Xruhakxs-Wtc 1x 300rmc - 95 110kv Zn-tf-530 - Uk

The document provides a technical specification for the XRUHAKXS-WTC 1x300RMC/95 64/110(123)kV cable, detailing its construction, electrical and mechanical data, and application guidelines. It includes information on materials used, dimensions, resistance values, ampacity, and testing requirements. The cable is designed for laying in various environments and has specific temperature ratings for operation and short circuits.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
78 views3 pages

Xruhakxs-Wtc 1x 300rmc - 95 110kv Zn-tf-530 - Uk

The document provides a technical specification for the XRUHAKXS-WTC 1x300RMC/95 64/110(123)kV cable, detailing its construction, electrical and mechanical data, and application guidelines. It includes information on materials used, dimensions, resistance values, ampacity, and testing requirements. The cable is designed for laying in various environments and has specific temperature ratings for operation and short circuits.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Page 1 of 3

TECHNICAL SPECIFICATION
XRUHAKXS-WTC 1x300RMC/95 64/110(123)kV acc. to IEC 60840; ZN-TF-530
CONSTRUCTION (x) The picture is informative only
❑ Round, stranded watertight – not in scale
aluminum conductor. Class 2
❑ Extruded semi-conducting APPLICATION
conductor screen
❑ Laying in ground
❑ Insulation XLPE – dry cured
(wet or dry locations)
❑ Extruded semi-conducting
❑ Laying in air
insulation screen
❑ Laying in ducts
❑ Semi-conducting swelling tape
❑ Metallic screen:
Highest permissible conductor
copper wire screen and
copper equalizing tapes temperature
❑ Semi-conducting swelling tape
❑ Continuous operation 90C
❑ Longitudinal aluminum foil
❑ Overload 105C
❑ Sheath – black HDPE ST7 type
❑ Short circuit 250C
(duration max 5s)

Laying is possible without any special


MARKING measures at natural cable temperatures and
TF KABLE, product name, year of ambient temperature not lower than -20ºC,
manufacture, standard, meter marking with Tele-Fonika supervising

DESCRIPTION UNIT DETAILS


CONSTRUCTION DATA Uo/U/Um 64/110(123)kV
Conductor
❑ material Aluminum
❑ number of wires No 34
Nominal cross sectional area mm2 300
Conductor diameter and tolerance mm 20.0 -0,2+0,3
Min./Nom. thickness semi-conducting XLPE on conductor mm 0.6 / 1.0
Nominal insulation thickness XLPE mm 15.5
Insulation thickness: minimum at a point mm 13.95
Diameter over insulation – nominal mm 53.0 -0,6+0,4
Min./Nom. thickness semi-conducting XLPE on insulation mm 0.6 / 1.0
Thickness of semi-conducting swelling tape No x mm 2 x ~ 0.35
Metallic screen mm2 95
❑ Copper wires No x mm 60 x 1.44
❑ Copper equalizing tapes No x mm x mm 2 x 10 x 0.18
Mean diameter over metallic screen mm 58.5
Thickness of semi-conducting swelling tape No x mm 2 x ~ 0.35
Thickness of aluminum foil mm 0.2
Diameter over aluminum foil mm 60.3
Nominal outer sheath thickness / min mm 3.1 / 2.53
Approximate overall diameter
completed cable (D e) mm 66.6
Weight of complete cable (approx.) kg/km 4600
DELIVERY DATA
Diameter of wooden drum m 2.8 3.2
❑ type 28OP 32OS
Length per drum m 600 1000
Weight of heaviest reel, including cable kg 4100 6500

(x)
Diameters are calculated values and subject to manufacturing tolerances
Page 2 of 3

ELECTRICAL DATA at 50Hz


Maximum D.C. conductor resistance at 20C /km 0.1000
Maximum A.C. conductor resistance at 90C /km 0.1290
Maximum D.C. metallic screen resistance at 20C /km 0.188
0.133
Maximum D.C. aluminum foil resistance at 20C /km 0.680
Operating inductance
❑ trefoil formation mH/km 0.432
❑ flat formation (*) mH/km 0.617
Induction reactance
❑ trefoil formation /km 0.136
❑ flat formation (*) /km 0.194
Capacitance F/km 0.135 (+ 8 %)
Capacitance reactance k/km 23.39
Impedance
❑ trefoil formation /km 0.187
❑ flat formation (*) /km 0.233
Zero sequence reactance /km 0.084
Max. electric stress at conductor screen / (at insulation) kV/mm 6.55 / 2.45
Dielectric losses (tg = 0.001) – per phase W/m 0.175
Partial discharge test – at 1.5Uo pC ≤5
Charging current – per phase A/km 3.27
Charging power kVA/km 175
Earth fault current – per phase A/km 8.21
MECHANICAL DATA
Recommended min. bending radius for laying m 1.66
Recommended permissible bending radius at final
installation m 1.33
Maximum permissible pulling force: kN 9
SHORT CIRCUIT CURRENTS
Maximum permissible thermal short-circuit (IEC 60949)
Current for 1,0s
Phase conductor 90 → 250C kA 28.8
Metallic screen 80 → 350C kA 19.5
AMPACITY (**) – Bonding of the metallic screens single-point / both-ends
In earth
❑ flat formation (*) A 502 / 449
❑ trefoil formation A 475 / 459
In air (shaded)
❑ flat formation A 628 / 571
❑ trefoil formation A 560 / 547
TESTS
AC – test voltage – (2.5Uo, 30min) kV 160
Impulse voltage kV 550
Partial discharge test kV 96

Marking: TF-KABLE 5 XRUHAKXS-WTC 1x300RMC/95 64/110(123)kV IEC 60840 2020


(*)
Distance between cable axes laid in flat formation De+De mm (diameter of cable)
(**)
Current rating guideline (Calculated with CymCap 7.3 based on IEC Pub. 60287 and the following conditions)

Standard condition
❑ Ground temperature +20C
❑ Ground thermal resistivity 1.0 K·m/W
❑ Load factor 1.0
❑ Air temperature +35.0C

(x)
Diameters are calculated values and subject to manufacturing tolerances
Page 3 of 3
Standard working conditions
Cables in ground – single-point or cross-bonded

depth 1,0m
ampacity 502A

ampacity 575A

Date: 2020-02-11; Mp20003


Prepared by: Michał Pstrągowski

(x)
Diameters are calculated values and subject to manufacturing tolerances