CURRENT TRANSDUCER
CTR-632
APPLICATIONS
Field Interface device
Impedance matching of
Transmitters and Receiver
Isolation of field signals
Distribution of signals
Factory automation
Powering of field Transmitters
Mechanical Dimensions
Body Dimensions
A1 A2
CTR 632
76
36
Z2 Z1
S2 S1
O/P-2 O/P-1
28 85
FRONT VIEW RIGHT SIDE VIEW
All dimensions are in mm
Connection Diagram
CTR 632-A2-AA-00
Supply Input
100 To 270V AC 0 To 5Amp AC
50/60Hz, 4VA
A1 A2
CTR 632
Z2 Z1
S2 S1
O/P-2 O/P-1
Output 2 Output 1
4 To 20mA DC 4 To 20mA DC
[Link] Made in India
CTR-632 Current Transducer
[Link] Page01
TECHNICAL DATA
Input 0 TO 1A AC/ 0 TO 5A AC (Factory set any one)
Output 4 To 20mA DC / 0 To 10V DC / 0 To 20mA DC
(Factory Set any one)
Power Supply 100 to 270V AC/DC ,50/60Hz
24V DC (Factory set any one)
Accuracy 0.2 % FSD
Features Output
2KV isolation between supply, input & output Output 4 To 20mA DC /0 To 10V DC
Linearized O/P 0 To 20mA DC
(Factory set any one)
Zero & span correction facility through trim port
Output Impedance > 500ΩoneachO/P
Din Rail Mounting
Input Environmental
0 To 1A AC / 0 To 5A AC Ambient Temperature 0 to 55°C
Input
(Factory set any one) Relative Humidity 95% RH Non-Condensing
CMRR >120 db ( Typical ) Conformal Coating on PCB
Protection
Temperature Co-efficient <100 PPM
Power Supply Mechanical Characteristics
Auxiliary Voltage 100 - 270V AC Mounting Type DIN Rail Mount
24V DC (Factory set any one) Dimension (HxWxD) mm 76 x 28 x 85
Power Consumption less than 4VA Material Body Polycarbonate (PC)
Isolation type Optical - 3 way Terminal Screw Size M3
Isolation Screw Torque (N.m) 0.5
Isolation between supply and Input At least 2KV AC for 1 min. Wire Guage (AWG) 28 - 12
Isolation between supply and Output At least 2KV AC for 1 min. Unpacked : 110
Weight (Approx) gms
Isolation between Input and Output At least 2KV AC for 1 min. Packed : 120
CTR-632 Current Transducer