Testing Notes
Testing Notes
Tan Delta, also called Loss Angle or Dissipation Factor testing, is a diagnostic method of testing electrical equipment to determine the integrity of the insulation. This is done to try to predict the remaining life expectancy of the equipment. If the insulation free from defects, it approaches the properties of a perfect capacitor. It is very similar to a parallel plate capacitor with the conductor and the neutral being the two plates separated by the insulation material. In a perfect capacitor, the voltage and current are phase shifted 90 degrees and the current through the insulation is capacitive. If there are impurities in the insulation,for example, moisture, the resistance of the insulation decreases, resulting in an increase in resistive current through the insulation. It is no longer a perfect capacitor. The current and voltage will no longer be shifted 90 degrees. It will be something less than 90 degrees. The extent to which the phase shift is less than 90 degrees is indicative of the level of insulation contamination, hence quality/reliability. This "Loss Angle" is measured and analyzed. Below is a representation of an insulation. The tangent of the angle is measured. This will indicate the level of resistance in the insulation. By measuring IR/IC (opposite over adjacent the tangent), we can determine the quality of the insulation. In a perfect insulation, the angle would be nearly zero. An increasing angle indicates an increase in the resistive current through the insulation, meaning contamination. The greater the angle, the worse is the insulation.
Insulation power factor is the angle 90-. If the insulation is excellent, the tan delta or dissipation factor is equal to the power factor. Essentially, both tan delta and power factor are just the same.
TYPE TESTS
S. No. 1 2 Type test Measurement of winding resistance Measurement of voltage ratio and check of voltage vector relationship Measurement of impedance voltage/ short-circuit impedance (principal tapping) and load loss Measurement of no-load loss and current Measurement of insulation resistance Dielectric tests (Lightning impulse on line terminals Temperature rise test Tests on on-load tap changer (where appropriate) Purpose To know resistance of winding utilized To know correct voltage ratio at each tap and to check vector symbol (To ascertain phase displacement) To know copper (load) loss and impedance voltage To know core loss & excitation current To check insulation strength To verify impulse voltage withstand capacity of insulation (Line terminal to earth & other winding) To check temperature rise of transformer under loading conditions To ensure proper operation of OLTC
4 5 6
7 8
S. No. 1
Purpose
2 3 4
5 6
To verify impulse voltage withstand capacity of insulation (Neutral terminal to earth & other winding) Measurement of zero sequence To check zero sequence impedance of 3impedance of 3-phase transformers phase transformers Short circuit test To ensure mechanical strength under short circuit condition Measurement of acoustic noise level To measure sound level produced by transformer during rated excitation under no-load condition Measurement of harmonics of the no- To measure harmonics of the no-load load current current Measurement of power taken by fans To know power consumption of fans & & oil pumps oil pumps
SP E CI A L TE ST S
ROUTINE TESTS
S. Routine test Purpose No. Type Tests 1,2,3,4,5,6, and 9 will also be the Routine Tests. In addition, the following Dielectric tests will be performed as a Routine test Dielectric Tests
To verify power frequency withstand capacity of winding (winding to other winding and to earth) To verify power frequency withstand capacity of winding (phases to earth and other winding)
Temp rise test This test is made to determine the temperature rise of the transformer under rated Load. Thermometers or thermocouples are installed to measure ambient temperatures, oil surface temperatures in the transformer tank and at some point (perhaps 2 or 3 inches) below the oil surface where maximum temperatures may be expected. Readings on these are taken before the
test is started to obtain base temperatures on which to determine the rise at rated load These are also read periodically during the test, and continued until temperatures do not vary more than a few degrees over a paeriod of hours, and hence may be considered as stabilized.
While the motor is in drying out process,the small vents,if provided,on both the sides of motor should kept open for escape of moisture.A tested temperature gauge( capillary type) should be placed on the motor to record the optimum temperature the windings achieved and to control the temperature to below 85 degree centigrate.It is necessary to cover the motor with asbestos clothing to prevent heat radiation. Insulation resistance must be measured at an interval of every hour till the insulation value stabilizes at certain point,then the heating process is to be discontinued.When the motor cools down to the ambient temperature will get favourable insulation resistance reading.
