EEE-1(b)
EEE-1(b)
Transformer
Introduction
Types and Construction of Transformers
The Ideal Transformer
Theory of Operation of Real Single-Phase Transformers
The Equivalent Circuit of a Transformer
The Per-Unit System of Measurements
Transformer Voltage Regulation and Efficiency
Three-Phase Transformer Connections
Introduction
A transformer is a static device that changes ac electric power at one
voltage level (primary) to ac electric power at another voltage level
(secondary) through the action of a magnetic field without the change
in frequency.
Transformer consists of
a core assemble of laminated ferromagnetic core
The transformer has not rotating part; hence it is often called a static
device. Although a transformer is not classified as an electrical
machine, the principles of its operation are fundamental for the
induction motor and synchronous machines. 2
Cont.…
It consists of one or more coils of wire wrapped around a common
ferromagnetic core.
The transformer winding connected to the power source is called the
primary winding or input winding.
The transformer winding connected to the loads is called the
secondary winding or output winding.
The primary and secondary windings are not connected electrically, but
coupled magnetically.
The transformer with three windings is called triple or three –winding
transformer. The third winding on the transformer is called the tertiary
winding. 3
Cont.…
4
Types and Construction of Transformers
All transformers have the following essential parts.
Electrical windings or coils
9
Cont.…
10
Cont.…
Power transformers used in power systems are sometimes referred as
follows:
A power transformer connected to the output of a generator and used to
step its voltage up to the transmission level (110 kV and higher) is called a
unit transformer.
A transformer used at a substation to step the voltage from the
transmission level down to the distribution level (2.3 … 34.5 kV) is called a
substation transformer.
A transformer converting the distribution voltage down to the final level
(110 V, 220 V, etc.) is called a distribution transformer.
In addition to power transformers, other types of transformers are used.
11
Working Principle of a Transformer
The basic principle on which the
transformer works is Faraday’s Law
of Electromagnetic Induction or
mutual induction between the two
coils.
The transformer consists of two
separate windings placed over the
laminated silicon steel core.
It works on the alternating current only
because an alternating flux is required for
mutual induction between the two
12
windings.
Ideal Transformer
An ideal transformer is a lossless device with an input winding and
an output winding. The idealizing assumptions made are:
i) The primary and secondary windings have zero resistance (no
ohmic power loss and no resistive voltage drop).
ii) There is no leakage flux so that all the flux is confide to the core and
links both windings.
iii) The core has infinite permeability so that zero magnetizing current is
needed to establish the requisite amount of flux in the core.
iv) The core loss (hysteresis and eddy current loss) is considered zero
13
Cont.…
We consider a lossless transformer
with an input (primary) winding
having 𝑁𝑝 turns and a secondary
winding of 𝑁𝑠 turns.
The relationship between the
voltage applied to the primary
winding 𝑉𝑝 (𝑡) and the voltage
produced on the secondary winding
𝑉𝑠 𝑡 is
𝑉𝑝 (𝑡) 𝑁𝑝
= =𝑎 Where a is the turns ration of the transformer.
𝑉𝑠 𝑡 𝑁𝑠 14
Cont.…
The relationship between the The phase angles of primary and
primary 𝑖𝑝 (𝑡) and secondary 𝑖𝑠 (𝑡) secondary voltages are the same.
currents is The phase angles of primary and
𝑁𝑝 𝑖𝑝 𝑡 = 𝑁𝑠 𝑖𝑠 (𝑡) secondary currents are the same
𝑖𝑝 (𝑡) 1 also.
=
𝑖𝑠 𝑡 𝑎
The turns ratio of the ideal
In the phasor notation transformer affects the magnitudes
𝑉𝑝 𝐼𝑃 1 of the voltages and currents, but not
= 𝑎 𝑎𝑛𝑑 =
𝑉𝑠 𝐼𝑆 𝑎 their angles.
15
Cont.…
One winding’s terminal is usually 2) If the primary current flows into
marked by a dot used to determine the dotted end of the primary
the polarity of voltages and winding, the secondary current will
currents. flow out of the dotted end of the
1) If the voltage is positive at the secondary winding.
dotted end of the primary winding at
some moment of time, the voltage at
the dotted end of the secondary
winding will also be positive at the
same time instance.
16
The current ratio on a transformer
The last approximation is valid for well-
designed unsaturated cores. Therefore:
𝑖𝑝 𝑁𝑠 1
𝑁𝑝 𝑖𝑝 = 𝑁𝑠 𝑖𝑠 ≈ =
𝑖𝑠 𝑁𝑝 𝑎
An ideal transformer (unlike the real one) can
be characterized as follows:
1.The core has no hysteresis or eddy currents. Magnetization
curve of an ideal
2.The magnetization curve is transformer
3.The leakage flux in the core is zero.
