LAD 240 Spec
LAD 240 Spec
■ ■
‧ ‧
‧ ‧
‧
‧
‧ •
‧
‧
‧
‧℃ ■
https://www.meanwell.com/serviceGTIN.aspx
‧
‧
‧
‧
‧
■
■
File Name:LAD-240-SPEC 2024-10-30
240W Economical Security/Fire Alarm PSU with Battery Charger/UPS L A D - 2 4 0 series
SPECIFICATION
MODEL LAD-240A LAD-240B LAD-240C LAD-240D
OUTPUT NUMBER CH1 CH2 CH1 CH2 CH1 CH2 CH1 CH2
DC VOLTAGE 13.8V 13.8V 27.6V 27.6V 41.5V 41.5V 55.2V 55.2V
RATED CURRENT 16.4A 1A(Battery Charger) 7.7A 1A(Battery Charger) 4.78A 1A(Battery Charger) 3.4A 1A(Battery Charger)
CURRENT RANGE 0 ~ 17.4A -------- 0 ~ 8.7A -------- 0 ~ 5.78A -------- 0 ~ 4.4A --------
RATED POWER 240.12W 240.12W 239.87W 242.88W
RIPPLE & NOISE (max.) Note.2 150mVp-p -------- 150mVp-p -------- 240mVp-p -------- 240mVp-p --------
VOLTAGE ADJ. RANGE CH1: 10.8 ~ 14.5V CH1: 21.6 ~ 29V CH1: 32.4 ~ 43.5V CH1: 43.5 ~ 58V
OUTPUT
VOLTAGE TOLERANCE Note.3 ±1.5% -------- ±1.0% -------- ±1.0% -------- ±0.5% --------
LINE REGULATION ±0.5% -------- ±0.5% -------- ±0.5% -------- ±0.5% --------
LOAD REGULATION ±1.0% -------- ±0.5% -------- ±0.5% -------- ±0.5% --------
SETUP, RISE TIME 2000ms, 50ms/230VAC 2000ms, 50ms/115VAC at full load
HOLD UP TIME (Typ.) 16ms/230VAC 12ms/115VAC at full load
BATTERY STATIC DISCHARGE
<100μA
CURRENT
VOLTAGE RANGE 90 ~ 132VAC / 180 ~ 264VAC by switch 240 ~ 370VDC (Default switch at 230VAC)
FREQUENCY RANGE 47 ~ 63Hz
INPUT EFFICIENCY (Typ.) 85.5% 87.5% 88% 88%
AC CURRENT (Typ.) 4.4A/115VAC 2.4A/230VAC
INRUSH CURRENT (Typ.) COLD START 60A/115VAC 60A/230VAC
LEAKAGE CURRENT <0.5mA / 240VAC
CH1:105 ~ 135% CH2:90 ~ 110%
Protection type : CH1 OLP, CH2 with battery: The unit will enter to UPS mode when CH1 is around 105%~120%,
OVERLOAD when total output of CH1 + CH2 reach around 125%~135% output shuts down
CH1 OLP, CH2 without battery:Shut down o/p voltage,re-power on to removed
CH2 : Constant current limiting; fault condition does not affect CH1 working,recovers automatically after fault
PROTECTION condition is removed (External fuse is mandatory in series connection with battery for protection)
CH1:15.5 ~ 18V CH1:31 ~ 36V CH1:47 ~ 55V CH1:59 ~ 69V
OVER VOLTAGE Protection type : Shut down o/p voltage, re-power on to removed
OVER TEMPERATURE Protection type : Shut down o/p voltage, re-power on to removed
BATTERY REVERSE POLARITY Protected when reverse polarity , no damage, recovers automatically after fault condition is removed
BATTERY CUTOFF 9.5V±0.5V 21.5V±0.5V 32V±0.5V 43V±0.5V
AC OK TTL signal, High / Open : AC Fail ; Low : AC OK ; Ice : max. 30mA@ 50VDC
BATTERY DISCONNECT/
REVERSE POLARITY TTL signal, High / Open : Battery connect/normal ; Low : Battery disconnect/reverse polarity; Ice : max. 30mA@ 50VDC
FUNCTION BATTERY LOW TTL signal, High / Open : Battery normal ; Low : Battery low; Ice : max. 30mA@ 50VDC
BATTERY FULL TTL signal, High / Open : Battery charging ; Low : Battery full ; Ice : max. 30mA@ 50VDC
DISCHARGE TTL signal, High / Open : Charge ; Low : Discharge ; Ice : max. 30mA@ 50VDC
WORKING TEMP. -20 ~ +60℃ (Refer to "Derating Curve")
WORKING HUMIDITY 20 ~ 95% RH non-condensing
ENVIRONMENT STORAGE TEMP., HUMIDITY -30 ~ +85℃, 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT ±0.03%/℃ (0 ~ 50℃)
VIBRATION 10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes
SAFETY STANDARDS UL62368-1, BS EN/EN62368-1, AS/NZS62368.1, EAC TP TC 004 approved; Design refer to GB 17945-2010
