Preface
___________________
Application and properties 1
___________________
LEDs and connectors 2
SIMATIC NET
___________________
Installation, connecting up,
commissioning 3
S7-1200 - TeleControl
CP 1243-1 ___________________
4
Configuration
___________________
Program blocks 5
Operating Instructions
___________________
Diagnostics and upkeep 6
___________________
Technical data 7
___________________
Approvals A
___________________
Dimension drawings B
___________________
Documentation references C
04/2017
C79000-G8976-C365-03
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
Figure 1 CP 1243-1
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 3
Preface
Behind the top hinged cover of the module housing, you will see the hardware product
version to the right of the article number printed as a placeholder "X". If the printed text is, for
example, "X 2 3 4", "X" would be the placeholder for hardware product version 1.
You will find the firmware version of the CP as supplied behind the top hinged cover of the
housing to the left below the LED field.
You will find the MAC address under the lower hinged cover of the housing.
CP 1243-1
4 Operating Instructions, 04/2017, C79000-G8976-C365-03
Preface
Required experience
To install, commission and operate the CP, you require experience in the following areas:
● Automation engineering
● Setting up the SIMATIC S7-1200
● SIMATIC STEP 7 Basic / Professional
Cross references
In this manual there are often cross references to other sections.
To be able to return to the initial page after jumping to a cross reference, some PDF readers
support the command <Alt>+<Left arrow>.
License conditions
Note
Open source software
The product contains open source software. Read the license conditions for open source
software carefully before using the product.
You will find license conditions in the following document on the supplied data medium:
● OSS-CP1243-1_86.pdf
Firmware
The firmware is signed and encrypted. This ensures that only firmware created by Siemens
can be downloaded to the device.
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 5
Preface
Security information
Siemens provides products and solutions with industrial security functions that support the
secure operation of plants, systems, machines and networks.
In order to protect plants, systems, machines and networks against cyber threats, it is
necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial
security concept. Siemens’ products and solutions only form one element of such a concept.
Customer is responsible to prevent unauthorized access to its plants, systems, machines
and networks. Systems, machines and components should only be connected to the
enterprise network or the internet if and to the extent necessary and with appropriate security
measures (e.g. use of firewalls and network segmentation) in place.
Additionally, Siemens’ guidance on appropriate security measures should be taken into
account. For more information about industrial security, please visit
Link: (http://www.siemens.com/industrialsecurity)
Siemens’ products and solutions undergo continuous development to make them more
secure. Siemens strongly recommends to apply product updates as soon as available and to
always use the latest product versions. Use of product versions that are no longer supported,
and failure to apply latest updates may increase customer’s exposure to cyber threats.
To stay informed about product updates, subscribe to the Siemens Industrial Security RSS
Feed under
Link: (http://www.siemens.com/industrialsecurity).
CP 1243-1
6 Operating Instructions, 04/2017, C79000-G8976-C365-03
Table of contents
Preface ................................................................................................................................................... 3
1 Application and properties ..................................................................................................................... 11
1.1 Properties of the CP................................................................................................................11
1.2 Communications services .......................................................................................................11
1.3 Other services and properties .................................................................................................12
1.4 Security functions ....................................................................................................................13
1.5 Configuration limits and performance data .............................................................................15
1.6 Configuration examples ..........................................................................................................17
1.6.1 Sending e-mails ......................................................................................................................17
1.6.2 TeleControl Basic ....................................................................................................................18
1.6.3 DNP3 / IEC .............................................................................................................................20
1.6.3.1 Configuration with 1 subnet ....................................................................................................20
1.6.3.2 Configuration with connections over the Internet ...................................................................21
1.6.3.3 Configuration with a redundant control center ........................................................................22
1.7 Requirements for use..............................................................................................................23
1.7.1 Hardware requirements ..........................................................................................................23
1.7.2 Software requirements ............................................................................................................23
2 LEDs and connectors ............................................................................................................................ 25
2.1 Opening the covers of the housing .........................................................................................25
2.2 LEDs .......................................................................................................................................26
2.3 Electrical connectors ...............................................................................................................30
2.3.1 Power supply ..........................................................................................................................30
2.3.2 Ethernet interface X1P1 ..........................................................................................................30
3 Installation, connecting up, commissioning ............................................................................................ 31
3.1 Important notes on using the device .......................................................................................31
3.1.1 Notices on use in hazardous areas ........................................................................................31
3.1.2 Notices on use in hazardous areas according to IECEx / ATEX ............................................32
3.1.3 Notices regarding use in hazardous areas according to UL HazLoc .....................................33
3.1.4 Notices on use in hazardous areas according to FM .............................................................33
3.2 Installing, connecting up and commissioning .........................................................................34
3.3 Note on operation ...................................................................................................................36
4 Configuration ........................................................................................................................................ 37
4.1 Security recommendations .....................................................................................................37
4.2 Configuration in STEP 7 .........................................................................................................40
4.3 Addressing and authentication ...............................................................................................41
4.3.1 TeleControl Basic ....................................................................................................................41
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 7
Table of contents
CP 1243-1
8 Operating Instructions, 04/2017, C79000-G8976-C365-03
Table of contents
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 9
Table of contents
CP 1243-1
10 Operating Instructions, 04/2017, C79000-G8976-C365-03
Application and properties 1
1.1 Properties of the CP
Application
The CP is intended for operation in an S7-1200 automation system. The CP allows
connection of the S7-1200 to Industrial Ethernet or via the Internet to the following control
center systems:
● Telecontrol server (OPC server application TCSB V3)
● DNP3 master station
● IEC master station
With the combination of different security functions such as firewall and protocols for data
encryption, the CP protects the station and even entire automation cells from unauthorized
access and protects the communication between the remote S7 station and the master
station (TCSB) from espionage and manipulation.
Communications services
The following communications services are supported:
● Telecontrol communication
The CP is a communications processor of the SIMATIC S7-1200 for system attachment
to the control center systems named above. The CP can communicate with redundant
control systems.
For each control center system the relevant telecontrol protocol is activated on the CP
("Type of communication"). The protocols allow IP-based data transmission for telecontrol
applications.
You will find the usable security functions in the section Security functions (Page 13).
● Messages / e-mail
With special events, the CP can send messages as e-mails.
You will find the requirements and functions in the section E-mail configuration (Page 69).
● S7 communication and PG/OP communication with the following functions:
– PUT/GET as client and server for data exchange with S7 stations
– PG functions
– Operator control and monitoring functions (HMI)
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 11
Application and properties
1.3 Other services and properties
CP 1243-1
12 Operating Instructions, 04/2017, C79000-G8976-C365-03
Application and properties
1.4 Security functions
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 13
Application and properties
1.4 Security functions
CP 1243-1
14 Operating Instructions, 04/2017, C79000-G8976-C365-03
Application and properties
1.5 Configuration limits and performance data
● SNMPv3
For secure transmission of network analysis information safe from eavesdropping
● Protection for devices and network segments
The protection provided by the firewall can cover individual devices, several devices or
even entire network segments.
Note
Plants with security requirements - recommendation
Use the following options:
• If you have systems with high security requirements, use the secure protocols
NTP (secure), HTTPS and SNMPv3.
• If you connect to public networks, you should use the firewall. Think about the services
you want to allow access to the station via public networks. By using the "bandwidth
limitation" of the firewall, you can restrict the possibility of flooding and DoS attacks.
See also section Security recommendations (Page 37).
For configuring the security functions refer to the section Security (Page 63).
You will find further information on the functionality and configuration of the security functions
in the information system of STEP 7 and in the manual /4/ (Page 142).
