3.2, Transformers 2 - Copy
3.2, Transformers 2 - Copy
3.2.TRANSFORMERS
2
Learning Objectives
1. Describe transformer equivalent circuit and phasor
diagram
2. Explain the open circuit and short circuit tests
3. Describe the losses which occur in transformer
4. Calculate transformer efficiency and regulation
5. Describe the construction of Autotransformer.
3
Practical Transformer
Certain assumptions made for an ideal
transformer are not valid in a practical
transformer.
In practical transformer :
(i) the windings have resistance
(ii) core has finite permeability
(iii) there is leakage flux
(iv) efficiency is not 100% due to losses
4
Complete circuit model (equivalent circuit)
of a real transformer
7
Referred values
Power consumed by R2’ when carrying the primary
current should be equal to the power consumed by
R2 due to secondary current
I R I R2
1
2 '
2
2
2
2
I2
R
I
'
2 R2
1
R2 k 2 Since:
8
Referred values
Similarly , let X2’ the reactance of the secondary
winding referred to the primary side.
For X2’ to produce the same effect in the primary
side as X2 in the secondary side, each must
absorb the same reactive voltamperes (VAr)
I12 X 2' I 22 X 2
2
I2
X
I
'
2 X2 Since:
1
X 2k 2
9
Equivalent values referred to primary
2
V
Re1 R1 R2 ' R1 R2 1 R1 R2 k 2
V2
2
V
X e1 X 1 X 2 ' X 1 X 2 1 X 1 X 2k 2
V2
2
V
Z e1 Z1 Z 2' Z1 Z 2 1 Z1 Z 2 k 2
V2
Where magnitude of Ze
In complex notation:
Ze = Re+ jXe Ze Re2 X e2
Re Ze cose X e Z e sin e
Xe
tan e
Re
10
Equivalent values referred to secondary
The equivalent values referred to the secondary
can also be found in the same manner.
If Re2 , Xe2 and Ze2 denote the equivalent
resistance, equivalent reactance and equivalent
impedance respectively referred to the
secondary, then: 2
V2 R1
Re 2 R2 R1' R2 R1
V
R2 2
1 k
2
V2 Z1
Z e 2 Z 2 Z1' Z 2 Z1
V
Z 2 2
1 k
2
V2 X1
X e 2 X 2 X 1' X 2 X 1
V
X 2 2
1 k
11
Equivalent circuit of transformer
Approximate equivalent circuit referred to the primary can be
derived from complete equivalent circuit as follows:
(i) referred to primary as the square of the transformation ratio:
R2 k2 R2
X2 k2 X2
ZL k2 ZL
13
The exact equivalent circuit of a real
transformer
The transformer’s equivalent
circuit (a)
(a) (b)
Referred to Referred to
the primary the
side. secondary
side.
(c) (d)
A F
O
D
18
Voltage regulation at lagging power
factor
Vs is taken as the reference phasor
Is lags behind V2 by angle Φ
IsReq is in phase with IS and IsXeq leads Is by 900
Es (= ) is the phasor sum of VS, IsReq and IsXeq
19
Voltage regulation at lagging
power factor
It follows:
20
Voltage regulation at lagging
power factor
EsVs Vs I s Re coss X e sins Vs
Per _ unit _VR
Vs Vs
21
Voltage regulation for different power
factor loads
For lagging loads, VP / a > VS so the voltage regulation with lagging loads
is > 0.
22
Voltage regulation for different power
factor loads
With a leading power factor, VS is higher than the referred VP so VR < 0
23
Transformer Tests
The transformer tests are performed to
determine the circuit constants, efficiency
and voltage regulation
We distinguish between two typical tests:
- Open Circuit Test (O.C test / No load test)
- Short Circuit Test (S.C test/Impedance test)
These tests are economical and convenient
26
Open-circuit test
27
Short-circuit Test
31
Transformer losses
The transformer losses are classified into electrical
losses (copper losses) and Magnetic losses (Iron losses).
Copper losses occur in both the primary and secondary
windings.
Pcu I1 R1 I 2 R2
2 2
Produces HEAT.
Caused by resistance of windings.
Determine by Short Circuit Test
33
Core loss or iron loss
Independent of the load
Produces HEAT.
Determined by Open Circuit Test.
Eddy current loss is minimised by using
laminations.
Hysteresis loss minimised by using silicon
steel.
34
Behavior of magnetic losses and efficiency with loading
1.4
Cu Losses η%
1.2
Losses (W)
1.0
Fe Losses 97.00
0.8
0.6
η%
0.4
0.2
0.0 96.00
0 10 20 30 40 50 60 70 80 90 100 110
% Load
Power Power
In Out
Overcome Overcome
Some Power Copper
is used to: Iron
Losses Losses
36
Efficiency
Efficiency is normally expressed as a percentage:
Output Power
η% 100
Input Power
VS I S cos
x100%
PCu Pcore VS I S cos
37
All Day Efficiency
The primary of a distribution transformer is
connected to the line for 24 hours a day.
Thus the core losses occur for the whole day
whereas copper losses occur only when the
transformer is on load.
Distribution transformers operate well below the
rated power output for most of the time.
Performance of the distribution transformer is more
appropriately represented by all day efficiency.
The all-day efficiency of a transformer is defined as
the ratio of total energy output for a certain period to
the total energy input for the same period.
38
All day efficiency
The energy efficiency can be calculated for a specified
period.
When the energy efficiency is calculated for a 24 hours it
is called the all-day efficiency.
out put in watts
Ordinary commercial efficiency
input in watts
output in kWh
All day efficiency :all day ( for 24 hours)
Input in kWh
40