240W Economical Security/Fire Alarm PSU with Battery Charger/UPS L A D - 2 4 0 series

UL62368-1 TPTC004 AS/NZS62368.1 IEC62368-1 (Note 6)

■  ■ 
‧ ‧
‧ ‧
 ‧
 ‧
‧ •
 ‧
‧
‧


‧℃ ■ 
 https://www.meanwell.com/serviceGTIN.aspx
‧
‧
‧
‧
‧

■ 
              
             

              
             


■ 
   




File Name:LAD-240-SPEC 2024-10-30
240W Economical Security/Fire Alarm PSU with Battery Charger/UPS L A D - 2 4 0 series
SPECIFICATION
MODEL LAD-240A LAD-240B LAD-240C LAD-240D
OUTPUT NUMBER CH1 CH2 CH1 CH2 CH1 CH2 CH1 CH2
DC VOLTAGE 13.8V 13.8V 27.6V 27.6V 41.5V 41.5V 55.2V 55.2V
RATED CURRENT 16.4A 1A(Battery Charger) 7.7A 1A(Battery Charger) 4.78A 1A(Battery Charger) 3.4A 1A(Battery Charger)
CURRENT RANGE 0 ~ 17.4A -------- 0 ~ 8.7A -------- 0 ~ 5.78A -------- 0 ~ 4.4A --------
RATED POWER 240.12W 240.12W 239.87W 242.88W
RIPPLE & NOISE (max.) Note.2 150mVp-p -------- 150mVp-p -------- 240mVp-p -------- 240mVp-p --------
VOLTAGE ADJ. RANGE CH1: 10.8 ~ 14.5V CH1: 21.6 ~ 29V CH1: 32.4 ~ 43.5V CH1: 43.5 ~ 58V
OUTPUT
VOLTAGE TOLERANCE Note.3 ±1.5% -------- ±1.0% -------- ±1.0% -------- ±0.5% --------
LINE REGULATION ±0.5% -------- ±0.5% -------- ±0.5% -------- ±0.5% --------
LOAD REGULATION ±1.0% -------- ±0.5% -------- ±0.5% -------- ±0.5% --------
SETUP, RISE TIME 2000ms, 50ms/230VAC 2000ms, 50ms/115VAC at full load
HOLD UP TIME (Typ.) 16ms/230VAC 12ms/115VAC at full load
BATTERY STATIC DISCHARGE
<100μA
CURRENT
VOLTAGE RANGE 90 ~ 132VAC / 180 ~ 264VAC by switch 240 ~ 370VDC (Default switch at 230VAC)
FREQUENCY RANGE 47 ~ 63Hz
INPUT EFFICIENCY (Typ.) 85.5% 87.5% 88% 88%
AC CURRENT (Typ.) 4.4A/115VAC 2.4A/230VAC
INRUSH CURRENT (Typ.) COLD START 60A/115VAC 60A/230VAC
LEAKAGE CURRENT <0.5mA / 240VAC
CH1:105 ~ 135% CH2:90 ~ 110%
Protection type : CH1 OLP, CH2 with battery: The unit will enter to UPS mode when CH1 is around 105%~120%,
OVERLOAD when total output of CH1 + CH2 reach around 125%~135% output shuts down
CH1 OLP, CH2 without battery:Shut down o/p voltage,re-power on to removed
CH2 : Constant current limiting; fault condition does not affect CH1 working,recovers automatically after fault
PROTECTION condition is removed (External fuse is mandatory in series connection with battery for protection)
CH1:15.5 ~ 18V CH1:31 ~ 36V CH1:47 ~ 55V CH1:59 ~ 69V
OVER VOLTAGE Protection type : Shut down o/p voltage, re-power on to removed
OVER TEMPERATURE Protection type : Shut down o/p voltage, re-power on to removed
BATTERY REVERSE POLARITY Protected when reverse polarity , no damage, recovers automatically after fault condition is removed
BATTERY CUTOFF 9.5V±0.5V 21.5V±0.5V 32V±0.5V 43V±0.5V
AC OK TTL signal, High / Open : AC Fail ; Low : AC OK ; Ice : max. 30mA@ 50VDC
BATTERY DISCONNECT/
REVERSE POLARITY TTL signal, High / Open : Battery connect/normal ; Low : Battery disconnect/reverse polarity; Ice : max. 30mA@ 50VDC
FUNCTION BATTERY LOW TTL signal, High / Open : Battery normal ; Low : Battery low; Ice : max. 30mA@ 50VDC
BATTERY FULL TTL signal, High / Open : Battery charging ; Low : Battery full ; Ice : max. 30mA@ 50VDC
DISCHARGE TTL signal, High / Open : Charge ; Low : Discharge ; Ice : max. 30mA@ 50VDC
WORKING TEMP. -20 ~ +60℃ (Refer to "Derating Curve")
WORKING HUMIDITY 20 ~ 95% RH non-condensing
ENVIRONMENT STORAGE TEMP., HUMIDITY -30 ~ +85℃, 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT ±0.03%/℃ (0 ~ 50℃)
VIBRATION 10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes
SAFETY STANDARDS UL62368-1, BS EN/EN62368-1, AS/NZS62368.1, EAC TP TC 004 approved; Design refer to GB 17945-2010
WITHSTAND VOLTAGE I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
Parameter Standard Test Level / Note
BS EN/EN55032 (CISPR32), Class A
Conducted
EAC TP TC 020
BS EN/EN55032 (CISPR32), Class A
SAFETY & EMC EMISSION Radiated
EAC TP TC 020
EMC
(Note 4 & 5)
Harmonic Current ----- -----
Voltage Flicker ----- -----
Parameter Standard Test Level / Note
ESD BS EN/EN61000-4-2 Level 3, 8KV air ; Level 2, 6KV contact; criteria A
Radiated BS EN/EN61000-4-3 Level 3, 10V/m ; criteria A
EFT / Burst BS EN/EN61000-4-4 Level 3, 2KV ; criteria A
EMC IMMUNITY
Surge BS EN/EN61000-4-5 Level 3, 1KV/Line-Line ;2KV/Line-FG ;criteria A
Conducted BS EN/EN61000-4-6 Level 3, 10V ; criteria A
Magnetic Field BS EN/EN61000-4-8 Level 4, 30A/m ; criteria A
MTBF 1394.9K hrs min. Telcordia SR-332 (Bellcore); 156.7K hrs min. MIL-HDBK-217F (25℃)
OTHERS DIMENSION 215*115*30mm (L*W*H)
PACKING 0.75Kg; 15pcs/12.25Kg/0.7CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1μF & 47μF parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on
360mm*360mm metal plate with 1mm of thickness. Radiation testing requires adding 13*26*30NIZN magnetic loops or buckles to the battery
 For guidance on how to perform these EMC tests, please refer to
“EMI testing of component power supplies.” (as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf )
5. This power supply does not meet the harmonic current requirements outlined by BS EN/EN61000-3-2. Please do not use this power supply
NOTE under the following conditions:
a) the end-devices is used within the European Union, and
b) the end-devices is connected to public mains supply with 220Vac or greater rated nominal voltage, and
c) the power supply is:
- installed in end-devices with average or continuous input power greater than 75W, or
- belong to part of a lighting system
Exception:
Power supplies used within the following end-devices do not need to fulfill BS EN/EN61000-3-2
a) professional equipment with a total rated input power greater than 1000W;
b) symmetrically controlled heating elements with a rated power less than or equal to 200W
6. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).
※ Product Liability Disclaimer:For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

