PSG_UNIT_II
PSG_UNIT_II
Electromagnetic Relays
Unit – II ELECTROMAGNETIC RELAYS
• Operating principles of relays
• Electromagnetic Relays –
• Over current,
• Directional,
• Differential,
Relays
Construction
Time of Digital Numerical
& principle of Application Static relays
operation operation relays relays
Classification based on application
Functional Relay Types
Regardless of the principle involved ,relays are generally classified
according to the function they are called upon to perform in the
protection of electric power circuits.
• Instantaneous relays
Time of • Definite time lag relays
operation • Inverse time lag relays
• Inverse definite minimum time lag relays
Non Directional Overcurrent Relay
50%
200%
• The control torque is provided by the spiral spring. When current exceeds its preset value, the disc rotates and
moving contacts on spindle make the connection with trip circuit terminals. The angle through which the disc
rotates is between 0° to 360°. The travel of the moving contacts can be adjusted by adjusting the angle of
rotation of the disc.
• This gives the Non-directional Induction Overcurrent Relay any desired time setting which is indicated by
a pointer on a time setting dial. The dial is calibrated from 0 to 1. This does not give direct operating time but
it gives multiplier which can be used along with the time-plug setting multiplier curve to obtain the actual
operating time of the relay. The time-plug setting multiplier curve is provided by the manufacturer.
• Parts of the rotor in which rotor currents flow –
negligible self-inductance → rotor currents
Torque Production
(induced eddy currents) are in phase with the
respective induced voltages.
• The induced voltages are proportional to the rate
of change of fluxes and hence the eddy currents
also are proportional to the rate of change of
fluxes.
∴ F ∝ F2 - F1
∴ F ∝ φ2 i1 - φ1 i2
Torque Production
Substituting the proportional expressions of φ1, φ2, i1, i2 in the
above equation we get,
induction-type-relays-working-principle-construction-types
The equation above gives the net force acting on the disc which is
proportional to sin ∝.
Time – Current Characteristics
• Substituting the r.m.s values of the fluxes instead of maximum values we
get,
F ∝ φ1 φ2 sin ∝
• It is important to note that the net force or torque acting on the disc is same
at every instant.
• The action of Induction relay under such force is free from vibrations.
• It can be observed from the above equation that if ∝ is zero then the net
force is zero and disc cannot rotate. Hence there must exist a phase
difference between the two fluxes. The torque is maximum when the phase
difference ∝ is 90°.
• The direction of the net force which decides the direction of rotation of disc
depends on which flux is leading the other. In practice, various
constructions are used to produce phase displacement between the two
fluxes.
Non Directional Overcurrent Relay
• Characteristics show the inverse relation between time
and current for small values of currents.
• As current increases, some definite time is required by
the relay. So the characteristics becomes straight line
for higher values of currents. Such IDMT
characteristics can be obtained by saturating the iron in
the upper magnet so that there cannot be increase in the
flux once current achieves certain high value.
The torque is produced due to induction principle, as explained in Non directional Induction Type
Overcurrent Relay. This torque is opposed by restraining force produced by spiral springs. Under normal
conditions, the restraining force is more than driving force hence disc remains stationary. Under fault
conditions when the current becomes high, the disc rotates through the preset angle and makes contact with
the fixed contacts of the trip circuit. The trip circuit opens the circuit breaker, isolating the faulty part from
rest of the healthy system
Practically, it is necessary to calculate the actual operating time of the relay, under the specific fault current levels. For these
calculations, the following parameters related to the Non-directional Induction Overcurrent Relay must be known.
2. Current setting.
1. Using the C.T ratio, convert the fault current level to relay coil current level.
2.Calculate the plug setting multiplier from the relay coil current and current setting.
3. From the Time/P.S.M curve on data, obtain the time corresponding to the plug setting multiplier calculated above.
4. Multiplying the time obtained by time multiplier setting, the actual relay time can be obtained.
Necessity of Directional Relays
• Consider a radial system fed at both ends.
• If only one relay is installed, then fault current may be supplied from the
other source.
• Hence, relays are also installed at other end of line to detect fault and
disconnect transmission line from the other end as well.
Necessity of Directional Relays
• Additional discrimination feature is to be provided to distinguish
between faults that it should respond to, and others that it should
not respond to.
Equation
Directional Overcurrent Relay
It consists of two relay elements mounted on a common case viz.
1.Directional element and
2.Non-directional element.