Connection resources
● Telecontrol connections
With the various telecontrol protocols the CP can establish connections to the following
master station types:
– To non-redundant or redundant telecontrol servers (TCSB).
– To up to four non-redundant or redundant DNP3 masters
– To up to four non-redundant or redundant IEC masters
With the Telecontrol Basic protocol, in addition to this, inter-station communication with
up to 15 S7 stations with a CP 1243-1 can be operated via the telecontrol server.
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 15
Application and properties
1.5 Configuration limits and performance data
User data
The data to be transferred by the CP is assigned to various data points in the STEP 7
configuration.
The size of the user data per data point depends on the data type of the relevant data point.
You will find details in the section Datapoint types (Page 89).
Messages (e-mail)
● Sending of up to 10 messages (e-mails) can be configured with the message editor.
● Sending e-mails via the TMAIL_C program block
CP 1243-1
16 Operating Instructions, 04/2017, C79000-G8976-C365-03
Application and properties
1.6 Configuration examples
Firewall rules
The maximum number of firewall rules in advanced firewall mode is limited to 256.
The firewall rules are divided up as follows:
● Maximum 226 rules with individual addresses
● Maximum 30 rules with address ranges or network addresses
(e.g. 140.90.120.1 - 140.90.120.20 or 140.90.120.0/16)
● Maximum 128 rules with limitation of the transmission speed ("Bandwidth limitation")
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 17
Application and properties
1.6 Configuration examples
In the telecontrol applications of the example shown, SIMATIC S7 stations communicate with
a non-redundant telecontrol server (TCSB) in the master station.
● Telecontrol communication between stations and master station
The communication is via the following paths and communications modules:
– Communication via the Internet: S7-1200 with CP 1243-1
– Communication via the GSM network and the Internet: S7-1200 with CP 1242-7 or
S7-200 with MODEM MD720
The establishment of terminal connections with encryption is initiated automatically by the
telecontrol protocol used by the various communications modules.
The creation of VPN connections between the CP 1243-1 and telecontrol server is
optional.
The telecontrol server monitors the connections established by the remote stations.
● Inter-station communication
Stations of the same type, for example S7-1200 with CP 1243-1, can communicate with
each other by sending the frames via the telecontrol server.
CP 1243-1
18 Operating Instructions, 04/2017, C79000-G8976-C365-03
Application and properties
1.6 Configuration examples
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 19
Application and properties
1.6 Configuration examples
Figure 1-4 Configuration example with a non-redundant control center and stations in one IP subnet
The S7-1200 stations are connected to the Internet via the CP and connected to the control
center.
When using the DNP3 protocol, for example, SIMATIC PCS 7 TeleControl or the system of a
third-party provider can be used as the control center. If you use SIMATIC PCS 7
TeleControl as the DPN3 master in the control center, you require the necessary DPN3
driver.
CP 1243-1
20 Operating Instructions, 04/2017, C79000-G8976-C365-03
Application and properties
1.6 Configuration examples
As an alternative to the router SCALANCE 812, you can also use a standard DSL modem
and establish the VPN connection with a security module SCALANCE S.
Addressing
Refer to the information in the section DNP3 / IEC (Page 41).
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 21
Application and properties
1.7 Requirements for use
CP 1243-1
22 Operating Instructions, 04/2017, C79000-G8976-C365-03
Application and properties
1.7 Requirements for use
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 23
Application and properties
1.7 Requirements for use
CP 1243-1
24 Operating Instructions, 04/2017, C79000-G8976-C365-03
LEDs and connectors 2
2.1 Opening the covers of the housing
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 25
LEDs and connectors
2.2 LEDs
2.2 LEDs
(red / green)
(green)
CONNECT Status of the connections to the communications partner
(green)
VPN Status of the VPN configuration
(green)
SERVICE Status of a connection for online functions
(green)
Symbol -
CP 1243-1
26 Operating Instructions, 04/2017, C79000-G8976-C365-03
LEDs and connectors
2.2 LEDs
Note
LED colors when the module starts up
When the module starts up, all its LEDs are lit for a short time. Multicolored LEDs display a
color mixture. At this point in time, the color of the LEDs is not clear.
DIAG Meaning
(red / green) (if more than one point listed: alternative meaning)
Basic statuses of the CP
• Power OFF
• Incorrect startup
Running (RUN) without serious error
green
• Partner not connected
• Starting up
flashing red-green
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 27
LEDs and connectors
2.2 LEDs
Startup - phase 1
red
- Startup - phase 2
flashing red
- - - - Running (RUN) without serious error
green
Incorrect startup
red
- - - Missing STEP 7 project data
flashing red
- - Backplane bus error
flashing red
Connection to Industrial Ethernet
- - - - Connection to Industrial Ethernet exists
green
- - Partner not reachable
flashing
green
CP 1243-1
28 Operating Instructions, 04/2017, C79000-G8976-C365-03
LEDs and connectors
2.2 LEDs
green
- - Attempt to establish connection for online
functions
green
- - - No connection to engineering station
green
VPN connection
- - VPN connection established
green
- - VPN connection configured but not estab-
lished.
flashing flashing
green green
- - - - No VPN connection configured on the CP
Loading firmware
Loading firmware. The DIAG LED flashes
alternating red and green.
Firmware was successfully loaded.
flashing
green
Error loading firmware
flashing red
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 29
LEDs and connectors
2.3 Electrical connectors
Power supply
The CM is supplied with power from the backplane bus. It does not require a separate power
supply.
Ethernet interface
The Ethernet connector is located behind the lower hinged cover of the module. The
interface is an RJ-45 jack according to IEEE 802.3.
The pin assignment and other data relating to the Ethernet interface can be found in the
section Technical data (Page 133).
CP 1243-1
30 Operating Instructions, 04/2017, C79000-G8976-C365-03
Installation, connecting up, commissioning 3
3.1 Important notes on using the device
Overvoltage protection
NOTICE
Protection of the external power supply
If power is supplied to the module or station over longer power cables or networks, the
coupling in of strong electromagnetic pulses onto the power supply cables is possible. This
can be caused, for example by lightning strikes or switching of higher loads.
The connector of the external power supply is not protected from strong electromagnetic
pulses. To protect it, an external overvoltage protection module is necessary. The
requirements of EN61000-4-5, surge immunity tests on power supply lines, are met only
when a suitable protective element is used. A suitable device is, for example, the Dehn
Blitzductor BVT AVD 24, article number 918 422 or a comparable protective element.
Manufacturer:
DEHN+SOEHNE GmbH+Co.KG Hans Dehn Str.1 Postfach 1640 D-92306 Neumarkt,
Germany
WARNING
EXPLOSION HAZARD
DO NOT OPEN WHEN ENERGIZED.
WARNING
The device may only be operated in an environment with pollution degree 1 or 2 (see IEC
60664-1).
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 31
Installation, connecting up, commissioning
3.1 Important notes on using the device
WARNING
The equipment is designed for operation with Safety Extra-Low Voltage (SELV) by a
Limited Power Source (LPS).
This means that only SELV / LPS complying with IEC 60950-1 / EN 60950-1 / VDE 0805-1
must be connected to the power supply terminals. The power supply unit for the equipment
power supply must comply with NEC Class 2, as described by the National Electrical Code
(r) (ANSI / NFPA 70).
If the equipment is connected to a redundant power supply (two separate power supplies),
both must meet these requirements.
WARNING
EXPLOSION HAZARD
DO NOT CONNECT OR DISCONNECT EQUIPMENT WHEN A FLAMMABLE OR
COMBUSTIBLE ATMOSPHERE IS PRESENT.
