MANUAL GOSPOWER
MANUAL GOSPOWER
6KVA~6KVA)
www.gospower.com
E-mail: [email protected]
Version:1.01
Date:2023.07.28
LCD operation flow chart 19
Base information Page 19
Setting Page 21
Energy stored data Page 26
BMS information Page 27
Rated information Page 27
Lithium Battery Communication 29
30
30
30
33
33
35
35
36
Parallel connection quantity up to 12units for 6KVA model(Battery must be connected)
Intelligent fan control greatly reduces fan noise
Battery pack
GPEO-3K6L1 GPEO-6KL1
3600VA 6000VA
3600W 6000W
24V 48V
230Vac
280Vac±3V
270Vac±3V
280Vac±3V
GPEO-3K6L1 GPEO-6KL1
5 Gospower batteries
15.6A/3600W 27.3A/6000W
GPEO-3K6L1 GPEO-6KL1 GPEO-3K6L1 GPEO-6KL1
24V 48V
120A 120A
50±0.3Hz/60±0.3Hz(Adjustable)
500V 93%
PV voltage range 85V-450V
5.5s@≥150%load;10.5s@105%~150%load
120A 120A
120A 120A
27A 27A
23V 46V
80V
21.5V 43V
21V 42V
31V 0.2V
29V 0.2V
Power Limitation
When battery voltage is lower than 50Vdc,
output power will be derated If
connected load is higher than this
derated power the AC output voltage will
decrease until the output power reduces
to this derated power. The minimum AC
output voltage is 90V. 50
28.2V/56.4V 27V/54V
29.2V/58.4V 27V/54V
12kG 13kG
30V/60V
14kG 15kG
120x345x443MM
140x365x463MM
Current sharing cable x 1 O-shaped terminal x 2 Expansion bolt x 3
6
-10℃ and 55℃ to
6
6
Parallel communication
6
Inevter unit x 1 Manual x 1 RS-232 cable x 1 cable x 1
two screws.
Battery+ Battery-
3.6kVA 35
6kVA 35
3.6KVA 6
6KVA 10
Maximum bypass
Models Recommended circuit breaker
input current
2.Max. power voltage (Vmp) should be during PV array MPPT voltage range.
3.6KVA 6KVA
500V
85
Wiring System for Inverter
BAT+ BAT+
05
07
three
16 17
Setting page
On base information page, pressing and holding "ENTER" key for 3 sec, the unit will enter parameters page.
Press "UP" or "DOWN" key to switch the selection and press "ENTER" key to enter selected page. Press "ESC" key
to back to previous page.
18 19
Date
230V 230V 2023-06-01
Setting Page
01
02,03 and04.
24V model
02 01,
24.0V to 30.0V
20 21
48V model Parallel to support three-phase equipment.
01, It’s required to have at least one
inverter in each phase or it’s up to
ten inverters in one phase.
L1 Phase Please select “3P1” in program 20
24V model for the inverters connected to L1
01, phase, “3P2” in program 20 for the
24.0V to 30.0V inverters connected to L2 phase and
L2 Phase “3P3” in program 20 for the inverters
connected to L3 phase.
48V model Do NOT connect share current cable
01,
between units on different phases.
L3 Phase Before starting up inverters, please
connect all N wires of AC output
together
24V model
01, 220V
21.0V to 27.0V
240V
24V model
22.0V to 27.0V
50Hz
48V model
60Hz
UPS mode
48V model
30A
Setting range is from 10A to 120A. 5.
10
Increment of each click is 1A.
22 23
PV and Utility Disable
PV Only Enable
Disable
Disable If selected, inverter will esase all historical
data of PV and Load energy, and stop
record historical data for PV and Load
Enable energy.
Energy stored
data for PV If selected, inverter will record
and Load Enable historical data for PV and Load energy.
Disable NOTE: Before selected, please double
check if date and time is correct, if
incorrect, please set date and time in
50~55.
Enable
Year
Time 23
setting- Year
Disable
Month
Time
Setting rage is from 1 to 12
setting- Month
Enable
Day
Time
Setting rage is from 1 to 31
setting- Day
Disable
Hour
Time Setting rage is from 0 to 23
setting- Hour
Enable
Minute
Time
Setting rage is from 0 to 59
Disable setting- Minute
Second
Time
Enable Setting rage is from 0 to 59
setting- Second
Disable
Enable
24 25
Energy stored data Page BMS information Page
The energy stored data
PV generated energy today PV generated energy this month Battery pack number / mean SOC
88 kWh 88 kWh Connected battery pack number is 4, mean SOC is 97%
26 27
Rated battery voltage / Max. charge current Lithium Battery Communication
Rated battery voltage is 48V, Max. charge current is 100A
1. Connect power cables between lithium battery and inverter. Please pay attention to the terminals of positive
and negative. Make sure the positive terminal of battery is connected to the positive terminal of inverter, and
the negative terminal of battery is connected to the negative terminal of inverter.
2. The communication cable is bundled with lithium battery. Both sides are RJ45 port. One port is connected to
the BMS port of inverter and another one is connected to the COMM port of lithium battery.
