DISEÑO O Calculo Redes Agua Potable Bombeo

The document outlines the calculations for a potable water supply system for the Talambo project, including current and future population estimates, water consumption rates, and reservoir volume requirements. It details the pumping system specifications, including pipe diameters, pump power requirements, and distribution network parameters. The document also includes various technical data points necessary for the design and implementation of the water supply system.

Uploaded by

Avaluos Bim
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
12 views6 pages

DISEÑO O Calculo Redes Agua Potable Bombeo

The document outlines the calculations for a potable water supply system for the Talambo project, including current and future population estimates, water consumption rates, and reservoir volume requirements. It details the pumping system specifications, including pipe diameters, pump power requirements, and distribution network parameters. The document also includes various technical data points necessary for the design and implementation of the water supply system.

Uploaded by

Avaluos Bim
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 6

CALCULOS PARA REDES DE AGUA POTABLE

( Sistema por Bombeo )

1.- NOMBRE DEL PROYECTO AGUA POTABLE TALAMBO


2.- NUMERO DEL EXPEDIENTE 06990368
3.- OFICINA ZONAL TRUJILLO

A.- POBLACION ACTUAL 1150


B.- TASA DE CRECIMIENTO (%) 2.00
C.- PERIODO DE DISEÑO (AÑOS) 20
D.- POBLACION FUTURA 1610
Pf = Po * ( 1+ r*t/100 )
E.- DOTACION (LT/HAB/DIA) 80
F.- CONSUMO PROMEDIO ANUAL (LT/SEG)
Q = Pob.* Dot./86,400 1.491

G.- CONSUMO MAXIMO DIARIO (LT/SEG)


Qmd = 1.30 * Q 1.938
H.- CAUDAL DE LA FUENTE (LT/SEG)
I.- VOLUMEN DEL RESERVORIO (M3)
V = 0.30 * Qmd *86400/1000 50.23
A UTILIZAR : 50.00
J.- CONSUMO MAXIMO HORARIO (LT/SEG)
Qmh = 2.00 * Qmd = 2.60 Q 3.876

LINEA DE SUCCION E IMPULSION

CAUDAL DE BOMBEO (m3/seg.)


Qb = ( 24 / N ). Qmd 0.01163
N : N° de horas de bombeo = 4.00

LINEA DE IMPULSION
D = 1.3 (N/24)^(1/4). (Qb)^(1/2) = 0.090 m = 4.00 "
Diámetro asumido 4.00 "

LINEA DE SUCCION
Diámetro asumido "
(Se recomienda un diámetro comercial mayor al de Impulsión)

POTENCIA DE LA BOMBA

Altura de Succión : Hs = 25.00 m Altura de Impulsión : Hi =


Long. tubo Succión : Ls = 30.00 m Long. tubo Impulsión: Li =
Velocidad : V = Qb / A = 1.43 m/seg.
Pérdidas de carga : hf = f.(L/D).(V^2/2g) = 43.96 m
Altura Dinámica Total : HDT = Hs + Hi + hf = 93.96 m

POTENCIA TEORICA DE LA BOMBA :


P = ( 1000 . Qb . HDT ) / ( 75 . E ) = 24.28 H.P.

Potencia Instalada : Pi = P + dP = P + 0.5 P = 36.42 H.P.

Nota :
En la Línea de Succión utilizará tubería PVC. SAP. Cl-10 0.00 "
En la Línea de Impulsión se utilizará tubería F°G° 4.00 "
Se recomienda utilizar una Motobomba de Potencia 30.00 H.P.

RED DE DISTRIBUCION
( Red Abierta )

Qmh : 3.876 lt/seg.


N° Piletas : 9.00 und.
Qunit. : 0.431 lt/seg.