WARNING
EXPLOSION HAZARD
SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION
2 OR ZONE 2.
WARNING
WARNING
Requirements for the cabinet/enclosure
To comply with EU Directive 94/9 (ATEX95), the enclosure or cabinet must meet the
requirements of at least IP54 in compliance with EN 60529.
WARNING
If the cable or conduit entry point exceeds 70 °C or the branching point of conductors
exceeds 80 °C, special precautions must be taken. If the equipment is operated in an air
ambient in excess of 50 °C, only use cables with admitted maximum operating temperature
of at least 80 °C.
CP 1243-1
32 Operating Instructions, 04/2017, C79000-G8976-C365-03
Installation, connecting up, commissioning
3.1 Important notes on using the device
WARNING
Take measures to prevent transient voltage surges of more than 40% of the rated voltage.
This is the case if you only operate devices with SELV (safety extra-low voltage).
WARNING
EXPLOSION HAZARD
DO NOT DISCONNECT WHILE CIRCUIT IS LIVE UNLESS AREA IS KNOWN TO BE
NON-HAZARDOUS.
This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D or non-
hazardous locations only.
This equipment is suitable for use in Class I, Zone 2, Group IIC or non-hazardous locations
only.
WARNING
EXPLOSION HAZARD
Do not connect or disconnect while the circuit is live or unless the area is known to be free
of ignitible concentrations.
This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D or non-
hazardous locations only.
This equipment is suitable for use in Class I, Zone 2, Group IIC or non-hazardous locations
only.
WARNING
EXPLOSION HAZARD
The equipment is intended to be installed within an ultimate enclosure. The inner service
temperature of the enclosure corresponds to the ambient temperature of the module. Use
installation wiring connections with admitted maximum operating temperature of at least
30 ºC higher than maximum ambient temperature.
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 33
Installation, connecting up, commissioning
3.2 Installing, connecting up and commissioning
CAUTION
Read the system manual "S7-1200 Programmable Controller"
Prior to installation, connecting up and commissioning, read the relevant sections in the
system manual "S7-1200 Programmable Controller", refer to the documentation in the
Appendix.
When installing and connecting up, keep to the procedures described in the system manual
"S7-1200 Programmable Controller".
NOTICE
Turning off the station when plugging/pulling the module
Before pulling or plugging the module, always turn off the power supply to the station.
CP 1243-1
34 Operating Instructions, 04/2017, C79000-G8976-C365-03
Installation, connecting up, commissioning
3.2 Installing, connecting up and commissioning
* Width B: The distance between the edge of the housing and the center of the hole in the DIN rail mounting clip
You will find detailed dimensions of the module in the section Dimension drawings
(Page 139).
Installation location
NOTICE
Installation location
The module must be installed so that its upper and lower ventilation slits are not covered,
allowing adequate ventilation. Above and below the device, there must be a clearance of 25
mm to allow air to circulate and prevent overheating.
Remember that the permitted temperature ranges depend on the position of the installed
device. You will find the permitted temperature ranges in the section Technical
specifications of the CP 1243-1 (Page 133).
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 35
Installation, connecting up, commissioning
3.3 Note on operation
Note
Connection with power off
Only wire up the S7-1200 with the power turned off.
NOTICE
Closing the front panels
To ensure interference-free operation, keep the front panels of the module closed during
operation.
CP 1243-1
36 Operating Instructions, 04/2017, C79000-G8976-C365-03
Configuration 4
4.1 Security recommendations
Keep to the following Security recommendations to prevent unauthorized access to the
system.
General
● You should make regular checks to make sure that the device meets these
recommendations and other internal security guidelines if applicable.
● Evaluate your plant as a whole in terms of security. Use a cell protection concept with
suitable products.
● Do not connect the device directly to the Internet. Operate the device within a protected
network area.
● Keep the firmware up to date. Check regularly for security updates of the firmware and
use them.
● Check regularly for new features on the Siemens Internet pages.
– Here you will find information on network security:
Link: (http://www.siemens.com/industrialsecurity)
– Here you will find information on Industrial Ethernet security:
Link: (http://w3.siemens.com/mcms/industrial-communication/en/ie/industrial-ethernet-
security/Seiten/industrial-security.aspx)
– You will find an introduction to the topic of industrial security in the following
publication:
Link:
(http://w3app.siemens.com/mcms/infocenter/dokumentencenter/sc/ic/InfocenterLangu
agePacks/Netzwerksicherheit/6ZB5530-1AP02-
0BA4_BR_Network_Security_en_112015.pdf)
Physical access
Restrict physical access to the device to qualified personnel.
Network attachment
Do not connect the PC directly to the Internet. If a connection from the CP to the Internet is
required, arrange for suitable protection before the CP, for example a SCALANCE S with
firewall or use the CP 1543SP-1.
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 37
Configuration
4.1 Security recommendations
Passwords
● Define rules for the use of devices and assignment of passwords.
● Regularly update the passwords to increase security.
● Only use passwords with a high password strength. Avoid weak passwords for example
"password1", "123456789" or similar.
● Make sure that all passwords are protected and inaccessible to unauthorized personnel.
See also the preceding section for information on this.
● Do not use one password for different users and systems.
Protocols
CP 1243-1
38 Operating Instructions, 04/2017, C79000-G8976-C365-03
Configuration
4.1 Security recommendations
Protocol / function Port number (pro- Default of the port Port status Authentication
tocol)
DNP3 listener 20000 (TCP) Closed Open after configuration No
port
IEC listener port 102 (TCP) Closed Open after configuration No
S7 and online 2404 (TCP) Open Open after configuration * No
connections
Online security 8448 (TCP) Closed Open after configuration No
diagnostics
HTTP 80 (TCP) Closed Open after configuration No
HTTPS 443 (TCP) Closed Open after configuration Yes
SNMP 161 (UDP) Open Open after configuration Yes (with SNMPv3)
* For information on avoiding opening the port during diagnostics, see section Online
security diagnostics via port 8448 (Page 123).
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 39
Configuration
4.2 Configuration in STEP 7
Configuration in STEP 7
You configure the modules and networks in SIMATIC STEP 7. You will find the required
version in the section Software requirements (Page 23).
CP 1243-1
40 Operating Instructions, 04/2017, C79000-G8976-C365-03
Configuration
4.3 Addressing and authentication
IP address of the CP
Since the CP always establishes the connection with TCSB, a dynamic IP address can be
assigned to the CP by the Internet service provider.
To change the IP address during operation, refer also to the section Changing the IP
address during runtime (Page 119).
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 41
Configuration
4.4 Time-of-day synchronization
Note
Time-of-day synchronization of the CP
With applications that require time-of-day synchronization (e.g. telecontrol), you need to
synchronize the time of day of the CP regularly. If you do not synchronize the time of day of
the CP regularly, there may be deviations of several seconds per day in the time information
of the CP.
With security functions enabled, you need to enable time-of-day synchronization.
Note
Recommendation for setting the time
Synchronization with a external clock at intervals of approximately 10 seconds is
recommended. This achieves as small a deviation as possible between the internal time and
the absolute time.
CP 1243-1
42 Operating Instructions, 04/2017, C79000-G8976-C365-03
Configuration
4.4 Time-of-day synchronization
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 43
Configuration
4.4 Time-of-day synchronization
Note
Recommendation: Time-of-day synchronization only by 1 module
Only have the time of day of the station from an external time source synchronized by a
single module so that a consistent time of day is maintained within the station.
When the CPU takes the time from the CP, disable time-of-day synchronization of the CPU.
