................................................................................................................................................................................30
Figure 28 Input Panel Screws .................................................................................................................................................................................................31
Figure 29 Partition Labels ..........................................................................................................................................................................................................31
Figure 30 Partition Insert ...........................................................................................................................................................................................................32
Figure 31 Label Input Panel ......................................................................................................................................................................................................32
Figure 32 Label Input Panel Cover.......................................................................................................................................................................................32
Figure 33 Input Power Terminal Block Positions.......................................................................................................................................................33
Figure 34 Rectifier / Converter and Shelf Numbering ...........................................................................................................................................33
Figure 35 Rectifier Dual Feed Jumper Positions – ac feeds only ....................................................................................................................33
Figure 36 Input Conduit Locations ......................................................................................................................................................................................34
Figure 37 Input Jumper Dividers ..........................................................................................................................................................................................34
Figure 38 AC Bridging Jumper ..............................................................................................................................................................................................34
Figure 39 Input Panel Sections ..............................................................................................................................................................................................35
Figure 40 Battery Trays ...............................................................................................................................................................................................................36
Figure 41 Batteries in Tray – 48V ...........................................................................................................................................................................................37
Figure 42 Place Batteries ...........................................................................................................................................................................................................38
Figure 43 Battery Inter-Cell Bus Bars ................................................................................................................................................................................38

Page 4

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Figure 44 Battery Disconnect Switch ...............................................................................................................................................................................39
Figure 45 Batt Disconnect Switch Input Bus ...............................................................................................................................................................39
Figure 46 Battery Cable -48V ..................................................................................................................................................................................................40
Figure 47 Battery Cable +24V .................................................................................................................................................................................................40
Figure 48 Battery Return Cable -48V ................................................................................................................................................................................41
Figure 49 Battery Return Cable +24V ................................................................................................................................................................................41
Figure 50 Anderson Battery Connector ...........................................................................................................................................................................42
Figure 51 Battery Connections - Anderson ....................................................................................................................................................................42
Figure 52 Battery Cable Direct -48V ...................................................................................................................................................................................43
Figure 53 Battery Cable Direct +24V ..................................................................................................................................................................................43
Figure 54 Battery Return Cable Direct -48V .................................................................................................................................................................43
Figure 55 Battery Return Cable Direct +24V .................................................................................................................................................................44
Figure 56 External Battery Connections ..........................................................................................................................................................................44
Figure 57 Battery Additional Landings .............................................................................................................................................................................44
Figure 58 Battery and Return Bus Lug Spacers .........................................................................................................................................................44
Figure 59 Battery Bus Labels ...................................................................................................................................................................................................45
Figure 60 Bullet Distribution Panel - Selectable Voltage ....................................................................................................................................46
Figure 61 2-Pole and 3-Pole Breaker Install ...................................................................................................................................................................47
Figure 62 GMT Fuse Module ....................................................................................................................................................................................................48
Figure 63 Bolt-In Breaker or Fuse Holder Mounting ...............................................................................................................................................49
Figure 64 Bolt-in TPL-C Fuse Holder Wiring ................................................................................................................................................................49
Figure 65 Bolt-in Breaker Wiring ..........................................................................................................................................................................................49
Figure 66 Bolt-in Position Return Bar ...............................................................................................................................................................................50
Figure 67 850038647 Alarm Cable ......................................................................................................................................................................................50
Figure 68 Remove bullet breaker panel and replace with TPL fuse panel ..............................................................................................53
Figure 69 Rectifier Positions ....................................................................................................................................................................................................54
Figure 70 Labeling of rectifier/converter shelves .....................................................................................................................................................54
Figure 71 ESD Grounding Connector .................................................................................................................................................................................55
Figure 72 Alarm Relay Jumpers – Pulsar Plus ..............................................................................................................................................................55
Figure 73 Alarm Relay Jumper Positions - Pulsar Plus ..........................................................................................................................................56
Figure 74 1-Wire Jumper - Pulsar Plus ..............................................................................................................................................................................57
Figure 75 Controller Connections ........................................................................................................................................................................................57
Figure 76 Modbus RTU Interface ..........................................................................................................................................................................................61
Figure 77 Local Port - Pulsar Plus .........................................................................................................................................................................................61
Figure 78ESD Grounding Connector .................................................................................................................................................................................61
Figure 79 Millennium II Circuit Card...................................................................................................................................................................................62
Figure 80 Controller Connections ........................................................................................................................................................................................62
Figure 81 Alarm Connections Millennium II ..................................................................................................................................................................64
Figure 82 RS232 Connection - Millennium II ................................................................................................................................................................65
Figure 83 Insert Rectifier ............................................................................................................................................................................................................65
Figure 84 Open Rectifier Door ...............................................................................................................................................................................................66
Figure 85 Close Rectifier Door ................................................................................................................................................................................................66
Figure 86 Open Rectifier Door ...............................................................................................................................................................................................66
Figure 87 Remove Rectifier ......................................................................................................................................................................................................66
Figure 88 Inventory Screen ......................................................................................................................................................................................................68
Figure 89 Main Screen - web ...................................................................................................................................................................................................69
Figure 90 NE830 Alarm Cable Connector ......................................................................................................................................................................70
Figure 91 Front Panel - Pulsar Plus Controller .............................................................................................................................................................70
Figure 92 Front Panel - Millennium II Controller .......................................................................................................................................................72
Figure 93 Rectifier Face Plate .................................................................................................................................................................................................86

Page 5

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Table of Tables
Table 1 Rectifiers and Converters..........................................................................................................................................................................................14

Table 2 Conduit Size - Input Feed ........................................................................................................................................................................................35

Table 3 Alarm Defaults – Standard Pulsar Plus ...........................................................................................................................................................56

Table 4 Analog Interface Connector Signals – Pulsar Plus ..................................................................................................................................58

Table 5 Auxiliary Input Connector Signals - Pulsar Plus........................................................................................................................................59

Table 6 Alarm Signals - Pulsar Plus .....................................................................................................................................................................................60

Table 7 Power and Sense Signals - Millennium II ......................................................................................................................................................63

Table 8 Power Connections - NE830 ..................................................................................................................................................................................70


Table 9 Alarm Connections - NE830 ...................................................................................................................................................................................70

Table 10 Push Buttons - Millennium II ...............................................................................................................................................................................73


Table 11 Rectifier/Converter LEDs .........................................................................................................................................................................................86

Table 12 Alarm and Control - Signal Names and BSL Pins ..................................................................................................................................89

Table 13 Alarm - Descriptions, BLS Pins, and Signal Names...............................................................................................................................90

Table 14 Alarm and Control Inputs - Descriptions, BLS Pins, and Signal Names .................................................................................91

Table 15 TR Leads and Associated Rectifiers .................................................................................................................................................................93

Page 6

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Introduction
This manual is intended as a guide in assisting equipment understanding, installation, testing, and troubleshooting.
For additional assistance contact Technical Support or access additional information on-line.

Reference Documents

Document Title

Infinity M Product Line Brochure – Specifications and Ordering Guide

H5692448-AD NE System, 24V and/or 48V and/or 58V Assembly Drawing

CC848815341 Galaxy Pulsar Plus2 Family Product Manual

108994645 Galaxy Millennium II3 Installation and User’s Guide

107570517 RPM J85501G-1 Product Manual

850049786 Pulsar Troubleshooting Guide for NE-M with SNMP Traps

850047312 Quick Start Guide for 150044438 Modbus to RS232 Interface

Contact Information
Phone: +1 972 244-9288
Email: [email protected]
Web site: omnionpower.com

2
Referred to as “Pulsar Plus” throughout this document.
3
Referred to as “Millennium II” throughout this document.

Page 7

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Product Description
Infinity M (NE-M) is available in multiple system arrangements. Block diagram - Figure 1.

Refer to the Infinity M Product Line Brochure for detail description.

Single or Dual Output Voltage

Primary DC Voltage Secondary DC Voltage

(Battery and Rectifiers) (dc/dc Converters)

24V none

24V 48V

48V none

48V 24V

48V 58V

Battery Connections
• Direct connection to NE-M system bus
• Through a Low Voltage Battery Disconnect (LVBD)
• Through battery maintenance switches or circuit breakers located at the battery
DC Distribution
• Panel Positions: 2, 3, or 4 (13U, 18U, or 22U systems)
• Panels: Bullet Positions, Selectable Bullet Positions, Bolt In Breakers / Fuses
• DC Voltage: Primary only or Primary and Secondary
• Selectable distribution options
Power Shelves
• Universal power shelf accepts rectifiers or converters interchangeably in any power slot
• Rectifier power shelf for 48V rectifiers only.
• Can be installed with no AC connected, as a converter only shelf
AC Feeds
• Front accessible terminal blocks
• One or two rectifier positions per feed
• Side access AC conduit knockouts
Controller
The controller monitors and controls system operation.
• Pulsar Plus (Eco features included)
• Millennium II
Framework
• 84 inch, or 42 inch frame
• Sub-frame - mount in customer provided 23 inch frame

Page 8

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Supplemental Frame
The optional Supplemental Frame and adds DC distribution, power shelves, and battery connections.
• Millennium II controller required in Initial Frame.
Eco Capable Systems - Pulsar Plus only
Eco capable systems (Eco systems) add support for multiple power inputs of multiple types, including PV (photo
voltaic or solar) arrays.
Power Input
• PV (photo voltaic or solar) arrays
• AC generators
• AC mains
Rectifiers
Infinity Eco Rectifiers4

• Input - AC or DC (PV or solar) input


• MPPT (Maximum Power Point Tracking) maximizes power harvested from PV arrays
• Recommended for all rectifier positions in Eco systems
Controller
• Pulsar Plus
• Eco features included (PV, Gen Set, etc.)

4
REQUIRED – Eco rectifiers in all DC (PV or solar) powered rectifier positions.
RECOMMENDED – Eco rectifiers in all Eco system rectifier positions.
NOT RECOMMENDED – non-Eco rectifiers in Eco systems.
Non Eco rectifiers will not function properly when powered by DC (PV or solar) input in Eco systems.
Use of non-Eco rectifiers in Eco systems increases the risk of improperly filling all system rectifier positions.
Non Eco rectifiers may be installed in AC powered rectifier positions of Eco systems.

Page 9

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Figure 1 Block Diagram

Page 10

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Components
• Systems (with 4 rectifier shelves)
• 13 U with 2 distribution panel positions
• 18 U with 3 distribution panel positions
• 22 U with 4 distribution panel positions
• Frameworks:
• Full-Height Frame
• Half-Height Frame
• Sub frame with frame mounting brackets
• Pulsar Plus or Millennium II controller
• NE830 Redundant Voltage Monitor
• Infinity (NE)-Series Rectifiers and Converters AC Input
• Front accessible AC terminal blocks Terminals, DC
Output
• Battery Options and Monitoring: Distribution,
and Battery
• Battery Trays with Disconnect Breakers Connections
• Battery Trays with Anderson PowerPole® disconnects
• Battery Trays with direct Cable Connections
Milllennium NE830
• LVBD Contactors Controller Voltage
• Thermal/Voltage Probes Display

• External Ambient Temperature Probes


• Battery Shunt (Standard in all systems)

NE Series
• DC distribution options: Rectifiers and
Converters
• Bullet Terminal Panels – 26 position
• Fit in 1 distribution position Figure 2 NE-M Components
• Single Voltage (24 or 48V) or Selectable Voltage (24V/48V,
48V/24V, or 48V/58V) per position
• Integrated return bar
• Bullet terminal breakers up to 400A
• TPS fuses up to 70A
• GMT module fuses up to 15A – 6 position and 10 position
• Shunt option
• Bolt-in Large Distribution Panel (12 position) mounted in:
• Bottom 2 distribution positions with integrated return bar
or
• Bottom distribution position with top of frame return bar.
or
• Top and Bottom distribution positions with integrated
return bar (22U 4 distribution panel bay only)
• KS22012 breakers up to 1200A
• TPL-C Fuse holders
• Additional Power shelves
9 shelves maximum
7 AC powered shelves maximum

Page 11

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Controller - Pulsar Plus

Plant Status LEDs

Plant Voltages and


Load Currents

RS-232 and LAN


Ports for PC
Web Pages

Voltage Test Jacks Plant Mode


Menu Navigation

Figure 3 Pulsar Front Panel

• LVBD and LVLD Low Voltage Disconnect contactor


• Local or remote viewing and configuration of
control and monitoring
system parameters, alarm thresholds, and user-
definable alarm inputs and relays • dc Distribution monitoring

• Extensive rectifier/converter Monitoring and Control • Standard and Programmable Alarms

• Advanced Battery Management to maximize and • Extensive Voltage, Current, Temperature, and Binary
manage battery health Input monitoring

• Emergency Power Off (EPO) to meet local • Standard and programmable Office Alarm relays
emergency services code requirements
• Digital communications to all system devices
• System voltage and current monitoring

See the Galaxy Millennium II Installation and User’s Guide for further detail.

Controller – Millennium II
Number of Alarms Plant Voltage and Load Current
Plant Status LEDs Alarm Test and Warnings Date and Time

Plant Mode

RS-232 Port Increment / Decrement


Voltage Test Jacks Menu Navigation

Figure 4 Millennium II Controller Front Panel

Page 12

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
• Local or remote viewing and configuration of • LVBD and LVLD Low Voltage Disconnect contactor
system parameters, alarm thresholds, and user- control and monitoring
definable alarm inputs and relays • dc Distribution monitoring
• Extensive rectifier/converter Monitoring and Control • Standard and Programmable Alarms
• Advanced Battery Management to maximize and • Extensive Voltage, Current, Temperature, and
manage battery health Binary Input monitoring
• Emergency Power Off (EPO) to meet local • Standard and programmable Office Alarm relays
emergency services code requirements • Digital communications to all system devices
• System voltage and current monitoring • Remote Peripheral Modules (RPMs)

See the Galaxy Millennium II Installation and User’s Guide for further detail.

Aux Display - NE830A (Optional)


The Aux Display is a voltage monitor that alarms when the voltage of the power system is out of the normal operating
range. It is mounted on the door of the distribution box

• Fully independent of the main system controller


• Display one or two system voltages and battery state:

• Single voltage systems, -48V, +24V, -58V


• Dual voltage systems, -48V, +24V, -58V with common return
• The display and LED color indicates battery charge state and wiring errors:
• Green display = batteries are not discharging
• Red display = batteries are discharging
• Amber display = wiring error
Figure 5 NE830 Display
• A Battery on Discharge alarm relay with form-C contacts is provided
• Can be panel, wall or frame rail mounted within 150 ft. of the power system

Rectifiers and Converters


NE-Series rectifiers and converters are hot-pluggable for quick, simple, plug-and-play installation without tools.

Type
Badge

Figure 6 Rectifier and Converter Type Badge

NE Eco Rectifiers
Input AC or DC (PV or solar)
Compatibility All Infinity Rectifier Positions
Eco Feature MPPT (Maximum Power Point Tracking) maximizes power harvested from PV arrays
NE Non-Eco Rectifiers
Input AC only
Compatibility All AC powered Infinity Rectifier Positions5
5
Non Eco rectifiers will not function properly when powered by DC (PV or solar) input in Eco systems.

Page 13

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Table 1 Rectifiers and Converters

Rectifier/Converter Input Output Eco Compatible

Eco Rectifier
ac 110/200-277 Vac
dc 60Vdc (+/-30V)
NE050ECO48ATEZ 48V, 50A10 Yes6
to 310Vdc (+/-155)
11A max
Blue

Eco Rectifier
ac 110/200-277 Vac
dc 60Vdc (+/-30V)
NE100ECO24TEZ 24V, 100A7 Yes6
to 310Vdc (+/-155)
11A max
Orange

Converter
NE040DC48ATEZ 48V, 40A No
24 Vdc
NE030DC48A 48V, 30A No
blue

Converter

NE075DC24A 48 Vdc 24V, 75A No

Orange

Converter

NE070DC58A 40-58 Vdc 58V, 70A No

Blue

NE075AC48ATEZ 110/200-277 Vac 48V, 75A8


Rectifier
NE075AC48ATEZ+ 110/200-277 Vac 48V, 75A8
NE055AC48ATEZ 110/200-277 Vac 48V, 55A10 AC Only9
NE050AC48ATEZ 110/200-277 Vac 48V, 50A10
Blue
NE050AC48A12 200-240 Vac 48V, 50A12
Rectifier NE100AC24ATEZ 110/200-277 Vac

24V, 100A12 AC Only9


NE100AC24A12 208/200-240 Vac
Orange

NE Slot Filler
6
REQUIRED – Eco rectifiers in all DC (PV or solar) powered rectifier positions.
RECOMMENDED – Eco rectifiers in all Eco system rectifier positions.
NOT RECOMMENDED – non-Eco rectifiers in Eco systems.
Non Eco rectifiers will not function properly when powered by DC (PV or solar) input in Eco systems.
Use of non-Eco rectifiers in Eco systems increases the risk of improperly filling all system rectifier positions.
Non Eco rectifiers may be installed in AC powered rectifier positions of Eco systems.
7
44A with 120Vac input
8
22A with 120Vac input
9
NOT RECOMMENDED for use in Eco systems - Non Eco rectifiers will not function properly when powered by DC (PV or solar) input in Eco systems.
Use of non-Eco rectifiers in Eco systems increases the risk of improperly filling system rectifier positions. These rectifiers can be used by the AC
sources only.
10
25A with 120Vac input
11
50A with 120Vac input
12
Non-TEZ rectifiers are no longer orderable and have lower efficiency than TEZ rectifiers
Page 14

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Power Input Panel

Power Input
Terminal Blocks Accept 24-6 AWG wire.
Terminal blocks in a front access Conduit Ground Straps provided to
panel at the bottom of the ¼-20 x 0.75” or 0.625” feed rectifier pairs.
Studs
distribution box.

