Amps X 100 BAL-13.8 (Nom. kV=13.8, Plot Ref. kV=13.

8)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K

500 500

300 300

100 100

BAL-587-W2 - P - 51
50 OC1 50
Schweitzer
30
551 30
CT Ratio 1200:5
U3 - U.S. Very Inverse
Pickup = 5.1 (0.5 - 16 Sec - 5A)
Time Dial = 2.38
10
3x = 1.38 s, 5x = 0.614 s, 8x = 0.376 s 10
BAL-351_REV - P - 51
OC1 - 67
5 Schweitzer 5
Seconds

Seconds
351
3 CT Ratio 1200:5 3
U3 - U.S. Very Inverse
Pickup = 0.7 (0.02 - 3.2 Sec - 1A)
Time Dial = 2.28
3x = 1.33 s, 5x = 0.588 s, 8x = 0.36 s
1 1

.5
BAL-01R - P .5
TCC 1 ∆ 0.2 s BAL-587-W2 - 3P
∆ 0.203 s
.3
Cooper .3
Form 6 ∆ 0.231 s
ANSI - Extremely Inverse
Pickup = 300 (5 - 800 Primary)
High Current = 16.558 (1 - 32 xTOC Pickup)
.1
Time Delay = 0.118 s BAL-351_REV - 3P .1
Interrupting Time = 45 ms
Minimum Response Time = 0.01 s
3x = 3.69 s, 5x = 1.34 s, 8x = 0.614 s
.05 .05
Clearing

.03 .03

OCR
OCR
BAL‐587‐W2
BAL‐351_REV

BAL‐01R

.01 79
.01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps X 100 BAL-13.8 (Nom. kV=13.8, Plot Ref. kV=13.8)


ETAP Star 22.5.0C

Project: BEL Transmission System 2023 Date: 24-07-2024


Location: Belize SN: BELIZE-ELE
Contract: Rev: Base
Engineer: Bruno Samos Fault: Phase
Filename: C:\Users\bsamos\Downloads\ETAP_2024_version5\BEL ETAP MODEL 2024.OTI
Phase coordination