ELEMENTO NIVEL DINAMICO


LONGITUD
CAUDAL
(Km) DEL TRAMO
PENDIENTEDIAMETRO
S (")
DIAM.COMEVELOCIDAD
Reserv. 111.70
Pto. A 101.85 0.036 0.915 273.61 0.89 2.00 0.45
Pto. B 100.90 0.070 0.915 151.54 1.01 2.00 0.45
Pto. C 105.98 0.102 0.915 50.53 1.26 2.00 0.45
Pto. D 104.29 0.076 0.915 82.88 1.14 2.00 0.45
Pto. E 105.14 0.103 0.915 48.96 1.27 2.00 0.45
Pto. F 103.10 0.091 0.915 71.78 1.17 2.00 0.45
Pto. G 105.30 0.086 0.915 44.72 1.29 2.00 0.45
Pto. H 102.79 0.105 0.915 56.16 1.23 2.00 0.45
Pto. I 101.52 0.052 0.915 127.03 1.04 2.00 0.45
Pto. J 101.34 0.042 0.814 154.94 0.96 2.00 0.40
Pto. K 101.28 0.043 0.712 148.53 0.92 1.50 0.62
Pto. L 101.12 0.024 0.610 248.35 0.78 1.50 0.54
Pto. M 101.91 0.051 0.509 96.56 0.88 1.50 0.45
Pto. N 100.68 0.025 0.407 231.23 0.68 1.50 0.36
Pto. O 100.67 0.047 0.305 120.63 0.69 1.50 0.27
Pto. P 101.87 0.060 0.203 72.27 0.66 1.00 0.40
Pto. Q 101.11 0.154 0.102 29.34 0.61 1.00 0.20
P. 9 101.21 0.020 0.102 200.10 0.41 1.00 0.20

Pto. I 101.52 #VALUE! #VALUE!


P. 1 101.55 0.010 0.102 629.75 0.33 0.75 0.36

Pto. J 101.34 #VALUE! #VALUE!


P. 2 101.37 0.013 0.102 484.37 0.34 0.75 0.36

Pto. K 101.28 #VALUE! #VALUE!


P. 3 101.24 0.025 0.102 233.62 0.40 0.75 0.36

Pto. L 101.12 #VALUE! #VALUE!


P. 4 101.11 0.013 0.102 440.35 0.35 0.75 0.36

Pto. M 101.91 #VALUE! #VALUE!


P. 5 100.98 0.026 0.102 210.80 0.41 0.75 0.36

Pto. N 100.68 #VALUE! #VALUE!


P. 6 101.65 0.012 0.102 390.80 0.36 0.75 0.36

Pto. O 100.67 #VALUE! #VALUE!


P. 7 100.62 0.009 0.102 620.67 0.33 0.75 0.36

Pto. P 101.87 #VALUE! #VALUE!


P. 8 101.80 0.025 0.102 153.11 0.44 0.75 0.36

Pto. Q 101.11 #VALUE! #VALUE!


P. 9 101.21 0.020 0.102 200.10 0.41 0.75 0.36

1.340
25.00 m
2100.00 m
Hf H. PIEZOM. PRESION
COTA PIEZ. SALIDA
111.70 111.70
0.19 111.51 9.66 111.51
0.37 111.13 10.23 111.13
0.55 110.59 4.61 110.59
0.41 110.18 5.89 110.18
0.55 109.63 4.49 109.63
0.49 109.15 6.05 109.15
0.46 108.69 3.39 108.69
0.56 108.13 5.34 108.13
0.28 107.85 6.33 107.85
0.18 107.67 6.33 107.67
0.59 107.08 5.80 107.08
0.25 106.83 5.71 106.83
0.37 106.46 4.55 106.46
0.12 106.34 5.66 106.34
0.13 106.21 5.54 106.21
0.58 105.63 3.76 105.63
0.42 105.21 4.10 105.21
0.05 105.16 3.95 105.16
#VALUE! ### #VALUE!
#VALUE! ### 107.85
0.11 107.74 6.19 107.74
#VALUE! ### #VALUE!
#VALUE! ### 107.67
0.14 107.52 6.15 107.52
#VALUE! ### #VALUE!
#VALUE! ### 107.08
0.27 106.81 5.57 106.81
#VALUE! ### #VALUE!
#VALUE! ### 106.83
0.14 106.69 5.58 106.69
#VALUE! ### #VALUE!
#VALUE! ### 106.46
0.28 106.18 5.20 106.18
#VALUE! ### #VALUE!
#VALUE! ### 106.34
0.13 106.21 4.56 106.21
#VALUE! ### #VALUE!
#VALUE! ### 106.21
0.10 106.11 5.49 106.11
#VALUE! ### #VALUE!
#VALUE! ### 105.63
0.27 105.35 3.55 105.35
#VALUE! ### #VALUE!
#VALUE! ### 105.21
0.22 104.99 3.78 104.99
#VALUE! ### #VALUE!