CP 1243-1
44 Operating Instructions, 04/2017, C79000-G8976-C365-03
Configuration
4.5 Communication types
Note
Forwarding the time to the CPU
Depending on the firmware version of the modules involved, the time-of-day of the CP is
forwarded to the CPU in different ways:
• Optional forwarding of the CP time to the CPU using a PLC tag
• Obligatory forwarding of the CP time to the CPU via the backplane bus
The forwarding of the CP time to the CPU depends on the firmware version of the CP and
the CPU. Note the following behaviour.
● CP firmware ≤ V2.1.6x
With this firmware version the CP can make the time-of-day available to the CPU as an
option via a PLC tag. When this PLC tag is read cyclically by the CPU, the CPU adopts
the CP time.
In the parameter group "Communication with the CPU", you can set whether or not the
current time of day of the CP will be made available to the CPU via a PLC tag. For TLC
tags, see parameter group "Communication with the CPU" of the CP.
● CP firmware ≥ V2.1.77 and CPU firmware ≥ V4.2
If both modules in the station have the named firmware versions, the time of day of the
CP is automatically forwarded to the CPU.
Since the CPU automatically adopts the CP time, you no longer require the forwarding
option using the PLC tag.
If for the CPU the option "CPU synchronizes the modules of the device" is enabled in
"PROFINET interface > Time synchronization", all smart modules of the station are
synchronized with the CPU time.
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 45
Configuration
4.6 Ethernet interface
4.6.1 CP identification
The parameter group is available only when telecontrol communication is enabled.
CP addressing
The parameter group is used for addressing and identification of the CP in the network.
● TeleControl Basic
You will find the parameters for the TeleControl Basic protocol in "Security", refer to the
section CP iIdentifcation with the TeleControl Basic protocol (Page 64).
● DNP3
The station address is the DNP address.
Entry of the station address (digits only). Permitted range of values: 1...65519.
● IEC
The station address is the “common address of the ASDU" or the address of the
information object.
Entry of the station address (digits only). Permitted range of values: 1...65534.
Time-of-day synchronization
For the configuration of the time-of-day synchronization read the section Time-of-day
synchronization (Page 42).
CP 1243-1
46 Operating Instructions, 04/2017, C79000-G8976-C365-03
Configuration
4.6 Ethernet interface
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 47
Configuration
4.6 Ethernet interface
Note
If the partner cannot be reached, connection establishment via the mobile wireless
network can take several minutes. This may depend on the particular network and current
network load.
Depending on your contract, costs may result from each connection establishment
attempt.
CP 1243-1
48 Operating Instructions, 04/2017, C79000-G8976-C365-03
Configuration
4.6 Ethernet interface
The value configured in TCSB is transferred by the telecontrol server to the CP the first
time the connection is established.
Each time the CP transfers data to TCSB and receives the acknowledgment from the
telecontrol server, the CP starts the watchdog cycle. When the watchdog cycle has
expired the CP sends a watchdog frame to the telecontrol server.
After sending a watchdog frame, the CP starts the watchdog monitoring time within which
the CP expects a reply from the telecontrol server. If the CP does not receive a reply from
the Telecontrol server within the monitoring time, it terminates and re-establishes the
connection.
Default setting: 30 s. Permitted range: 0...65535 s. If you enter 0 (zero), the function is
disabled.
● Key exchange interval
Here, you enter the interval in hours after which the key is exchanged again between the
CP and the telecontrol server. The key is a security function of the telecontrol protocol
used by the CP and TCSB V3.
Default setting: 8 s. Permitted range: 0...65535 s. If you enter 0 (zero), the function is
disabled.
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 49
Configuration
4.6 Ethernet interface
CP 1243-1
50 Operating Instructions, 04/2017, C79000-G8976-C365-03
Configuration
4.6 Ethernet interface
You will find details of how the image buffer and send buffer work as well as the options for
transferring data in the section Process image, type of transmission, event classes, triggers
(Page 97).
Note
Settings on the master
When configuring the monitoring times t1 and t2 make sure that you make the
corresponding settings on the master so that there are no unwanted error messages or
connection aborts.
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 51
Configuration
4.6 Ethernet interface
CP 1243-1
52 Operating Instructions, 04/2017, C79000-G8976-C365-03
Configuration
4.7 SNMP
4.7 SNMP
SNMP
The CP supports the following SNMP versions:
● SNMPv1
Available with security functions disabled.
Note that with this read and write access to the module is possible. In this case, other
settings are not possible.
The configuration of the community strings is only possible if the security functions are
enabled.
The CP uses the following community strings to authenticate access to its SNMP agent
via SNMPv1:
Access to the SNMP agent in the CP Community string for authentication in SNMPv1
*)
● SNMPv3
Available only when security functions are enabled
For information on the configuring SNMPv3, refer to the section SNMP (Page 70).
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 53
Configuration
4.8 Partner stations
Configuration
● "Enable SNMP"
If the option is enabled, communication via SNMPv1 is enabled on the CP.
If the option is disabled, queries from SNMP clients are not replied to by the CP either via
SNMPv1 or via SNMPv3.
Listener port
CP 1243-1
54 Operating Instructions, 04/2017, C79000-G8976-C365-03
Configuration
4.8 Partner stations
Connection to partner
● Partner IP address
IP address or host name (FQDN) of the partner. This can, for example, also be the FQDN
of a DynDNS service.
– Note on TeleControl Basic
If the CP is connected to a TCSB redundancy group (TCSB V3), here configure the
public IP address of the DSL router via which the telecontrol server can be reached
from the Internet. Set the port forwarding on the DSL router so that the public IP
address (external network) is led to the virtual IP address of the TCSB server PCs
(internal network). The station does not therefore receive any information telling it
which of the two computers of the redundancy group it is connected to.
See also section Addressing in the redundant TCSB system (Page 57).
● Connection monitoring
Only for TeleControl Basic and DNP3
When the function is enabled, the connection to the communications partner is monitored
by sending keepalive frames.
The TCP connection monitoring time is set for all TCP connections of the CP in the
parameter group of the Ethernet interface. The setting applies to all TCP connections of
the CP.
Here in the parameter group "Partner stations", the globally set TCP connection
monitoring time can be set separately for the partner. The value set here for the partner
overwrites the global value that was set in the "Ethernet interface (X1) > Advanced
options > TCP connection monitoring" parameter group.
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 55
Configuration
4.8 Partner stations
CP 1243-1
56 Operating Instructions, 04/2017, C79000-G8976-C365-03
Configuration
4.8 Partner stations
● Protocol type
Only for DNP3
Selection of the protocol type on the transport layer: TCP / UDP
● Partner port
Only with TeleControl Basic
Number of the listener port of the telecontrol server.
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 57
Configuration
4.8 Partner stations
Inter-station communication
In this table, you specify the S7 stations with which the current station will use inter-station
communication. Connections for inter-station communication run via the telecontrol server.
Partner
The partner number is assigned by the system. It is required during data point configuration
to assign data points to their communications partners.
For inter-station communication, the partner is addressed with the parameters "Project",
"Station" and "Slot".
Project
Here, enter the project number of the CP in the partner station. (Parameter group "Security >
CP identification" on the partner)
Station
Here, enter the station number of the CP in the partner station. (Parameter group "Security >
CP identification" on the partner)
CP 1243-1
58 Operating Instructions, 04/2017, C79000-G8976-C365-03
Configuration
4.8 Partner stations
Slot
Here, enter the slot number of the CP in the partner station via which the connection will be
established.
Frame memory
Activate the option for enabling inter-station communication.
The frames are stored in the send buffer (frame memory) of the CP if the connection is
disturbed. Note that the capacity of the frame memory is shared by all communications
partners.