Knockouts
each side:
(2) 1” and
(2) 1-1/2”

Figure 7 Power Input Panel

Battery Options and Monitoring Features

Battery Options
• Designed for operation with OmniOn flooded, VRLA and Durathon
Sodium batteries, as well as other vendors’ batteries.
• Battery trays are available for 100Ahr to 170Ahr batteries with Anderson
PowerPole® connectors or circuit breaker disconnects.
• Half-height and third-height systems can be mounted on floor-mounted
VRLA strings or on OmniOn Universal Battery Stands.
Battery Monitoring Features
• Open String (OS) Alarms
• Emergency Power Off (EPO) for disconnecting batteries from the system
• Temperature/voltage probes (up to 16) used in Battery Management
options
• Slope Thermal Compensation – High and Low Temperature
• Battery High Temp Disconnect
• Mid-String Voltage Monitoring
• Battery Discharge Test
• Battery Shunt
• Low Voltage Battery Disconnect/Reconnect Contactor (LVDB)
with Emergency Power Off (EPO)

Figure 8 Battery Stand

Page 15

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
DC Distribution and Battery Termination
Distribution panels are factory installed.

Examples Features

• 11 pair Battery and Return bus landings for battery


cables
26 Position Bullet Panel
• LVBD Contactor option
• 26 Bullet Distribution positions per panel arranged for:
26 Position Bullet Panel • Bullet terminal breakers to 250A
• TPS fuse holders for fuses to 70A
• GMT Fuse Module - 6 position
26 Position Bullet Panel
• 12 Bolt-in positions
• KS22012 circuit breaker
• TPL-C Fuse holders
26 Position Bullet Panel

• Distribution Panel Positions

System Distribution Panel Positions


13U 2

18U 3

Figure 9 DC Distribution 4 Bullet Panels 22U 4

• Universal Power Shelves

26 Position Bullet Panel

Battery Bus
Battery
26 Position Bullet Panel Return Bus

Panel A

12 Position Bolt-in Panel B


Panel with integrated
return bar Mounts in
bottom 2 distribution Panel C
panel positions

Panel D

AC Terminal
Blocks
1
Figure 10 DC Distribution – Bolt In Panel with return bar Shelf 2
Positions 3
4
22U System Examples

Rectifier
Positions Figure 11 NE-M System – 22U

Page 16

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Shunt Bus Arrangement

Shunt

Shunt

Figure 12b Old Shunt Bus Arrangement


Figure 12a New Shunt Bus Arrangement (series 1:3 )

Page 17

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Installation
Follow all site engineering instructions. This section is provided only as a guide

Preparation
Safety

Read and follow all safety statements, warnings, and precautions in the Safety section of this manual and manuals of
all other equipment before installing, maintaining or repairing the equipment.

Installation Tools

You will need the following tools

• Wire cutters and strippers • 12" extension for socket

• Heat shrink gun • Masonry drill kit as required

• Digital meter with an accuracy of ±0.02% • Compression tool for installation of various
compression lugs
• Screw drivers (flat-blade and Phillips)
• Protective canvas
• ESD wrist strap
• Insulating rubber mat
• 24/58V or 48V test load
• Standard insulated installation tools, screwdrivers, etc.
• Calibrated clamp-on dc current meter (0.1 ADC
sensitivity) • Windows-based personal computer laptop (PC) and
cable to connect the PC communications port to the
• Torque wrench
local port of the controller or a CAT5 LAN cable.
• Sockets -: SAE and metric (Optional. See the controller manual for more
information).
5/16”, 7/16”, 9/16”, 19 mm, etc.

Equipment Identification
Identify the equipment you have received. Follow procedural steps which match the equipment being installed.

Page 18

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Anchor Frame
Ventilation space is required to the rear of the equipment: 4” to solid surface, 6” to heat producing surface.
Floor Mounted Frame
Using the 4600403406P Floor Anchor is recommended (minimum of 4).

Anchor Type (Hilti) Wrench Torque

720 in-lb
(4) 12 mm Cap Bolts 19 mm 60 ft-lb
82 Nm

Frame Isolation Kits for isolated ground applications. Each kit includes an isolation pad, (4) isolation washers and (4) 2”
hold down plates.
Non-Seismic - 1600389835A
Seismic (includes 4 - 12mm Red-Head Cap bolts) - 1600407312A.

Note: If using Equivalent Floor Anchors, make sure the floor anchors are rated for this application.
Note: An optional Supplemental Frame (without controller) may be located on either side of the Initial Frame (with
Millennium II controller).

Step Action

Figure 13 Frame Mount Footprint


7ft Frames

CAUTION: Health Hazard


Follow safe floor drilling procedures to prevent possible asbestos exposure.

1 Drill anchor holes.

2 Place frame and install floor anchors per manufacturer requirements.

3 Repeat for Supplemental Frame, if it is to be installed.

Page 19

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Battery or Battery Stand Mounted Frame

Step Action

Verify that battery or battery stand is positioned to provide adequate ventilation space to the rear of the
equipment: 4” to solid surface, 6” to heat producing surface. Figure 13 shows the placement of the base of
the floor mounted frame to meet ventilation space requirements.
Place and secure frame to battery or battery stand per instructions provided with the battery stand or
adapter.

1
Minimum Distance to Surface
7.5" to Solid Surface
9.5" to Heat Producing Surface

Figure 14 Battery Stand Mount

Sub-frame Mounted Systems:


Sub-frame mounted systems can be mounted in any standard 23” equipment mounting rack or frame with EIA-310
standard 1-3/4” rack spaces or 1” standard rack spaces. The brackets are 36.75” (21U) tall. Comcode CC848819607 kit
provides two brackets and 20 12-24 mounting screws.

Step Action

Verify that the rack is positioned to provide adequate ventilation space to the rear of the equipment: 4”
to solid surface, 6” to heat producing surface.
Distance required to rear of mounting rails: 16.5” to solid surface, 18.5” to heat producing surface.
Position the sub-frame system in the rack as desired.
Secure the sub-frame system into the rack with at least (12) frame mounting screws, 6 screws per side.
Torque to 35 in-lb – 5/16 socket.

Figure 15 Mount Sub-Frame

Page 20

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Ground Frame
Floor Mounted Frame
Select a Frame Ground landing on the top of the frame and clean.

Step Action
Secure Frame Ground connection with
Use either of two frame ground lug
provided hardware: landing locations.
(2) ¼-20 x ¾” HH Bolt
(2) ¼-inch lock washer
(2) ¼-inch flat washer
If required by local code or practice, treat with
an oxidation inhibitor such as NO OX.

1 6 AWG minimum recommended.


Torque to 65 in-lb - 7/16” socket.

Note: Lug landings are 1/4” on 5/8”and 1” centers.


Figure 16 Ground Frame

Battery or Battery Stand Mounted Frame


If required by local code or practice, battery or battery stand mounted frames may be grounded to the frame or
chassis of the other equipment. Select a Frame Ground landing at the side of the frame and clean.

Step Action

Secure Frame Ground connection with


provided hardware:
(2) ¼-20 x ¾” HH Bolt
(2) ¼-inch lock washer
(2) ¼-inch flat washer
If required by local code or practice, treat with
an oxidation inhibitor such as NO OX.
1
6 AWG minimum recommended.
Torque to 65 in-lb - 7/16” socket.

Note: Lug landings are 1/4” on 5/8”and 1” centers.

Figure 17 Ground Short Frame

Page 21

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Connect Central Office Ground (COG)

Step Action

CO Ground
Lug Landing

Secure COG connection with provided hardware:


(2) 3/8-16 nut
(2) 3/8-inch lock washer
(2) 3/8-inch flat washer
1
If required by local code or practice, treat with an
oxidation inhibitor such as NO-OX.
Figure 18 CO Ground Landing
Torque to 240 in-lb - 9/16” socket.
Lug landings are 3/8” on 1” centers Lugs not provided.

Connect Supplemental Frame


This section applies only to installations with an Initial and a Supplemental Frame.
The Initial Frame must be equipped with a Millennium II controller.
Interconnecting bus bars, hardware, and cables are shipped loose with the Supplementary Frame.

Initial Frame Supplemental Frame

Figure 19 Supplemental Frame

Page 22

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Connect Interframe Bus Bars

Step Action

1
848414611 Lexan Cover (2)

8500051755 Interframe Bus (2)

847760204 T-Bus Return (2)

847760196 T-Bus -48V (2)


4
850046677or Link Bus (4)
2
5
3 8600264175P

5/16” Hardware
5/16” Hardware
3/8” Hardware
3/8” Hardware

Primary Bus
Rear View Return Bus
Rear View
Figure 20 New Interframe Bus Bars

Page 23

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Connect Interframe Bus Bars

WARNING: Energy Bus bars of systems with powered rectifiers or batteries connected provide hazardous
electrical energy.

Are Initial Frame rectifiers ON or batteries connected?


Yes – go to Step 1. No – go to Step 2.
Verify AC power is OFF and Batteries are disconnected.
Use appropriate lock-out tag-out procedures before continuing.
1
• Turn all AC breakers off and lock-out tag-out.
• Disconnect all batteries.

Attach 850046677 Link Buses 5 to Primary voltage-buses and Return buses in both cabinets (4 places).
2
Secure with 3/8” hardware provided – Torque to 240 in-lb (27 Nm) – 9/16” socket.

Attach T-Bus bars 3 & 4 as shown (4 places).


3
Secure with 5/16” hardware provided – Torque to 160 in-lb (18 Nm) – 1/2” socket.
Attach Interframe Bus bars 2 as shown (2 places).
4
Secure with M8 hardware provided – Torque to 160 in-lb (18 Nm) – 1/2” socket.
Cover Interframe Bus bars with two 848414611 Lexan Covers 1.
5
Remove paper covering on covers before installing.

Page 24

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Connect Interframe Secondary Voltage Cables

Step Action

WARNING: Energy Bus bars of systems with powered rectifiers or batteries connected provide hazardous
electrical energy.

L635L Dual Voltage Panels

Figure 21 L635L Dual Voltage Panel Location


Are Initial and Supplemental Frames both equipped with L635L Dual Voltage Distribution Panels in their
bottom shelf positions?

Yes – go to step 1. No – go to next section.


Two 4/0 AWG cables will be installed between the two frames, connecting their secondary buses together.
Systems with 24V rectifiers - install the cables on the 48V secondary buses.
Systems with 48V rectifiers - install the cables on the 24V/58V secondary buses.

Existing 5/16” Bolts


2-Hole Lugs
Figure 22 Secondary Voltage Bus
24V/58V Secondary 48V Secondary
Voltage Bus Voltage Bus

System with 48V Rectifiers System with 24V Rectifiers

Page 25

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Verify AC power is OFF and Batteries are disconnected.
Use appropriate lock-out tag-out procedures before continuing.
• Turn all AC breakers off and lock-out tag-out.
• Disconnect all batteries.

3 Remove the rear covers of the cabinets in both frames.

Connect two 4/0 cables to the Secondary Voltage bus of the Supplement Frame.
a. Remove the existing 5/16 bolts connecting the vertical bus link to the L635L panel at the bottom
position of the secondary frame.
b. Apply 2-hole lugs to both 4/0 cables – lugs provided.
4 Apply heat shrink to the lug shanks.
c. Connect the cables to the hole sets.
Apply No-Ox.
Use the bolts removed in a. and the 5/16 hardware supplied.
d. Torque to 135 in-lbs.

Route both new 4/0 Flex cables up through the rear of the secondary frame, across and down to the same
5
positions within the primary frame.

Connect two 4/0 cables to the Secondary Voltage bus of the Primary Frame.
a. Remove the existing 5/16 bolts connecting the vertical bus link to the L635L panel at the bottom
position of the secondary frame.
b. Apply 2-hole lugs to both 4/0 cables – lugs provided.
6 Apply heat shrink to the lug shanks.
c. Connect the cables to the holes with the cables routing up.
Apply No-Ox.
Use the bolts removed in a. and the 5/16 hardware supplied.
d. Torque to 135 in-lbs.

7 Replace the rear covers of the cabinets in both frames.

Page 26

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Connect Interframe Signal Cables

Step Action

6 BIC 10

7 Millennium II Controller

8 Shunt RPM

Initial Frame Supplemental Frame

W
BL
Battery Shunt Leads to
P9 P6 Connector
Coupler
P6

J3

J2
Factory cable to Rectifier
J1 Shelves in Supplemental
Frame
BIC 10
Pin10-BL to Supp Frame BIC 10 TB1-SH-
Pin 4-W to Supp Frame BIC10 TB1-SH+

Figure 23 Interframe Cables

Connect RJ45 Cables

Connect 10 ft. RJ45 cable (847690799) into J2 on BIC 10.


1 Route to Millennium II Controller in Initial Frame.
Disconnect Factory RJ-45 cable from P9 and insert into Coupler.

Connect 10 ft. RJ45 cable (847690799) into J3 on BIC 10.


2
Route to Millennium II Controller in Initial Frame, insert in P9 connector of Millennium II Controller.

Connect Battery Shunt Cable


3 Connect 20 ft. 2-wire cable (850052873) bare ends to BIC 10 TB1: BL to SH-, W to SH+.
4 Route cable to Millennium II Controller P6.
5 Connect wires to butt splices on lead of P6 wire set – W to W-BL & BL to BL.

6 After applying power, configure Second battery shunt – see Configure Millennium II Controller section.

Page 27

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
To next panel or to Frame FAJ

24V FAJ

To next panel or to Frame FAJ

48V FAJ

Figure 24 Breaker Panel Alarm Connections

Connect Breaker Panel Alarms

Each Breaker panel has FAJ Faston® connections on the left side of the panel.
Single voltage panels have a either a 24V or a 48V or a 58V FAJ pin and the selectable panel (if present) has both.
Alarms for the Primary voltage in the both frames should be factory jumpered together.

a. Verify that all supplemental frame breaker panel Primary voltage FAJ alarms are
7 jumpered together.
b. Connect them to the same FAJ connection on the initial frame (white wire).

Connect Secondary voltage FAJ alarm from supplemental frame breaker panel to the
8
same FAJ connection in the Initial frame (yellow wire).

Page 28

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Figure 25 RPM Connections
Connect RPMs
RPMs in Supplemental Frame?
Yes – go to Step 9. No – go to next section.
9 Connect 407377704 RPM cable between RPMs as shown.

10 Set RPMs to unique addressed using RPM SW1 and DW2 rotary switches (refer to RPM manual).

Move 560 Ohm resistor from RPM in Initial frame to the last RPM in the daisy chain in the Supplemental
11 frame.
Only the last RPM in the daisy chain should have the resistor.

After applying power


12 a. Configure Plant Shunt 2 for Supplemental Frame -see Configure Millennium II Controller section.
b. Configure the RPM channels per site installation instructions – refer to RPM manual.

Page 29

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Set Supplemental Frame ID on BIC 10

Step Action

10’s 1’s

Frame ID

Figure 26 Set Frame ID on BIC 10

1 Verify Supplemental frame ID is set to 2. (Factory default is Frame 2.)

Install PV/AC Partition Kit – NE-M Eco systems only


This section applies only to NE-M Eco systems.
NE-M Eco systems power some rectifiers from PV (photo voltaic or solar array) and others from ac, typically a
generator.
Each terminal block powering rectifiers can be connected to either PV or ac, but not both.
The PV/AC Partition Kit (150028727) divides the Input panel into separate input sections for PV and AC fed terminal
blocks.

Figure 27 Eco Input Panel

Page 30

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
CAUTION: Personal injury and Equipment Damage
PV Disconnect Panel with disconnects rated at 400Vdc on each PV conductor is required for
use with Solar Arrays (PV sources).

Step Action

1 Remove the Input Panel cover (4 captive screws).

Figure 28 Input Panel Screws

Apply labels onto PV/AC Partition as shown.

2 • Place “PV WIRING” label on the left (PV) side of partition.


• Place the “AC WIRING” label on the right (AC) side of
partition.

