buffer tank
buffer tank
Substance to be cooled
water flow rate. Cooling equipment
Initial temp. (˚C) Final temp. (˚C) Process amount (kg/h) Load fluctuation (%)
Load conditions
Allow for an extra 10 to 15% in terms of load after Specific heat (kcal/kg˚C) Specific gravity (kg/m3) Process amount (kg/h) Load fluctuation (%)
also considering the heat generated by the pump and Physical properties
Not specified
Flow rate L/min precision
Q = (Q1 + Q2 + Q3) × 1.05~1.1 · Net cooling load
Specified
Chiller specifications
Operating period Time Period ___ ~ __
__
Mo Mo
• Q1: Net load (kW) Water-
Air-cooled/Water-cooled Air-cooled Outdoor ˚C Cooling water inlet ˚C
cooled
• Q2: Heat generated by the pump (kW) … Motor output Yes
Special atmosphere
Location Indoor/Outdoor
(corrosion/explosion)
• Q3: Piping heat loss (kW) Laws and regulations, specified colors, start-up method, contamination factor, etc.
No
Remarks
[Note]
The calculation above assumes that a sufficient amount
of time has passed.
Depending on the substance to be cooled, a load can
instantaneously be put on the system. For this reason,
actual measurement data and the like are used in
determinations in some cases.
(E.g.: Reactor vessel cooling often results in
instantaneous load on the system.)
When
When load
load fluctuation
fluctuation is
is small
small
<Examples of use>
• General air conditioning • Computer room air conditioning
• Fermentation tank cooling • Constant temperature, constant
• Precision forming equipment humidity facilities
cooling • Printing equipment cooling
Installation of an intermediate heat exchanger at the equipment side is
required for the following uses:
When
When load
load fluctuation
fluctuation is
is relatively
relatively large
large
Cushion tank
4.5.3 Precautions when selecting a chiller and discussing the system with a client
Simple comparison between air-cooled and water-cooled
Comparison between air-cooled and water-cooled
Cooling capacity { {
Power consumption* ∆ {
COP* ∆ {
[ °C (Return water temp.) – °C (Supply water temp.)] × Water flow rate (L/h) × Specific heat × Specific gravity
Q (kW) =
860 kcal/kW
Air-cooled… Airflow (high pressure) control with fan; Installation of a windshield; Prevention of chilled
water freezing
Water-cooled… Control of cooling water temp.; (Control of cooling tower fan, 3-way valve control, etc.)
Minimum flow rate… A low flow rate increases the amount of scale that adheres to the inner surface of the piping,
resulting in corrosion and the development of pinholes (Pitting). Moreover, this can have a
significant adverse effect on capacity. (The minimum is approximately 0.4 m/sec, though this
depends on the model.)
Water flow usage range [Example] UWAP-G (DAIKIN domestic models)
Model UWAP1180G6 (K) UWAP1500G6 (K) UWAP1800G6 (K) UWAP2360G6 (K) UWAP3000G6 (K) UWAP3550G6 (K)
[Note] When selecting a differential of 1°C, be sure to use a chiller with more than the rated water flow to prevent compressor hunting.
[Reference] FAQ
Q: Can a chiller be operated when the temperature difference is ∆t = 10°C?
A: A response to the effect of "It can be easily addressed according to the operable water flow range as per
the engineering material" would be incorrect.
∆t = 10°C is possible in relation to the machine's rated capacity. (It is best to respond by citing the
minimum flow rate.)
«Example»
Q: Does the UWAP3550G6 allow for operation when ∆t = 10°C for chilled water?
A: Confirm the capacity required by the customer.
If the required capacity is 320 kW, the flow rate is 459 L/min at ∆t =10°C. Therefore, ∆t = 10°C cannot
be addressed. The minimum flow rate that would allow the chiller to address ∆t = 10°C is 509 L/min.
• If the quantity of holding water within the chilled water circuit is too low, the following problems will occur:
(1) The ON/OFF frequency of the chiller will increase, which shortens the machine life.
(2) Load fluctuation disrupts the temperature of the supply water. In a particular case, it may activate the anti-
freezing mechanism.
(3) A drastic decrease in the hot water temperature occurs during defrosting, which causes a cold draft by
the secondary unit (if using a heat pump).
Rationale behind the calculations of the minimum holding water quantity within chilled water circuit
<Basic theory for DAIKIN domestic model> (Note) Values may differ depending on the model.
118 × 0.225 × 860 – 1/2 × 118 × 0.225 × 860 = W × 2 × 60/4 Therefore, W = 380 L 400 L
(Value in the engineering material)
Even if the minimum holding water quantity in a circuit is secured, other measures may become necessary depending
on how the water-side system is set up.
Air If the chiller does not have a tank, it is either necessary to use a 3-way
conditioner
valve in one place in a circuit that allows for securing the holding water
quantity or set up a circuit that allows for constant circulation of a certain
quantity of water.
Air
conditioner
If the system has a header bypass only, it can easily cause
insufficient holding water quantity during a low load period.
pH (25°C) 6.5-8.2 6.0-8.0 6.8-8.0 6.8-8.0 6.8-8.0 7.0-8.0 7.0-8.0 7.0-8.0 7.0-8.0 { {
Iron (mg Fe/L) Up to 1.0 Up to 0.3 Up to 1.0 Up to 1.0 Up to 0.3 Up to 1.0 Up to 0.3 Up to 1.0 Up to 0.3 { {
Copper (mg Cu/L) Up to 0.3 Up to 0.1 Up to 1.0 Up to 1.0 Up to 0.1 Up to 1.0 Up to 0.1 Up to 1.0 Up to 0.1 {
Reference items
Ammonium ion (mg NH4+/L) Up to 1.0 Up to 0.1 Up to 1.0 Up to 1.0 Up to 0.1 Up to 1.0 Up to 0.1 Up to 1.0 Up to 0.1 {
Residual chlorine (mg Cl/L) Up to 0.3 Up to 0.3 Up to 0.3 Up to 0.3 Up to 0.3 Up to 0.25 Up to 0.3 Up to 0.1 Up to 0.3 {
Free carbon dioxide (mg CO2/L) Up to 4.0 Up to 4.0 Up to 4.0 Up to 4.0 Up to 4.0 Up to 0.4 Up to 4.0 Up to 0.4 Up to 4.0 {
Note: (1) The nomenclature of items, definition of terms and units of items are based on JIS K0101. Incidentally, the units and numerals in { } are conventional
figures inserted for reference purposes.
(2) The circle ({) in the table indicates factors affecting the corrosion or scale-generation tendency.
(3) If the temperature is high (over 40°C), the corrosion tendency is usually high. Especially, when iron material with no protective coating comes in direct
contact with water, it is preferable to take anti-corrosion measures such as the application of anti-corrosive agents or deaeration.
(4) In regard to a cooling water circuit that employs a closed type cooling tower, the water quality standards for the medium temperature water circuits
should be applied to closed circuit circulating water and its make-up water and the water quality standards for circulating type cooling water circuits
should be applied to sprinkling water and its make-up water.
(5) City water, industrial water and ground water should be used as source water to be supplied/replenished, and deionized water, miscellaneous water, softened
water and the like should be avoided.
(6) The 15 items listed above show typical factors of corrosion and scale problems.