1. Directional element:
It is essentially a directional power relay which operates when power
flows in a specific direction. The potential coil of this element is
connected through a potential transformer (P.T.) to the system voltage.
The current coil of the element is energised through a C.T. by the circuit
current. This winding is carried over the upper magnet of the non-
directional element. The trip contacts (1 and 2) of the directional element
are connected in series with the secondary circuit of the overcurrent
element. Therefore, the latter element cannot start to operate until its
secondary circuit is completed. In other words, the directional element
must operate first (i.e. contacts I and 2 should close) in order to operate
the overcurrent element.
Directional Overcurrent Relay
• Non-directional element: It is an overcurrent element similar in all
respects to a non-directional overcurrent relay. The spindle of the disc
of this element carries a moving contact which closes the fixed
contacts (trip circuit contacts) after the operation of directional
element.
• It may be noted that plug-setting bridge is also provided in the relay
for current setting but has been omitted in the figure for clarity and
simplicity. The tappings are provided on the upper magnet of
overcurrent element and are connected to the bridge.
Operation
• Under normal operating conditions, power flows in the normal direction in the
circuit protected by the relay. Therefore, Induction Type Directional Overcurrent
Relay (upper element) does not operate, thereby keeping the overcurrent
element (lower element) unenergised. However, when a short-circuit occurs,
there is a tendency for the current or power to flow in the reverse direction.
Should this happen, the disc of the upper element rotates to bridge the fixed
contacts 1 and 2. This completes the circuit for overcurrent element.
• The disc of this element rotates and the moving contact attached to it closes the
trip circuit. This operates the circuit breaker which isolates the faulty section. The
two relay elements are so arranged that final tripping of the current controlled by
them is not made till the following conditions are satisfied :
1.current flows in a direction such as to operate the directional element.
2.current in the reverse direction exceeds the pre-set value.
3.excessive current persists for a period corresponding to the time setting of
overcurrent element.
Case Study: Behaviour of Directional Relays
Source : Left side
Load : Right side
CB 2 & 8 : Open
The current flows into the polarity mark of the CT on Breaker 3, and into the Directional Overcurrent (67)
Relay using the same direction. Any current flowing into the polarity mark is considered to be the
forward direction.
• It is based on the fact that any internal fault in an electrical equipment would
cause the current entering it to be different from the current leaving it.
❖ During heavy external fault, the fault current may saturate the CTs and
cause unequal secondary currents.
Percentage or Biased Differential Relay
I1 + I2
No I1 − I2 > Nr
2
Nr I1 + I2
I1 − I2 >
No 2
Id > 𝐾Ir
Percentage or Biased Differential Relay
• The relay will be on the verge of operation when,
Id = KIr
• For the operation of the relay, the differential current must be greater than
this fixed percentage of the restraining current. Hence this relay is called
percentage differential relay.
• Under normal condition or through fault condition, the restraining toque will
be more than the operating torque. Hence the relay is inoperative.
• During any internal fault condition, the operating torque will be more than
the restraining torque. Hence relay will operate.
Percentage or Biased Differential Relay
Balanced Voltage Differential protection
Normal condition & External Fault
Balanced Voltage Differential protection
Internal Fault
Distance Relays
• It is used widely for the protection of HV and EHV transmission
lines.
Impedance Admittance
Relays Reactance Relays Relays
Distance or Impedance Relay
• Deflecting torque becomes more than restoring torque and dynamic parts of
the relay starts moving which ultimately close the Normally Open contact of
relay.
Impedance Relays – Definite Distance Relay
• One beam is placed horizontally and supported by hinge on the middle.
• One end of the beam is pulled downward by the magnetic force of voltage coil, fed from
potential transformer attached to the line. Other end of the beam is pulled downward by the
magnetic force of current coil fed from current transformer connected in series with line. Due
to torque produced by these two downward forces, the beam stays at an equilibrium
position. The torque due to voltage coil, serves as restraining torque and torque due to
current coil, serves as deflecting torque.
Time Distance Impedance Relays
This relay automatically adjusts its operating time according to the
distance of the relay from the fault point. The time distance impedance
relay will not only be operated depending upon voltage to current
ratio, its operating time also depends upon the value of this ratio. That
means,
Again, speed of rotation of induction element approximately proportional to current in this element. Hence, time
of operation is inversely proportional to current.
• This type of relay operates whenever the impedance (V/I) of the protected
zone falls below a predetermined value.
Impedance Relays
• The relay will only operate when this voltage to current ratio
becomes less than its predetermined value. Hence, it can be said
that the relay will only operate when the impedance of the line
becomes less than predetermined impedance (voltage/current).