Access ID
The access ID displayed here is formed from the hexadecimal values of project number,
station number and slot. The parameter of the type DWORD is allocated as follows:
● Bits 0 - 7: Slot
● Bits 8 - 20: Station number
● Bits 21 - 31: Project number
Advanced settings
● Partner monitoring time
If the CP does not receive a sign of life from the communications partner within the
configured time, the CP interprets this as a fault/error on the partner. The CP aborts the
connection and attempts to re-establish it.
If you enter 0, the function is deactivated.
● DNP3 level
Only for DNP3
Indicates the DNP3 implementation level supported by the CP
In the DNP3 specification, various levels of protocol conformity are and they describe the
supported range of functions (subset) of a master or a station. These levels
(implementation levels) are known as "DNP3 Application Layer protocol Level" and
abbreviated with DNP3-L1 to DNP3-L4.
For the communication between the CP and the master, the DNP3 level supported by the
master must be known.
The selection of the level used by the DNP3 CP which must correspond to that of the
connected master is set separately in STEP 7 for each individual communications partner
(DNP3 master).
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 59
Configuration
4.8 Partner stations
CP 1243-1
60 Operating Instructions, 04/2017, C79000-G8976-C365-03
Configuration
4.8 Partner stations
The fourth parameter "Frame memory size" decides the size of the send buffer on the CP for
frames of data points that are configured as an event.
● Cycle pause time
Wait time between two scan cycles of the CPU memory area
● Max. number of write jobs
Maximum number of write jobs to the CPU memory area within a CPU scan cycle
● Max. number of read jobs
Maximum number of low-priority read jobs from the CPU memory area within a CPU scan
cycle.
● Frame memory size
Here, you set the size of the frame memory for events (send buffer).
The size of the frame memory is divided equally among all configured communications
partners. You will find the size of the frame memory in the section Configuration limits
and performance data (Page 15).
You will find details of how the send buffer works (storing and sending events) as well as
the options for transferring data in the section Process image, type of transmission, event
classes, triggers (Page 97).
Watchdog bit
● CP monitoring
Via the watchdog bit the CPU can be informed of the status of the telecontrol
communication of the CP.
CP time of day
● CP time to CPU
Using this function, the CP can make its time of day available to the CPU.
You will find details in the STEP 7 information system.
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 61
Configuration
4.8 Partner stations
CP diagnostics
With the parameter group, you have the option of reading out advanced diagnostics data
from the CP using PLC tags.
● Enable advanced CP diagnostics
Enable the option to be able to use advanced CP diagnostics.
If the option is enabled, at least the "Diagnostics trigger tag" must be configured.
The following PLC tags for the individual items of diagnostics data can be enabled
selectively.
● Diagnostics trigger tag
If the PLC tag (BOOL) from the user program of the CPU is set to 1, the CP updates the
values of the PLC tags that can then be configured for the advanced diagnostics.
After writing the current values to the following PLC tags, the CP sets the "Diagnostics
trigger tag" to 0 signaling the CPU that the updated values can be read from the PLC
tags.
Note
Fast setting of the diagnostics trigger variable
Triggers must not be set faster than a minimum interval of 500 milliseconds.
CP 1243-1
62 Operating Instructions, 04/2017, C79000-G8976-C365-03
Configuration
4.9 Security
● VPN status
The PLC tag (BOOL) indicates whether a VPN tunnel is established:
– 0 = No VPN tunnel established
– 1 = VPN tunnel established
4.9 Security
You will find an overview of the range and use of the security functions in section Security
functions (Page 13).
For the configuration limits of the security functions refer to the section Configuration limits
and performance data (Page 15).
Parameter groups
If the security functions of the CP are enabled, you will find the following parameter groups
for configuring the CP:
● CP identification
Only with the TeleControl Basic protocol
Here, you configure parameters for authenticating the CP with the telecontrol server. You
will find detailed information about the parameters below.
● DNP3 security options
Only with the DNP3 protocol
Here, you configure protocol-specific security functions. You will find detailed information
about the parameters below.
● Firewall
See section Firewall (Page 67).
● Time synchronization
For the configuration of the time-of-day synchronization read the section Time-of-day
synchronization (Page 42).
● E-mail configuration
See section E-mail configuration (Page 69).
● Log settings
Here you make the settings for logging events relevant for security.
See section Log settings - Filtering of the system events (Page 70).
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 63
Configuration
4.9 Security
● SNMP
Here you make the settings for the SNMP agent on the CP.
See section SNMP (Page 70).
● Certificate manager
See section Certificate manager (Page 72).
In the global security settings of STEP 7 among other things you will find the following
parameter groups:
● VPN groups
Here you configure the VPN communication, refer to the section VPN (Page 74).
● User management
Here you configure the users, roles and rights for the TeleService access, refer to the
section Configuration of the TeleService access (Page 80).
CP 1243-1
64 Operating Instructions, 04/2017, C79000-G8976-C365-03
Configuration
4.9 Security
Partner'X'
Parameters
● Enable DNP3 security options
Enable the option if you want to use the security mechanisms.
● IKE mode
Selection of the mode for key exchange. Range of values:
– Aggressive Mode
The Aggressive Mode is somewhat faster but transfers the identity unencrypted.
– Main Mode
The Main Mode is the standard mode.
Default setting: Aggressive Mode
● Security statistics
Specifies whether the statistics of security events are sent to the master. Security events
are authentication requests to the CP. If the option is enabled, all authentication requests
with date, time and result are saved on the CP and sent to the master for further
evaluation.
Range of values:
– Do not send security statistics
– Send security statistics
Default setting: Do not send security statistics
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 65
Configuration
4.9 Security
● SHA-1 interlock
Setting to select whether the CP may use the secure hash algorithm SHA-1 if "SHA-256"
was configured as the Secure hash algorithm and the master does not support SHA-256.
Range of values:
– SHA-1 mode not allowed
The CP may not use SHA-1. If the master does not support SHA-256, no connection
will be established.
– SHA-1 mode allowed
The CP can use SHA-1 if the master does not support SHA-256.
Default setting: SHA-1 mode not allowed
● Secure hash algorithm (SHA)
Selection of the Secure Hash Algorithm (SHA)
Range of values:
– SHA-1
– SHA-256
Default setting: 256
● Key wrap algorithm
Selection of the Advanced Encryption Standard (AES)
Range of values:
– AES-128
– AES-256
Default setting: AES-128
● Key length
Specifies the length of the pre-shared key in bytes.
Permitted range: 16 - 128 Depending on the secure hash algorithm configured in STEP 7
above, the following lengths are preset:
– For SHA-1: 16
– For SHA-256: 32
The value 0 (zero) is not permitted.
● Max. number of statistics queries
If the configured number of statistics queries of the master is exceeded within the key
exchange interval, the CP enters a message in the diagnostics buffer of the CPU.
Range of values: 2...255 Default setting: 5
CP 1243-1
66 Operating Instructions, 04/2017, C79000-G8976-C365-03
Configuration
4.9 Security
4.9.4 Firewall
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 67
Configuration
4.9 Security
4.9.4.3 Firewall settings for configured connection connections via a VPN tunnel
See also
Settings for online security diagnostics and downloading to station with the firewall activated
(Page 68)
4.9.4.4 Settings for online security diagnostics and downloading to station with the firewall
activated
CP 1243-1
68 Operating Instructions, 04/2017, C79000-G8976-C365-03
Configuration
4.9 Security
7. In the table, insert a new IP rule for the previously created global services as follows:
– Action: Allow; "From external -> To station " with the globally created "Echo request"
service
– Action: Allow; "From station -> to external" with the globally created "Echo reply"
service
8. For the IP rule for the Echo Request, enter the IP address of the engineering station in
"Source IP address". This ensures that only ICMP frames (ping) from your engineering
station can pass through the firewall.
