Ceiling Concealed Unit for DCBL District
Cooling FWW-DA
Literature No.: LF-FWW-DA(DCBL)-202202
Building nature
based on science Energy
saving
Quiet Comfortable
and technology
For over one hundred years, DAIKIN has been dedicated to research in air conditioning technologies.
Recently, with a view to fitting into the ever increasing demands for energy saving in the world, and
responding actively to the trend of high delta temperature and low water flow application, DAIKIN strives hard
to develop district cooling DC brushless fan coil unit to make it a new classic product based on its almost up
to one hundred years’ experience in fan coil structure and performance. The units are widely used in places
with higher requirements for energy saving and comfort, such as commercial and office building, high-end
residences, hospitals and governmental projects.
Energy saving
• T
he high efficiency DC brushless motor adopts Distribution of system energy consumption under the full load operating condition
Fan coil 8%
advanced proportional digital core algorithm. 3% for the area water pump 6% for the chilled water pump
Compared to the traditional fan coil, the unit 5% for the cooling water pump
2% for the cooling tower
saves energy by over 50% and achieves more 76% for the
refrigerator
Distribution of system energy consumption under
the partial load operating condition
remarkable energy saving effect at medium or low 28% for the fan coil
speed
6% for the area water pump
8% for the cooling water pump
4% for the chilled water pump
• T
he unit employs the FOC space vector control
1% for the cooling tower
53% for the
refrigerator
system to adjust the corresponding motor speed
in time, reduce unnecessary waste in electric
energy and enhance energy utilization efficiency In the actual application, energy consumption of
significantly the fan coil accounts for 28% of the total energy
• T
he heat exchangers of the full series of units consumption of air conditioning system. The air
adopt hydrophilic aluminum foil, which is not easy conditioner operates at partial load at 90% of time.
to condense into waterdrops and can improve heat The traditional fan coil takes up about 28% of total
exchange efficiency. energy consumption because it cannot regulate its
power consumption as needed.
Stable performance output
AC motor
Fan speed
(%) (rpm) DC motor
High
speed Load change
100 DC motor
080
AC motor Medium
060 speed
Stepless
regulation
040
020
Low
speed
0
Fan speed (rpm) Time (8:00-20:00)
*Note: The foregoing statistical data may differ from the actual engineering data due to regional and climatic changes.
Quiet
• T he DC brushless motor adopts electronic commutation to avoid
electromagnetic interference and noises, ensuring a quiet and comfortable
indoor environment during operation.
• The motor adopts stepless speed regulating technology, ensuring a stable
noise band curve and remarkable sound quality. The medium/low speed has
more advantages compared with traditional motors.
• The unit uses the wide impeller fan following the aerodynamic design and has
passed the static and dynamic balance tests, with even air supply and lower
noises.
Comfortable
• T
he standard control module for unit regulates air flow intelligently, 0~10V adaptor is provided which allows
for realizing precise stepless air flow regulation to enable the optimum comfort for people indoors.
