Start_F: starting floor; Target_F: Expected arrival floor; S_Pluse: start pulse number;
Pluse: indicates the number of pulses when the fault occurs.
Speed_1: Given speed; Speed_2: feedback speed; Current: Output current; DC Bus:
DC bus voltage.
6.3 Control fault code table
Code Fault Reason Solution
Safety switch
Safety switch (X13)disconnects
E01 disconnects Check safety loop
during operation
during operation
Door lock
Hall door feedback switch Check hall door lock
E02 disconnects
disconnects during operation loop
during operation
The door lock is
Car door feedback (X15) is Check car door lock
E03 disconnected
disconnected during operation circuit
during operation
Upper limit
E04 operates during Running upper limit (X6) action Check upper limit
operation
Lower limit
E05 operates when Run lower limit (X9) action Check lower limit
running
The running drive
E06 Running drive failure (X30) action Check driver
is faulty.
Driver operates No feedback from driver ready
E07 Check driver
error signal (X31)
Pulse detection
No pulse signal was detected in 3
E08 error during
seconds during operation Check PG and PG line
operation
Inspection (X10)during
E09 Inspection Check inspection loop
operation
during operation
No level signal was detected at the
Leveling switch
time set for F4 Check leveling switch
E10 fault during
When the elevator starts, the and Connecting wires
operation
leveling switch does not operate
53
FJP8000 Elevator Integrated Controller User manual
for 6 seconds
When the elevator decelerates, the
leveling switch does not operate
for 16 seconds
Brake switch fault Brake switch fault during
E11 Check brake switch
during operation operation
Running The single run time exceeds the Set the value of the F6
E12
overtimes value set by F6 parameter correctly
Check terminal switch
E17 UPL Err UPL Err
positions
Check terminal switch
E18 DNL Err DNL Err
positions
The phase sequence relay is Check phase sequence
E19 Safe Err abnormalsequence relay is
Safety loop opreates Check safety loop
abnormal
Fault code table for
E20 Drive fault Drive fault
processing
The output contactor is damaged. Change the contactor.
Output contractor
E21 Check connections
fault X18 Signal anomaly
and Settings
The lock contactor is damaged. Change the contactor.
Brake contactor
E22 Check connections
feedback fault. X16 Signal anomaly
and settings
Normally open/normally closed
The brake switch with feedback from the brake
E23 Set up correctly
feedback is fault. switch
setup fault.
Check the hall door
Front door
E24 The front door won't close and car door of back
closing fault
door
Check the hall door
Back door closing
E25 The back door won't close and car door of back
fault
door
WhenPre open door the contactor
Pre open door Check connections
E26 operates,
UCMP feedback and relays
No feedback detected
54
FJP8000 Elevator Integrated Controller User manual
DLock DLimit The lock or door limit is Check the door lock
E27
Err abnormal. and door limit.
Check the hall door,
Door opening
E28 The door didn't open in time. car door and door
fault
limit.
Check the hall door,
Closing the door more often or
E29 Door closing fault car door and door
longer than set
limit.
Car Check the
The car board and the main board
E30 communication communication cable
are abnormal.
error connection
Change contactor
E31 Gate Lock SH1 Gate Lock SH1 Check the door lock
for short circuit
Change contactor
Check the door lock
E32 Gate Lock SH2 Gate Lock SH2
for short circuit
Safety relay is
E33 The safety relay is adhered or Change contactor
adhered.
stuck
The mainboard data is not Data is initialized on
E34 Uninitialized
initialized. the mainboard.
In the unit time (10 minutes), the
Fault running failure occurs frequently,
E35 Troubleshooting
overfrequency and the number of times exceeds
the value set by F5
Input port The input port Settings of J1 and Change the input port
E36
duplication J3 are repeated Settings
Error with the When the elevator stops at the up
upper short terminal, Check upper short
E37
deceleration Upper short deceleration switch deceleration switch
switch does not operate
Error with the When the elevator is at the down Check the lower short
E38
lower short terminal, deceleration switch
55
FJP8000 Elevator Integrated Controller User manual
56
FJP8000 Elevator Integrated Controller User manual
capacity;
Whether the braking
resistance is normal;
Overvoltage The DC voltage of the main loop
E68 Whether the power
protection exceeds the detected value
supply voltage is too
high;
Confirm whether the
wiring of the main
circuit power supply is
broken or wrong, and
Undervoltage
E69 Main circuit undervoltage whether there is a lack
protection
of phase. Check
whether the terminal
of the input power
supply is loose;
E70 PG line anomaly Encoder wiring error Check Encoder wiring
PG initialization PG magnetic pole shift calculation
E71 Check encoder
error error
Check the motor
connection;
The current is too large, too small Whether the weight
E72 Current anomaly
or out of phase and low-speed gain
integrals are
overtuned
Encoder A and B are phase
E73 PG misphase Check encoder wiring
reversed
If the Monarch line is
PG cable does not meet the
E74 PG cable error used, F021 in B8 is
requirements
changed to 1
E77 BB Base locked
Check whether the
output UVW is
The IGBT module is damaged or
E78 IGBT fault short-circuited.
the output cable is short-circuited
Contact the
manufacturer