Figure 29 Partition Labels

Make space for the PV/AC Partition - Separate DIN rail


Terminal Blocks to make space for the PV/AC Partition.
3 Loosen screws securing all DIN spacer blocks to the left of
the Partition location specified in the site engineering
instructions.

Page 31

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Slide Terminal Blocks and spacer to the left of the Partition
4
location to the left to allow installation of the PV/AC Partition.

Figure 30 Partition Insert

Install PV/AC Partition in the location specified in the site


5 engineering instructions.
Snap the Partition onto the DIN rail.

Slide the loosened Terminal Blocks and spacer block to the


right snugly against the Partition.
6
The Partition lower edge will be under the Terminal Block on
its left.

Tighten screws securing all DIN spacer blocks s to the left of


7
the Partition.

Apply labels to the Input Panel chassis.

• Place “PV Wiring” label on the left (PV) side of


8
partition.
• Place the “AC Wiring” label on the right (AC) side
of partition.

Figure 31 Label Input Panel

9 Replace the Input Panel cover and secure fasteners.

Apply 2 labels to Input Panel cover in any available space.


10 • Warning label
• Max Power-Point label

Figure 32 Label Input Panel Cover

Page 32

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Connect Input Power

WARNING: Shock Hazard


Disconnect all input branch circuits prior to making input connections to the system. When
connecting to any source, ensure compliance to all local and national wiring rules.

CAUTION: Equipment Damage


PV inputs must be current limited to 11A maximum.

Terminal Block are arranged to allow addition of shelves (to the bottom) and terminal blocks (from the inside out).
Shelves 1 through 7 may be rectifier shelves.
Additional converter only shelves may be added as needed – no AC power provided.

Figure 33 Input Power Terminal Block Positions

Shelf Slot ID
Label

Figure 34 Rectifier / Converter and Shelf Numbering

Figure 35 Rectifier Dual Feed Jumper Positions – ac feeds only

Page 33

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Step Action

Route and attach conduit or other commercial fittings.


Input power is connected to terminal blocks located
within the Input Panel. Terminal blocks for up to 7
rectifier shelves may be present. Conduit Knockouts
(both sides)
AC Bridging jumpers 13
1
• AC inputs – jumpers may be installed to power two
rectifier positions with one AC feed.
• PV inputs - Do not apply AC bridging jumpers.
Each PV feed must power a single rectifier.
Figure 32 shows Input Power Terminal Block Positions. Input Panel

Figure 36 Input Conduit Locations

AC input feeds to rectifier pairs?

Yes – go to Step 2. No – go to Step 4.

L2/N Terminals

Snap loose L1 and L2/N plastic dividers on Input terminal


2 blocks for each single fed rectifier pair.
Figure 34 shows rectifier AC dual feed jumper positions. L1 Terminals

R13 R14
Figure 37 Input Jumper Dividers

Install AC bridging jumpers connecting each AC fed


rectifier pair L1 positions.
3 Install AC bridging jumpers to connect each AC fed
rectifier pair L2/N positions.
Torque to 10 in-lb.
R13 and R14 R13 and R14
L1 Bridging Jumper L1 AC feed

Figure 38 AC Bridging Jumper

CAUTION: Equipment Damage or Malfunction


NE-M Eco systems must keep PV input feeds separate from AC input feeds.
The PV/AC partition separates PV inputs from AC inputs.
Connect PV input feeds only to the PV section of the Input Panel.
Connect AC input feeds only to the AC section of the Input Panel

CAUTION: Equipment Damage or Malfunction


NE-M Eco systems PV input feeds must be connected as follows:
Positive PV to L1
Negative PV to L2/N.

13
shipped with each system

Page 34

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Step Action

Pull and terminate input feed wires to the terminal


blocks in the Input Panel.
• ac input feeds to the AC section of the Input Panel
• PV input feeds to the PV section of the Input Panel
4 Positive PV to L1
Negative PV to L2/N.
PV Section ac Section
NE-M Eco only NE-M Eco only
Torque to 10 in-lb.
Figure 33 shows rectifier and shelf numbering.
PV/AC Partition
Eco only

Figure 39 Input Panel Sections

Table 2 Conduit Size - Input Feed


#14of Rectifiers Minimum Conduit
Rectifies Min. External Wire Conductors per
AC per Conductor Size
per feed Breaker Gage Conduit16 17
Feeds Conduit Rating15 (minimum)

AC Feeds NE075AC48xxxx at 200-240V~ or 200-277V~, 22A


(16) 4 1 30A (4) 8 33.5A 9 (70% derated) 1”
(55A*0.87*0.7)
(28) 7 1 30A (7) 6 32.6A 15 (50% derated) 1-1/2”
(75A*0.87*0.5)
(24) 6 2 60A (3) 6 52.2A 7 (80% derated) 1”
(75A*0.87*0.8)

AC Feeds NE0100AC24xxxx and NE050AC48xxxx at 200-240V~ or 200-277V~, 15A


NE055AC48xxxx at 200-240V~ or 200-277V~, 16A
(28) 7 1 20A (7) 10 17.4A (40A *0.87*0.5) 15 (50% derated) 1”
(28) 15 1 20A (15) 10 15.7A (40A *0.87*0.45) 31 (45% derated) 1-1/2”
(28) 10 1 20A (10) 8 23.9A (55A *0.87*0.5) 21 (50% derated) 1-1/2”
(24) 6 2 40A (3) 8 38.3 (55A*0.87*0.8 7 (80% derated) 1”
(28) 8 2 40A (4) 6 45.7A (75A*0.87*0.7) 9 (70% derated) 1-1/2”

PV Feeds
(28) 7 1 15A/400Vdc (7) 12 17.4A 15 (50% derated) 1”
(40A*0.87*0.5)
(28) 10 1 15A/400Vdc(10) 12 17.4A 21 (50% derated) 1-1/2”
(40A*0.87*0.4)
14
28 power units maximum in 7 power shelves maximum.
15
Based on NEC: 90°C Conductor, 45°C Ambient, and Number of Wires in Conduit.
16
Includes 1 ground per conduit - not considered in derating.
17
AC and PV feeds must be in separate conduits

Page 35

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Install Battery Trays
Optional battery trays are suitable for use with general trade batteries such as Northstar Battery NSB110FT and
NSB170FT.

Step Action

Position the battery tray in the


frame with frame mounting
brackets on both front and back
1 of frame as shown.
Secure with provided screws.
Back view
Front view
Torque to 35 in-lb – 5/16” socket.
Figure 40 Battery Trays

Page 36

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Install Batteries

WARNING: Energy and Chemical Burn


All batteries contain hazardous electrical energy.
Lead-acid batteries contain sulfuric acid and explosive hydrogen gas.
Follow all precautions noted in the literature accompanying the batteries.
Use only insulated tools.

CAUTION: Equipment Damage


Equipment frame anchoring, load rating, and seismic zone rating should be verified before
field installing trays and batteries.

Tray Mounted Batteries


The system can be configured with battery trays sized for various batteries and may include optional factory installed
battery disconnect or battery mid-string voltage and temperature monitoring units. Compatible batteries include.

• North Star NSB110


• Power Battery CSL-12100
• North Star NSB170
• East Penn 12AVR100-3ET
• East Penn 12AVR150-3ET
• Equivalent 100 AH front-terminal batteries
• Equivalent 110-210AH front-terminal batteries

2/0 Cable Connect Return Cable


to this battery post

VT Probe Cable

Switch Cover
ES771 Card

Battery Spacer (3)


848466884

Figure 41 Batteries in Tray – 48V

Page 37

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Step Action
Notes:
1. Steps show four 12V batteries per shelf – one string of -48V batteries.
2. 1 Battery Disconnect Switch per shelf shown.
Other options
• 2 Battery Disconnect Switches per shelf (left and right) (two 24V battery strings per shelf)
• 1 or 2 Anderson Disconnects per shelf
• No Battery Disconnect Switches or Anderson Disconnects - Battery cables shipped loose.

1 Place four batteries on each battery tray. Spacer

Position three Battery Spacers between the


2
batteries.

Figure 42 Place Batteries

48V Battery Strings: Top Rail


Inter-cell bus bars
Interconnect three inter-cell bus bars to
configure one 48V battery string per the
battery manufacturer’s instructions.
3
24V Battery Strings:
Interconnect two inter-cell bus bars to
configure two 24V battery strings per the
battery manufacturer’s instructions.

Middle bus bar for 48V systems only


4 Attach the battery securing top rail.
Figure 43 Battery Inter-Cell Bus Bars

External Batteries

Step Action
Place batteries on battery trays, battery stands, or other satisfactory supporting surface and interconnect
1
per manufacturer’s instructions to create 24V or 48V strings as required.
Is an external disconnect switch being used?
Yes – go to Step2. No – Finished.
Physically mount switch to an appropriate place and ensure it is in the OFF position prior to making any
2
connections
Connect the battery hot conductor (s) to the line side of the disconnect switch and torque connection per
3
manufacturer's specification.

Connect the load side conductor to the disconnect switch and torque connection per manufacturer's
4
specification.

Page 38

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Connect Batteries
Connect Tray Mounted Batteries
Go to the procedure for the disconnect method provided on the trays:

• Battery Disconnect Switch Connection

• Anderson Connector Connection

• Direct to Battery Bus Connection


Battery cables from factory mounted battery trays are factory installed and terminated to the distribution panel.
Battery Disconnect Switch Connection

Step Action

Disconnect
Ensure disconnect switch is in the OFF position Switch
(downward) prior to making any connections.
1
Remove the two 6/32 screws to remove the
plastic cover.

Figure 44 Battery Disconnect Switch

Input Bus

Connect one end of the 2/0 cable to the input


bus of the disconnect switch with 1/4-20 hex nuts
2 provided.

Torque to 65 in-lb – 7/16” socket.

Figure 45 Batt Disconnect Switch Input Bus

Re-attach clear plastic cover to disconnect switch


3
and secure with 6-32 screws.

Page 39

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Step Action
4 Connect Battery Cable (hot side)

48V Battery Strings

Connect the 2/0 cable between the V- post of the


left-most battery and the input bus of the
disconnect switch.

Torque to battery manufacturer’s specification.

Figure 46 Battery Cable -48V

24V Battery Strings

Connect the 2/0 cable between the V+ post of the


right-most battery of the left string and the input
bus of the left disconnect switch.

Connect the 2/0 cable between the V+ post of the


right-most battery of the right string and the
input bus of the right disconnect switch.

Torque to battery manufacturer’s specification.

Figure 47 Battery Cable +24V

Page 40

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Step Action Action

5 Connect Battery Return Cable (ground side)

48V Battery Strings

Connect the factory-wired battery return cable to


the V+ post of the right-most battery.

Torque to battery manufacturer’s specification.

Figure 48 Battery Return Cable -48V

24V Battery Strings

Connect the factory-wired battery return cables


to the V- posts (left most posts) of both strings.

Torque to battery manufacturer’s specification.

Figure 49 Battery Return Cable +24V

Battery installation is complete.

Follow site engineering instructions regarding when to turn the disconnect switches ON.

Page 41

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Anderson Connector Connection

Step Action

Figure 50 Anderson Battery Connector

Connect Anderson pigtail terminals to battery


string positive and negative terminals.

Positive Anderson Pigtail terminal to the


Positive (right-most) battery terminal
1
Negative Anderson Pigtail terminal to the
Negative (left-most) battery terminal.

Torque to battery manufacturer’s


specification.

Figure 51 Battery Connections - Anderson

Battery installation is complete.

Follow site engineering instructions regarding when to mate the Anderson connectors.

Page 42

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Direct to Battery Bus Connection

Step Action
Direct battery bus connections are not factory installed.

Run cables from the battery buses to the tray


mounted battery strings.
1

Insulate the battery end of the cable.

Make battery cable connections to the system


2 battery bus per the procedure in the Connect
External Batter section.
3 Connect Battery Cable (hot side)

48V Battery Strings

Connect the 2/0 cable between the V- post of the


left-most battery and the input bus of the
disconnect switch.

Torque to battery manufacturer’s specification.

Figure 52 Battery Cable Direct -48V

24V Battery Strings

Connect the 2/0 cable between the V+ post of the


right-most battery of the left string and the input
bus of the left disconnect switch.

Connect the 2/0 cable between the V+ post of the


right-most battery of the right string and the input
bus of the right disconnect switch.

Torque to battery manufacturer’s specification.

Figure 53 Battery Cable Direct +24V


4 Connect Battery Return Cable (ground side)

48V Battery Strings

Connect the factory-wired battery return cable to


the V+ post of the right-most battery.

Torque to battery manufacturer’s specification.

Figure 54 Battery Return Cable Direct -48V

Page 43

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
24V Battery Strings

Connect the factory-wired battery return cables to


the V-posts (left most posts) of both strings.

Torque to battery manufacturer’s specification.

Figure 55 Battery Return Cable Direct +24V

Battery installation is complete.

Connect External Batteries

Step Action

Return Bus Battery Bus

Battery and Return Cable Connections


Secure Battery Cable lugs with hardware (per cable): (2 Figure 56 External Battery Connections
sets) 3/8-16 bolt, lock washer, and flat washer. (Lower row of landings not visible.)

If required by local code or practice, treat with an 850044744 Bus Bars


oxidation inhibitor such as NO-OX.
Torque to 240 in-lb - 9/16” socket.
Note: Lug Landings are 3/8” on 1” centers spaced 1.30”
apart. 848383501 lug
spacer
For lugs wider than 1.25”, use every other
connection (6 total battery connections).
1
For additional battery landings, install two
850044744 bus bars as shown.
Figure 57 Battery Additional Landings
Additional return connections can also be made
by installing 848383501 lug spacers on the Lug landings are 3/8” on 1”
centers
lower row of landings as shown (8 total). Lugs not provided.
(Max lug width = 1.2 inches)

Figure 58 Battery and Return Bus Lug Spacers

Page 44

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Connect Battery Probes

Battery probes are optional controller peripherals.


See the controller manual and instructions accompanying the probes.

Verify Battery Bus Voltage and Polarity

Step Action

CAUTION: Equipment Damage


Do not install rectifiers before battery bus voltage and polarity has been verified.
Rectifiers and system damage will result from incorrect battery bus polarity.
The damage may not be immediately evident.

Battery Return Bus


Label Battery Bus
Verify that the measured voltage matches the Label
bus label using a meter. Please note that the
Battery Return conductors for a -48V power
1 system will be the (+) battery string
conductors and the “hot ” or Battery Bus
terminations will be the (-) battery string
conductors.

Figure 59 Battery Bus Labels

Connect Load Wiring

WARNING: Shock Hazard and Equipment Damage


Do not install circuit breakers or load fuses until the load equipment is ready to be energized.
When a load is ready to be energized
1.Connect the load to the distribution panel.
2.Install the circuit breaker of fuse.

CAUTION: Equipment Damage


Ensure Circuit Breakers are in the OFF position prior to installation.
Ensure Fuse Holders are empty prior to installation.

Notes:
1. Connect the Load Return cable before the Load cable for each load.
The Load Return connection is blocked by the Load cable, if installed.
2. Follow steps of each section below as appropriate to breakers and fuses to be installed.
3. Repeat steps of each section as appropriate.
4. Bolt-in breakers/fuse holders may be factory installed.
5. Bullet Terminal distribution panels accept Bullet Terminal Circuit Breakers, TPS Fuse Holders, and GMT Fuse
Modules.
6. GMT Modules must be installed before loads are connected to the GMT Module.

Page 45

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
1-Pole Breakers and TPS Fuse Holders (bullet)

• +24V protectors install into ORANGE positions


• -48V protectors install into BLUE positions
• -58V protectors install into NAVY BLUE positions
Bullet Distribution Panels are either Single Voltage or Selectable Voltage:
• Single Voltage Panels – all positions of the panel are +24V (Blue) or -48V (Orange) or –58V
(Navy blue).
• Selectable Voltage Panels – each position of the panel may be either +24V or -48V or –58V.

Return Bus

Protector
Alarm Pin (up)
Load Bus

Protector
Alarm Pin (up)

+24V Protector
Note Orienta-
tion
-48V Protector
Note Orientation

+24V Protector positions -48V Protector positions


Orange Terminals Blue Terminals
Upper positions Lower positions

Return Bus

Protector Alarm Pin (up) Load Bus

Protector Alarm Pin (up)

-58V Protector
Note Orientation
-48V Protector
Note Orientation

-58V Protector positions -48V Protector positions


Navy blue Terminals Blue Terminals
Upper positions Lower positions

Figure 60 Bullet Distribution Panel - Selectable Voltage

Page 46

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
1-Pole Breakers and TPS Fuse Holders (bullet) - Continued
Lug Landings – 1/4” on 5/8” centers.
1 Secure Load and Return Cable connections with provided 1/4-20 nuts.
Torque to 65 in-lb - 7/16” socket.

