0% found this document useful (0 votes)
49 views20 pages

Enga C-Trac3 Setup Monitoring and Commisioning SMC Software Manual Nov 06

The C-TRAC3 SMC Software Manual provides installation and operational guidance for the SMC software compatible with desktop, Pocket PC, and Palm devices. It outlines the software's capabilities for monitoring, troubleshooting, and communication setup for C-TRAC3 systems, along with detailed installation procedures for each platform. Additionally, it describes the software interface and access levels for users and servicemen, including calibration and override functions.

Uploaded by

stevefawkes
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
49 views20 pages

Enga C-Trac3 Setup Monitoring and Commisioning SMC Software Manual Nov 06

The C-TRAC3 SMC Software Manual provides installation and operational guidance for the SMC software compatible with desktop, Pocket PC, and Palm devices. It outlines the software's capabilities for monitoring, troubleshooting, and communication setup for C-TRAC3 systems, along with detailed installation procedures for each platform. Additionally, it describes the software interface and access levels for users and servicemen, including calibration and override functions.

Uploaded by

stevefawkes
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 20

C-TRAC3

SETUP, MONITORING, AND COMMISIONING


(SMC) SOFTWARE MANUAL
FOR

Desk Top, Pocket PC and Palm®

UNIT MODEL NO. _________________


UNIT SERIAL NO. _________________
SERVICED BY: ___________________
TEL. NO: ________________________

CANADIAN USA CANADIAN


HEAD OFFICE HEAD OFFICE EASTERN FACTORY
AND FACTORY AND FACTORY

1401 HASTINGS CRES. SE 32050 W. 83rd STREET 1175 TWINNEY DRIVE


CALGARY, ALBERTA DESOTO, KANSAS NEWMARKET, ONTARIO
T2G 4C8 66018 L3Y 5V7
Ph: (403) 287-4774 Ph: (913) 583-3181 Ph: (905) 898-1114
Fx: 888-364-2727 Fx: (913) 583-1406 Fx: (905) 898-7244

SALES OFFICES ACROSS CANADA AND USA


www.engineeredair.com

Retain instructions with unit and maintain in a legible condition.


Please give model number and serial number when contacting
factory for information and/or parts.

Nov 06
TABLE OF CONTENTS

TABLE OF CONTENTS.............................................................................................................. 0
A. INTRODUCTION .................................................................................................................. 1
B. THE SMC SOFTWARE INSTALLATION............................................................................. 1
1. Installing the SMC software to a Windows Laptop........................................................................... 1
2. Installing the SMC software to a Palm® Handheld.......................................................................... 2
3. Installing the SMC software to a Pocket PC ..................................................................................... 3
4. Setting up the Bluetooth................................................................................................................... 4
C. THE SMC PROGRAM ........................................................................................................... 7
1. The Starting Page ............................................................................................................................. 7
2. The Main Page ................................................................................................................................. 8
3. The Main2 Page.............................................................................................................................. 10
4. The About Page.............................................................................................................................. 13
5. The Hist CFG. and Hist View Pages .............................................................................................. 14
6. The Calibration Page ...................................................................................................................... 15
7. The Override Page.......................................................................................................................... 16
8. The RS485 Set up Page .................................................................................................................. 18
D . THE ONLINE HELP ........................................................................................................... 18
SMCv3.3.1 SOFTWARE MANUAL 2006

A. INTRODUCTION
This version of the SMC software can be used for monitoring, trouble shooting, and
communication set up. With this tool, you have real-time access to C-TRAC3 control variables
and status information.
Three types of service platforms can be used to access the C-TRAC3; a laptop computer, a
Palm® ® handheld PDA and a pocket PC PDA. To support these platforms, there are three
versions of the SMC software.
All three versions of the SMC software provide the same style interface. Navigating buttons are
provided for easy intuitive access to all pages.
SMC performs the following tasks:
· Real-time monitoring of C-TRAC3 sensors, alarms and operating status.
· Data trending for key variables.
· Program set up and equipment commissioning.
· Service and troubleshooting functions.
· Communications set up.
The software and manuals are available at http://www.engineered air.com.

B. THE SMC SOFTWARE INSTALLATION


There are three versions of the SMC software. They are for MS windows, Palm® OS system
and Pocket PCs (Windows CE) respectively. All three versions have the same features. This
section explains how to install the SMC program to these machines.