Nomenclature
FWW 02 D A S R C K N A E
E: Other Exporting Countries
Power Supply
220~240/1Ph/50[60]Hz
N-Without Electric Heater
Material of Drain Pan (See Drain Pan Features Sheet)
Down Withdraw Filter & Plenum
A-Back Returm Air Plenum with 5mm PE and 8mm Nylon Filter
B-Back Returm Air Plenum with 15mm F/G and 8mm Nylon Filter
C-Back Returm Air Plenum with 5mm PE and 25mm Aluminium Filter
D-Back Returm Air Plenum with 15mm F/G and 25mm Aluminium Filter
Pipe Connection
R-Facing Air Flow Right Hand
L-Facing Air Flow Left Hand
Motor & ESP
S-DCBL Motor IP42/B
50Pa External Static Pressure
Design SN
"A"-First Design Improve
Coil Type
D-4 Rows and 2-pipe(4+0) with High Delta T
Nominal Air Flow
02, 03 04 05, 06, 07, 08, 09, 10, 12, 14, 16, 18, 20 (*100CFM)
(CFM, 1CFM=1.7m3/h)
Daikin Horizontal Ceiling Concealed Fan Coil Unit
Drain Pan Features Sheet
Code Material Length Insulation
A standard standard 6mm NBR
B standard +100mm 6mm NBR
E SUS standard 6mm NBR
F SUS +100mm 6mm NBR
K standard standard 6mm class"0" armaflex
P standard +100mm 6mm class"0" armaflex
L SUS standard 6mm class"0" armaflex
Q SUS +100mm 6mm class"0" armaflex
Specification
Ceiling Concealed Unit for DCBL District Cooling FWW-DA
MODEL 02DA 03DA 04DA 05DA 06DA 07DA 08DA 10DA 12DA 14DA 16DA 18DA 20DA
High 390 510 650 790 1010 1170 1200 1510 1770 1890 2220 2550 3280
Air flow
Medium 370 490 620 750 990 1140 1170 1490 1730 1860 2090 2530 3140
(m3/h)
Low 310 410 520 650 860 1020 1000 1360 1550 1690 1700 2130 2560
High 55 54 56 52 53 54 53 52 53 52 56 53 54
ESP (Pa) Medium 50 50 50 50 50 50 50 50 50 50 50 50 50
Low 35 36 36 38 38 40 40 42 40 41 34 36 33
High 2087 2179 3238 3939 4567 5453 5527 7333 8505 8785 9947 11598 14422
Total cooling
Medium 2038 2160 3187 3860 4540 5323 5400 7234 8399 8723 9630 11587 14053
capacity (W)
Low 1748 1933 2822 3537 4165 4977 4907 6860 7742 8327 8500 10531 12498
High 1473 1512 2184 2677 3285 3859 3944 5178 6064 6311 7309 8468 10647
Sensible
cooling Medium 1423 1484 2137 2608 3259 3772 3864 5123 5931 6255 7031 8466 10347
capacity (W)
Low 1201 1307 1856 2354 2954 3504 3461 4807 5396 5902 6072 7550 8988
High 4.8 5.3 12 18.7 8.7 13 13.4 13.5 18.2 19.4 16.3 22.6 24.3
Water
Pressure Medium 4.7 5.3 11.8 18.2 8.7 12.7 13.1 13.3 17.8 19.1 15.5 22.6 23.4
Drop (Pa)
Low 4.1 4.7 10.2 16.3 7.9 11.6 11.6 12.4 15.2 17.5 12.8 19.3 19.5
Rated power
High* 42 63 71 92 124 131 135 187 217 238 344 417 555
Input (W)
High 42.5 43.5 44 45 47.5 47.5 48 48.5 50.5 51.5 52 53.5 57
Sound
pressure Medium 41.5 43 43 44 46.5 46.5 47.5 48 49.5 51 51 53 56
level (dB(A))
Low 37 40 41 42 43.5 44.5 44.5 46.5 47 48 47 49.5 52
Coil material Copper
Fin material Hydrophilic aluminum 0.11mm
Filter withdraw Bottom withdraw
Max. working pressure 1.6MPa
Cooling water pipe
Rc 3/4 Female thread
size
Condensation water
R3/4 Male thread
pipe size
Type Galvanized steel double stage impeller forward centrifugal
Fan
Quantity 1 1 2 2 2 2 2 3 4 4 3 3 4
Type DCBL motor IP42/B
Motor
Quantity 1 1 1 1 1 1 1 2 2 2 2 2 2
NOTES:
1) THE AIR FLOW IS DRY AIR FLOW TESTED ON STANDARD AIR CONDITION WITHOUT WATER IN COIL.
2) THE COOLING CAPACITY ARE TESTED UNDER FOLLOWING CONDITION: ENTERING AIR DB/WB: 24°C DB/18°C, WATER
INLET 5.5°C, WATER OUTLET 14.5°C.
3) ALL PERFORMANCE ARE TESTED UNDER 230V~/50HZ WITH BACK PLENUM AND 25MM ALUMINUM FILTER.
4) WHEN THE WATER CONNECT DIRECTION IS CHANGED IN FIELD,THE CAPACITY SHOULD BE REDUCED BY 15%.
5) SOUND PRESSURE MEASURED AT 1M IN FRONT OF THE UNIT AND 1M BELOW THE VERTICAL CENTER LINE OF THE UNIT.