2 Verify voltage and polarity between the Return bus and each distribution input bus using a voltmeter.

3 Verify wiring polarity at the input of the load equipment.

Install breaker or fuse holder as shown above.


4 Leave breaker switches in the OFF position and do not install load fuses until the load equipment is ready
to be energized.

2-Pole and 3-Pole Breakers (bullet)


Adapter Bus on Return Bus
Studs facing to rear

Adapter Bus on Load Buses

Return Bus

Load Buses

+24V Protector
Orange (Upper) positions -48V Protector
Handle is in OFF position Blue (Lower) Positions
Note Orientation Handle is in OFF position
Note Orientation

Figure 61 2-Pole and 3-Pole Breaker Install

Install adapter buses on Return bus with studs facing to rear to all proper clearance.
Secure Two-Pole or Three-Pole adapter buses to the distribution Load and Return buses with provided 1/4-20
1
nuts.
Torque to 65 in-lb - 7/16” socket.
Secure Load Cable connections with provided hardware (per cable):

Adapter with Lug Landings 1/4” on 5/8” centers Adapter with Lug Landings 3/8” on 1” centers
(2) 1/4-20 nut (2) 3/8-16 nut
2 (2) 1/4-inch lock washer (2) 3/8-inch lock washer
(2) 1/4-inch flat washer (2) 3/8-inch flat washer
Torque to 65 in-lb - 7/16” socket. Torque to 240 in-lb - 9/16” socket.

3 Verify voltage and polarity between the Return bus and each distribution input bus using a voltmeter.

4 Verify wiring polarity at the input of the load equipment.

Install breaker as shown above.


5 Leave breaker switches in the OFF position and do not install load fuses until the load equipment is ready to
be energized.

Page 47

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
GMT6A Style Fuse Module (bullet)

GMT Module GMT Module


in -48V positions in +24V positions

Max Fuse 12A


Max Wire 12 AWG
Max Module Current 57.6A

Figure 62 GMT Fuse Module

GMT6A Module must be installed before load connection is made.


Install GMT Module into specified bullet positions: -48V (Blue) or +24V (Orange).

1 Secure GMT Module Return bus bar to the distribution panel Return bus bar with provided nuts.
Note: Return bus on GMT Module is adjustable for -48V or for +24V installation – see GMT Module
Installation Guide.
Torque to 65 in-lb - 7/16” socket.

Strip Load and Load Return wires 3/8” and secure in the GMT module terminal block.
2
Torque to 13 in-lb - screw driver.

3 Dress and wire tie with service loop to provide strain relief.

4 Verify voltage and polarity between the Return bus and each distribution input bus using a voltmeter.

5 Verify wiring polarity at the input of the load equipment.


Do not install load fuses until the load equipment is ready to be energized.

Page 48

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Bolt-In Breakers or TPL-C Fuse Holders
• Bolt-in breakers must be installed before load connection is made.
• Bolt-in breakers can either be factory installed or field installed.
• Breaker kits include mounting hardware, load bus bars, and signal cables (alarm and shunt monitoring).
• Load Return bar may be at the top of the bolt-in panel or at the top of the frame.
• Kits include a load shunt that must be wired to an RPM Shunt Module to monitor the current
(Millennium II Controller only).
• Breaker kits are 1-pole, 2-pole,3-pole, 4-pole,5-pole or 6-pole depending on the ampacity of the breaker.
Discard any excess hardware.

Battery Return
Bus Fastons Bus Fastons

2-Pole Bolt-In Breaker

TPL-C Fuse Holder

Figure 63 Bolt-In Breaker or Fuse Holder Mounting

Figure 64 Bolt-in TPL-C Fuse Holder Wiring

Figure 65 Bolt-in Breaker Wiring

Page 49

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Bolt-In Breakers or TPL-C Fuse Holders

For bolt-in breakers only (skip this step for fuse holders)
Assemble load bus bar to breaker using provided screws, nuts, and washers.
1
Torque nuts to 240 in-lb – 9/16” socket.

Install shunt monitor cable and alarm daisy chain cable and to breaker or fuse holder.
Alarm cables daisy-chain from 850038647 cable through all bolt in breakers.
2
1. Connect alarm cable to pins 8 & 9.
2. Connect shunt monitor cable to pins 12 & 13 (if equipped with shunt monitor RPM).

Install Bolt-in breaker(s) into specified position using provided hardware.


1. Install standoffs - torque to 65 in-lb.
3
2. Secure load bus to standoffs with flat head screws - torque to 65 in-lb.
3. Secure breaker to load bus with 3/8” bolt, lock washer, and flat washer – torque to 240 in-lb – 9/16” socket.

Secure Load Cable connections with provided hardware (per cable):


(2) 3/8-16 nut or bolt
(2) 3/8-inch lock washer Bolt-In Breakers
(2) 3/8-inch flat washer
4
Torque to 240 in-lb - 9/16” socket. Top of Panel Return Bus

Note: Load Return bar for bolt-in panel may be at the top of the bolt-in
panel or at the top of the frame.
Top of Frame Return Bus

Figure 66 Bolt-in Position Return Bar


Connects to leftmost breaker of fuse holder of each panel.

Connect breaker or fuse holder alarm to the system.

Cabinets come equipped with an 850038647 alarm


cable for each bolt-in protector panel.
Pull the 2-pin connector from the wiring bundle along
5 the left side of the cabinet.

Connect the leftmost (first) breaker or fuse holder to


the 2-pin connector of the 850038647 cable.
Daisy chain alarms between additional breakers and
fuse holders.

Figure 67 850038647 Alarm Cable Connection

Connect breaker or fuse holder shunt wires to a shunt monitor RPM (if equipped) – Figure 64
1. Route black and white shunt monitoring wires to a shunt monitor RPM on the front door.
2. Identify the shunt wire pair for labeling RPM channels.
3. Connect shunt monitor cable to a shunt monitor RPM.

Page 50

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Bolt-In Breakers or TPL-C Fuse Holders
Configure Millennium II controller RPM Shunt Channels per site installation instructions (if equipped with
RPMs) – refer to RPM manual.
Shunts:
Fuse Holders 50 mV, 1500 A
7
Breakers 25 mV, amp rating same as breaker rating, e.g. 600 A breaker has 600 A, 25
mV shunt.
Configure RPM channel descriptions, A, and mV in Millennium II controller for each load shunt.

8 Verify polarity (using a voltmeter) of the voltage between the Return bus and the distribution input bus.

9 Verify wiring polarity at the input of the load equipment.


Leave breaker switches in the OFF position until the load equipment is ready to be energized.

Remove bullet breaker panel and replace with TPL fuse panel

Remove bullet breaker panel Replace with TPL fuse panel

Remove fasteners from both sides to disconnect bullet breaker panel


Distribution Options for Group
212L,222L,G222M

Distribution Options for Group


212L,222L,G222M,G222V

TPL Fuse Panel

Page 51

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Remove bullet breaker panel Replace with TPL fuse panel

Remove fasteners from both sides to disconnect bullet breaker panel


TPL Fuse Panel

Distribution Options for Group Distribution Options for Group


213L,223L,G223M,G223V 213L OR 223L

TPL Fuse Panel


Remove fasteners from both sides to disconnect bullet breaker panel

Distribution Options for Group


213L,223L,G223M,G223V Distribution Options for Group
213L,223L,G223M

Page 52

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Remove bullet breaker panel Replace with TPL fuse panel

Remove fasteners from both sides to disconnect bullet breaker panel TPL Fuse Panel

Distribution Options for


Distribution Options for Group Group 214L OR 224L,G224M
214L,224L,G224M

Figure 68 Remove bullet breaker panel and replace with TPL fuse panel

Removing bullet breaker panel and replace with TPL fuse panel
1 Remove the fasteners to disconnect the bullet breaker panel from the associated structure.
2 Attach the TPL-C fuse panel (G636, G637, G637A, G639) to the structure with fasteners.

Page 53

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Verify Installation
Perform the following verification checklist after installation of batteries and wiring:

Step Action
1 Verify cabinet is properly grounded (using Digital Multimeter (DMM)).
2 Verify the AC equipment ground is properly connected.

3 Verify the correct ground cable gauge is used. Use the standard grounding principles for the office.

4 Verify the AC voltage supplied matches the AC input voltage of the rectifiers.
5 Verify all cables are properly installed for the distribution and labeled as 48 V or 24 V.
Examine to assure no sharp corners are in contact with dressed wires.
6
Modify to correct any problems found.
7 Check for conductor clearance within the frame associated with high power.
8 Check that all breakers are OFF and all fuses not inserted.
Verify the battery contactors (LVBD) are open, if equipped.
9
Manually operate them to the open position, if necessary, by pushing the contacts apart.
10 Verify the polarity of all battery cables (using DMM).
Verify no shorts are present between frame ground and the AC service. Measure resistance from each AC
11
input line terminal block position to frame ground.

Verify shelves and rectifier positions are properly


identified. Label positions as necessary.
12
Example is for 7-shelf (row) system (front view).

Front View
Figure 69 Rectifier Positions
Apply labels shown below over existing labels according to usage,

48V Rectifier Only 48/58V Universal Shelf 48/24V Universal Shelf

13

Figure 70 Labeling of rectifier/converter shelves

14 Verify battery negative cables are connected to the appropriate bus bar.
15 Verify battery positive cables are connected to the appropriate bus bar.
Visually verify cables the RS485 cables are properly installed and that shelf ID settings at the rear of the
16
frame are: [Shelf 1, Shelf 2, Shelf 3, etc.] from top to bottom.
Page 54

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Install Controller
Follow the procedures for the controller present in the system.

Install Pulsar Plus

Note: The controller is factory installed and connected to the NE-M equipment.
Connections to the controller made during installation are described here .

CAUTION: Equipment Damage


ESD NOTE: You must protect against ESD prior to configuring and installing the following
circuit cards.

Step Action – Pulsar Plus

Configuring Individual Alarm Output Contact Type – “Close” on or “Open” on alarm


The factory default configuration for all alarm outputs is “Open On Alarm” on alarm.
Is this acceptable?

Yes – go to Step 4. No – go to Step 1.

Attach an ESD wrist strap or equivalent to the


ESD grounding connector on right hand side of
1 the inside of the frame.
ESD Grounding
Connector

Figure 71 ESD Grounding Connector


Locate configuration jumpers for alarm relays on the controller.

Jumpers for each of the 10 output alarms are visible on the back of the door-mounted controller.

Alarm Relay Jumpers


Figure 72 Alarm Relay Jumpers – Pulsar Plus

Page 55

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Step Action – Pulsar Plus
Configure alarm relays to “Open On Alarm” or “Close On Alarm” as specified in site engineering
instructions.

Each Alarm Relay Jumper select “Open On Alarm” or “Closed On Alarm” for one alarm signal and each
signal output can be configured independently.

Carefully move each Alarm Relay Jumper to select “Open On Alarm” or “Close On Alarm” position as per site
engineering instructions with an insulated tool.

Figure 73 Alarm Relay Jumper Positions - Pulsar Plus

The following table contains the alarms along with the factory default alarm assignments to user relays
R1-R7.

3
Utilize the web interface to change any of the alarm user relay alarm assignments.

Table 3 Alarm Defaults – Standard Pulsar Plus


Jumper Signal Standard
Number Name Defaults
1 PCR Power Critical Alarm severity indicator
2 PMJ Power Major Alarm severity indicator
3 PMN Power Minor Alarm severity indicator
4 R1 BD - Battery on Discharge alarm
5 R2 VLV - Very Low Voltage alarm
6 R3 FAJ - External Fuse Major alarm
7 R4 ACF – single rectifier input (AC or DC) Fail alarm
8 R5 RFA - single Rectifier Fail alarm
9 R6 MRFA - multiple Rectifier Fail alarm
10 R7 HV - High Voltage shutdown alarm

4 Using optional ES771 Mid-String Voltage Modules?

Yes – go to Step 5. No – Go to next section.

Page 56

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Step Action – Pulsar Plus
Configure the 1-Wire serial bus reference
The ES771 modules must be referenced to the most negative potential of the DC bus. This reference is
achieved by the proper setting of Jumper 11 (System Voltage) next to the relay configuration jumpers.
Following are the appropriate settings for negative and positive power plants. The jumper is set in the
factory for positive systems unless the controller is shipped with an assembled system that has a pre-
determined primary output bus. It is suggested that an insulated tool be used to set the jumpers. See
Figure 69.

-48V systems Jumper Position

+24V systems Jumper Position


5

Figure 74 1-Wire Jumper - Pulsar Plus

Connect Controller Wiring – Pulsar Plus


All connections to the controller are made through appropriate cable assemblies. The controller has been designed to
separate outputs, inputs, communication, and plant specific items onto to individual connectors.

J5 J4 J3 J2 J1

Figure 75 Controller Connections

Many systems are shipped with the appropriate controller connections wired by the factory. The following provides a
brief description of how and what to connect to the controller. Use only those sections that apply to the system
configuration.

Page 57

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Step Action – Pulsar Plus
Analog Interface Connector
Connect and wire to shunt and alarms.

J1 is a 6-pin connector provided for analog interface to a plant shunt, distribution alarms, and open
battery string alarms. Typically, a factory installed plant wire harness plugs into this connector. This
wire set has a purple wire with a Faston ® receptacle for connecting the Open String Alarm from field
installed battery disconnect breakers.

1 Table 4 Analog Interface Connector Signals – Pulsar Plus


Pin Signal
1 Shunt+
2 Shunt Reference
3 Shunt-
4 Fuse Alarm Major +24V
5 Open String
6 Fuse Alarm Major -48V

1-Wire Peripheral Connector


Connect and wire to VT-Probe, external ambient probe, or Remote Voltage Monitor.
2
J2 is an RJ-45 receptacle for connecting to 1-Wire devices.

Page 58

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Step Action – Pulsar Plus
Auxiliary Input Connector
Connect and wire auxiliary inputs as required to Connector J3. J3 is an auxiliary input connector.
Utilize cable as necessary to obtain the desired connections to the inputs shown below.
Input Alarm Cable comcodes for J3 are: 50 ft.: CC848817651, 150 ft.: CC848817668.

Table 5 Auxiliary Input Connector Signals - Pulsar Plus

Pin Wire Signal Description18


Aux Input 1 Auxiliary input to monitor a contact closure or open to its respective
1 BK
(Aux1) return on pin 8, Auxiliary Input Return.
Aux Input 2 Auxiliary input to monitor a contact closure or open to its respective
2 BR
(Aux2) return on pin 8, Auxiliary Input Return.
Auxiliary input to monitor a contact closure to the non-grounded side
Aux Power of a dc bus (±24V/-48V) to create the standard Auxiliary Power Major
3 R Major Input alarm.
(AMJ)
Generator Running in Eco applications.
Plant Battery
Test/ Group Dedicated input to be monitored for a contact closure to its respective
4 O return on pin 9, Plant Battery Return. This signal is used for the Plant
Standby/TR
Battery Test and Group Standby Feature.
(GSTR)
Emergency
Dedicated EPO input to be monitored for a contact closure to its
5 Y Power Off
3 respective return on pin 10, Emergency Power Off Return.
(EPO)
Aux Input 3 Auxiliary input to monitor a contact closure or open to its respective
6 G
(Aux3) return on pin 8.
Aux Input 4 Auxiliary input to monitor a contact closure or open to its respective
7 BL
(Aux4) return on pin 8.
Aux Input
8 V Return Return for Auxiliary Inputs 1-4.
(Aux_R)
Plant Battery
Test/Group
9 S Return for Plant Battery Test and Group Standby.
Standby/TR
Ret.(GSTR_R)
Emergency
Power
10 W Return for EPO input.
Off Ret.
(EPO_R)
18
Inputs are reconfigured for specific use for specific Eco applications.

Page 59

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Step Action – Pulsar Plus
Output Alarm Connector
Connect and wire remote alarm output circuits to Connector J4. J4 is output alarm connector.

Utilize cable as necessary to obtain the desired connections to the outputs shown below.
Output Alarm Cable comcodes for J4 are: 50ft: CC848817635, 150ft: CC848817643.

Table 6 Alarm Signals - Pulsar Plus


Signal Defaults
Pin Wire Signal Name19 Pin Wire
Name19 Standard Eco
PCR
1 BL PCR 11 BL/BK PCR_C
(Power Critical)
PMJ
2 O PMJ 12 O/BK PMJ_C
(Power Major)
PMN
3 G PMN 13 G/BK PMN_C
(Power Minor)
BD
4 4 W UR1 14 W/BK UR1_C (Battery on
Discharge)
VLV
5 BK UR2 15 BK/W UR2_C
(Very Low Voltage)
FAJ
6 BL/W UR3 16 BL/R UR3_C (External Fuse
Major)
ACF
Generator Start/
7 O/R UR4 17 R UR4_C (rectifier input AC
Stop
or DC) Fail)
RFA
8 G/W UR5 18 R/G UR5_C
(Rectifier Fail)
MRFA
9 W/R UR6 19 R/W UR6_C
(Multi Rectifier Fail)
HV Generator
10 BK/R UR7 20 R/BK UR7_C
(High Voltage) Maintenance
19
Relays are reconfigured for specific use for specific Eco applications.