1. Installing the SMC software to a Windows Laptop.


Requirements:
1) Hardware requirements: a personal computer, a 9-pin NULL MODEM cable with 2
FEMALE serial port connectors.
2) Software requirements: Windows 95, 98, ME, NT, 00 and XP.
Installation:
1) Download or copy the applicable installation program Ctrac3.3.1 Setup.exe to your
PC from either the EngA web site or the CD provided. The SMC V3.3.1 is compatible
with version 3.3, 3.2 and 3.1.
2) Double click Ctrac3.3.1 Setup.exe file to start the CTRAC3 Set up Wizard . Click the
Next button to continue installation.
3) Select a folder to place the program, then click the Next button.

1
SMCv3.3.1 SOFTWARE MANUAL 2006

4) Check the box if a desktop icon is to be created by the wizard. Click the Next button
to finish the installation. After installation, you can run the SMC software for either
EngA CTRAC3.3 from Start menu or from the desktop icon.
5) Connect the cable to your PC and the C-TRAC3 controller.
6) Power up the C-TRAC3 controller. Start the SMC from the start menu or from the
shortcut on your desktop. If the starting page has a message of "is reading …" instead
of buttons, check the connections until you see buttons displaying on the screen.
7) Click on one of the buttons, if the window freezes with the massage "Sending ……"
shown, click on a button will bring up message box as shown below:

If all connections are OK then try a different communication port. The default
COM port # is 1. A valid port can be the built-in serial port #1 and #2 or virtue port #3
and #4 etc. that is the USB to serial converter. Click on the COM# you want to use, then
click on a button on the starting page the window should change if the selected port
number is valid. Once a valid port number has been found the program will save it as the
default port number automatically.
Note: If the installation process halts and the SMC can not be installed successfully, check if
your windows operating system has Msvcrt.dll and mfc42.dll files. If these files are missing, you
can down load them from http://www.caslsoft.com/download.html. Down load the mfcdll.exe file
to your PC. Run this program to install the above two files to your computer. Then start from
step 1.

2. Installing the SMC software to a Palm® Handheld


The system requirements for Palm® OS Devices:
Palm® or Palm® compatible PDA with a 3.x, 4.x or 5.x operating system. The
handheld must also have a serial or universal connector port. In order to communicate
with the C-TRAC3.x you must have either BlueTooth wireless communication function
2
SMCv3.3.1 SOFTWARE MANUAL 2006

or a serial cable. Palm® P10804U universal connector cable for the 15 pin universal port
devices.
Some compatible Palms include; Palm® V, Palm® VII, m130, m515, Zire 71, Tungsten
W, Tungsten T, and Tungsten C.
Installation:
1) Download or copy the SMC for (Palm® ) folder from the EngA web site or from the
CD provided to a desktop PC.
2) If you have not already done so, install the Palm® Desktop program that comes with
the Palm you purchased. If the Palm® Desktop program has already been installed,
go to the next step.
3) Connect the Palm to you PC using the Hotsync cradle.
4) Open the SMC for Palm folder and double click the Setup.exe file to start the
installation wizard.
5) Click the Start Install button when you have selected a user name. The
Synchronization setup window opens.
6) Check the "Restart synchronization manager now" box and click the Finish button to
finish the installation.
7) Push the synchronize button on the cradle to load the program from your PC.
Installation Done.
8) Using the serial cable, connect the Palm® to the C-TRAC3 controller. See 4. Setting
up the Bluetooth for Bluetooth settings.
9) Power up the C-TRAC3 controller. Click the C-TRAC3 icon on Palm® main page to
start the SMC program. The handheld should now communicate with the EngA C-
TRAC3 controller. If the starting page has a message of "is reading …" instead of
buttons, check the Ctrac power and cable connections.

3. Installing the SMC software to a Pocket PC (Version 3.3 and earlier)


The system requirements for the Pocket PC Device
Pocket PC 2002/Windows CE 3.x, and Pocket PC 2003/Windows Mobile, with ARM,
SH3, MIPS microprocessors. The handheld must have either blueTooth wireless
communication function or a serial or universal port along with a serial or universal cable.
Make sure the correct version (BlueTooth version or Serial cable version) of SMC is
obtained from Engineered Air.