4.The resistance of the windings is zero.
17
Power in an ideal transformer
Assuming that 𝜃𝑝 and 𝜃𝑠 are the angles between voltages and currents on
the primary and secondary windings respectively, the power supplied to the
transformer by the primary circuit is:
𝑃𝑖𝑛 = 𝑉𝑝 𝐼𝑝 cos 𝜃𝑝
The power supplied to the output circuits is
𝑃𝑜𝑢𝑡 = 𝑉𝑠 𝐼𝑠 cos 𝜃𝑠
Since ideal transformers do not affect angles between voltages and currents:
𝜃𝑝 = 𝜃𝑠 = 𝜃
The primary and secondary windings of an ideal transformer have the same
power factor.
18
Cont.…
Since for an ideal transformer the following holds:
𝑉𝑝
𝑉𝑠 = 𝐼𝑠 = 𝑎𝐼𝑝
𝑎
Therefore:
𝑉𝑝
𝑃𝑜𝑢𝑡 = 𝑉𝑠 𝐼𝑠 cos 𝜃𝑠 = 𝑎𝐼𝑝 cos 𝜃 = 𝑉𝑃 𝐼𝑝 cos 𝜃 = 𝑃𝑖𝑛
𝑎
The output power of an ideal transformer equals to its input power – to be
expected since assumed no loss. Similarly, for reactive and apparent powers:
𝑄𝑜𝑢𝑡 = 𝑉𝑠 𝐼𝑠 sin 𝜃 = 𝑉𝑝 𝐼𝑝 sin 𝜃 = 𝑄𝑖𝑛
𝑆𝑜𝑢𝑡 = 𝑉𝑠 𝐼𝑠 = 𝑉𝑝 𝐼𝑝 = 𝑆𝑖𝑛
19
Impedance Transformation
The impedance of a device or an The apparent impedance of the
𝑉𝑝
element is defined as the ratio of primary circuit is: 𝑍𝐿 = ൗ𝐼𝑝
′
21
Analysis of Circuits Containing Ideal Transformers
A simple method to analyze a circuit containing an ideal transformer is by
replacing the portion of the circuit on one side of the transformer by an
equivalent circuit with the same terminal characteristics.
Next, we exclude the transformer from the circuit and solve it for voltages
and currents.
The solutions obtained for the portion of the circuit that was not replaced
will be the correct values of voltages and currents of the original circuit.
Then the turns ratio of the transformer can be used to determine the
voltages and currents on the other side of the transformer.
The process of replacing one side of a transformer by its equivalent at the other side's
voltage level is known as referring the first side of the transformer to the second side. 22
The voltage ratio across a real transformer
If the source voltage 𝑉𝑝 (𝑡) is applied to ∅𝑠 = ∅𝑚 + ∅𝐿𝑠
the primary winding, the average flux in
average secondary flux
the primary winding will be: mutual flux
1
∅𝑝 = න 𝑉𝑃 𝑡 𝑑𝑡
𝑁 The portion of the flux that
goes through one of the
A portion of the flux produced in the
transformer coils but not the
primary coil passes through the secondary
other one is called leakage
coil (mutual flux); the rest is lost (leakage
flux.
flux): ∅𝑝 = ∅𝑚 + ∅𝐿𝑝
average primary flux mutual flux
24
Cont.…
From the Faraday’s law, the primary coil’s voltage is:
𝑑∅𝑝 𝑑∅𝑚 𝑑∅𝐿𝑝
𝑉𝑝 𝑡 = 𝑁𝑝 = 𝑁𝑝 + 𝑁𝑝 = 𝑒𝑝 𝑡 + 𝑒𝐿𝑝 (𝑡)
𝑑𝑡 𝑑𝑡 𝑑𝑡
The secondary coil’s voltage is:
𝑑∅𝑠 𝑑∅𝑚 𝑑∅𝐿𝑠
𝑉𝑠 𝑡 = 𝑁𝑠 = 𝑁𝑠 + 𝑁𝑝 = 𝑒𝑠 𝑡 + 𝑒𝐿𝑠 (𝑡)
𝑑𝑡 𝑑𝑡 𝑑𝑡
The primary and secondary voltages due to the mutual flux are:
𝑑∅𝑚 𝑑∅𝑚
𝑒𝑝 𝑡 = 𝑁𝑝 𝑒𝑠 𝑡 = 𝑁𝑠
𝑑𝑡 𝑑𝑡
Combining the last two equations:
𝑒𝑝 (𝑡) 𝑑∅𝑚 𝑒𝑠 (𝑡)
= =
𝑁𝑝 𝑑𝑡 𝑁𝑠 25
Cont.…
Therefore:
𝑒𝑝 (𝑡) 𝑁𝑝
= =𝑎
𝑒𝑠 (𝑡) 𝑁𝑠
That is, the ratio(turn ratio)
For well-designed transformers:
∅𝑚 ≫ ∅𝐿𝑝 𝑎𝑛𝑑 ∅𝑚 ≫ ∅𝐿𝑠
Therefore, the following approximation normally holds:
𝑉𝑝 (𝑡) 𝑁𝑝
≈ ≈𝑎
𝑉𝑠 (𝑡) 𝑁𝑠
26
The magnetization current in a real transformer
Even when no load is connected to the secondary coil of the transformer, a
current will flow in the primary coil. This current consists of:
The magnetization current 𝑖𝑚 needed to produce the flux in the core;
The core-loss current 𝑖ℎ+𝑒 hysteresis and eddy current losses.