Network (LAN) Connection (Optional)


Connect to network.

The controller provides an Ethernet connection for a LAN and or Craft port connection. Connector J5
provides a standard RJ45 shielded receptacle connection for a standard Cat-5 connection to the
5 controller’s 10/100Base-T port. This port has two main modes of operation: Server mode, LAN mode (Static
and DCHP Client). In server mode, the port can be used as a local Craft interface. In this mode, a local
laptop can be connected through J5 and its standard web browser used to directly access the controller
by typing in network address http://192.168.2.1. A connection should never be made between the controller
and LAN while the controller is in Server mode.

Is the controller equipped with the Modem Option?


Yes – go to Step 6. No – go to Step 7.

Page 60

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Step Action – Pulsar Plus Action – Pulsar Plus
Unplug the existing RS232 Modem cable
from the controller and connect it to the
RS232 Craft Port of the Interface.
Modbus RTU Interface (Optional).
Connect cable
between the
Door-mount Modbus RTU option converts RS232 Modem
RS232 Modem port to RS-485 terminal NE843E Pulsar port of the
Plus controller Interface and
Block. the RS232
Modem port
6 of the Pulsar
The Modbus RTU interface installs under Plus
the edge of the Pulsar Plus controller and controller.
Mount Interface with
plugs into the RS-232 Modem Port J-12. mounting hardware of
Pulsar Plus controller RS-485 terminal block
Refer to Quick Start Guide 850047312 -
Modbus Network Connection—2-
Pulsar Plus Modbus RTU Interface, for Wire Balanced Pair
installation and start up procedures.
Figure 76 Modbus RTU Interface

Modem is mounted on door above the controller.

RS-232
Local RS232 Serial Port Connector

Connect notebook computer, PC or


external modem to RS232 port.

7 The Local RS232 and future Craft Ethernet


connectors are located inside the door on
the front of the controller.

RS-232 is DCE (Data Communication


Figure 77 Local Port - Pulsar Plus
Equipment).

Install Millennium II
Note: The controller is factory installed connected to the NE-M equipment.
Connections to the controller made during installation are described here.

CAUTION: Equipment Damage


ESD NOTE: You must protect against ESD prior to configuring and installing the following
circuit cards.

Attach an ESD wrist strap or equivalent to the ESD


grounding connector on right hand side of the inside ESD Grounding
1 Connector
of the frame.

Figure 78 ESD Grounding Connector

Install Circuit Cards

CAUTION: Equipment Damage


ESD NOTE: You must protect against ESD prior to configuring and installing the following
circuit cards.
Page 61

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
RPM Modules

Alarm Board

MCR1 Card

Figure 79 Millennium II Circuit Card

BSL Alarm Termination Board

An insulation displacement (punch down) type alarm terminal board (BSL3, 848741711) is provided with the system. For
a wire wrap type terminal board, order BSL4 (848749507) and perform the following steps:

Step Action – Millennium II


1 In the upper right hand corner of the MCR1 board, find the alarm board already installed.

2 Remove the two screws holding the board at the top.

Holding the board on both sides, slowly, but firmly, remove the alarm board from the P8 connector.
3

4 Connect the new alarm board to P8 and press down firmly, until the board is seated.

5 Secure the alarm board at the top using the two screws removed earlier.

Connect Controller Wiring – Millennium II


All connections to the controller are made through appropriate cable assemblies. The controller has been designed
to separate outputs, inputs, communication, and plant specific items onto to individual connectors.

Page 62 Figure 80 Controller Connections

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Many systems are shipped with the appropriate controller connections wired by the factory. The following provides a
brief description of how and what to connect to the controller. Use only those sections that apply to the system
configuration.

Step Action – Millennium II


Power and Sense Connector
Connect and wire to shunt and alarms.

P6 is a 6-pin connector provided for analog interface to a plant shunt, distribution alarms, and open
battery string alarms. Typically, a factory installed plant wire harness plugs into this connector. This wire set
has a purple wire with a Faston ® receptacle for connecting the Open String Alarm from field installed
battery disconnect breakers.

Table 7 Power and Sense Signals - Millennium II


P15 – Secondary Voltage
Pin Wire P6 – Primary Voltage Signal Pin Wire
Signal
1 BR Return 1 BL Secondary Voltage
2 S 1-Wire Reference 2 BR Return
1 3 GR Ground 3 BL/W Secondary Voltage
4 W/BL SH2+ (Second Battery Shunt) 4 Y FAJ (Secondary)
5 W/BR Return 5 - -
6 W/BK SH1+ (Battery Shunt) 6 BR/
Return
W
7 O Primary Voltage
8 W FAJ (Primary)
9 O/BK Primary Voltage
10 BL SH2- (Second Battery Shunt)
11 W/O Primary Voltage
12 BK SH1- (Battery Shunt)

1-Wire Peripheral Connector


Connect and wire to VT-Probe, external ambient probe, or Remote Voltage Monitor.
2
P7 is an RJ-45 receptacle for connecting to 1-Wire devices.

Page 63

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Step Action – Millennium II
Alarm and Control Connections
Connect and wire alarm and control signals to the BSL card as specified in site engineering instructions.

See Millennium II Alarm & Control Signals section for details.

Figure 81 Alarm Connections Millennium II

NOTE: Wire Wrap Use 24 to 30 AWG wire.


Strip approximately 1 inch of insulation from wire.
Use a standard wire wrap tool to connect each wire to its terminal.
Punch Down Use 18 to 22AWG (if less than 18AWG, use multi-conductor cable for mechanical integrity).
Secure wires to terminals using a punch down tool or
Phillips #1 or #2 screwdriver inserted into a punch down insulating cap20.

Network (LAN) Connection (Optional)


Connect to network.

The controller provides an Ethernet connection for a LAN and or Craft port connection. Connector P2
provides a standard RJ45 shielded receptacle connection for a standard Cat-5 connection to the
4 controller’s 10/100Base-T port. This port has two main modes of operation: Server mode, LAN mode (Static
and DCHP Client). In server mode, the port can be used as a local Craft interface. In this mode, a local
laptop can be connected through J5 and its standard web browser used to directly access the controller
by typing in network address http://192.168.2.1. A connection should never be made between the controller
and LAN while the controller is in Server mode.

Is the controller equipped with the Modem Option?


Yes – go to Step 6. No – go to Step 7.

Telephone Line Connection (Optional).

Door-mount MODEM option provide their own RJ11


5 connection for the telephone line. Modem is mounted on door near the controller.

Use appropriate routing techniques to connect the


controller respective RJ11 to the telephone line.

20
Punch down caps are furnished with the controller.

Page 64

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Step Action – Millennium II Action – Millennium II

Local RS232 Serial Port Connector

Connect notebook computer, PC or external modem


to RS232 port.
The Local Port connector is at the lower left of the
controller card. This connector is factory cabled to
6 the Local Port connector on front right of the front
panel, for convenient local connection of a laptop PC.
Front RS-232 Port
If connecting to a modem or other device which is
Figure 82 RS232 Connection - Millennium II
connected permanently, use the Local Port
connector on the controller card.
Connect to the RS-232 connector as Data Circuit-
terminating Equipment (DCE).

Install BSM6 Modem


The optional BSM6 Modem is field installed. Instructions accompany the modem.
Install Optional Controller Peripherals
Optional Controller Peripherals are field installed. See the controller manual and instructions accompany the
options.

Install Rectifiers/Converters
Rectifier/Converter Installation Procedure

Step Action

CAUTION: Improper Operation


Install only Eco rectifiers in Eco system DC (PV or solar) powered positions.21
Eco systems require Eco rectifiers in all DC powered positions.
Eco rectifiers have unique badge symbols - Table 1.

CAUTION: Equipment Damage


Do not install rectifiers before battery bus voltage and polarity has been verified.
Rectifiers and system damage will result from incorrect battery bus polarity.
The damage may not be immediately evident.

Is this a DC (PV or solar) powered rectifier position in an Eco system?


Yes – Proceed. No – go to Step 2.
1 Verify rectifier is Eco type by examining the rectifier type badge - Table 1.
2 Verify rectifier Output Voltage by examining the rectifier type badge - Table 1.

3 Slide the rectifier/converter part way into a slot.

Figure 83 Insert Rectifier

21
Non-Eco rectifiers may be installed in AC powered position – NOT RECOMMENDED.

Page 65

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Step Action

Open the faceplate by sliding the black latch to the


4
left to release the faceplate.

Figure 84 Open Rectifier Door

5 Push the unit firmly into the shelf until seated.


Air Filter (If supplied)
6
Install optional air filter by placing it inside the faceplate.

Swing the faceplate closed until it is secured by the


7
latch.

Figure 85 Close Rectifier Door

Verify green LED and only green LED is on.


8
If this isn’t the case, see the Troubleshooting section.

Rectifier/Converter Removal Procedure

Step Action

Open the faceplate to disengage the rectifier/


1
converter.

Figure 86 Open Rectifier Door

2 Remove the unit from the shelf.

Figure 87 Remove Rectifier

Page 66

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Install Rectifiers
• Refer to the controller manual for details of controller operations.
• Use the above rectifier/converter installation and removal procedures as needed in the following steps.

Step Action

CAUTION: Improper Operation


Install only NE Eco rectifiers in Eco systems DC (PV or solar) powered positions 22.
Eco systems require Eco rectifiers in all DC powered positions.
Eco rectifiers have unique badge symbols - Table 1.

CAUTION: Equipment Damage


Do not install rectifiers before battery bus voltage and polarity has been verified.
Rectifiers and system damage will result from incorrect battery bus polarity.
The damage may not be immediately evident.

1 Turn on input power circuit breakers23 to apply power to the system rectifier positions.
2 Install a rectifier in an available rectifier position.

3 Wait until the rectifier establishes communications with the controller (the red Fail LED stops flashing).

4 Verify rectifier green Norm LED is lit.


5 Apply 10 amperes of load to the system.
6 Verify the contactor closes and connects the battery strings (if equipped).
7 If an audible alarm is present, press the ENTER key to MUTE the audible alarm.

8 Verify all LEDs are green on the controller and the display is visible with the proper voltage shown.

9 Increase the system load current to 20 amperes.


10 Install rectifier in the next position.

11 Wait until the rectifier establishes communications with the controller (the red Fail LED stops flashing).

12 Verify green rectifier Norm LED is lit.


Verify that each rectifier is present and verify the rectifier output currents by using the controller front
13 panel
(Menu > Status > Rectifiers > Rectifier Currents).
14 Repeat from Step 10 for to install each rectifier.
Continue after installing all rectifiers.
15 Increase the system load current to 50 amperes.
Verify the rectifiers share the load and the voltage regulation is correct. Rectifiers should load share after
16
2 minutes to within 2% of the total average output.
17 Verify front panel display voltage is within 0.5% of the Float Setpoint.
18 Remove a rectifier and ignore the request to remove missing equipment.
Verify the controller identifies the rectifier as missing to verify that the Minor Communication Fail alarm is
19
operational.
20 Re-install the rectifier and verify that the alarm clears.
22
Non-Eco rectifiers may be installed in AC powered positions of Eco systems – NOT RECOMMENDED.
Use of non-Eco rectifiers in Eco systems increases the risk of improperly filling system rectifier positions.
23
AC and PV input power circuit breakers for Eco systems

Page 67

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Verify Rectifier Positions

Refer to site engineering instructions for rectifier type per position.

Step Action

1 Verify that proper rectifiers are installed in all powered rectifier positions.

2 Verify that rectifiers in all DC powered positions have Eco type badges24 - Table 1.

Verify that rectifiers in all DC powered positions are displayed with the Eco leaf in the ECO Support
3
column on the controller web Inventory report screen – Figure 84.

Verify that rectifiers in all DC powered positions are displayed with the “Eco leaf” in the controller web
4
main screen25 – Figure 85.
24
RECOMMENDED – Eco rectifiers in all Eco system rectifier positions (AC and DC powered).
NOT RECOMMENDED – Non-Eco rectifiers may be installed in AC powered positions of Eco systems.
Use of non-Eco rectifiers in Eco systems increases the risk of improperly filling system rectifier positions.
25
The “Eco leaf” displays for rectifier positions after being DC powered while connected to the controller.
All populated rectifier positions are reported as AC powered until DC input is applied.

Eco type rectifiers display the Eco leaf

Figure 88 Inventory Screen

Page 68

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Eco leaf symbols Indicate
DC Powered Rectifiers25

Rectifier Capacity

AC Powered

DC Powered25

Figure 89 Main Screen - web

Install Converters
Repeat the above steps for converters:

• Install in converter-only slots first if provided. These are labeled “Converter Only” and are the lowest mounted
shelves.
• If installing a converter in a universal power shelf, install only in top 2 shelves
For more information on rectifiers and converters, see the Troubleshooting section.

Install Battery Voltage Temp (VT)-Probes


QS873A VT Probes can be used with or without mid-string voltage monitoring. Only one probe is required to allow
the battery slope thermal compensation function to be utilized.
Refer to the Galaxy Pulsar Plus Family Product Manual for installation instructions.

Install Aux Display (NE830A) Alarm Cable (Optional)


The optional NE830 Aux Display, when ordered separately, will require field installation. To do so, perform the
following steps:

Step Action

Is the NE830A factory installed?

No – go to Step1. Yes –no action required. Go to next section.

1 Connect and wire to field installed NE830A.

Install wiring per NEC and local rules for Class 3 circuits.
2
Note: Cable supplied with NE830A is suitable for Class 3 circuits.

Page 69

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Step Action
Apply appropriate terminals (if necessary) to the cable after removing the supplied had 1/4 inch Faston ®
terminals:

Table 8 Power Connections - NE830

Pin Wire Signal Name Connect to:

3 1 Green Earth Ground Frame Ground

2 White 24V+/- 24V point to be monitored (+24V or -24V)

3 Red 48V- -48V point to be monitored (-48V only)

4 Black Common Return Return for signals on pins 2 & 3

Connect and wire connection to NE830A. Alarm cable comcodes are


15ft: CC847922101, 150 ft.: CC848804765.

Table 9 Alarm Connections - NE830


Pin Wire Signal Name
4 1 Black Common

2 Brown Open On Alarm

3 Bare Close On Alarm Alarm Cable


Connector

Figure 90 NE830 Alarm Cable Connector

Configure Controller – Minimum


This section covers the basic operations that must be performed so that the controller is minimally configured. See the
controller manual for further detail.

Configure Pulsar Controller

Plant Status LEDs

Plant Voltage and


Load Current

RS-232 Port

Voltage Test Jacks Plant Mode Menu Navigation

Figure 91 Front Panel - Pulsar Plus Controller

Page 70

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
This display shows the front panel display for a system with both rectifiers and converters. The display (V1 versus V2)
correlates with test jacks. The large font indicates the “Primary” or rectifier dc bus; the smaller font shows the
“Secondary” or converter dc bus.

Menu Navigation Buttons

Parameter
Increase or decrease the value of the selected parameter.
Change

Navigate Navigate menus – move to different selected menu item.

Enter a sub-menu or confirms a parameter change.


Enter Button
Go to the Main Menu from the Normal display.

ESC Button Go up one menu level or exits a parameter change without saving.

Configuration
Step Attribute Menu Path/Action - Pulsar
to Change

1 Date Format This field allows you to select one of the following date formats: MM/DD/YY, DD/MM/YY,
YY/MM/DD, MM/DD/YYYY, DD/MM/YYYY, YYYY/MM/DD. Use the <+> or <-> key to select
the desired format and press <ENTER> to save the change.
Month Use this field to change the month; the possible value is from 1 to 12.
Day Use this field to change the day of the month; the possible value is from 1 to 31.

Year Use this field to change the year; the possible value is from 1992 and up.
Note: The system will validate the entries before the system date is modified.
Time
This field allows you to select one of the following time display formats: 12 or 24 hour.
Use the <+> or <-> key to select the desired format and press <ENTER> to save the
2 Time Format
change.

Time Allows you to change/set the time.

Daylight Enables or Disables Daylight Savings per the new standards created by the Energy
Policy Act of 2001. (Started in 2007.)

3
Batteries

Page 71

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Configuration Attribute
Step Menu Path/Action - Pulsar
to Change

The configuration of this field selects the battery type, Flooded or Valve
Regulated (sealed). This parameter is used in reserve time prediction and
4 Type enhanced battery test features. Move the cursor to the field and use the <+> or <-
> key to adjust the threshold value. Press <ENTER> to save the change.