3
SMCv3.3.1 SOFTWARE MANUAL 2006

Installation:
1) Download or copy the SMC software for pocket PC folder from the EngA web site or
from the CD provided to a desk a PC.
2) Install the Microsoft ActiveSync program that comes with the pocket PC you
purchased. When the Microsoft ActiveSync program has been installed, close it and
go to the next step.
3) Connect the Pocket PC to your desktop PC using the USB cradle cable.
4) Open the SMC for pocket PC folder, then double click the Setup.exe file to start the
installation wizard.
5) Click the Start Install button. The wizard will let you to confirm the file location.
Select Yes to continue. When the installation is complete, a message appears on the
screen asking you to check the pocket PC for any reminding messages. Click OK if
no additional steps are required.
6) Using the serial cable, connect the Pocket PC to the C-TRAC3 controller. See 4.
Setting up the Bluetooth for Bluetooth settings.
8) Power up C-TRAC3 controller. Click the Ctrac3 icon on the program screen to load
the starting page of the SMC program. The Pocket PC should be able to communicate
with the EngA C-TRAC3 controller. If the starting page has a message of "is reading
…" instead of buttons, check the cable connections.

4. Setting up the Bluetooth

Pocket PC Bluetooth:

1) Bluetooth adapter "PSDv3B-121488" connection procedures: Power up C-TRAC3,


turn off the Bluetooth adapter, plug the adapter to the RS232 port on C-TRAC3, turn
the adapter ON.
2) Serieal port COM#: Go to the Serial Port page and select the Bluetooth Manager,
write down the COM# under label "Outbound COM Port". This information can also
be found from the Pocket PC Manual.
3) Network setting: From the Bluetooth Manager, go to the Dial-up Networkig page, set
the Baud rate to 9600 and the Flow control to "Hardware (Rts/Cts).
4) Setting the port COM#: Run the SMC program or restart the Pocket PC, the PDA Port
Setting page shows up. For a serial connection, select COM1, for Bluetooth wireless
connection select the COM number found in step 1. For example, if a HP Pocket PC
is used, the COM8 is the Bluetooth outbound COM port.)

4
SMCv3.3.1 SOFTWARE MANUAL 2006

Bluetooth Console
Bluetooth Browser
Select a Bluetooth device

PSDv3B-121488

Cancel

5) Selecting device: Click the "Connect" button to open Bluetooth Console window.
Click on the adapter used to finish.

Whenever the Pocket PC is turned on, pay


attension to the connection type shown on the
starting page of the SMC program. The note can
be either "Assuming wireless" or "Assuming
Serial Cable". Make sure the note matches the
physical connection type (cable or wireless). If
they do not match, click the "COM#?" button to
go to the PDA Port Setting page to set the correct
COM port.

To switch between the Serial port and the Bluetooth


port, restart the Pocket PC then go to the PDA Port Setting
to set the correct port.

When starting or running the SMC program if the


following warning message pops up, go to the PDA Port
Setting to set the correct port.

Palm® Bluetooth:

1) Bluetooth adapter "PSDv3B-121488" connection procedures: Power up C-TRAC3,


turn off the Bluetooth adapter, plug the adapter to the RS232 port on C-TRAC3, turn
the adapter ON.
2) Turning the Bluetooth on: On the home page of Palm® , click the Bluetooth icon to
go to the Bluetooth page. If the Bluetooth is OFF, check the ON box.

5
SMCv3.3.1 SOFTWARE MANUAL 2006

3) Making connection: From the Bluetooth Discovery Results


page, click the Connect button to select Show: Nearby devices
the device to connect. Select the Select a device:
Bluetooth adapter then click OK.
PSDv3B-121488

OK Cancel Find
More

6
SMCv3.3.1 SOFTWARE MANUAL 2006

C. THE SMC PROGRAM

1. The Starting Page


After the SMC software is successfully installed and the communication between the C-
TRAC3 controller and a PDA/PC/Pocket PC has been established, you should be able to read
from and write data to the C-TRAC3 Ctrac3 controller. When you launch the SMC program, the
SMC starting page (interface) opens as shown below. There are two levels of access to the C-
TRAC3 control data and air conditioning system information. Level one is mainly monitoring
and is designed to be a customer access level. Level two is designed for the serviceman and
allows calibration, overrides and communication set up. Level 2 requires a password. At each
access level, several interface pages can be opened for displaying and or writing data from and to
the C-TRAC3 controller. To open a page simply click on the page button.