Ignoring flux leakage and assuming time-harmonic primary voltage, the
average flux is:
1 1 𝑉𝑚
ഥ=
∅ න 𝑉𝑝 𝑡 𝑑𝑡 = න 𝑉𝑚 cos 𝜔𝑡𝑑𝑡 = sin 𝜔𝑡 [𝑊𝑏]
𝑁𝑝 𝑁𝑝 𝜔𝑁𝑝
If the values of current are comparable to the flux they produce in the
core, it is possible to sketch a magnetization current. We observe:
27
Cont.…
1. The magnetization current in the transformer is not sinusoidal. The higher
frequency components in the magnetization current are due to magnetic
saturation in the transformer core.
2. Once the peak flux reaches the saturation point in the core, a small increase
in peak flux requires a very large increase in the peak magnetization current.
3. The fundamental component of the magnetization current lags the voltage
applied to the core by 90°.
4. The higher-frequency components in the magnetization current can be
quite large compared to the fundamental component. In general, the further a
transformer core is driven into saturation, the larger the harmonic
components will become. 28
Cont.…
Assuming a sinusoidal flux in the core, the eddy currents will be largest when flux passes zero.
29
Typical magnetization curve
Cont.…
The other component of the no- Core-loss current is:
load current in the transformer is 1. The core- loss current is nonlinear
the current required to supply because of the nonlinear effects of
power to make up the hysteresis hysteresis.
and eddy current losses in the core. 2. The fundamental component of
this is the core-loss current. the core- loss current is in phase with
the voltage applied to the core. Non
linear due to nonlinear effects of
hysteresis;
Core-loss current
30
Cont.…
The total no-load current in the
core is called the excitation current
of the transformer: It is just the
sum of the magnetization current
and the core- loss current in the
core:
𝑖𝑒𝑥 = 𝑖𝑚 + 𝑖ℎ+𝑒
31
The Current Ratio on a Transformer
If a load is connected to the Where 𝑅 is the reluctance of the
secondary coil, there will be a transformer core. For well-designed
current flowing through it. transformer cores, the reluctance is
A current flowing into the dotted very small if the core is not
end of a winding produces a saturated. Therefore:
positive magnetomotive force F: 𝐹𝑛𝑒𝑡 = 𝑁𝑝 𝑖𝑝 − 𝑁𝑠 𝑖𝑠 ≈ 0
𝐹𝑝 = 𝑁𝑝 𝑖𝑝 𝐹𝑠 = 𝑁𝑠 𝑖𝑠
The net magnetomotive force in
the core
𝐹𝑛𝑒𝑡 = 𝑁𝑝 𝑖𝑝 − 𝑁𝑠 𝑖𝑠 = ∅𝑅
32
The Equivalent Circuit of a Transformer
To model a real transformer accurately, we need to account for the
following losses:
Copper losses(𝐼 2 𝑅) – resistive heating losses in the windings:
Eddy current losses – resistive heating losses in the core: proportional to
the square of voltage applied to the transformer.
Hysteresis losses – energy needed to rearrange magnetic domains in the
core: nonlinear function of the voltage applied to the transformer.
Leakage flux – the fluxes ∅𝐿𝑝 and ∅𝐿𝑆 that escapes from the core and flux
that passes through one winding only. These escaped fluxes produce a self-
inductance in the primary and secondary coils.
33
The Exact Equivalent Circuit of a Real Transformer
Copper losses are modeled by the resistors 𝑅𝑝 and 𝑅𝑠 .