Plant Shunt Monitors:


Menu > Configuration > Shunt Monitors > Plant Shunt Type - Battery
Shunt Monitors Menu > Configuration > Shunt Monitors > Plant Shunt Rating:
2000 (13U systems)
3000 (18U & 22U systems)
Use the STATUS menu to confirm the equipment installed:
Rectifiers: Menu > Status > Rectifiers
Distribution Modules: Menu > Status > Shunt Currents
Thermal Probes: Menu > Status > Batteries

Status Rectifiers Rectifier


Currents
Confirm Equipment
5
Installed
Batteries

Shunt Currents

Configure Millennium II Controller

Plant Voltage and


Number of Alarms
Plant Status LEDs Alarm Test Date and Time

Plant
Mode

Voltage Test Jacks RS-232 Port Menu Navigation Increment / Decrement

Figure 92 Front Panel - Millennium II Controller

Page 72

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Table 10 Push Buttons - Millennium II

Button Function Action

+ Display Contrast Increase or decrease the display contrast (in Main Display).

- Parameter Change Increase or decrease the value of the selected parameter.


◄ ◄ Navigate Navigate menus – move to different selected menu item.

Enter Enter Enter a sub-menu or confirms a parameter change.

ESC Escape Go up one menu level or exits a parameter change without saving.

Menu Menu Go to the Main Menu.

Help Help Display available Help information.

The Millennium II controller’s primary user interface is the front panel, which includes a backlit LCD, and an array of
pushbutton controls. SW202-8 must be set to ENABLED for changes to be made from the front panel. This section
covers the basic operations that must be performed so that the controller is minimally configured

Configuration
Step Menu Path/Action = Millennium II
Attribute to Change

This field allows you to select one of the following date formats: MM/DD/YY,
Date Format DD/MM/YY, YY/MM/DD, MM/DD/YYYY, DD/MM/YYYY, YYYY/MM/DD. Use the <+>
or <-> key to select the desired format and press <ENTER> to save the change.

Month Use this field to change the month; the possible value is from 1 to 12.

Day Use this field to change the day of the month; the possible value is from 1 to 31.

Year Use this field to change the year; the possible value is from 1992 and up.
NOTE Please note that the system will validate the entries before the system date is modified.

Page 73

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Step Configuration Attribute to Change

Time Format This field allows you to select one of the following time display formats: 12 or 24
hour. Use the <+> or <-> key to select the desired format and press <ENTER> to
save the change.
2
Time Allows you to change/set the time.
Daylight Enables or Disables Daylight Savings per the new standards created by the
Energy Policy Act of 2005. (Started in 2007.)

Batteries

Model The configuration of this field selects the installed battery type from a list of pre-
defined battery types used in reserve time prediction and enhanced battery test
features. Move the cursor to the field and use the <+> or <-> key to adjust the
threshold value. Press <ENTER> to save the change.

Strings The configuration of this field selects the number of battery strings in the
3 system. This parameter is used in reserve time prediction and enhanced battery
test features. Move the cursor to the field and use the <+> or <-> key to adjust
the threshold value. Press <ENTER> to save the change.

Cells/String The configuration of this field selects the number of installed cells in the battery
strings. This parameter is used in reserve time prediction and enhanced battery
test features. Move the cursor to the field and use the <+> or <-> key to adjust
the threshold value. Press <ENTER> to save the change.

Type The configuration of this field selects the battery type, Flooded or Valve
Regulated (sealed). This parameter is used in reserve time prediction and
enhanced battery test features. Move the cursor to the field and use the <+> or <
-> key to adjust the threshold value. Press <ENTER> to save the change.

Plant Shunt –
Supplemental Frame
Menu Configuration Shunt Plant Shunt
(if equipped)

4 Shunt2 Set to Battery

AMP2 Set to 2000 (13U systems) or 3000 (18U & 22U systems)
MV2 Set to 50

Page 74

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Acceptance Testing
NOTE: The controller may report a limited recharge alarm during these tests.
NOTE: At any time you encounter difficulty with these steps, refer to the Troubleshooting Section

Communication with Rectifiers and Converters

Step Action

1 Place external battery disconnect switches in the ON (connected) position if equipped.

2 Turn on all circuit breakers supplying rectifiers.

Adjust the contrast (if needed) for the site’s ambient condition
(Menu > Configuration > System Settings > Display Contrast).
3
Millennium II only: use the up and down arrow keys at the Main Menu.

Wait 30 seconds.

Are all lit LEDs on all components including rectifiers, the controller, LVD control boards, and Aux Displays
green?

Yes – Go to Step 7. No – go to Step 4.

Initiate the Clear Events and Uninstall Equipment operations


(in Menu > Control / Operations).
4 Non-existent alarm conditions should clear.

Refer to the controller manual as needed.

5 If the controller appears not to be powered or not responsive, remove and reseat the controller.

If all lit LEDs still aren’t green, review the installation procedure or refer to the Troubleshooting section in
this manual. The controller display should indicate “NO ALARMS”. The system float voltage, total load
6
current, and system operating mode should be observable as indicated and the controller’s back-light shall
be illuminated green for no alarms and the system rectifier voltage should be displayed.

If Slope Thermal Compensation (STC) is active disable STC:


7
(Menu > Configuration > Batteries > Batt Temp Management > Temperature Comp)

Page 75

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Step Action

Check the voltage readings on the controller display.

The controller is factory configured with a rectifier Float voltage set-point of -54.50V for -48V rectifier
systems and ±27.25V for ±24V rectifier systems. If converters are present, the display shows their voltage
and current in smaller font. The controller is factory configured with a converter output voltage set-point of
8 -54.50V for -48V converters and +27.25V for +24V converters.

Note: If Slope Thermal Compensation (STC) is active or if the connected batteries are not fully charged, the
bus voltage may be different than the set-point. If possible, open the external battery disconnect
prior to making measurements to eliminate these effects. If QS873 VT probes are installed in the
system. STC may be active. This will be indicated by the Plant Mode “FLOAT – TEMP COMP”.

Enable Slope Thermal Compensation (STC) if it was disabled in Step 7:


9
(Menu > Configuration > Batteries > Batt Temp Management > Temperature Comp)

Remove and Replace Rectifier and Verify Results:

10 Remove a rectifier from its slot.

11 Verify the controller LED and display are light amber which indicates a missing rectifier condition.

12 When the controller prompts to remove, equipment press enter ■.

13 Verify the controller LED and display are light green.


14 Replace the removed rectifier in its original slot.

15 Verify the controller LED and displays remain green.


Repeat Steps 9-14 for converters, if equipped.

Miscellaneous Alarms

(Batteries must be connected)

Distribution Alarms

Step Action
1 Manually connect a piece of wire from the circuit breaker feed bus to the distribution alarm strip.

2 Verify an FAJ – Fuse Alarm Major is reported by the controller.

3 Remove the wire. Verify the alarm clears.


Repeat test for each distribution panel or sub-system.

Page 76

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
ac Fail Alarms26

Step Action

1 Turn off AC circuit breaker feeding a single rectifier.27

2 Verify ACF – AC Fail Minor is reported for the correct rectifier ID.

3 Restore input and verify alarms clear and the controller returns to Normal.

4 Remove input from two or more rectifiers.

5 Verify MACF – Multiple AC Fail Major is reported for the correct rectifier IDs.

6 Turn on input circuit breaker turned off in Step 1 and verify alarms clear and the controller returns to Normal.

26
Rectifier Input Fail Controller Alarms: is displayed and labeled “ACF” and “MACF”.
Input Fail Rectifier LED: non-Eco rectifiers LED is labeled “ACF”. Eco rectifiers LED is labeled “INF” (INput Fail).
27
DC fed Eco rectifiers do not report a failure (INF) when DC input is removed.

Battery On Discharge Alarms28

Step Action
Change BD alarm to 2 volts below float voltage
1
(Menu > Configuration > Float Settings > Voltage Alarms > BD).
2 Adjust the load to 50 amperes.

3 Verify the BD alarm occurs when the system voltage decreases to BD threshold.

4 Verify the BD alarm clears once the voltage has exceeded 0.5V above the BD alarm threshold.

5 Restore the BD alarm threshold to its previous setting.


28
Eco systems do not alarm for battery discharges and may have BD thresholds settings different than non-Eco systems.

High Voltage Alarms

Step Action
1 Confirm the HV alarm threshold (Menu > Configuration > Float Settings > Voltage Alarms > High Minor).
Adjust the float voltage to a value greater than this threshold
2
(Menu > Configuration > Float Settings > Set Point).
3 Verify an HV alarm is reported by the controller.

4 Restore the float voltage back to its original setting.

5 Restore the HV setting back to its original setting.


6 Verify the alarms clear and the controller returns to Normal.

Page 77

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Manual Contactor Control and Alarms29

Step Action
1 Open the contactor by controller command (Menu > Control / Operations > Disconnects).
2 Verify the controller reports a Contactor Open alarm.30
3 Close the contactor by controller command.
4 Verify the alarms clear and the controller returns to Normal.
29
Skip if contactors are not present.
30
Contactor Open Alarm may be delayed by imminent LVD Alarm delay if enabled and configured.

Page 78

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Troubleshooting

Page 79
System

Pulsar Controller Status Millennium Rect/ Dist. Possible Problem(s) Possible Solution(s)
Display Controller Status Conv Module
Display LED

No Alarms

© 2023 OmniOn Power Inc. All rights reserved.


Norm
green green Normal Operation
Normal green

MIN AC Fail • Single rectifier 1.Verify rectifier input


not receiving AC circuit breaker is
power. closed.
• ac input circuit 2.Verify AC power to
breaker has rectifier is available
green opened. and in range.
• ac input voltage 3.If problem not corrected,
is out of range. replace rectifier.

Infinity M and HC_IG


A rectifier has been Issue the Menu > Control /
removed from the Operations > Uninstall
system while it is Equipment command for
Norm green unpowered. any rectifier that was
green removed while unpowered

MAJ Multiple AC Fail • Multiple 1. Verify rectifier input


rectifiers not circuit breakers are
receiving AC closed.
power. 2. Verify AC power to
ACF • ac input circuit rectifiers is available
amber breakers have and in range.
Minor AC System (Multiple opened. 3. If problem not
green corrected, replace
red amber Units) • ac input voltage
is out of range rectifiers.

One or more Issue the Menu > Control /


rectifiers have been Operations > Uninstall
Norm green removed from the Equipment command for
green
system while it is any rectifier that was
unpowered removed while unpowered.

Rev. 6.1
Millennium Rect/ Dist.

Page 80
Pulsar Controller Status
Controller Status Conv Module Possible Problem(s) Possible Solution(s)
Display
Display LEDs LED

MAJ Battery on Discharge


BD AC DC System voltage has
Major Battery Norm fallen below the
red on green green
battery on discharge
red green green Dischar
ge red threshold set by the
user.
-54.48V1 1000A
FLOAT

© 2023 OmniOn Power Inc. All rights reserved.


Display Red 1. Investigate other alarms that may be
Major Battery Rectifier is in current
on Norm
present such as rectifier related
red green limit.
Dischar amber problems.
ge red
2. If AC power is present but the system
voltage remains low, call your local
MAJ Battery on Discahge • Rectifier not
field representative.
and AC Fail receiving ac
power.
BD AC DC
ACF
• ac input voltage
green is out of range.
Major AC amber
red amber green red Sys Battery
ambe on
Dischar
-54.48V1 1000A ge red
FLOAT

Infinity M and HC_IG


Display Red

MIN Rectifier Fail • Rectifier output 1. Verify that there is no obstruction of


has dropped
below 18V (36V), the airflow path and fans are turning.
BD AC DC rectifier has shut 2. Reset the rectifier by removing the
down. 31
Fail • Excessive rectifier, waiting approximately 30
green
Red ambient seconds, and replacing the rectifier.
green green green Minor Rectifier/ (One Unit) temperature,
amber Converter rectifier has shut 3. If problem persists, replace the
-54.48V1 1000A amber down. rectifier.
FLOAT
• A rectifier or 4. If problem persists, call your local field
rectifier fan has
failed. representative.
Display Amber • A rectifier high
voltage shut
down31.

31
When a rectifier or converter senses an over- or under-voltage condition it will shutdown, wait 4 seconds, and then attempt to restart. If the over- or under-voltage condition remains it will
cycle again. If the over- or under-voltage condition remains after 3 restart attempts the unit will lock out, and user intervention is required to restart.

Rev. 6.1
Page 81
Pulsar Controller Status Millennium Controller Rect/ Dist. Possible Problem(s) Possible Solution(s)
Display Status Display Conv Module
LEDs LED
MAJ Multiple Rectifier
Fail, 1. Reset the rectifiers by removing
MAJ Battery on the rectifiers, waiting
Discharge Multiple rectifier outputs have
approximately 30 seconds, and
dropped below 18V (36V);
replacing the rectifiers.
rectifiers have shut down32.
BD AC DC
2. If problem not corrected, replace
rectifiers.

© 2023 OmniOn Power Inc. All rights reserved.


red green green
1. Verify that there is no obstruction
Major Rectifier/ Fail red
of the vertical airflow path and fans
-54.48V1 1000A
FLOAT red Converter (Multiple green are turning.
• Excessive ambient
amber units) 2. Reset rectifies by removing them,
temperature; multiple
waiting approximately 30 seconds,
rectifiers have shut down32
and replacing them.
Display Red • Multiple rectifiers have 3. If problem persists, replace the
failed. rectifiers.
4. If problem persists, call your local
field representative.

1. Remove controller and reset the


rectifiers by removing the
• All rectifier outputs have
rectifiers, waiting approximately
dropped below 18V (36V);
30 seconds, and replacing the
Fail red
all rectifiers have shut
rectifiers.

Infinity M and HC_IG


(Multiple green down32
2. If output voltage does not go to
units) • Defective controller set-point previously set by user,
call your local field representative

MAJ High Voltage • High output voltage from


rectifier(s). 1. Check and adjust VLV threshold to
BD AC DC • Rectifier(s) high voltage above float set point.
shut down32. 2. Reset the rectifier(s) by removing
• Internal rectifier(s) failure. the rectifier(s), waiting
Major Rectifier
green green green red amber • VHV threshold set below approximately 30 seconds, and
Fail red
float set point replacing the rectifier(s).
-54.48V1 1000A green 3. If problem persists, replace
FLOAT
(Multiple
units) rectifier(s).
4. If problem persists, call your local
field representative.
Display Red

32
When a power unit senses an over- or under-voltage condition it will shutdown, wait 10 seconds, and then attempt to restart. If the over- or under-voltage condition remains it will cycle
again. If the over- or under-voltage condition remains after 3 restart attempts the power unit will lock out, and user intervention is required to restart.

Rev. 6.1
Page 82
Pulsar Controller Status Millennium Controller Rect/ Dist. Possible Problem(s) Possible Solution(s)
Display Status Display Conv Module
LED

MAJ Fuse Major


BD AC DC

green green red


One or more output circuit 1. Clear circuit fault(s).
breakers or fuses have 2. Reset circuit breaker(s) or replace
-54.48V1 1000A Minor Distribution Red

© 2023 OmniOn Power Inc. All rights reserved.


FLOAT amber Norm opened. fuse(s).
red
green

Display Red

MAJ Contactor Open


BD AC DC

green green red


One or more LVD contactors Place disconnect switch(s) in ON
are manually forced open. position.
-54.48V1 1000A
Battery
FLOAT Minor amber Norm
red Red
green

Infinity M and HC_IG


Display Red

MIN Battery High


Temperature

BD AC DC

Batteries have exceeded


green green green 1. Check the threshold setting.
Battery temperature threshold set by
Minor green 2. Call your local field representative.
-54.48V1 1000A amber amber Norm user.
FLOAT green

Display Red

Rev. 6.1
Pulsar Controller Status Millennium Controller Rect/ Dist. Possible Problem(s) Possible Solution(s)

Page 83
Display Status Display Conv Module
LEDs LED

MIN Thermal Probe Fail 1. Ensure thermal probe is properly


BD AC DC connected to thermal probe cable.
2. Ensure cable is properly
connected to the rear of the
green green red
Battery thermal probe failed. Distribution Module.
Battery Norm 3. If problem persists, replace
-54.48V1 1000A Minor green
FLOAT
amber green
amber thermal probe.
4. If problem persists, call your local

© 2023 OmniOn Power Inc. All rights reserved.


Display Red field representative.
No response 1. Check controller to ensure it is
properly inserted into its slot. If so,
perform the following steps:
Controller failure, all devices 2. Remove the controller input
BD AC DC power connector for 1 minute and
on the communication bus
reporting loss of then reset.
Red communication with 3. If problem persists, replace
Fail blink controller.
Red controller with new controller
Display Blank Blink
board.
Display blank 4. If problem persists, call your local
field representative.

