HPW-65 T5
Powered by:
PERKINS 1104C 44TG3
60 kVA at 50 Hz
Directive 97/68/EC (Stage II)
Generating Set Performance 50 Hz
SERVICE P.R.P Standby
(1) (2)
Rated output kVA 60 63
Active power output * kW 48 50
Rated speed r.p.m. 1.500
Standard Voltage V 400 / 230
Voltage available V 230 / 132 - 230
Performance data refers to Standard Reference Conditions of ISO 8528 : + 25 °C , 100 m ALT, relative humidity 30 %
During running-in period the output increases by approx. 5 % which is taken into consideration at delivery.
Power reduction acc. to DIN ISO 3046. Standard values: Above 100 m ALT approx. 1 % per 100 m. Above 25 °C (77 °F) approx. 4 % per 10 °C (50 °F).
* Considering cos phi= 0,8
Prime Mover Performance 1.500 r.p.m.
SERVICE P.R.P Standby
(1) (2)
Rated output kW 56 62
Manufacturer Perkins
Engine model 1104C 44TG3
4 stroke Diesel Engine - Injection type DIRECT
Aspiration type TURBOCHARGED
Cylinders, number and arrangement 4-L
Bore x stroke mm 105 x 127
Total displacement L 4,4
Cooling system WATER
Lube oil specifications SAE 15 W 40
Compression ratio 18.23 : 1
Specific fuel consumption 100% (1.500 P.R.P) L/h 15,3
Specific oil consumption (at full load) % 0,15 del consumo de combustible
Lube oil maximum capacity L 8,5
Total coolant capacity L 12,6
Speed governor Type mechanical
Air filter Type DRY
(1) Prime Power (P.R.P.) - ISO 8528: prime power is the maximum power available during a variable power sequence, which may be run for an unlimited number of hours per year,
between stated maintenance intervals. The permissible average power output during a 24 hours period shall not exceed 80% of the prime power. 10% overload available for governing
purposes only.
(2) Max Stand-by power (ISO 3046 Fuel Stop power): power available for use at variable loads for limited annual time (500h), within the following limits of maximum operating time: 100%
loads 25 h per year - 90% loads 200 h per year No overload available. Applicable in case of failure of the main in areas of reliable electrical network.
Synchronous Generator *
Poles Nº 4
Winding connections (standard) Star - serie
1/2
Frame mounting SAE 3 - 11
Insulation class H
Enclosure (according to IEC-34-5) IP 23
Phases 3+N
Voltage regulator A.V.R (Electronic)
Steady voltage precision within ± 1,5% from no load to full loading with cosf=0,8÷1
*Alternator used by HIMOINSA Gensets meet the requirements of following Standard: BS5000, VDE 0530, NEMA MG1-32, IEC34, CSA C22.2-100, AS1359.
Directive 97/68/EC (Stage II) HPW 65 T5 - 60 kVA at 50 Hz
Generating Set Installation Data 1.500 r.p.m.
EXHAUST SYSTEM
ºC 535
Max. exhaust temperature at full load
ºF 995
Exhaust gas flow m3/min 10,9
Engine coolant flow 35 kPa restriction l/min 142
Maximum allowed back pressure mmca N.D.
AIR REQUIREMENT
Air requirement for combustion m3/min 4,32
at 100% load / rated speed ft3/min 152,56
ELECTRIC STARTING SYSTEM
kW 3
Starting motor output CV 4,08
Minimum recommended battery capacity Ah 65
Auxiliary voltage Vcc. 12V
LIQUID CAPACITY
Lube oil system including sump, filters, etc. L 12,6
FUEL TANK CAPACITY
Open Skid Genset LL 145
Soundproofed LL 175
Generating Set transport data
Pub. I_HPW-65 T5 02/08- Himoinsa reserves the right to modify any characteristic without prior notice.
WEIGHT AND DIMENSIONS OPEN SKID GENSET
Length m - ft 1,88 - 6,16
Weights and dimensions based on products standars and sec / Ilustration may include optional equipment.
Width m - ft 0,75 - 2,46
Height m - ft 1,42 - 4,67
Shipping volume seaworthy (Standard supplier) m3 - ft3 2,00 - 70,76
Dry weight (with standard accessories) kg - lb 925 - 2.035
WEIGHT AND DIMENSIONS SOUNDPROOFED GENSET
Length m - ft 2,75 - 9,02
Width m - ft 1,1 - 3,60
Height m - ft 1,5 - 4,92
Shipping volume seaworthy (Standard supplier) m3 - ft3 4,53 - 159,76
Dry weight (with standard accessories) kg - lb 1.485 - 3.267