Requirements
The following requirements must be met in the configuration for sending e-mails:
● The security functions are enabled.
● The time of the CP is synchronized.
● In the "E-mail configuration" entry, the protocol to be used and the data for access to the
e-mail server are configured.
E-mail configuration
With the default setting of the SMTP port 25, the module transfers unencrypted e-mails.
If your e-mail service provider only supports encrypted transfer, use one of the following
options:
● Port no. 587
By using STARTTLS, the module sends encrypted e-mails to the SMTP server of your e-
mail service provider.
Recommendation: If your e-mail provider offers both options (STARTTLS / SSL/TLS), you
should use STARTTLS with port 587.
● Port no. 465
By using SSL/TLS (SMTPS), the module sends encrypted e-mails to the SMTP server of
your e-mail service provider.
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 69
Configuration
4.9 Security
Communications problems if the value for system events is set too high
If the value for filtering the system events is set too high, you may not be able to achieve the
maximum performance for the communication. The high number of output error messages
can delay or prevent the processing of the communications connections.
In "Security > Log settings > Configure system events", set the "Level:" parameter to the
value "3 (Error)" to ensure the reliable establishment of the communications connections.
4.9.7 SNMP
SNMP
The range of functions of the CP for SNMP can be found in the section SNMP (Page 125).
If the security functions are enabled, you have the following selection and setting options.
SNMP
● "Enable SNMP"
If the option is enabled, communication via SNMP is released on the device. As default,
SNMPv1 is enabled.
If the option is disabled, queries from SNMP clients are not replied to either via SNMPv1
or via SNMPv3.
CP 1243-1
70 Operating Instructions, 04/2017, C79000-G8976-C365-03
Configuration
4.9 Security
● "Use SNMPv1"
Enables the use of SNMPv1 for the CP. For information on the configuration of the
required community strings see below (SNMPv1).
● "Use SNMPv3"
Enables the use of SNMPv3 for the CP. For information on the configuration of the
required algorithms see below (SNMPv3).
SNMPv1
The community strings need to be sent along with queries to the CP via SNMPv1.
● "Reading community string"
The string is required for read access.
Leave the preset string "public" or configure a string.
● "Allow write access"
If the option is enabled write access to the CP is released and the corresponding
community string can be edited.
● "Writing community string"
The string is required for write access and can also be used for read access.
Leave the preset string "private" or configure a string.
Note the use of lowercase letters with the preset community strings!
SNMPv3
The algorithms need to be configured for encrypted access to the CP via SNMPv3.
● "Authentication algorithm"
Select the authentication method to be used from the drop-down list.
● "Encryption algorithm"
Select the encryption method to be used from the drop-down list.
Note the information on security of the possible algorithms in the online help of the SCT.
User management
In the user management that you will find in the global security settings, assign the various
users their role.
Below the properties of the roles you can see the rights list of the particular role, for example
the various types of access using SNMP. For new roles, you can freely configure individual
rights.
You will find information on users, roles and the password policy in the information system of
STEP 7.
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 71
Configuration
4.9 Security
Assignment of certificates
If you use communication with authentication for the module, for example SSL/TLS for
secure transfer of e-mails, certificates are required. You need to import certificates of non-
Siemens communications partners into the STEP 7 project and download them to the
module with the configuration data:
1. Import the certificates of the communications partners using the certificate manager in the
global security settings.
2. Then assign the imported certificates to the module in the table below the local security
settings of the module.
For a description of the procedure, refer to the section Handling certificates (Page 72).
You will find further information in the STEP 7 information system.
Note
No certificate with security functions disabled.
If the security functions of the CP are disabled in the STEP 7 project, no certificate will be
generated for the CP.
For the secure transfer of e-mails via SSL/TLS and SSL certificate is created for the CP. It is
visible in STEP 7 in "Global security settings > Certificate manager > Device certificates".
The table "Device certificates" shows the issuer, validity, use of a certificate
(service/application) and the use of a key. You can call up further information about a
certificate by selecting the certificate in the table and selecting the shortcut menu "Show".
The table also shows all other certificates generated by STEP 7 and all imported certificates.
CP 1243-1
72 Operating Instructions, 04/2017, C79000-G8976-C365-03
Configuration
4.9 Security
So that the CP can communicate with non-Siemens partners when the security functions are
enabled, the relevant certificates of the partners must be exchanged during communication.
To supply the CP with third-party certificates, follow the steps below:
1. Importing third-party certificates from communications partners
⇒ Global security settings of the project (certificate manager)
2. Assigning certificates locally
⇒ Local security settings of the CP ("Certificate manager" table)
These two steps are described in the next two sections.
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 73
Configuration
4.9 Security
You export the certificate of the CP for communications partners from third-party vendors in
much the same way as when importing (see above). Follow the steps outlined below:
1. In the STEP 7 project open the global certificate manager:
Global security settings > Certificate manager
2. Open the "Device certificates" tab.
3. In the table select the row with the required certificate and select the shortcut menu
"Export".
4. Save the certificate in the file system of the PC of the connected engineering station.
Now you can transfer the exported certificate of the CP to the system of the third-party
vendor.
4.9.10 VPN
VPN tunnel
Virtual Private Network (VPN) is a technology for secure transportation of confidential data in
public IP networks, for example the Internet. With VPN, a secure connection (tunnel) is set
up and operated between two secure IT systems or networks via a non-secure network.
One of the main features of the VPN tunnel is that it forwards all frames even from protocols
of higher layers (HTTP, FTP etc.).
The data traffic between two network components is transported practically unrestricted
through another network. This allows entire networks to be connected together via a
neighboring or intermediate network.
CP 1243-1
74 Operating Instructions, 04/2017, C79000-G8976-C365-03
Configuration
4.9 Security
Properties
● VPN forms a logical subnet that is embedded in a neighboring (assigned) network. VPN
uses the usual addressing mechanisms of the assigned network, however in terms of the
data, it transports its own frames and therefore operates independent of the rest of this
network.
● VPN allows communication of the VPN partners with the assigned network.
● VPN is based on tunnel technology and can be individually configured.
● Communication between the VPN partners is protected from eavesdropping or
manipulation by using passwords, public keys or a digital certificate (authentication).
Areas of application
● Local area networks can be connected together securely via the Internet ("site-to-site"
connection).
● Secure access to a company network ("end-to-site" connection)
● Secure access to a server ("end-to-end" connection)
● Communication between two servers without being accessible to third parties (end-to-end
or host-to-host connection)
● Ensuring information security in networked automation systems
● Securing the computer systems including the associated data communication within an
automation network or secure remote access via the Internet
● Secure remote access from a PC/programming device to automation devices or networks
protected by security modules via public networks.
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 75
Configuration
4.9 Security
Requirements
To allow a VPN tunnel to be created for S7 communication between two S7 stations or
between an S7 station and an engineering station with a security CP (for example CP 1628),
the following requirements must be met:
● The two stations have been configured.
● The CPs in both stations must support the security functions.
● The Ethernet interfaces of the two stations are located in the same subnet.
Note
Communication also possible via an IP router
Communication between the two stations is also possible via an IP router. To use this
communications path, however, you need to make further settings.
Procedure
To create a VPN tunnel, you need to work through the following steps:
1. Creating a security user
If the security user has already been created: Log on as a user.
2. Select the "Activate security features" check box
3. Creating the VPN group and assigning security modules
4. Configure the properties of the VPN group
5. Configure local VPN properties of the two CPs
You will find a detailed description of the individual steps in the following paragraphs of this
section.