• As the impedance of a transmission line is directly proportional to
its length, it can easily be concluded that a distance relay can only
operate if fault is occurred within a predetermined distance or
length of line.
Impedance Relays
• Torque produced by voltage element is α K1.V2
• Torque produced by current element is α K1.I2
• The equation for the operating torque is given by,
𝑇 = 𝐾1 𝐼 2 − 𝐾2 𝑉 2 − 𝐾3
𝑇 = 𝐾1 𝐼 2 − 𝐾2 𝑉 2
• Hence the relay will operate when
𝐾1 𝐼 2 > 𝐾2 𝑉 2
𝑉 2 𝐾1 𝑉 𝐾2
2
< 𝑜𝑟 <
𝐼 𝐾2 𝐼 𝐾1
𝑍<𝐾
Operating Characteristics
• We know that 𝑍 = 𝑅2 + 𝑋 2 is the equation
of a circle having a radius of Z.
𝑉 K1
sinα < ; 𝑍 𝑠𝑖𝑛𝛼 < 𝐾
𝐼 K2
𝑋<𝐾
Operating Characteristics of Reactance relay
Mho Relays
• Impedance relays normally not used because it requires an
additional directional relay.
• Mho relays naturally have the directional feature and hence they
are used widely.
• This relay measures the admittance of the line and operates when
the measured value of line admittance is less than the pre-set
value of admittance.
Operation of Mho Relays
• Flux produced in the operating coil
interacts with the polarizing coil flux
to produce an operating torque.
𝑇𝑜 = 𝐾1 𝑉𝐼 cos 𝜃 − 𝛼
• Now the relay will operate when the torque T is positive. i.e. when,
K1 VI cos θ − α > K 2 V 2
K1 I cos θ − α > K 2 V
I K2
>
V K1 cos θ − α
K
Y>
cos θ − α
Operating Characteristics of Mho relay
Frequency Relay
Negative Sequence Relays
• Negative sequence relays are generally used to give protection to
generators and motors against unbalanced currents.
𝐼𝑅
𝐼𝑍1 = 𝐼𝑍3 =
3
300
600 300
IZ3
• Currents from B phase divide into two equal components IZ2 and IZ4 at
point C. IZ2 leads IZ4 by 600.
• The current entering the relay at point B = IZ1 + IZ4 + IY
IR 0
IB
= leading IR by 30 + lagging IB by 300 + IY
3 3
Relay Operation for Positive sequence current
-
IY
I IZ IZ
4
I
B 1 R
30 30
0 0
30 30
IZ 0 0 IZ
2 3
IY
Relay Operation for Negative sequence current
• The current entering the relay at point B = IZ1 + IZ4 + IY
IRelay = IZ1 + IZ4 + IY
IY
• From phasor diagram, it is clear that,
IZ1 = −IZ4
• Therefore, current flowing through relay is,
IRelay = −IZ4 + IZ4 + IY = IY
• Hence the relay will operate and trip the circuit breaker for
the flow of negative sequence current.
IZ IZ
4 1
I IZ IZ I
B 2 3 R
Types of Induction Relays
T ∝ I² sin ∝
∴ T = kI²
• Very fast in operation; Operating time: order of 10 milliseconds; This is because the rotor is light having very low moment of
(induction loop) inertia. The induction cup structure can be used for two quantity or single quantity relays. A single quantity
relay means both the coils are fed by the same actuating quantity with a fixed phase angle shift in between them. To reduce
the rotor inertia and to make the operation faster, double induction loop structure is used. (as shown in figure)
• In all, the induction relays are widely used for protective relays involving ac quantities. High, low and adjustable speeds are
possible in these relays. Various shapes of time against operating quantity curves can be obtained.
Universal Relay – Torque equation
• The universal torque equation explains the working of an electrical relay.
• Generally, electromagnetic relays consist current and voltage windings. The current through the winding
produces magnetic flux. The torque is produced by the interaction of the flux of the same winding or between
the flux of both the windings.
If both the current and voltage windings are used, the torque developed by the interaction between the fluxes is
given by the equation
universal-torque-equation-2
where θ is the angle between V and I and the τ is the relay maximum torque angle.
where K1, K2, K3 are the tap setting or constant of V and I. The K4 is the mechanical restraint due to spring or
gravity.
The operating characteristic of all types of relays is obtained by adding and subtracting all the other constants
and letting others be zero or by adding other similar terms.