Level 1 Level 2

Level 1 pages: Main and Main2: Display sensor, operating status and set point information.
About: Software version information.
History: Viewing C-TRAC3 key sensor history.
Level 2 page: Calibration: Calibrating input signals.
Override: Set point override and EMS enabling.
RS485: RS485 communication configuration.

7
SMCv3.3.1 SOFTWARE MANUAL 2006

Standard buttons
The following 4 standard buttons are on most pages.

By clicking <<Back button, the


previous page is displayed

Click or Tap the cursor on the After clicking the Send button, all the data shown on the
data or offset you wish to current page will be send to the Ctrac3 controller. If you
change. Now click or tap the forget to send the data, all the changes you made will be lost
INC or DEC button. when you leave the page.

2. The Main Page


Clicking the Main button will open this page.
This is a read-only page. This page displays information
such as unit operating modes, blower status, sensor
readings, discharge set points, etc. Table 1 gives
explanations for all possible messages.

Table 1. Detailed explanation table for Main page


Label Status Descriptions
Operation: Alarm One of the general alarms happened (Low limit, open sensor,
and heat failure)
NIGHT Unit is running in night mode / unoccupied mode
DAY Unit is running in day mode / occupied mode
OFF Unit is OFF
Mode: None There’s no temperature control
Mzone Multizone unit
RH_Dual Reheat unit / Dehumidification, Both heating and cooling are
on
Returning Reheat unit, dehumidification call is satisfied, unit is
transitioning from dual mode to single control mode.
Heat Current control mode is heating
Econ Current control mode is economizer
C+E Current control modes are mechanical cooling + economizer
together
Cool Current control mode is mechanical cooling
Mode Timing Current control mode cannot satisfy the temperature.
change: After a delay, the C-TRAC3 will select a new control
mode.

8
SMCv3.3.1 SOFTWARE MANUAL 2006

Not required No control mode change is required. The change mode timer
is reset.
Blocked No valid mode is available, so mode change is blocked
Hold until change Mode change timer is timed out, but the required control mode
enab. is not available. The C-TRAC3 will stay in the current mode
until the required mode becomes available then go to that
mode immediately.
Cooling Disabled Prog. Cooling lock out due to general alarm
Status: Cycling ON A compressor is cycling ON. (2.5 to 13 minutes load and
application dependent)
Cycling OFF A compressor is cycling OFF. (2.5 to 13 minutes load and
application dependent)
Cooling ON At least one compressor is running or water cooling coil is
modulating
Cooling Enabled Cooling is ready to run
Not required Mechanical cooling is not required.
None No cooling device in this unit
Disabled, term.A Cooling is locked out, because Terminal A is not powered.
On blocked by Amb. Compressor starting is prevented by low ambient temperature.
See control / program manual for complete description.
% on Limited by Ctrac3 won’t bring on another compressor because the VFD
VFD air flow volume is too low. See control / program manual for
complete description.
OFF Unit is OFF, so cooling is OFF
Stages ON: % Percent of cooling stages running.
ModOut: V Modulating cooling output, vdc,
Econ stat: Disabled Prog. Economizer lock out due to general alarm
Not reqd Economizer is not required to be on
Disab by E Economizer is locked out, because Terminal E is powered.
Disab, Amb Economizer is disabled because the outside ambient is too
high.
None There is No economizer installed in this unit
Econ ON Dampers are modulating
LL OR The economizer minimum position setting is being overridden
because the discharge temperature is approaching the low limit
trip point.
Damp. open Outside damper is opened
OFF Outside damper is closed
= x.xv (min) Output volts to the ED terminal. (min): damper is at min.
position; (mod): damper is modulating.
Min Pos: % Minimum outside air percent
Set By: Pda /Ems /Pot Minimum outside air percent is currently set by Pda or Ems
(serial communication from Energy management system) or
Pot.
Heating HEAT FAILURE Heat failure (Flame fail, purge fail, wiring or flame relay)
status: Disabled Prog. Heating lock out due to general alarm.