CP 1243-1
76 Operating Instructions, 04/2017, C79000-G8976-C365-03
Configuration
4.9 Security
Note
Current date and current time on the CP for VPN connections
Normally, to establish a VPN connection and the associated recognition of the certificates to
be exchanged, the current date and the current time are required on both stations.
The establishment of a VPN connection to an engineering station that is also the telecontrol
server at the same time (TCSB installed), runs as follows along with the time of day
synchronization of the CP:
On the engineering station (with TCSB), you want the CP to establish a VPN connection.
The VPN connection is established even if the CP does not yet have the current time.
Otherwise the certificates used are evaluated as valid and the secure communication will
work.
Following connection establishment, the CP synchronizes its time of day with the PC
because the telecontrol server is the time master if telecontrol communication is enabled.
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 77
Configuration
4.9 Security
Note
Specifying the VPN properties of the CPs
You specify the VPN properties of the CPs in the "Security" > "Firewall" > "VPN" parameter
group of the relevant module.
Result
You have created a VPN tunnel. The firewalls of the CPs are activated automatically: The
"Activate firewall" check box is selected as default when you create a VPN group. You
cannot deselect the check box.
Download the configuration to all modules that belong to the VPN group.
CP 1243-1
78 Operating Instructions, 04/2017, C79000-G8976-C365-03
Configuration
4.9 Security
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 79
Configuration
4.9 Security
Configure the permission for VPN connection establishment for the CP as a passive
subscriber as follows:
1. In STEP 7, go to the devices and network view.
2. Select the CP.
3. Open the parameter group "VPN“ in the local security settings.
4. For each VPN connection with the CP as a passive VPN subscriber, change the default
setting "Initiator/Responder" to the setting "Responder".
4.9.10.7 SYSLOG
CP 1243-1
80 Operating Instructions, 04/2017, C79000-G8976-C365-03
Configuration
4.9 Security
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 81
Configuration
4.10 Data points
Note
Number of PLC tags
Remember the maximum possible number of PLC tags the can be used for data point
configuration in the section Configuration limits and performance data (Page 15).
The formats and S7 data types of the PLC tags that are compatible with the protocol-specific
data point types of the module can be found in the section Datapoint types (Page 89).
CP 1243-1
82 Operating Instructions, 04/2017, C79000-G8976-C365-03
Configuration
4.10 Data points
Creating obects
With the data point or message editor open, create a new object (data point / message) by
double clicking "<Add object>" in the first table row with the grayed out entry.
A preset name is written in the cell. You can change the name to suit your purposes but it
must be unique within the module.
You configure the remaining properties of every object using the drop-down lists of the other
table columns and using the parameter boxes shown at the bottom of the screen.
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 83
Configuration
4.10 Data points
Note
Assignment of parameter values to PLC tags
The mechanisms described here also apply when you need to assign the value of a
parameter to a PLC tag. The input boxes fro the PLC tag (e.g.: PLC tag for partner status
support the functions described here for selecting the PLC tag.
CP 1243-1
84 Operating Instructions, 04/2017, C79000-G8976-C365-03
Configuration
4.10 Data points
When it does, click immediately on the column header. The column width adapts itself
to the broadest entry in this column.
● Showing / hiding columns
You call this function using the shortcut menu that opens when you click on a column
header with the right mouse key.
● Copying, pasting, cutting and deleting objects
If you click in a parameter box of an object in the table with the right mouse key, you can
use the functions named with the shortcut menu (copy, paste, cut, delete).
You can paste cut or copied objects within the table or in the first free row below the
table.
When it is exported the data point information of a module is written to a CSV file.
Export
When you call the export function, the export dialog opens. Here, you select the module or
modules of the project whose data point information needs to be exported. When necessary,
you can export the data points of all modules of the project at one time.
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 85
Configuration
4.10 Data points
In the export dialog, you can select the storage location in the file directory. When you export
the data of a module you can also change the preset file name.
When you export from several modules, the files are formed with preset names made up of
the station name and module name.
The file itself contains the following information in addition to the data point information:
● Module name
● Module type
● CPU name
● CPU type
CP 1243-1
86 Operating Instructions, 04/2017, C79000-G8976-C365-03
Configuration
4.10 Data points
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 87
Configuration
4.10 Data points
Note:
Modules with the same telecontrol protocol are compatible with each other:
● TeleControl Basic
All SIMATIC NET modules with the TeleControl Basic protocol:
CP 1243-1, CP 1242-7 GPRS V2, CP 1243-7 LTE, CP 1542SP-1 IRC
● ST7
CP 1243-8 IRC, TIM modules capable of ST7
● DNP3
CP 1243-1, CP 1243-8 IRC, TIM modules capable of DNP3
● IEC
CP 1243-1, CP 1243-8 IRC
Data points can be imported and exported between compatible modules.
Assignment repair
If you have named the PLC tags in a station into which you want to import differently from
the station from which the CSV file was exported, the assignment between data point and
PLC tag is lost when you import.
You then have the option to either rename the existing PLC tags appropriately or add
missing PLC tags. You can then repair the assignment between unassigned data points and
PLC tags. This function is available either via the shortcut menu of the module (see above)
or with the following icon to the upper left in the data point editor:
If a PLC tag with a matching name is found for a data point by the repair function, the
assignment is restored. However the data type of the tag is not checked.
After the assignment repair make sure that you check whether the newly assigned PLC tags
are correct.
CP 1243-1
88 Operating Instructions, 04/2017, C79000-G8976-C365-03
Configuration
4.10 Data points
Note
Effect of the change of arrays for data points
If an array is modified later, the data point must be recreated.
Format (memory requirements) Data point type Direction S7 data types Operand area
Bit Digital input in Bool I, Q, M, DB
Digital output in Bool Q, M, DB
Byte Digital input in Byte, Char, USInt I, Q, M, DB
Digital output out Byte, Char, USInt Q, M, DB
Integer with sign (16 bits) Analog input in Int I, Q, M, DB
Analog output out Int Q, M, DB
Counter (16 bits) Counter input in Word, UInt I, Q, M, DB
Integer with sign (32 bits) Analog input in DInt Q, M, DB
Analog output out DInt Q, M, DB
Counter (32 bits) Counter input in UDInt, DWord I, Q, M, DB
Floating-point number with sign (32 Analog input in Real Q, M, DB
bits) Analog output out Real Q, M, DB
Floating-point number with sign (64 Analog input out LReal Q, M, DB
bits) Analog output out LReal Q, M, DB
Data block (1 .. 64 bytes) Data in / out ARRAY 1) DB
Data in / out ARRAY 1) DB
1) For the possible formats of the ARRAY data type, refer to the following section.