AND TESTED IN SEMI-ANECHOIC ROOM,WITH BACKGROUND SOUND PRESSURE LEVEL: 11.5DB (A).
6) *THE RATED POWER INPUT OF HIGH FAN SPEED IS BASED ON ESP 50PA.
Dimension Diagram
I
F 104
E 20
28
14
D 20
WATER RETURN Rc3/4
K
J
WATER SUPPLY Rc3/4
TERMINAL BOX
131
16
MOUNTING HOLES 6-10 x 16 242
262
L
CONDENSATE DRAIN PIPE R3/4
187
AIR VENT VALVE
44
Model A B C D E F G H I J K L M
B FWW02DA 675 452 487 469 522 540
35 C M FWW03DA 675 452 487 469 522 540
A FWW04DA 825 592 627 649 702 720
FWW05DA 925 692 727 749 802 820
FWW06DA 995 772 807 789 842 860
151 143 529 211 243 382 72
FWW07DA 1095 872 907 889 942 960
FWW08DA 1095 872 907 889 942 960
FWW10DA 1425 1202 1237 1219 1272 1290
FWW12DA 1525 1302 1337 1359 1412 1420
FWW14DA 1525 1302 1337 1359 1412 1420
35 FWW16DA 1425 1202 1237 1239 1289 1307
FWW18DA 1525 1302 1337 1322 1372 1390 201 194 599 266 297 413 82
FWW20DA 1825 1602 1637 1622 1672 1690
Electric Wiring Diagram
MODEL: FWW02~14DA MODEL: FWW16~20DA
FAN MOTOR2 APPLY TO Y/G
Y/G FWW10~14DA UNITS
M2
M2
L
PE
M2
L
PE
N
M1
N
M1
N
M1
PCB
N
M1
PCB
PROG
POWER SUPPLY
JP1
PROG
PE HF MF LF AI+ AI-
JP1
L
COM1
LS
N HF MF LF AI+ AI-
COM1
LS
Y/G
0-10V input signal
POWER SUPPLY
PE
NOTE: RED
L 1 M2
L
1.Power cable wiring sequence,please strictly follow the wiring diagram! N 2
BLUE PE
N
2.The PCB board program has been matched with the unit motor and unit static pressure,and 3
N
M1
it is forbidden to change without authorization.
N
4
BLACK
M2
0-10V input signal PCB
3.The PCB board black fence terminal block withstands maximum torque ≤0.8N.M. 5
WHITE
4.LS port is shorted by default. TB
PROG
5.JP1 jumper is closed by default. JP1
6.HF,MF and LF are reserved Three-Speed control ports, one of which is 0-10V control. HF MF LF AI+ AI-
SYMBOL DESCRIPTION:
COM1
LS
PCB DC brushless motor power board
M1/M2 Brushless DC motor FACTORY WIRING
TB Terminal block FIELD WIRING
DWG NO.:M08024069752
Installation Dimension Diagram
OBSTACLE
OBSTACLE
�U+01AF(H+150)mm
N A
L
≥300mm
WATER OUTLET
B A
WATER INLET
C
≤15mm
M
≥400mm ≥200mm
D
CEILING ACCESS PANEL
WITH AIR RETRUN
CEILLING
DRAIN PIPE WATER LEVEL
The suggested slope of the The level of water in the drain CEILING
drain pipe is at least 1:50. pan should be less than 15mm.
H=the height of FCU
DISCHANGE AIR RETRUN AIR
NOTE:
EXPANSION SCREW Dimension M and N was determined by air duct design, air duct should
be fire-proof, refer to concerned country national and local regulations.
RUBBER MATS
Circulatory air pressure drop should be approximately equal to the
HANGING ROD External Static Pressure.
NUT
FLAT WASHER&SPRING WASHER
FAN COIL UNIT
Detail A
* T he products described in the publications may be discrepant with the actual products. When purchasing a
product, refer to the physical product.
* All data has been carefully reviewed. In case of any omission or error, DAIKIN shall not be held liable for
the consequence arising therefrom.
* Models, parameters, and performance of the products are subject to changes due to product improvement
without a prior notice. For details about technical parameters, refer to their nameplates.