Infinity M and HC_IG


MIN Minor 1. Reset the rectifier by removing
Communication Fail the rectifier, waiting
approximately 30 seconds, and
Fail green
Rectifier lost communication replacing.
Red
with controller. 2. If problem persists, replace the
Blink
BD AC DC
(one rectifier.
unit)
3. If problem persists, call your local
green green green
field representative.
Minor
-54.48V1 1000A amber Issue the Menu > Control /
FLOAT Rectifier removed from a
Operations > Uninstall Equipment
Norm running system, but not
green green command for any rectifier that was
Display Red
uninstalled.
removed.

Rev. 6.1
Page 84
Rect/ Dist.
Pulsar Controller Status Millennium Controller
Conv Module Possible Problem(s) Possible Solution(s)
Display Status Display
LEDs LED

MAJ Major 1. Clear blinking red LEDs on all


Communication Fail devices.
See other conditions with blinking
BD AC DC red LEDs.

© 2023 OmniOn Power Inc. All rights reserved.


2. Correct communication with each
• LVD Board lost device.
green green red
communication with the
Norm Red 3. Issue the Menu > Control /
Minor controller.
green Blink Operations > Uninstall
red
-54.48V1 1000A
• Multiple devices no longer
FLOAT communicating with the Equipment command.
controller. . (This only removes this alarm for
unconnected devices.)
Display Red 4. Replace Distribution Module
Board.
5. If problem persists, call your local
field representative.

MIN Clock Battery Low

Infinity M and HC_IG


BD AC DC

1. Replace the Controller Clock


green green green Controller Controller Clock Battery Is Battery
Minor amber Low.
Norm green 2. If problem persists, call your local
amber green
-54.48V1 1000A field representative
FLOAT

Display Red

Rev. 6.1
Page 85
Rect/ Dist.
Pulsar Controller Status Millennium Controller
Conv Module Possible Problem(s) Possible Solution(s)

© 2023 OmniOn Power Inc. All rights reserved.


Display Status Display
LEDs LED

No Alarm, but individual


Shunt Currents are
displayed at or above
their maximum display 1. Verify that the respective shunt
values (≥600A for loads, has its green and yellow wire
≥800A for battery) connections attached used for
the current measurements.
BD AC DC 2. Verify the shunt connection to the
One or both QS871A shunt
QS871A is good by verifying the
Norm Norm green inputs is open-circuit. green and yellow wire
green green
connections from the shunt
green green red
follows through to the 10-pin

Infinity M and HC_IG


connector at the respective
QS871A.

Display Green

Rev. 6.1
Rectifiers/Converters
Status of a rectifiers and converters is provided by LEDs on their faces, and by extensive real time data, alarm and
event history accessible through the system controller.

Serial Number and CLEI Code


Cooling Fan Air
(text and barcode) Inlet

(INF on Converter)

Type Badge

Figure 93 Rectifier Face Plate

Non-Eco rectifiers powered by PV (solar) panels will not operate properly.


• Under some conditions their LEDs may indicate normally operation: Norm LED ON.
• Various other LED conditions and rectifier status (observed via the controller) may occur with variations in DC
input and load.

Rectifier/Converter Troubleshooting
1. Verify rectifier positions per the procedure in the Verify Rectifier Positions section.
2. Observe and compare Rectifier/Converter Status LEDs with Controller Status information.
3. Use the table below as a troubleshooting guide.

Rectifier/Converter LEDs

Table 11 Rectifier/Converter LEDs

LEDs33 Condition

Normal operation: No alarms, inputs and outputs are in their normal range,
communicating with the system controller.

Unpowered: No input or output voltage present.


1.Remove and reinsert unit.
2.Check input voltage with a voltmeter;
if input voltage is present, replace unit.
3.Check output bus voltage with a voltmeter;
if output bus voltage is present, replace unit.

Standby: The unit is okay, but has been placed in Standby by the controller and is
not delivering power.
Note: If a unit in standby loses communications with the controller it will exit
Standby mode and deliver power
33
ACF LED on rectifiers is replaced by INF LED on Converters.

Page 86

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Table 11 Rectifier/Converter LEDs
Output Limit: The unit is okay and delivering maximum output:
• At max rated output
• At configured current limit
• At thermal limit
1. If rectifiers/converters are equipped with optional air filters and reporting
thermal limiting, check air filters. Clean or replace all filters if necessary.
2. View unit currents:
Status > Rectifiers > Rectifier Currents or Status > Converters > Converter
Currents
ACF - ac Fail: Rectifier input is missing or out of range.
Correct AC fault.
INF34 - Input Fail: Converter input is out of range.
Correct converter input fault.
Shutdown35: The unit cannot deliver output.
• High Voltage Shutdown
• Thermal Shutdown
• Under Voltage Protect
• Component failure
1. Check rectifier or converter status on controller display to determine cause of
shutdown
2. Correct system output short, high temp, etc.
3. Remove and reinsert unit. If fault remains and other units are functioning
correctly, replace unit.
Communication Fail: Blinks to indicate the unit is not communicating with a
system controller.
Remove and reinsert unit. If fault remains and other units are communicating
correctly, replace unit.
34
INF LED on converters replaces ACF on rectifiers.
35
When a rectifier or converter senses an over- or under-voltage condition, it will shutdown, wait 4 seconds, and then attempt to restart. If the over-
or under-voltage condition remains it will cycle again. If the over- or under-voltage condition remains after 3 restart attempts the unit will lock out,
and user intervention is required to restart.

Voltage Temp (VT)-Probes


Checking for Defective VT-Probes
(If a Voltage Channel Failure and/or Thermal Probe Failure alarm occurs)

Step Action
1 Disconnect the first probe from its RJ-45 terminal block.

2 Run the command: Menu > Control / Operations > Uninstall Equipment.

Is the system controller green Normal LED lit?

Yes – Install new probe.


3 No – Reinstall the removed probe. go to Step 4.
Finished.

4 Remove the next probe.


5 Go to Step 2. Repeat steps for all probes.

Page 87

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Specifications and Application
Specifications and ordering information are in the Infinity M Product Line Brochure available at omnionpower.com
• External Surge Protective Device (SPD) is required on all AC inputs.

• Equipment and subassembly ports: 1. are suitable for connection to intra-building or unexposed wiring or cabling;
2. can be connected to shielded intra-building cabling grounded at both ends.

• Grounding / Bonding Network – Connect to an Isolated Ground Plane (Isolated Bonding Network) or an
Integrated Ground Plane (Mesh-Bonding Network or Common Bonding Network).

• Installation Environment - Install in Network Telecommunication Facilities, OSP, or where NEC applies.

• Battery return may be either Isolated DC return (DC-I) or Common DC return (DC-C).

Page 88

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Millennium II Alarm & Control Signals
In a standard Galaxy Power System (GPS) configuration, plant level alarms are sent to the controller via the Bay
Interface Card (BIC) through serial data communication. The following alarm inputs are provided for discretionary use
in other applications.

Table 12 Alarm and Control - Signal Names and BSL Pins


Pin Number Signal Name Pin Number Signal Name Pin Number Signal Name
1 PCRAO 33 MJFR 65 FAN
2 PCRAC 34 MNFR 66 AMN
3 PCRAR 35 MNFC 67 TFLT
4 PCRVR 36 MNFO 68 TBST
5 PCRVC 37 BDO 69 TRTN
6 PCRVO 38 BDC 70 PBTR
7 PCREO 39 BDR 71 PBT
8 PCREC 40 ACFR 72 OS
9 PCRER 41 ACFC 73 TR1
10 PMJAR 42 ACFO 74 TEQ
11 PMJAC 43 RFAO 75 IN-5
12 PMJAO 44 RFAC 76 IN5-R
13 PMJEO 45 RFAR 77 RO
14 PMJEC 46 HVR 78 ROR
15 PMJER 47 HVC 79 TR2
16 PMJVR 48 HVO 80 TR4
17 PMJVC 49 UR1O 81 RBRPO
18 PMJVO 50 UR1C 82 IN-1
19 PMNAO 51 UR1R 83 IN-2 / BTP
20 PMNAC 52 CTLRR 84 LVD1
21 PMNAR 53 CTLRC 85 TR3
22 PMNVR 54 CTLRO 86 -
23 PMNVC 55 UR2O 87 4-20mA
24 PMNVO 56 UR2C 88 4-20mA-R
25 5V 57 UR2R 89 IN-3/ BTPFLT
UR3R
26 - 58 90 LVD3/ BTMJ
Now VLVR
UR3C
27 - 59 91 EXT-V
Now VLVC
UR3O
28 PMNER 60 92 EXT-VR
Now VLVO
29 PMNEC 61 LVD2 93 ABS
30 PMNEO 62 LVD2R 94 ABS
31 MJFO 63 FAJ 95 DG
32 MJFC 64 AMJ 96 DG

Page 89

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Table 13 Alarm - Descriptions, BLS Pins, and Signal Names
Description BSL Pin Number Signal Name
1 PCRAO
Critical-Audio 2 PCRAC
3 PCRAR
4 PCRVR
Critical-Visual 5 PCRVC
6 PCRVO
7 PCREO
Critical-External 8 PCREC
9 PCRER
10 PMJAR
Power Major-Audio 11 PMJAC
12 PMJAO
13 PMJEO
Power Major –External 14 PMJEC
15 PMJER
16 PMJVR
Power Major –Visual 17 PMJVC
18 PMJVO
19 PMNAO
Power Minor-Audio 20 PMNAC
21 PMNAR
22 PMNVR
Power Minor –Visual 23 PMNVC
24 PMNVO
28 PMNER
Power Minor –External 29 PMNEC
30 PMNEO
31 MJFO
Major Fuse 32 MJFC
33 MJFR
34 MNFR
Minor Fuse 35 MNFC
36 MNFO
37 BDO
Battery On Discharge 38 BDC
39 BDR
40 ACFR
AC Fail 41 ACFC
42 ACFO
43 RFAO
Rectifier Fail 44 RFAC
45 RFAR
46 HVR
High Voltage 47 HVC
48 HVO
49 UR1O

User Relay 1 50 UR1C

51 UR1R
52 CTLRR

Controller Fail 53 CTLRC

54 CTLRO

Page 90

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Table 13 Alarm - Descriptions, BLS Pins, and Signal Names
Description BSL Pin Number Signal Name
55 UR2O
User Relay 2 56 UR2C
57 UR2R
58 VLVR
Very Low Voltage 59 VLVC
60 VLVO

Table 14 Alarm and Control Inputs - Descriptions, BLS Pins, and Signal Names
Description BSL Pin Number Signal Name
Low Voltage 2 Disconnect State Detect 61 LVD2
Fuse Alarm Major 63 FAJ
Fuse Alarm Minor 65 FAN
Auxiliary Alarm Major 64 AMJ
Auxiliary Alarm Minor 66 AMN
Timer Float Control 67 TFLT
Timer Boost Control 68 TBST
Plant Battery Test 71 PBT
Open String Detect 72 OS
Transfer Rectifier 1 73 TR1
General Purpose Input 4 IN-4
74
Previously TEQ Previously TEQ
General Purpose Input -5 IN-5
75
Previously Engine Transfer Previously ETR
General Purpose Input -5 RTN IN-5R
76
Previously Engine Transfer Return Previously ETRR
Reserve Operation 77 RO
Reserve Operation RTN 78 ROR
Transfer Rectifier 2 79 TR2
Transfer Rectifier 4 80 TR4
Reserve Battery-Emergency Power Off 81 RBRPO
General Purpose Input 1 82 IN-1
BTP or General Purpose Input 2 83 IN-2/BTP
Low Voltage 1 Disconnect State Detect 84 LVD1
Transfer Rectifier 3 85 TR3
General Purpose 4-20mA Measuring Circuit 87 4-20mA
General Purpose 4-20mA Measuring Circuit-RTN 88 4-20mAR
BTPFLT or Generic Input 3 89 IN-3/ BTPFLT
Low Voltage 3 Disconnect State Detect
Also 90 LVD3/ BTMJ
Battery Thermal Protect Major
External Voltage Input 91 EXT-V
External Voltage Input -RTN 92 EXT-VR

Page 91

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Fuse Alarm Major (FAJ) - BSL-63

A battery potential input is required, which must use an external 1K ohm 2W current limiting resistor at the source. A
Fuse Alarm Major is generated when battery potential is received.

Fuse Alarm Minor (FAN) - BSL-65

A battery potential input is required, which must use an external 1K ohm, 2W current limiting resistor at the source. A
Fuse Alarm Minor is generated when battery potential is received.

Open String Alarm (OS) - BSL-72

A battery potential input is required, which must use an external 1K ohm 2W current limiting resistor at the source.
This circuit is used to signal the controller that a battery string protective device or switch is in the open position. An
Open String Alarm is generated when battery potential is received.
Aux Major (AMJ) - BSL-64

A battery potential input is required, which must use an external 1K ohm, 2W current limiting resistor at the source.
This circuit is used to allow the controller to monitor another power device and provide alarms for it. An Aux Major
Alarm is generated when battery potential is received.

Aux Minor (AMN) - BSL-66

A battery potential input is required, which must use an external 1K ohm, 2W current limiting resistor at the source.
This circuit is used to allow the controller to monitor another power device and provide alarms for it. An Aux Minor
Alarm is generated when battery potential is received.

Low Voltage Disconnect Active (LVD1) - BSL-84

A battery potential input is required, which must use an external 1K ohm, 2W current limiting resistor at the source if
not using standard Lineage Power LVD circuit cards or controller. This circuit is used to inform the controller that the
monitoring circuit of a Low Voltage Disconnect device has failed. In standard Galaxy Power Systems, the Bay Interface
Card (BIC) monitors these alarms and informs the Controller through the serial interface connection.

Low Voltage Disconnect Active (LVD2/LVD2R) - BSL-61/62

A closure between these points or a ground signal into LVD2/ BSL-61 is used to inform the controller that a Low
Voltage Disconnect device has opened. In standard Galaxy Power Systems, the Bay Interface Card (BIC) monitors these
alarms and informs the Controller through the serial interface connection.

External Boost Option (TFLT/TBST/PBT) - BSL-67-69

A variety of external devices may be used to initiate boost in the controller. Wiring is required from positions 67/68/69
on the BSL card for operation of this feature. Providing a contact closure between TBST and TRTN initiates the boost
feature. A contact closure between TFLT and TRTN returns the plant to float. Additional information on External Boost
can be found in the User’s Guide for Millennium II Controller Advanced Features manual.

Page 92

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Rectifier Hold OFF on Engine Option (RO/ROR) - BSL-77-78
The controller accepts a contact closure between RO/ROR (BSL-77-78) to hold OFF rectifiers configured as “Remote
Group Standby”
These controller inputs hold OFF individual rectifiers or groups of rectifiers under external control.
Internal Sequencing - The controller can hold OFF individual rectifiers when AC is being provided by emergency
generator. Internal Rectifier Sequencing requires external wiring to RO/ROR on BSL pin numbers 77/78, to function.
Rectifier External Sequence Option (TR1-TR4) - BSL-73/79/85/80
The controller accepts ground signals on TR1 to TR4 (BSL 73/79/ 85/80) from an external device to control the
sequencing of plant rectifiers by holding them OFF in groups as follows :

Table 15 TR Leads and Associated Rectifiers


TR Signal Rectifiers Held OFF by TR Signal
TR1 G01, G02, G09, G10, G17, G18, G25, G26, G33, G34, G41, G42, G49, G50, G57, G58
TR2 G03, G04, G11, G12, G19, G20, G27, G28, G35, G36, G43, G44, G51, G52, G59, G60
TR3 G05, G06, G13, G14, G21, G22, G29, G30, G37, G38, G45, G46, G53, G54, G61, G62
TR4 G07, G08, G15, G16, G23, G24, G31, G32, G39, G40, G47, G48, G55, G56, G63, G64

Additional information on the Rectifier Sequence Options can be found in the User’s Guide for Millennium II
Controller Advanced Features manual.

Page 93

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Safety
Safety Statements
• See equipment specifications for installation and environmental limitations.

• Do not install this equipment over combustible surfaces.

• Rules and Regulations - Follow all national and local rules and regulations when making field connections.

• Compression Connectors

• U. S. or Canada installations - use Listed/Certified compression connectors to terminate Listed/Certified


field-wire conductors.

• All installations - apply the appropriate connector to the correct size conductor as specified by the
connector manufacturer, using only the connector manufacturer’s recommended or approved tooling for
that connector.

• Electrical Connection Securing: Torque to the values specified on labels or in the product documentation.

• Cable Dress - dress to avoid damage to the conductors and undue stress on the connectors.

• Circuit Breakers and Fuses

• Use only those specified in the equipment ordering guide.

• Size as required by the National Electric Code (NEC) and/or local codes.
Safety Tested Limits - Refer to the equipment ratings to assure current does not exceed:
Continuous Load (List 1) - 60% of protector rating
Maximum Load (List 2 - typically end of discharge) - 80% of protector rating.

· GMT Style Fuses - Use only fuses provided with safety caps.