Leakage flux in a primary winding produces the voltage:
Since much of the leakage flux pass through air, and air has a constant
reluctance that is much higher than the core reluctance, the primary coil’s
leakage flux is:
𝑑∅𝐿𝑝
𝑒𝐿𝑝 𝑡 = 𝑁𝑝
𝑑𝑡
∅𝐿𝑝 = 𝑝𝑁𝑝 𝑖𝑝 where 𝑝 is permeance of flux path
𝑑 2 𝑑𝑖𝑝
Therefore: 𝑒𝐿𝑝 𝑡 = 𝑁𝑝 𝑝𝑁𝑝 𝑖𝑝 = 𝑁𝑝 𝑝
𝑑𝑡 𝑑𝑡
34
Cont.…
Recognizing that the self-inductance of the primary coil is
𝐿𝑝 = 𝑁𝑝 2 𝑝
The induced voltages in the primary coil and secondary coil are:
𝑑𝑖𝑝 𝑑𝑖𝑠
𝑒𝐿𝑝 𝑡 = 𝐿𝑝 𝑒𝐿𝑠 𝑡 = 𝐿𝑠
𝑑𝑡 𝑑𝑡
The leakage flux can be modeled by primary and secondary inductors.
The magnetization current can be modeled by a reactance 𝑋𝑀 connected
across the primary voltage source.
The core-loss current can be modeled by a resistance 𝑅𝐶 connected across
the primary voltage source.
Both currents are nonlinear; therefore, 𝑋𝑀 and 𝑅𝐶 are just approximations.
35
Cont.…
However, the exact circuit
is not very practical.
Therefore, the equivalent
circuit is usually referred
to the primary side or the
secondary side of the
transformer.
The exact equivalent circuit of real transformer
36
Cont.…
a) b)
39
c) d)
Determining the values of components
The open-circuit test
Full line voltage is applied to the
primary side of the transformer. The
input voltage, current, and power are
measured.
From this information, the power factor
of the input current and the magnitude
and the angle of the excitation
impedance can be determined. The susceptance of the
To evaluate 𝑅𝐶 and 𝑋𝑀 , we determine magnetizing inductor is:
the conductance of the core-loss 1
1 BM =
resistor is: 𝐺𝐶 = XM
𝑅𝐶 40
Cont.…
Since both elements are in parallel, their admittances add. Therefore, the
total excitation admittance is:
1 1
𝑌𝐸 = 𝐺𝐶 − 𝑗𝐵𝑀 = −𝑗
𝑅𝐶 𝑋𝑀
The magnitude of the excitation admittance in the open-circuit test is:
𝐼𝑜𝑐
𝑌𝐸 =
𝑉𝑜𝑐
The angle of the admittance in the open-circuit test can be found from the
circuit power factor (PF):
𝑃𝑜𝑐
cos 𝜃 = 𝑃𝐹 =
𝑉𝑜𝑐 𝐼𝑜𝑐
41
Cont.…
In real transformers, the power factor is always lagging, so the angle of the
current always lags the angle of the voltage by 𝜃 degrees. The admittance is:
𝐼𝑜𝑐 𝐼𝑜𝑐
𝑌𝐸 = < −𝜃 = < − cos −1 𝑃𝐹
𝑉𝑜𝑐 𝑉𝑜𝑐
The power-factor angle (𝜃) is given by
𝑃𝑜𝑐
𝜃= cos−1
𝑉𝑜𝑐 𝐼𝑜𝑐
Therefore, it is possible to determine values of 𝑅𝐶 and 𝑋𝑀 in the open-
circuit test.
42
The short-circuit test.
Fairly low input voltage is applied to the primary
side of the transformer. This voltage is adjusted
until the current in the secondary winding equals
to its rated value.
The input voltage, current, and power are again
measured.
Since the input voltage is low, the current
flowing through the excitation branch is The power factor of the
negligible; therefore, all the voltage drop in the current is given by:
transformer is due to the series elements in the Psc
PF = cos θ = (Lagging)
circuit. The magnitude of the series impedance Vsc Isc
referred to the primary side of the transformer
𝑉
is: 𝑍𝑆𝐶 = 𝑆𝑐 43
𝐼𝑆𝑐
Cont.…
𝑉𝑠𝑐 <0° 𝑉𝑠𝑐
Therefore: 𝑍𝑆𝐸 =
𝐼𝑠𝑐 <−𝜃°
=
𝐼𝑠𝑐
< 𝜃°
50
Cont.…
Considering the diagram referred
to the secondary side and by
applying the Kirchhoff ’s voltage
law, the primary voltage is:
𝑉𝑝
= 𝑉𝑠 + 𝑅𝑒𝑞 𝐼𝑠 + 𝑗𝑋𝑒𝑞 𝐼𝑠
𝑎
A transformer phasor diagram is a
graphical representation of this
equation.