9
SMCv3.3.1 SOFTWARE MANUAL 2006

Heating ON Heating is on.


Heating ON(Mheat) For two heating section reheat unit, main heat is on
Heating ON(Rheat) For two heating section reheat unit, reheat coil is on
None No heating device is installed in this unit
Not Required Heating is not required
Disabled by HS Heating is locked out, because terminal HS is not powered.
Disabled, Amb Heating is locked out due to high ambient temperature.
Heat Enabled Heating is ready to run but not yet on.
OFF When unit is OFF, heating is OFF
Heat output: Vdc Output volts to terminal HD
Blower Delay OFF Blower is delaying off for cool down and/or pump down
status: ON Blower is running
Delay ON Blower is delaying on for opening damper and/or warming up
Low Air Flow VFD units only.
OFF Blower is OFF
Dis. Temp: °F or °C Discharge temperature. Displays sensor 1 (Terminal Q) or
sensor 1+2 (Terminals Q+X) average if program and unit is set
up to do averaging.
Amb Temp: °F or °C Ambient temperature reading.
Final °F or °C Final leaving discharge air set point after all resets have been
Calculated added in. For multizones it is the final hot deck set point.
Disch. SP:

3. The Main2 Page


The Main2 page is a read-only page. Table 2 gives explanation for information displayed
in this page.

Push this button and the C-TRAC3


controller will reboot and the alarms
will be reset.

10
SMCv3.3.1 SOFTWARE MANUAL 2006

Table 2. Detailed explanation table for Main2 page


Label Status Descriptions
AC Inputs: 0 or 1 0 = digital input terminal is not powered (24vac).
1 = digital input terminal is powered (24vac).

Discharge PDA, xx°F The current base set point of sensor 1 is xx degrees and is set
SP by: by the PDA. You can enable or disable this option in the PDA
Override page.

EMS, xx°F The current base set point of sensor 1 is xx degrees and is
serially set by communication from the EMS computer. You
can enable or disable this option from the PDA Override page.

BMS, xx°F The current base set point of sensor 1 is xx degrees and is
calculated based on BMS input value and the upper and lower
discharge temperature range shown on this page. (0 vdc =
lower limit)

POT, xx°F Current base set point of sensor 1 is xx degrees and is set by
pot #1 on Ctrac3 face or from a remote set point pot connected
to terminal S.

Disch. Room, xx°F Room reset from a TE6100 thermostat. The room is calling for
Reset by: xx degrees of reset. You can adjust the room proportion band
and integral time from the PDA Calibration page.

Amb., xx°F Ambient reset . The ambient is calling for xx degrees of reset.

BMS, xx°F BMS reset. The 0-10 volt BMS signal is calling for xx degrees
of reset.

Term “X”: xx°F, Room Temp. Terminal X is used as a room sensor. It is reading xx degrees.
xx°F, Average Sens Terminal X is used as a second discharge sensor that is to be
averaged with the main discharge sensor. It is reading xx
degrees.
xx°F, Cold deck Sens Terminal X is used as the cold deck discharge sensor. It is
reading xx degrees.
xx°F, DH cool Sensor Terminal X is used as the cooling discharge sensor in
dehumidification mode. It is reading xx degrees.
- , OPEN Sensor mounted on terminal X is open
xx°F, Sensor reading X terminal is used for temperature read out.
Opened, Digital input X terminal is used as a digital input and the status is open
Closed, Digital input X terminal is used as a digital input and the status is closed

11
SMCv3.3.1 SOFTWARE MANUAL 2006

- Terminal X is not used

Term “Y”: xx°F, SP2 by PDA Cooling set point is set by PDA.

xx°F, SP2 by EMS Cooling set point is set by EMS.

xx°F, Day Room SP Terminal Y is the room thermostat set point setting.

xx°F, SP2 by POT Terminal Y is the base set point setting for sensor 2. It is set
from pot #2 on Ctrac3 face or remote pot connected to
Terminal Y. (Cooling set point for Multizone &
dehumidification function.
xx v, BMS SP2 Terminal Y is the BMS input signal. (0-10v)
- Terminal Y is a spare terminal and has no function

Term “+”: 0-10vdc BMS input signal, 0-10v

Cold deck xx °F The final set point after resets for the Multizone cold deck or
D/A the final cooling set point for the dehumidification circuit
calculated
SP:
Cool dis xx °F to xx °F The lower and upper set point limits for the cooling and
Range: economizer control modes. In no case, can the final discharge
set point, be set out of this range. These values can only be
changed from the EngA access level.

