1.02 The control plug is a pressure-balanced cone that reduces the force
necessary to open or close the valve. The plug is controlled by an EPDM
membrane associated with a conical stainless steel spring.
1.03 The proportional band must be sufficient to obtain stable control. This
means that the proportional band must be 40 to 50% of the set point
chosen.
1.04 Each differential pressure controller is coupled with a measuring valve for
pressure transmission. This also allows measurement of the stabilised
differential pressure and the water flow rate. The differential pressure
controller and its measuring valve are both provided with measuring
nipples and a shut-off function. They are manufactured in accordance with
ISO 9001.
1.06 Pressure measuring nipples must be integral with the body and with leak-
tight shutoff when not in use.
1.08 Material and pressure ratings (differential pressure control valve and its
measuring valve)