Farm Residence
Article 2.10.11 (d)
Single branch circuit
RURA For a dwelling unit having a floor area not more than
L 50 sq. meters it shall be permitted to have a single
ELECT 20-A 2-wire branch circuit provided that the total
RIFIC load does not exceed 3 680 VA
ATION
Farm Residence
Article 2.10.2
Branch circuit ratings
RURA Conductors – Minimum Ampacity and Size
L ❖ampacity shall not be less than
ELECT non-continuous load plus 125% of the
RIFIC continuous load (expected to continue for 3
ATION hours or more)
Farm Residence
Article 2.10.1.11
Branch circuits required
❖ Number of Branch Circuits – depends on the loads
RURA (appliances/equipment) present
L ❖ In addition to this,
ELECT
(1) One or more 20-A small appliance circuits are
RIFIC
required to provide power to receptacles in the kitchen,
ATION
pantry, breakfast room, dining area, and similar areas;
(2) At least one 20-A laundry branch circuit for the
laundry receptacle outlet(s) with no
other outlets on this circuit; and
(3) At least one 20-A for bathroom lighting and
receptacle outlet(s).
According to 2.20.2.7: 20-A branch circuit = 1500 VA load
Farm Residence
According to 2.20.2.7:
The 20-A branch circuit for Small Appliance, Laundry and
Bathroom shall be computed at 1500 VA load in the
RURA computation for the feeders and services.
L
ELECT These loads shall be permitted to be included with the
RIFIC general lighting load and subjected to the demand factors
ATION provided in Table 2.20.2.2
Demand factors for Non-dwelling Receptacle Loads
Portion of load to which demand Demand factor (%)
factor applies (VA)
First 3,000 or less 100
Next 3,001 to 120,000 35
Remainder over 120,000 25
DEMAND LOAD FOR FARM RESIDENCE
OCPD and Conductor Design
Conductor-OCPD
FLOOR AREA not more than 50 sq m
LOAD not exceeding 3680 VA
Example:
If Load = 3680 VA and Floor Area = 50 sq m
I = 16 A 2.0 sq mm Cu wires is sufficient (20A)
(THW, Tw or THHN)
But PEC Section 2.30.2.3(b) Exception states that
the minimum size of wire that can be used for
a single branch circuit is 3.5 sq mm Cu wires.
Then, a 20 AT OCPD can be used.
Conductor-OCPD
FLOOR AREA not more than 150 sq m
Demand Load = Sum of
a. Lighting, Convenience Outlet, Small Appliance
Load, Laundry Circuit
First 3,000 VA = 3,000 VA
Remainder @ 35% DF
b. Other Load
(ACU @ 100%DF, Cooking Load (%DF),
Motors(100%DF), etc)
Conductor-OCPD
FLOOR AREA more than 150 sq m
Demand Load = Sum of
a. ACU, Lighting, Convenience Outlet
b. Cooking Load (%DF)
c. Other Loads @ 40%DF
(Small Appliance Load, Laundry Circuit, etc)
Conductor-OCPD