51
Cont.…
A transformer operating at a
lagging power factor. It is seen
that 𝑉𝑝 Τ𝑎 > 𝑉𝑠 , 𝑉𝑅 > 0
A transformer operating at a unity
power factor. It is seen that 𝑉𝑅 > 0
A transformer operating at a
leading power factor. If the
secondary current is leading, the
secondary voltage can be higher
than the referred primary voltage;
𝑉𝑅 < 0. 52
Derivation of the approximate equation for 𝑽𝑷 Τ𝒂
For lagging loads the vertical component of 𝑅𝑒𝑞 and 𝑋𝑒𝑞 will partially
cancel each other. Due to that the angle of 𝑉𝑝 Τ𝑎 will be very small, hence
we can assume that 𝑉𝑝 Τ𝑎 is horizontal. Therefore the approximation will be
53
The Transformer Efficiency
The efficiency of a transformer is defined as:
𝑃𝑜𝑢𝑡 𝑃𝑜𝑢𝑡
𝜂= × 100% = × 100%
𝑃𝑖𝑛 𝑃𝑜𝑢𝑡 + 𝑃𝑙𝑜𝑠𝑠
Note: the same equation describes the efficiency of motors and generators.
Considering the transformer equivalent circuit, we notice three types of
losses:
Copper (𝐼 2 𝑅) losses – are accounted for by the series resistance
Hysteresis losses – are accounted for by the resistor 𝑅𝐶 .
Eddy current losses – are accounted for by the resistor 𝑅𝐶 .
54
Cont.…
Since the output power is
𝑃𝑜𝑢𝑡 = 𝑉𝑠 𝐼𝑠 cos 𝜃𝑠
The efficiency of the transformer can be expressed by:
𝑉𝑠 𝐼𝑠 cos 𝜃
𝜂= × 100%
𝑃𝑐𝑢 +𝑃𝑐𝑜𝑟𝑒 +𝑉𝑠 𝐼𝑠 cos 𝜃
Example?
55
Transformer taps and voltage regulation
Taps allow adjustment of the transformer in the field to accommodate for
local voltage variations.
Sometimes, transformers are used on a power line, whose voltage varies
widely with the load (due to high line impedance, for instance). Normal
loads need fairly constant input voltage though…
One possible solution to this problem is to use a special transformer called
a tap changing under load (TCUL) transformer or voltage regulator. TCUL
is a transformer with the ability to change taps while power is connected to
it. A voltage regulator is a TCUL with build-in voltage sensing circuitry that
automatically changes taps to keep the system voltage constant.
These “self-adjusting” transformers are very common in modern power systems. 56
The Autotransformer
Sometimes, it is desirable to change the voltage by a small amount (for
instance, when the consumer is far away from the generator and it is needed
to raise the voltage to compensate for voltage drops).
In such situations, it would be expensive to wind a transformer with two
windings of approximately equal number of turns. An autotransformer (a
transformer with only one winding) is used instead.
Diagrams of step-up and step-down autotransformers are shown below:
Output (up) or input (down) voltage is a sum of voltages across common
and series windings.
57
Cont.…
Series
winding
Series winding
60
The apparent power advantage of Autotransformers
Not all the power traveling from the primary to the secondary winding of the
autotransformer goes through the windings. As a result, an autotransformer can handle
much power than the conventional transformer (with the same windings).
Considering a step-up autotransformer, the apparent input and output powers are:
𝑆𝑖𝑛 = 𝑉𝐿 𝐼𝐿 𝑆𝑜𝑢𝑡 = 𝑉𝐻 𝐼𝐻
It is easy show that 𝑆𝑖𝑛 = 𝑆𝑜𝑢𝑡 = 𝑆𝐼𝑂
Where 𝑆𝐼𝑂 is the input and output apparent powers of the autotransformer.
However, the apparent power in the autotransformer’s winding is
𝑆𝑊 = 𝑉𝑐 𝐼𝐶 = 𝑉𝑆𝐸 𝐼𝑆𝐸
NC
SW = VL IL − IH = VL IL − VL IH = VL IL − VL IL
NSE +NC
(NSE + NC ) − NC NSE 61
= VL IL = SIO
NSE + NC NSE + NC
Cont.…
Therefore, the ratio of the apparent power in the primary and secondary of
the autotransformer to the apparent power actually traveling through its
windings is
SIO NSE + NC
=
SW NSE
The last equation described the apparent power rating advantage of an
autotransformer over a conventional transformer.