Heat dis xx °F to xx °F The lower and upper set point limits for the heating control
Range: mode. In no case, can the final discharge set point, be set out
of this range. These values can only be changed from the EngA
access level.

Alarms: None No alarms


Sensor_Q fail sensor 1 connected to terminal Q is open
Sensor_X fail sensor 2 connected to terminal X is open
Amb_sens fail ambient sensor is open

Lowlimit Low limit tripped


BurnerWiring For DJ/DG heating devices, burner wiring problem
Flame Relay For DJ/DG heating devices, Flame Relay failure
Pre-Purge For DJ/DG heating devices, Pre-Purge problem
Flame Fail For DJ/DG heating devices, flame failure
Heat Fail For Mtrac, LMK, general heat failure occurred

12
SMCv3.3.1 SOFTWARE MANUAL 2006

VFD fault FB Faulty VFD feedback signal


Clog Filters Clogged filter alarm

Cooling alarm Cooling problem

Low Air Flow Low air flow problem

Special alarm Custom defined alarm

Wheel turning The heat wheel is operating

Spe. Stat = ON Custom defined status is "ON"

Reset unit Reset unit Click this button to reset the C-TRAC3 controller.
button
Temp. Check boxes: Toggles display between °F and °C. Note: The temperature
Units: readings on the program setup and manual control pages are
°F, °C
always in °F.

4. The About Page


This page gives information such software versions,
the program number, unit address and a brief program
description for the selected program #.
Table 3 explains the information displayed on this page.

Table 3. Detailed explanation table for the About page


Label Status Descriptions
Unit Address: Number Default is 1, can be set through PDA, valid value is
from 1 to 255

Software Version: Ver 3.3.1 Coded in Program

Program Number: Number When unit is in the field, this number can’t be changed.
A change of the program# can only be made by an EngA
service personnel. Valid value is from 1 to 64.

Options(A: to C:): Number Display the Option package setup. Reading only.

Program Description Program Click this button to display an description of the selected
Button Description program.

13
SMCv3.3.1 SOFTWARE MANUAL 2006

5. The Hist CFG. and Hist View Pages


The History button on the starting page will open the History Configuration page. This
page is used to configure the History View page for displaying the required information.

Most recent
MPU error log
To clear all MPU
Second last and flame retry
MPU error log codes

Last MPU
error log

MPU CODE:
These codes are for Engineered Air usage only.
Flame fail reset:
This cell keeps track of the number of flame failure auto resets. Auto flame failure reset
is an option available for DJ and DG heat exchangers under 2500 MBTUH.
Alarm:
This is the alarm occurred in the past. Possible codes are listed in the following table.
Code Alarm
BW Burner wiring
FR Flame relay
PP Pre-purge
FF Flame fail
HF Heat fail
LL Low limit
SQ Sensor wired to Q
SX Sensor wired to X
SAmb Sensor wired to Amb
Cool Cooling alarm
Air Low air flow

14
SMCv3.3.1 SOFTWARE MANUAL 2006

History function
Due to memory limitations, the C-TRAC3 has a limited history function. Instead of
providing traditional trending data, the C-TRAC3 sets up time windows and records the
minimum and maximum values measured in that time window. Note if any changes are made
to the history configuration page, the configuration data is only stored when the reset/send button
is pressed. If the reset/send button is not pressed, any changes made will be lost.
Variable selection
To select a variable to trend, simply check the check box beside that variable name. Up
to 4 variables can be selected from a pre-defined list of 8 variables.
Window Size
The window size can be altered in 30 second “step” increments. If you enter 8 then the
window time interval = 8 * ½ min. = 4 minutes.
There are two history data recording styles. One is to continue recording (rewrite) and
stop at alarms (default setting). With this style, the newest window records overwrite the oldest
window records. The other is to start recording history from the moment you clear the buffer or
the moment you power the C-TRAC3. The recording will stop when the history record buffer is
full or at the alarms.
Reset / send button
Push this button, to clear the history
record and to save any history configuration
changes.
The Hist View page
The minimum and maximum values
are recorded for each of the variables selected
on the history set up page. The time frame
between windows is as set on the history set
up page. Window # 0 is the always most
recent data. Window #1 is a little older and so on. While viewing the data the C-TRAC3 is not
updating the display. If you want to update the display you need to click the update this page
button. If the unit is off or there is an alarm, the C-TRAC3 will stop recording.