File Name:LAD-240-SPEC 2024-10-30


240W Economical Security/Fire Alarm PSU with Battery Charger/UPS L A D - 2 4 0 series

Block Diagram

fosc : 65KHz

BAT+
BAT. CHARGER
BAT-
RELAY
S.W
UPS
FUNCTION
EMI FILTER RECTIFIERS +V
POWER
I/P & &
AC SWITCHING -V
RECTIFIERS FILTER
ON/OFF
S.W

O.L.P.
FG

DETECTION
ACTIVE CIRCUIT
PWM  
START
CONTROL Battery disconnect/
CIRCUIT polarity reverse
O.V.P. TTL Signal
Battery low
Battery full
Discharge

Derating Curve

100

80
LOAD (%)

60

40

20

-20 -10 0 10 20 30 40 50 60 (HORIZONTAL)


AMBIENT TEMPERATURE (℃)

Static Characteristics

100

90
180 ~ 264VAC
80 90 ~ 132VAC

70
LOAD (%)

60

50

40

90 95 100 105 110 115 120 125 132


180 190 200 210 220 230 240 250 264

INPUT VOLTAGE (VAC) 60Hz

File Name:LAD-240-SPEC 2024-10-30


240W Economical Security/Fire Alarm PSU with Battery Charger/UPS L A D - 2 4 0 series
Suggested Application

1.DC-UPS function
When AC voltage is abnormal,The UPS function will activate and power source switch battery backup.