𝑆𝑊 is the apparent power actually passing through the windings. The rest
passes from primary to secondary parts without being coupled through the
windings.
Note that the smaller the series winding, the greater the advantage! 62
Cont.…
For example, a 5 MVA autotransformer that connects a 110 kV system to a
138 kV system would have a turns ratio (common to series) 110:28. Such an
autotransformer would actually have windings rated at:
𝑁𝑆𝐸 28
𝑆𝑊 = 𝑆𝐼𝑂 = 5. = 1.015 MVA
𝑁𝑆𝐸 +𝑁𝐶 28+110
Therefore, the autotransformer would have windings rated at slightly over 1
MVA instead of 5 MVA, which makes is 5 times smaller and, therefore,
considerably less expensive.
However, the construction of autotransformers is usually slightly different.
In particular, the insulation on the smaller coil (the series winding) of the
autotransformer is made as strong as the insulation on the larger coil 63
64
Three Phase transformers
The majority of the power generation/distribution systems in the world are
3-phase systems. Transformers for 3-phase circuits can be constructed in
two ways:
Connect 3 single phase transformers
Three sets of windings wrapped around a common core.
A single three-phase transformer is lighter, smaller, cheaper, and slightly
more efficient, but using three separate single-phase transformers has the
advantage that each unit in the bank could be replaced individually in the
event of trouble.
65
Cont.…
70
2. Y- ∆ Connection
The primary voltage on each phase
of the transformer is
𝑉𝐿𝑃
𝑉∅𝑃 =
√3
The secondary phase voltage is
𝑉𝐿𝑆 = 𝑉∅𝑆
The overall voltage ratio is
𝑉𝐿𝑃 √3𝑉∅𝑃
= = √3𝑎
𝑉𝐿𝑆 𝑉∅𝑆
71
Cont.…
The Y- ∆ connection has no problem with third harmonic components due
to circulating currents in ∆. It is also more stable to unbalanced loads since
the ∆ partially redistributes any imbalance that occurs.
One problem associated with this connection is that the secondary voltage
is shifted by 30° with respect to the primary voltage. This can cause
problems when paralleling 3-phase transformers since transformers
secondary voltages must be in-phase to be paralleled. Therefore, we must
pay attention to these shifts.
In the U.S., it is common to make the secondary voltage to lag the primary
voltage. The connection shown in the previous slide will do it.
72
3. -Y Connection
The primary voltage on each phase
of the transformer is
𝑉∅𝑃 = 𝑉𝐿𝑃
The secondary phase voltage is
𝑉𝐿𝑆 = √3𝑉∅𝑆
The overall voltage ratio is
𝑉𝐿𝑃 𝑉∅𝑃 𝑎
= =
𝑉𝐿𝑆 √3𝑉∅𝑆 √3
73
4. - Connection
The primary voltage on each phase
of the transformer is
𝑉∅𝑃 = 𝑉𝐿𝑃
The secondary phase voltage is
𝑉𝐿𝑆 = 𝑉∅𝑆
The overall voltage ratio is
𝑉𝐿𝑃 𝑉∅𝑃
= =𝑎
𝑉𝐿𝑆 𝑉∅𝑆
74
3-phase transformer: per-unit system
The per-unit system applies to the 3-phase transformers as well as to single-
phase transformers. If the total base VA value of the transformer bank is
𝑆𝑏𝑎𝑠𝑒 , the base VA value of one of the transformers will be
𝑆𝑏𝑎𝑠𝑒
𝑆𝑙∅,𝑏𝑎𝑠𝑒 =
3
Therefore, the base phase current and impedance of the transformer are
𝑆𝑙∅,𝑏𝑎𝑠𝑒 𝑆𝑏𝑎𝑠𝑒
𝐼∅,𝑏𝑎𝑠𝑒 = =
𝑉∅,𝑏𝑎𝑠𝑒 3𝑉∅𝑏𝑎𝑠𝑒
(𝑉∅,𝑏𝑎𝑠𝑒 )2 3(𝑉∅,𝑏𝑎𝑠𝑒 )2
𝑍𝑏𝑎𝑠𝑒 = =
𝑆1∅,𝑏𝑎𝑠𝑒 𝑆𝑏𝑎𝑠𝑒
75
Cont.…
The line quantities on 3-phase transformer banks can also be represented in
per-unit system. If the windings are in :
𝑉𝐿,𝑏𝑎𝑠𝑒 = 𝑉∅,𝑏𝑎𝑠𝑒
If the windings are in Y:
𝑉𝐿,𝑏𝑎𝑠𝑒 = √3𝑉∅,𝑏𝑎𝑠𝑒
And the base line current in a 3-phase transformer bank is
𝑆𝑏𝑎𝑠𝑒
𝐼𝐿,𝑏𝑎𝑠𝑒 =
√3𝑉𝐿,𝑏𝑎𝑠𝑒
The application of the per-unit system to 3-phase transformer problems is
similar to its application in single-phase situations. The voltage regulation
76
77
Transformer ratings: Voltage and Frequency
Transformer ratings: Voltage and
Frequency
If a steady-state voltage
Magnetization current
Fig. The effect of the peak flux in a
transformer core upon the required
magnetization current
79
Transformer ratings: Voltage and Frequency
Therefore, the maximum applied voltage (and thus the rated voltage) is set
by the maximum acceptable magnetization current in the core.