6. The Calibration Page


You need a second level password to access this page. This page is used for calibrating
sensors, set point signals, and 0-10 vdc control signals. This page also sets room temperature
control parameters such as integration time, proportional band, night set back and night set up
values.

15
SMCv3.3.1 SOFTWARE MANUAL 2006

This column is read only. These values


are calculated using the actual reading +
calibration off set. After calibration, the
send button must be pushed.

Room reset integral rate (minutes /


degree): “5”, means the Discharge air set
point will ramp up/down 1° degree every
5 minutes. The range is from 8 to 40 min.
/ degree.

Room proportional band, The setting


range is 3 to 13 °F

Night set back (SB), deduct this number


from the room thermostat set point. Night
set up (Set UP), add this number to the
room thermostat set point.

Calibration offset
The program has an internal fixed Max/Min calibration offset limit. If you input a
number higher than the offset limit, the number will be reduced back to the Maximum or
Minimum offset value. For the BMS, Y Terminal the offset value will accept a number with one
decimal place.

7. The Override Page


Some C-TRAC3 data and operating
parameters can be overridden using the override page.
When determining who has control of the set points
etc, the C-TRAC3 follows this priority list ranked
from highest to lowest.
1. PDA
2. Serial communication from a central EMS
computer.
3. 0-10 vdc reset signal from a central building
computer.
4. Remote pots
5. Built in pots.

16
SMCv3.3.1 SOFTWARE MANUAL 2006

The PDA also has the authority to enable or disable serial communication to a central
energy management computer system.

Table 5. Descriptions of the Override page


Item Descriptions
Disable discharge air resets. (room, 0-10vdc and ambient) and BMS
Disable Resets set points, then use discharge air control only, set point can be POT,
EMS or PDA.
This setting will override all other means of set point adjustment (The
Override Base SP1 PDA has the highest priority). Once the box is checked a set point
Range (ll to hh) Input xx request line appears. You may enter any value as long as the value lies
between ll and hh.
Note! unless you disable the resets, they are still active.
Override Base SP2 This setting will override all other means of set point adjustment (The
This check box is only visible
PDA has the highest priority). Once the box is checked a set point
when a program has a second
request line appears. You may enter any value as long as the value lies
discharge set point.
Range (ll to hh) Input xx between ll and hh.
Note! unless you disable the resets, they are still active.

Override Minimum Position This setting will override all other means of Minimum position
adjustment (The PDA has the highest priority).
If this option is checked, the unit discharge air temperature set points and
Enable Remote Panel
minimum position setting can be set by the RS485 remote panel.
Enable EMS set points + If this block is checked, the discharge set point(s) and the economizer
MinPos. Minimum Position setting can be set by serial communication from a
central energy management computer. EMS control has the second
highest priority next only to PDA. Resets are disabled.
Enable EMS Unit On/Off The central energy management computer will have unit on/off control.

Enable EMS K and all disable If this block is checked, the EMS computer will control dehumidification
call (dehumidification programs only) and separately command each
operating mode (heat, economizer and mechanical cooling) to disable or
automatic operation.

Speed up timers for one hour Service tool. If checked, the timers ( mode change , compressor cycle,
alarms, etc.) are reduced to 1/2 of normal time. If you forget to disable
it, all the timers will go back to normal timing in an hour.

17
SMCv3.3.1 SOFTWARE MANUAL 2006

8. The RS485 Set up Page


The RS485 Set up page is used for setting up the RS485 serial communication
parameters.

Valid unit address is from 1


to 255. The default address
is 1

D. THE ONLINE HELP


Online helps have been built in with each page. The help text can be accessed from any
page.
The Help Topics page displays the topics of the help messages. Select a topic then a sub-
topic, the help message page with a description of the selected topic opens. Simply click the
Back buttons to go back to previous pages.

You can access to the Help Topics


Page by clicking this button in the
top right corner of each page.

18

You might also like