WITHSTAND VOLTAGE I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
Parameter Standard Test Level / Note
BS EN/EN55032 (CISPR32), Class A
Conducted
EAC TP TC 020
BS EN/EN55032 (CISPR32), Class A
SAFETY & EMC EMISSION Radiated
EAC TP TC 020
EMC
(Note 4 & 5)
Harmonic Current ----- -----
Voltage Flicker ----- -----
Parameter Standard Test Level / Note
ESD BS EN/EN61000-4-2 Level 3, 8KV air ; Level 2, 6KV contact; criteria A
Radiated BS EN/EN61000-4-3 Level 3, 10V/m ; criteria A
EFT / Burst BS EN/EN61000-4-4 Level 3, 2KV ; criteria A
EMC IMMUNITY
Surge BS EN/EN61000-4-5 Level 3, 1KV/Line-Line ;2KV/Line-FG ;criteria A
Conducted BS EN/EN61000-4-6 Level 3, 10V ; criteria A
Magnetic Field BS EN/EN61000-4-8 Level 4, 30A/m ; criteria A
MTBF 1394.9K hrs min. Telcordia SR-332 (Bellcore); 156.7K hrs min. MIL-HDBK-217F (25℃)
OTHERS DIMENSION 215*115*30mm (L*W*H)
PACKING 0.75Kg; 15pcs/12.25Kg/0.7CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1μF & 47μF parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on
360mm*360mm metal plate with 1mm of thickness. Radiation testing requires adding 13*26*30NIZN magnetic loops or buckles to the battery
For guidance on how to perform these EMC tests, please refer to
“EMI testing of component power supplies.” (as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf )
5. This power supply does not meet the harmonic current requirements outlined by BS EN/EN61000-3-2. Please do not use this power supply
NOTE under the following conditions:
a) the end-devices is used within the European Union, and
b) the end-devices is connected to public mains supply with 220Vac or greater rated nominal voltage, and
c) the power supply is:
- installed in end-devices with average or continuous input power greater than 75W, or
- belong to part of a lighting system
Exception:
Power supplies used within the following end-devices do not need to fulfill BS EN/EN61000-3-2
a) professional equipment with a total rated input power greater than 1000W;
b) symmetrically controlled heating elements with a rated power less than or equal to 200W
6. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).
※ Product Liability Disclaimer:For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx
Block Diagram
fosc : 65KHz
BAT+
BAT. CHARGER
BAT-
RELAY
S.W
UPS
FUNCTION
EMI FILTER RECTIFIERS +V
POWER
I/P & &
AC SWITCHING -V
RECTIFIERS FILTER
ON/OFF
S.W
O.L.P.
FG
DETECTION
ACTIVE CIRCUIT
PWM
START
CONTROL Battery disconnect/
CIRCUIT polarity reverse
O.V.P. TTL Signal
Battery low
Battery full
Discharge
Derating Curve
100
80
LOAD (%)
60
40
20
Static Characteristics
100
90
180 ~ 264VAC
80 90 ~ 132VAC
70
LOAD (%)
60
50
40
1.DC-UPS function
When AC voltage is abnormal,The UPS function will activate and power source switch battery backup.
AC mains Input
TTL
~
▪
▪
▪
▪
▪
CN2
Battery Load
PIN7,8
R
V
2 1
4
R
8 7
V
Note. The signals of battery disconnected and reverse polarity can only be detected during the first power transmission ,
it is can not be detected at any time.
2 1
4 3
R
8 7
V
2 1
4
5
8 7
R
2 1
4
V 6
8 7
R
2 1
8 7
215
32.5 150
36.7
CN2
BAT. connected/
Disconnected S.W
115
6
135
5
4 47.45
3
2
1
AC ON/OFF S.W
16
TB1
15
32.5 150
2
12.8 6.9
30
Air flow
12.5 direction
Accessory List
※ Bracket ( Optional accessory, Should ordered seperately )
Installation Diagram
M4*4
32.5mm 150mm
215mm
4*M4 L=6
150mm
Installation Manual
Please refer to : http://www.meanwell.com/manual.html