We notice that the maximum flux is also related to the frequency:
𝑉𝑚𝑎𝑥
∅𝑚𝑎𝑥 =
𝜔𝑁𝑃
Therefore, to maintain the same maximum flux, a change in frequency (say,
50 Hz instead of 60 Hz) must be accompanied by the corresponding
correction in the maximum allowed voltage. This reduction in applied
voltage with frequency is called derating. As a result, a 50 Hz transformer
may be operated at a 20% higher voltage on 60 Hz if this would not cause
insulation damage. 80
Transformer ratings: Apparent Power
The apparent power rating sets (together with the voltage rating) the
current through the windings. The current determines the 𝑖 2 𝑅 losses and,
therefore, the heating of the coils. Remember, overheating shortens the life
of transformer’s insulation!
In addition to apparent power rating for the transformer itself, additional
(higher) rating(s) may be specified if a forced cooling is used. Under any
circumstances, the temperature of the windings must be limited.
Note, that if the transformer’s voltage is reduced (for instance, the
transformer is working at a lower frequency), the apparent power rating
must be reduced by an equal amount to maintain the constant current.
81
Transformer ratings: Current inrush
Assuming that the following voltage is applied to the transformer at the
moment it is connected to the line:
𝑣 𝑡 = 𝑉𝑀 sin(𝜔𝑡 + 𝜃)
The maximum flux reached on the first half-cycle depends on the phase of
the voltage at the instant the voltage is applied. If the initial voltage is
𝑣 𝑡 = 𝑉𝑀 sin(𝜔𝑡 + 𝜃) = 𝑉𝑀 cos 𝜔𝑡
and the initial flux in the core is zero, the maximum flux during the first
half-cycle is equals to the maximum steady-state flux (which is ok):
𝑉𝑀
∅𝑚𝑎𝑥 =
𝜔𝑁𝑃
However, if the voltage’s initial phase is zero, i.e. 82
𝑣 𝑡 = 𝑉𝑀 sin(𝜔𝑡)
Cont.…
The maximum flux during the first Doubling the maximum flux in the core
half-cycle will be can bring the core in a saturation and,
𝜋Τ
𝜔
therefore, may result in a huge
1 magnetization current!
∅𝑚𝑎𝑥 = න 𝑉𝑀 sin 𝜔𝑡 𝑑𝑡
𝑁𝑃 Normally, the voltage phase angle
0
𝑉𝑀 cannot be controlled. As a result, a large
= cos 𝜔𝑡 inrush current is possible during the first
𝜔𝑁𝑃
2𝑉𝑀 several cycles after the transformer is
= turned ON.
𝜔𝑁𝑃 The transformer and the power system
Which is twice higher than a normal must be able to handle these currents.
steady-state flux!
83
Cont.…
87
88
INTRODUCTION
If one transformer fails, the continuity of supply can be maintained through other
transformers.
when the load on the substation becomes more than the capacity of the existing
transformers, another transformer can be added in parallel.
Any transformer can be taken out of the circuit for repair/routine maintenance
without interrupting supply to the consumers.
Some more reasons that necessitate parallel operation of transformers are as follows.
The power demand might have increased over a time necessitating augmentation of
the capacity. More transformers connected in parallel will then increase the capacity.
To ensure improved reliability. Even if one of the transformers gets into a fault or is
taken out for maintenance.
To reduce the spare capacity. If many smaller size transformers are used one machine
can be used as spare. If only one large machine is feeding the load, a spare of similar
rating has to be available. The problem of spares becomes more acute with fewer
machines in service at a location.
In order that the transformers work satisfactorily in parallel, the following conditions
should be satisfied:
1. Primary windings of the transformers should be suitable for the supply system
voltage and frequency.