• Field-wired Conductors - Follow all National Electric Code (NEC) and local rules and regulations.

• Insulation rating: 90°C minimum; 105°C (minimum) if internal to enclosed equipment cabinets.

• Size AC field-wired conductors with 75°C ampacity (NEC) equal to or greater than their panel board circuit
breaker rating.

• Size DC field-wired conductors with 90°C ampacity (NEC) equal to or greater than circuit breaker/fuse
rating.

• AC and DC input disconnect/protection - Provide accessible devices to remove input power in an emergency.

• Alarm Signals - Provide external current limiting protection. Rating 60V, 0.5A unless otherwise noted.

• Grounding - Connect the equipment chassis directly to ground. In enclosed equipment cabinets connect to the
cabinet AC service ground bus. In huts, vaults, and central offices connect to the system bonding network.

Page 94

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Déclarations de sécurité
• Voir les spécifications de l'équipement pour l'installation et les limites environnementales

• N'installez pas cet équipement sur des surfaces combustibles.

• Règles et réglementations - Suivez toutes les règles et réglementations nationales et locales lors des connexions
sur le terrain.

• Connecteurs à compression

• Installations aux États-Unis ou au Canada - utilisez des connecteurs de compression homologués/certifiés


pour terminer Conducteurs de fils de terrain certifiés.

• Toutes les installations - appliquez le connecteur approprié au conducteur de taille correcte tel que spécifié
par le fabricant de connecteurs, en utilisant uniquement l'outillage recommandé ou approuvé par le
fabricant de connecteurs pour ce connecteur.

• Fixation de la connexion électrique : Serrez aux valeurs spécifiées sur les étiquettes ou dans la documentation du
produit.

• Habillage de câble - Habillez-vous pour éviter d'endommager les conducteurs et une contrainte excessive sur les
connecteurs.

• Disjoncteurs et fusibles

• Utilisez uniquement ceux spécifiés dans le guide de commande de l'équipement.


• Taille requise par le National Electric Code (NEC) et/ou les codes locaux.
Limites de sécurité testées - Reportez-vous aux valeurs nominales de l'équipement pour vous assurer que
le courant ne dépasse pas:

Charge continue (Liste 1) - 60 % de la cote de protection

Charge maximale (Liste 2 - généralement en fin de décharge) - 80 % de la valeur nominale du protecteur.

• Fusibles de style GMT - Utilisez uniquement des fusibles fournis avec des capuchons de sécurité.

• Conducteurs câblés sur le terrain - Suivez tous les codes électriques nationaux (NEC) et les règles et
réglementations locales.

• Indice d'isolation : 90 °C minimum ; 105°C (minimum) si à l'intérieur des armoires d'équipement fermées.
• Dimensionnez les conducteurs CA câblés sur place avec un courant admissible de 75 °C (NEC) égal ou
supérieur à la valeur nominale du disjoncteur du panneau de distribution.

• Dimensionnez les conducteurs CC câblés sur place avec un courant admissible de 90 °C (NEC) égal ou
supérieur à la valeur nominale du disjoncteur/fusible.

• Déconnexion/protection des entrées CA et CC - Fournir des dispositifs accessibles pour couper l'alimentation
d'entrée en cas d'urgence.

• Signaux d'alarme - Fournit une protection de limitation de courant externe. Note 60V, 0.5A sauf indication
contraire.

• Mise à la terre - Connectez le châssis de l'équipement directement à la terre. Dans les armoires d'équipement
fermées, connectez-vous au bus de terre de service CA de l'armoire. Dans les huttes, les chambres fortes et les
bureaux centraux, connectez-vous au réseau de liaison du système.

Page 95

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Precautions
• Install, service, and operate equipment only by professional, skilled and qualified personnel who have the
necessary knowledge and practical experience with electrical equipment and who understand the hazards that
can arise when working on this type of equipment.

• Disconnect batteries from outputs and/or follow safety procedures while working on equipment. Batteries may be
connected in parallel with the output of the rectifiers. Turning off the rectifiers will not necessarily remove power
from the bus.

• Do not disconnect permanent bonding connections unless all power inputs are disconnected.

• Verify that equipment is properly safety earth grounded before connecting power. High leakage currents may be
possible.

• Exercise care and follow all safety warnings and practices when servicing this equipment. Hazardous energy and
voltages are present in the unit and on the interface cables that can shock or cause serious injury. When equipped
with ringer modules, hazardous voltages will be present on the ringer output connectors.

• Use the following precautions in addition to proper job training and safety procedures:

• Use only properly insulated tools.

• Remove all metallic objects (key chains, glasses, rings, watches, or other jewelry).

• Follow Lock Out Tag Out (LOTO) procedures: customer specified, site specific, or general as appropriate.
Disconnect all power input before servicing the equipment. Check for multiple power inputs.

• Wear safety glasses.

• Follow Personal Protective Equipment requirements: customer specified, site specific, or general as
appropriate.

• Test circuits before touching.

• Be aware of potential hazards before servicing equipment.

• Identify exposed hazardous electrical potentials on connectors, wiring, etc.

• Avoid contacting circuits when removing or replacing covers;

• Use a personal ESD strap when accessing or removing electronic components.

• Follow procedures for working at heights more than 4ft above the floor: customer specified, site specific, or
general as appropriate.

• Personnel with electronic medical devices need to be aware that proximity to DC power and distribution systems,
including batteries and cables, typically found in telecommunications utility rooms, can affect medical electronic
devices, such as pacemakers. Effects decrease with distance.

Page 96

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Précautions
• Installer, mettre en service et utiliser l'équipement uniquement par du personnel professionnel, compétent et
qualifié possédant les connaissances et l'expérience pratique nécessaires en matière d'équipement électrique et
qui comprennent les dangers qui peuvent survenir lors de l'utilisation de ce type de Équipement.

• Débranchez les piles des sorties et/ou suivez les procédures de sécurité tout en travaillant sur l'équipement. Les
batteries peuvent être connectées parallèlement à la sortie des redresseurs. Éteindre les redresseurs n'enlèva pas
forcément l'alimentation du bus.

• Ne débranchez pas les raccords de liaison permanents à moins que toutes les entrées d'alimentation ne soient
déconnectées.

• Vérifiez que l'équipement est correctement mis à la terre avant de brancher l'appareil. Des courants de fuite
élevés peuvent être possibles.

• Exercez des soins et respectez tous les avertissements et pratiques de sécurité lors de l'entretien de cet
équipement. L'énergie et les tensions dangereuses sont présentes dans l'unité et sur les câbles d'interface qui
peuvent choquer ou causer des blessures graves. Lorsqu'il est équipé de modules de sonnerie, des tensions
dangereuses seront présentes sur les connecteurs de sortie de la sonnerie.

• Utiliser les précautions suivantes en plus des procédures appropriées de formation et de sécurité d'emploi:

• n'utiliser que des outils correctement isolés.

• Enlevez tous les objets métalliques (porte-clés, lunettes, bagues, montres ou autres bijoux).

• suivez les procédures de lock out tag out (LOTO): client spécifié, spécifique au site ou général selon le cas.
Débranchez toutes les entrées d'alimentation avant d'entretenir l'équipement. Vérifiez l'alimentation de
plusieurs entrées.

• Portez des lunettes de sécurité.

• respectez les exigences relatives aux équipements de protection individuelle: client spécifié, spécifique au
site ou général selon le cas.

• tester les circuits avant de les toucher.

• être conscient des dangers potentiels avant d'entretenir l'équipement.

• identifier les potentiels électriques dangereux exposés sur les connecteurs, le câblage, etc.

• Évitez de contacter les circuits lors du démontage ou du remplacement des couvercles.

• utilisez une sangle ESD personnelle lors de l'accès ou de la suppression de composants électroniques.

• Suivez les procédures de travail à des hauteurs supérieures à 4 pieds au-dessus du sol : spécifiées par le
client, spécifiques au site ou générales, selon le cas.

• Le personnel équipé de dispositifs médicaux électroniques doit être conscient que la proximité des systèmes de
distribution et d'alimentation en courant continu, y compris les piles et les câbles, généralement dans les salles
de télécommunication, peut affecter les appareils électroniques médicaux, tels que les stimulateurs cardiaques.
Les effets diminuent avec la distance.

Page 97

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Special Installation Notes
Installation Guide

Input voltage : 200-277, +/- 30 (60) Vdc, or +/- 155 (310) Vdc.

Input current :

Max input current per rectifier (Using NE075AC48ATEZ Rectifiers):

21.8A 200Vac in

18.2A 240Vac in

15.7A 277Vac in

2100A bay configuration

616A 200Vac in

510A 240Vac in

440A 277Vac in

Input Power (Watts) : Max 123KW @ 200VAC in and 2100A Output.

Nominal frequency : 50 / 60 Hz

Model Number : Infinity NE-M

Dimensions are for reference only :

System in 7' Frame: 660mm x 533.4mm x 2133.6mm

System in 7' Frame with Battery Trays: 660mm x 612mm x 2133.6mm

Max. ambient temperature : 45°C

(Max. Operation temperature)

Caution: For continued fire protection, the fuse should only be replaced with one of the same type.

Power Supply is a Class I equipment / overvoltage category II

Install only in limited access rooms

Power plant should be installed and operated by trained personnel only.

Only suitable for installation on the floor or other combustible surface.)

The device does not have its own off switch, it must therefore be provided with an on and off switch in the supply
circuit.

The device is intended for installation in IT equipment in a frame (see further instructions)

When installing the device, make sure that all requirements according to EN60950 are met.)

CAUTION: HIGH LEAKAGE CURRENT

BEFORE CONNECTING TO THE SUPPLY CIRCUIT

BE SURE TO MAKE A GROUND CONNECTION

Page 98

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Besondere Installationshinweise

Installationsanleitung

Eingangsspannung: 200–277, +/- 30 (60) Vdc oder +/- 155 (310) Vdc.

Eingangsstrom :

Maximaler Eingangsstrom pro Gleichrichter (mit NE075AC48ATEZ-Gleichrichtern):

21.8A 200Vac in

18.2A 240Vac in

15.7A 277Vac in

2100A-Schachtkonfiguration

616A 200Vac in

510A 240Vac in

440A 277Vac in

Eingangsleistung (Watt): Max. 123 kW bei 200 VAC Eingang und 2100 A Ausgang.

Nennfrequenz: 50 / 60 Hz

Modellnummer: Infinity NE-M

Die Abmessungen dienen nur als Referenz:

System im 7'-Rahmen: 660 mm x 533,4 mm x 2133.6 mm

System im 7'-Rahmen mit Batteriefächern: 660 mm x 612 mm x 2133.6 mm

Max. Umgebungstemperatur: 45°C

(Max. Betriebstemperatur)

Achtung: Um den Brandschutz weiterhin zu gewährleisten, sollte die Sicherung nur durch eine Sicherung desselben
Typs ersetzt werden.

Das Netzteil ist ein Gerät der Klasse I / Überspannungskategorie II

Nur in Räumen mit eingeschränktem Zugang installieren

Das Kraftwerk darf nur von geschultem Personal installiert und betrieben werden.

Nur zur Montage auf dem Boden oder einer anderen brennbaren Oberfläche geeignet.)

Das Gerät verfügt über keinen eigenen Ausschalter, daher muss es im Versorgungsstromkreis mit einem Ein-
und Ausschalter versehen werden.
Das Gerät ist für den Einbau in IT-Geräte in einem Rahmen vorgesehen (siehe weitere Anleitung)

Achten Sie bei der Installation des Gerätes darauf, dass alle Anforderungen gemäß EN60950 erfüllt sind.)

VORSICHT: HOHER ABLEITSTROM

VOR DEM ANSCHLUSS AN DEN VERSORGUNGSKREIS

Stellen Sie sicher, dass Sie eine Erdungsverbindung herstellen

Page 99

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Notes d'installation spéciales

Guide d'installation

Tension d'entrée : 200-277, +/- 30 (60) Vdc, ou +/- 155 (310) Vdc.

Courant d'entrée :

Courant d'entrée maximum par redresseur (en utilisant les redresseurs NE075AC48ATEZ):

21.8A 200Vac in

18.2A 240Vac in

15.7A 277Vac in

Configuration de baie 2100A

616A 200Vac in

510A 240Vac in

440A 277Vac in

Puissance d'entrée (Watts) : Max 123KW à 200VAC en entrée et 2100A en sortie.

Fréquence nominale : 50 / 60 Hz

Numéro de modèle : Infinity NE-M

Les dimensions sont à titre indicatif seulement :

Système dans un cadre de 7': 660mm x 533,4mm x 2133.6mm

Système dans un cadre de 7' avec plateaux de batterie: 660mm x 612mm x 2133.6mm

Max. température ambiante: 45°C

(Température de fonctionnement maximale)

Attention: Pour une protection continue contre l'incendie, le fusible ne doit être remplacé que par un fusible du même
type.

L'alimentation est un équipement de classe I/catégorie de surtension II.

Installer uniquement dans des pièces à accès limité

La centrale électrique doit être installée et exploitée uniquement par du personnel qualifié.

Convient uniquement pour une installation sur le sol ou sur toute autre surface combustible.)

L'appareil ne dispose pas de son propre interrupteur d'arrêt, il doit donc être équipé d'un interrupteur marche et
arrêt dans le circuit d'alimentation.
L'appareil est destiné à être installé dans un équipement informatique dans un cadre (voir instructions
complémentaires)

Lors de l'installation de l'appareil, assurez-vous que toutes les exigences selon EN60950 sont respectées.)

ATTENTION : COURANT DE FUITE ÉLEVÉ

AVANT LE DE FAIREBRANCHEMENT AU CIRCUIT D'ALIMENTATION

ASSUREZ-VOUS UNE CONNEXION À LA TERRE

Page 100

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Notas especiales para instalaciones

Guía de instalación

Voltaje de entrada: 200-277, +/- 30 (60) Vcc o +/- 155 (310) Vcc.

Corriente de entrada :

Corriente de entrada máxima por rectificador (usando rectificadores NE075AC48ATEZ):

21.8A 200Vac in

18.2A 240Vac in

15.7A 277Vac in

Configuración de bahía 2100A

616A 200Vac in

510A 240Vac in

440A 277Vac in

Potencia de entrada (vatios): máx. 123 KW a 200 VCA de entrada y 2100 A de salida.

Frecuencia nominal: 50 / 60 Hz

Número de modelo: Infinity NE-M

Las dimensiones son sólo de referencia :

Sistema en marco de 7': 660 mm x 533,4 mm x 21336 mm

Sistema en marco de 7' con bandejas de batería: 660 mm x 612 mm x 2133.6 mm

Máx. temperatura ambiente : 45°C

(Temperatura máxima de funcionamiento)

Precaución: Para una protección continua contra incendios, el fusible sólo debe reemplazarse por uno del mismo tipo.

La fuente de alimentación es un equipo Clase I/categoría de sobretensión II

Instalar solo en habitaciones de acceso limitado

La instalación y operación de la central eléctrica debe ser realizada únicamente por personal capacitado.

Sólo apto para instalación en el suelo u otra superficie combustible).

El dispositivo no dispone de interruptor de apagado propio, por lo que debe estar provisto de un interruptor de
encendido y apagado en el circuito de alimentación.

El dispositivo está diseñado para su instalación en equipos informáticos en un marco (ver instrucciones adicionales)

Al instalar el dispositivo, asegúrese de que se cumplan todos los requisitos según EN60950).

PRECAUCIÓN: ALTA CORRIENTE DE FUGA

ANTES DE CONECTAR AL CIRCUITO DE ALIMENTACIÓN

ASEGÚRESE DE HACER UNA CONEXIÓN A TIERRA

Page 101

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
Change History (excludes grammar & clarifications)
Revision Date Description of the change
1.0 2016 April Initial Release
2.0 2016 June Updated Table 2
Add Supplemental Frame; update battery
3.0 2017 August
connections and load wiring
4.0 2021 May Template change
5.0 2022 January Published in letter format
-58V version added, Updated content of
6.0 06/23/2023 “Special Installation Notes”, Updated ICON’S
of rectifier and converters
6.1 12/06/2023 Updated as per OmniOn template

Page 102

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1
OmniOn Power Inc.
601 Shiloh Rd.
Plano, TX USA

omnionpower.com

We reserve the right to make technical changes or We reserve all rights in this document and in the subject
modify the contents of this document without prior matter and illustrations contained therein.
notice. OmniOn Power does not accept any Any reproduction, disclosure to third parties or utilization
responsibility for errors or lack of information in this of its contents – in whole or in parts – is forbidden without
document and makes no warranty with respect to prior written consent of OmniOn Power. This document
and assumes no liability as a result of any use of does not convey license to any patent or any intellectual
information in this document. property right. Copyright© 2023 OmniOn Power Inc. All
rights reserved.

Page 103

© 2023 OmniOn Power Inc. All rights reserved. Infinity M and HC_IG Rev. 6.1

You might also like