Firmware version
Firmware version is 1400
BAT+
01
28 29
4. Power up lithium battery and inverter. Wait a moment, if the communication is built between them, LCD
will show you “BMS” icon as below.
5. Roll LCD real time information pages by pressing “UP” or “DOWN” button, as below page, you can see
the parameters of SOC in the communication system.
72KW/72KVA.
72KW/72KVA 60KW/60KVA.
NOTE1:
NOTE 2: Under parallel operation modes, battery must be connected with inverters.
NOTE 3: Before starting up inverters, please connect all negative(-) wires of battery together.
60cm
Battery pack
60cm
6
6 NOTE:Before starting up inverters, please connect all negative(-) wires of battery together.
30 31
Single
Parallel
20 .
three inverters or
L1 Phase
20
20
20
L2 Phase
L3 Phase
20
32 33
Fan is locked(left)
Fan is locked(right)
20
03 Bus soft start fail Restart the unit, if the error happens again, please return to
repair center.
Internal components failed.
Inverter soft start fail Restart the unit, if the error happens again, please return to
10
repair center.
Over current or surge Restart the unit, if the error happens again, please return to
11
detected by Software repair center.
Over current or surge Restart the unit, if the error happens again, please return to
12
detected by hardware repair center.
34 35
Reduce the connected load.
Over current happen at PV Restart the unit, if the error happens again, please return to
13 Output voltage is too low Restart the unit, if the error happens again, please return to 43 port repair center.
repair center.
Restart the unit, if the error happens again, please return to Check if wiring is connected well.
Output voltage is too high 50 Fan is locked
14 repair center. Replace the fan.
15 Output short circuited Check if wiring is connected well and remove abnormal load.
The temperature of internal PV component is over the limitation.
Restart the unit, if the error happens again, please return to Over temperature happen at
51
16 Inverter current sensor failed PV circuit
repair center. ambient temperature is too high.
1. Restart the inverter.
The temperature of internal INV component is over the limitation.
2. Check if L/N cables are not connected reversely in all inverters. Over temperature happen at
3. For parallel system in single phase, make sure the sharing cables 52
INV circuit
ambient temperature is too high.
Current feedback into the are connected in all inverters. For supporting three-phase system,
17
inverter is detected. make sure the sharing cables are connected in the inverters in the The temperature of Convert L battery converter component is over
same phase, and disconnected in the inverters in different phases. Over temperature happen at the limitation.
4. If the problem remains, please contact your installer. 53
Convert L circuit
20 Overload time out Reduce the connected load by switching off some equipment. ambient temperature is too high.
The temperature of internal Convert H component is over the
Restart the unit, if the error happens again, please return to
21 OP current sensor failed Over temperature happen limitation.
repair center.
54 at Convert H circuit
Restart the unit, if the error happens again, please return to
22 Sharing current sensor failed ambient temperature is too high.
repair center.
The temperature of internal DC/DC TX is over the limitation.
1. Please check AC input and output wires are connected correctly. Over temperature happen
55
2. If this error happens during parallel installation, please check at LLC TX
The AC input and output wires ambient temperature is too high.
23 wires connection. If they are connected correctly, please funish
are inversely connected
60 CAN data loss
1. Check if communication cables are connected well and restart
3. If the problem remains, please contact your installer.
61 Host data loss the inverter.
Battery voltage is too high Check if spec and quantity of batteries are meet requirements. 2. If the problem remains, please contact your installer.
30 62 Synchronization data loss
Over current happen at Restart the unit, if the error happens again, please return to
31 DC/DC circuit repair center.
2. Check the version of each inverter via LCD setting and make sure
Restart the unit, if the error happens again, please return to the CPU versions are same. If not, please contact your installer to
32 DC/DC current sensor failed 63
repair center. inverter is not the same.
3. After updating, if the problem still remains, please contact your
No.2 DCDC current sensor Restart the unit, if the error happens again, please return to
33 installer.
failed repair center.
The output current of each 1. Check if sharing cables are connected well and restart the inverter.
34 DC/DC soft start fail. Restarttheunit,iftheerrorhappensagain,pleasereturntorepaircenter. 64
inverter is different. 2. If the problem remains, please contact your installer.
Over current happen at 1. Switch off the inverter and check LCD setting program 20.
Restart the unit, if the error happens again, please return to
35 DC/DC circuit detected 2. For parallel system in single phase, make sure no 3P1, 3P2 or
repair center.
by hardware AC output mode
65 3P3 is set on program 20. For supporting three-phase system, make
setting is different.
sure no “PAL” is set on program 20.
Over current happen at Restart the unit, if the error happens again, please return to repair
36 3. If the problem remains, please contact your installer.
LLC circuit center
1. Please check if single unit is installed to parallel system.
40 PV voltage is too high Reduce the number of PV modules in series.
2. If this error happens during parallel installation, please check
Short circuited happen at
Check if wiring is connected well. Single unit is installed wires connectiotn. If they are connected correctly, please funish
41 PV port 66
to parallel system
3. If the problem remains, please contact your installer.
36 37