3. The voltage ratings and voltage ratios of the transformers should be the same. i.e.
Same transformation ratio.
Figure (ii) shows the wrong method of connecting two single-phase transformers is parallel.
Here the two secondaries are so connected that their E.M.F.s 𝐸𝐴 and 𝐸𝐵 are additive.
This may lead to short-circuit conditions and a very large circulating current will flow in the
loop formed by the two secondaries. Such a condition may damage the transformers
unless they are protected by fuses and circuit breakers
Condition (3) - Same Voltage Rating and Voltage Ratio
This condition is desirable for the satisfactory parallel operation of transformers. If this
condition is not met, the secondary E.M.F.s will not be equal and there will be circulating
current in the loop formed by the secondaries. This will result in the unsatisfactory
parallel operation of transformers. Let us illustrate this point. Consider two single-phase
transformer A and B operating in parallel as shown in Figure below. Let 𝐸𝐴 and 𝐸𝐵 be their
no-load secondary voltages and 𝑍𝐴 and 𝑍𝐵 be their impedances referred to the
secondary. Then at no-load, the circulating current in the loop formed by the secondaries
is
Condition (3) - Same Voltage Rating and Voltage Ratio ---continued
• Even a small difference in the induced secondary voltages can cause a large circulating
current in the secondary loop because impedances of the transformers are small.
•This secondary circulating current will cause current to be drawn from the supply by the
primary of each transformer.
•These currents will cause copper losses in both primary and secondary. This creates
heating with no useful output. When load is connected to the system, this circulating
current will tend to produce unequal loading conditions i.e., the transformers will not
share the load according to their kVA ratings. It is because the circulating current will
tend to make the terminal voltages of the same value for both transformers.
-Therefore, transformer with smaller voltage ratio will tend to carry more than its
proper share of load. Thus, one transformer would tend to become overloaded than
the other and the system could not be loaded to the summation of
transformer ratings without overloading one transformer.
Condition (4) - Equal Percentage Impedance
Sometimes this condition is not fulfilled by the design of the transformers. In that case,
it can be corrected by inserting proper amount of resistance or reactance or both in
series with either primary or secondary circuits of the transformers where the
impedance is below the value required to fulfil this condition.
The percentage impedance of a transformer is the volt drop on full load due to the
winding resistance and leakage reactance expressed as a percentage of the rated
voltage.
It is also the percentage of the normal terminal voltage required to circulate full-load
current under short circuit conditions
Condition (5) - Same resistance/reactance (X/R) Ratio
If the resistance/reactance (X/R) ratios of the two transformers are not equal, the
power factor of the load supplied by the transformers will not be equal. In other
words, one transformer will be operating with a higher and the other with a
lower power factor than that of the load.
Advantages of Transformer Parallel Operation:
1) Maximize electrical system efficiency: Generally electrical power transformer gives the
maximum efficiency at full load. If we run numbers of transformers in parallel, we can switch
on only those transformers which will give the total demand by running nearer to its full load
rating for that time. When load increases, we can switch one by one transformer connected
in parallel to fulfill the total demand. In this way we can run the system with maximum
efficiency.
2) Maximize electrical system availability: If numbers of transformers run in parallel, we
can shutdown any one of them for maintenance purpose. Other parallel transformers in
system will serve the load without total interruption of power.
3) Maximize power system reliability: if any one of the transformers run in parallel, is
tripped due to fault of other parallel transformers is the system will share the load, hence
power supply may not be interrupted if the shared loads do not make other transformers
over loaded.
4) Maximize electrical system flexibility: There is always a chance of increasing or
decreasing future demand of power system, so options should be there to add or drop
parallel transformer.
Disadvantages of Transformer Parallel Operation:
The risk of circulating currents running from one transformer to another Transformer.
Circulating currents that diminish load capability and increased losses.
All the conditions which apply to the parallel operation of single-phase transformers
also apply to the parallel running of 3-phase transformers but with the following
additions :
The voltage ratio must refer to the terminal voltage of primary and secondary. It is
obvious that this ratio may not be equal to the ratio of the number of turns per
phase. For example, if V1, V2 are the primary and secondary terminal voltages, then
𝑽𝟏 𝑽𝟐
for Y/Δ connection, the turn ratio is 𝑽𝟐 /( )= 𝟑 .
𝟑 𝑽𝟏
The phase displacement between primary and secondary voltages must be the same
for all transformers which are to be connected for parallel operation.
All three transformers in the 3-phase transformer bank will be of the same
construction either core or shell.