AC mains Input

TTL

~
▪ 
▪ 
▪ 
▪ 
▪ 

Force start UPS mode Charging

CN2
Battery Load
PIN7,8

2.Function signals by TTL

 TTL Signal is sent out through pins from CN2.


 External voltage source is required for the TTL signal. The maximum voltage is 50VDC and the maximum sink current is 30mA.

R
V

External voltage and resistor


(The max. sink current is 30mA at 50VDC)

2.1 AC OK : Detection of AC status

Between pin 1 and pin 4 Description


Low
The signal is "Low" when the AC input is normal
(0.3V max. at 30mA)
High or open
The signal turns to be "High" when the AC input is abnormal
(External applied voltage 50V max.)

2 1
4
R
8 7
V

2.2 Battery Disconnected/Reverse Polarity: Battery status detection

Between pin 2 and pin 4 Description


Low
The signal is "Low" when the battery is not connected or inversely connected
(0.3V max. at 30mA)
High or open
The signal turns to be "High" when the battery is connected or normal
(External applied voltage 50V max.)

Note. The signals of battery disconnected and reverse polarity can only be detected during the first power transmission ,
it is can not be detected at any time.

File Name:LAD-240-SPEC 2024-10-30


240W Economical Security/Fire Alarm PSU with Battery Charger/UPS L A D - 2 4 0 series
2 1
4
R
8 7
V

2.3 Battery Low: Battery low detection

Between pin 3 and pin 4 Description


Low
The signal is "Low" when the battery is under voltage protected
(0.3V max. at 30mA)
High or open
The signal turns to be "High" when the battery is normal
(External applied voltage 50V max.)

2 1
4 3

R
8 7
V

2.4 Battery Full:Battery full detection

Between pin 4 and pin 5 Description


Low
The signal is "Low" when the battery is fully charged
(0.3V max. at 30mA)
High or open
The signal turns to be "High" when the battery is charged
(External applied voltage 50V max.)

2 1
4
5
8 7
R

2.5 Discharge: Discharge detection

Between pin 4 and pin 6 Description


Low
The signal is "Low" when the power supply is discharging
(0.3V max. at 30mA)
High or open
The signal is "High" when the main power is working
(External applied voltage 50V max.)

2 1
4
V 6
8 7
R

2.6 Forced Start: Forced start UPS mode


Pin 7 & 8 Status
Short Forced start UPS mode
Open Normal

2 1

8 7

File Name:LAD-240-SPEC 2024-10-30


240W Economical Security/Fire Alarm PSU with Battery Charger/UPS L A D - 2 4 0 series
Mechanical Specification
(Unit: mm , tolerance ± 1mm) Case No. 207

215
32.5 150

36.7
CN2
BAT. connected/
Disconnected S.W

115
6

135
5
4 47.45
3
2
1
AC ON/OFF S.W

16
TB1

15

32.5 150

2
12.8 6.9

30
Air flow
12.5 direction

6.5 6.5 4-M4(Both Sides) L=6mm

※ Connector Pin No. Assignment(CN2) ※ Terminal Pin No. Assignment(TB1)


Pin No. Assignment(TTL Signal) Mating Housing Terminal Pin No. Assignment
1 AC OK 1 AC/L
Battery disconnect/ 2 AC/N
2 reverse polarity 3 FG
3 Battery low 4 DC OUTPUT -V
TKP DH2 TKP DHT-1S(LF)
4 GND 5 DC OUTPUT +V
or equivalent or equivalent
5 Battery full 6 BAT -
6 Discharge 7 BAT +
Open : normal
7,8
Short : forced start UPS mode
DC OUTPUT -V and BAT - can not be shorted.

Accessory List
※ Bracket ( Optional accessory, Should ordered seperately )

MW’s Order No. Item Quantity

PGG2MHS012 4pcs/per model

File Name:LAD-240-SPEC 2024-10-30


240W Economical Security/Fire Alarm PSU with Battery Charger/UPS L A D - 2 4 0 series

Installation Diagram

M4*4

32.5mm 150mm

215mm

4*M4 L=6
150mm

Installation Manual
Please refer to : http://www.meanwell.com/manual.html

File Name:LAD-240-SPEC 2024-10-30