The standard describes a system for classifying the degrees of protection provided by the enclosures of electrical equipment. Developed by the European Committee for Electrotechnical Standardization (CENELEC), these standards are designed to numerically rate an electrical product on the level of protection its enclosure provides. By assigning different number codes, the product's degree of protection can be identified quickly and easily. In the code IP 55, which most of our motors meet, for example, IP identifies this standard, the first digital 5 describes the level of protection from solid objects, and the second digital 5 describes the level of protection from liquids. Below is the description of Ingress Protection (IP) Classification with 2 digits (IP **). 0 No Protection 1 Protected against solid objects up to 50mm e.g. accidental touch by hands 2 Protected against solid objects up to 12mm e.g. fingers 3 Protected against solid objects over 2.5mm e.g. tools 4 Protected against solid objects over 1mm e.g. wires 5 Protected against dust - limited ingress (no harmful deposit) 6 Totally protected against dust\The second digit 0 No Protection 1 Protected against solid objects up to 50mm e.g. accidental touch by hands 2 Protected against solid objects up to 12mm e.g. fingers 3 Protected against direct sprays of water up to 60 deg from the vertical 4 Protected against water sprayed from all directions - limited ingress permitted 5 Protected against low pressure jets of water from all directions - limited ingress permitted 6 Protected against strong jets of water e.g. for use on shipdecks - limited ingress permitted 7 Protected against the affects of immersion between 15cm and 1m 8 Protected against long periods of immersion under pressure IP code is also widely used in the articles about frequency inverter, and related industrial equipment.
Figure 4 Dual-Frequency Power Sources, 50 Hertz Power superimposed on 60 Hertz by Use of a Coupling Transformer
The frequency that the motor sees changes completely 10 times per second. This continuous change causes the revolving magnetic field inside the motor to change its synchronous speed between that of 50 hertz and 60 hertz. When the motor is under the influence of the 60-hertz supply, the motor accelerates towards the 60-hertz synchronous speed, drawing current in the process to achieve the acceleration and operating as a motor under high slip. However, because of its rotor inertia, it cannot reach that speed instantly. One tenth of a second later the motor sees 50-hertz power. The motor then decelerates towards the 50-hertz synchronous speed. The slip being negative, the motor now generates current and feeds it back to supply lines as an induction generator. With proper adjustments to input parameters, a steady operating condition can be achieved wherein the motor sees rated root-mean-square (rms) voltage and rated rms line current. The wave shapes are not sinusoidal, but tests show that they produce similar heating in the motor. Table 1 lists comparative test results reported by various manufacturers. The rated condition is generally reached when the 50-hertz input voltage reaches 20 to 30 percent of the 60-hertz rated voltage as measured at V1 and V2, respectively, in Figure 3.. During the duration of the heat run, the terminal voltage and current of the motor are maintained at their rated 60-hertz values. Volt, ampere, and kilowatt readings at the motor terminals are recorded along with the motor temperatures. After the machine temperatures (as indicated by stator resistance temperature detectors or auxiliary thermocouples) have stabilized, the voltages of the auxiliary power and the prime power are reduced. After the motor is stopped and all breakers are opened and locked out, resistance is measured to evaluate temperature rise. During the heat run, the motor is being supplied from two power sources at different frequencies, and is subjected to the oscillatory torques associated with these frequencies. Consequently, the vibration will be abnormal during this condition and may not meet the normal limits of vibration. For this reason a no-load cold vibration is measured at rated voltage before the application of the auxiliary power. Then, at the end of the heat run after the temperatures on the machine have stabilized, the auxiliary power is removed, and the vibration at rated frequency and voltage is measured again to determine the vibration of the machine at normal running temperature. This is done without stopping the test motor, which allows the hot vibration to be recorded quickly since the machine especially an open machine cools down rapidly after the auxiliary power is removed. IEEE 112 recommends that the vibrations should be measured while the motor is within 25 percent of the normal operating temperature.
Dual-frequency load testing is a cost-effective method for temperature testing of general purpose and vertical induction motors. The test setup is simple no test coupling, rigging, or alignment is required. It takes 50 to 60 percent less time to rig and test the motor than by the conventional coupled load method.
Things to cover: 1. Testing of bushings, determination of accuracy and error, testing of auxiliaries and safety devices, over voltage inter turn test, radio interfernce test 2. Hammer test, commissioning steps for I.M, commissionig of induction genreator, trouble shooting and maintenance of I.M 3. Isolator tesing(All things), substation grid earthing
Noise level and vibration testing: Paul Gill 291 Separate source voltage testing-350 JP transformer Induce voltage testing PG 321 Soil resistivity measurement-PG-701-740 Bus bar testing-- 366 pages