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 89
Configuration
4.10 Data points
Format (memory require- Data point type CP DNP3 object Direction S7 data types Operand area
ments) [Data point type TIM] group
[variations]
Bit Binary Input 1 [1, 2] in Bool I, Q, M, DB
Binary Input Event 2 [1, 2] in Bool I, Q, M, DB
Binary Output 1) 10 [2] out Bool Q, M, DB
Binary Output Event 1) 11 [1, 2] out Bool Q, M, DB
Binary Command 12 [1] out Bool Q, M, DB
Integer (16 bits) Counter Static 20 [2] in UInt, Word I, Q, M, DB
Frozen Counter 2) 21 [2, 6] in UInt, Word I, Q, M, DB
Counter Event 22 [2, 6] in UInt, Word I, Q, M, DB
Frozen Counter 23 [2, 6] in UInt, Word I, Q, M, DB
Event 3)
Analog Input 30 [2] in Int I, Q, M, DB
Analog Input Event 32 [2] in Int I, Q, M, DB
Analog Output Sta- 40 [2] out Int Q, M, DB
tus 4)
Analog Output 41 [2] out Int Q, M, DB
Analog Output 42 [2, 4] out Int Q, M, DB
Event 4)
Integer (32 bits) Counter Static 20 [1] in DWord I, Q, M, DB
Frozen Counter 2) 21 [1, 5] in DWord I, Q, M, DB
Counter Event 22 [1, 5] in DWord I, Q, M, DB
Frozen Counter 23 [1, 5] in DWord I, Q, M, DB
Event 3)
Analog Input 30 [1] in DInt Q, M, DB
Analog Input Event 32 [1] in DInt Q, M, DB
Analog Output Sta- 40 [1, 3] out DInt Q, M, DB
tus 4)
Analog Output 41 [1] out DInt Q, M, DB
Analog Output 42 [1] out DInt Q, M, DB
Event 4)
CP 1243-1
90 Operating Instructions, 04/2017, C79000-G8976-C365-03
Configuration
4.10 Data points
Format (memory require- Data point type CP DNP3 object Direction S7 data types Operand area
ments) [Data point type TIM] group
[variations]
Floating-point number (32 Analog Input 30 [5] in Real Q, M, DB
bits) Analog Input Event 32 [5, 7] in Real Q, M, DB
Analog Output Sta- 40 [3] out Real Q, M, DB
tus 4)
Analog Output 41 [3] out Real Q, M, DB
Analog Output 42 [5, 7] out Real Q, M, DB
Event 4)
Floating-point number (64 Analog Input 30 [6] in LReal Q, M, DB
bits) Analog Input Event 32 [6, 8] in LReal Q, M, DB
Analog Output 41 [4] out LReal Q, M, DB
Analog Output 42 [6, 8] out LReal Q, M, DB
Event 4)
Data block (1...64 Octet String / Oc- 110 [ - ] in, out 5) DB
bytes) 5) tet String Output
Octet String Event 5) 111 [ - ] in, out 5) DB
1) This object group can be configured in the Data point editor of STEP 7 using the substitute object group 12.
2) This object group can be configured in the Data point editor of STEP 7 using the substitute object group 20.
3) This object group can be configured in the Data point editor of STEP 7 using the substitute object group 22.
4) This object group can be configured in the Data point editor of STEP 7 using the substitute object group 41.
5) With these data point types, contiguous memory areas up to a size of 64 bytes can be transferred. All S7 data types with
a size between 1 and 64 bytes are compatible.
Substitute object groups (of the table footnotes 1), 2), 3), 4))
The initial data point types of the following object groups can be configured using the
substitute object groups listed above:
● 10 [2]
● 11 [1, 2]
● 21 [1, 2, 5, 6]
● 23 [1, 2, 5, 6]
● 40 [1, 2, 3]
● 42 [1, 2, 4, 5, 6, 7, 8]
To configure the DNP3 CP, use the specified substitute object group.
Assign each data point on the master using the configurable data point index in STEP 7. The
data point of the DNP3 CP is then assigned to the corresponding data point on the master.
Example of configuring the data point Binary Output (10 [2])
The data point is configured as follows:
On the DNP3 CP as Binary Command (12 [1])
On the master as Binary Output (10 [2])
With the data point types Binary Output Event (11) and Analog Output Event (42), you also
need to enable mirroring; refer to the next section.
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 91
Configuration
4.10 Data points
Configuration of the mirroring back for output events (object groups 11 and 42)
You first create the data point types Binary Output Event (object group 11) and Analog
Output Event (object group 42) as described above as data points of the object groups 12 or
41.
The local values of these two object groups can be monitored for change and the changes
transferred to the master (). Changing a local value can, for example, be caused by manual
operator input on site.
To allow the value resulting from local events or interventions to be transferred to the master,
the data point in question requires a channel for mirroring back. You configure this mirroring
back function is configured using the "Value monitoring" option in data point configuration,
General tab.
Remember that to use the mirror back function, you need to interconnect the local values in
the controller with the relevant PLC tag of the data point.
Format (memory Data point type IEC type Direction S7 data types Operand area
requirements)
Bit Single-point information <1> in Bool I, Q, M, DB
Single-point information with time tag <30> in Bool I, Q, M, DB
CP56Time2a 1)
Single command <45> out Bool Q, M, DB
Single command with time tag <58> out Bool Q, M, DB
CP56Time2a 1)
Double command with time tag <59> out Bool Q, M, DB
CP56Time2a 1)
Byte Step position information <5> in Byte, USInt I, Q, M, DB
Step position information with time <32> in Byte, USInt I, Q, M, DB
tag CP56Time2a 1)
Regulating step command with time <60> out Byte, USInt Q, M, DB
tag CP56Time2a 1)
Integer (16 bits) Measured value, normalized value <9> in Int I, Q, M, DB
Measured value, normalized value <34> in Int I, Q, M, DB
with time tag CP56Time2a 1)
Measured value, scaled value <11> in Int I, Q, M, DB
Measured value, scaled value with <35> in Int I, Q, M, DB
time tag CP56Time2a 1)
Set point command, normalised <48> out Int Q, M, DB
value
Set point command, scaled value <49> out Int Q, M, DB
Set point command, normalised <61> out Int Q, M, DB
value with time tag CP56Time2a 1)
Set point command, scaled value <62> out Int Q, M, DB
with time tag CP56Time2a 1)
CP 1243-1
92 Operating Instructions, 04/2017, C79000-G8976-C365-03
Configuration
4.10 Data points
Format (memory Data point type IEC type Direction S7 data types Operand area
requirements)
Integer (32 bits) Bitstring of 32 bits <7> in UDInt, DWord I, Q, M, DB
Bitstring of 32 bits with time tag <33> in UDInt, DWord I, Q, M, DB
CP56Time2a 1)
Integrated totals <15> in UDInt, DWord I, Q, M, DB
Integrated totals with time tag <37> in UDInt, DWord I, Q, M, DB
CP56Time2a 1)
Bitstring of 32 bits <51> out UDInt, DWord Q, M, DB
Bitstring of 32 bits with time tag <64> out UDInt, DWord Q, M, DB
CP56Time2a 1)
Floating-point Measured value, short floating point <13> in Real Q, M, DB
number (32 bits) number
Measured value, short floating point <36> in Real Q, M, DB
number with time tag CP56Time2a 1)
Set point command, short floating <50> out Real Q, M, DB
point number
Set point command, short floating <63> out Real Q, M, DB
point with time tag CP56Time2a 1)
Data block Double-point information <3> in 2) DB
(1...2 Bit) 2) Double-point information with time <31> in 2) DB
tag CP56Time2a 1)
Double command <46> out 2) DB
Regulating step command <47> out 2) DB
Double command with time tag <59> out 2) DB
CP56Time2a 1)
Regulating step command with time <60> out 2) DB
tag CP56Time2a 1)
Data block Bitstring of 32 bits 3) <7> in 3) DB
(1...32 Bit) 3)
Bitstring of 32 bits with time tag <33> in 3) DB
CP56Time2a 1) 3)
Bitstring of 32 bits 3) <51> out 3) DB
Bitstring of 32 bits with time tag <64> out 3) DB
CP56Time2a 1) 3)
1) For the format of the time stamp, see the following section.
2) For these data point types, create a data block with an array of precisely 2 bool.
3) With these data point types, contiguous memory areas up to a size of 32 bits can be transferred. Only the S7 Bool data
type is compatible.
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 93
Configuration
4.10 Data points
Note
Index for data points with inter-station communication
Note that for inter-station communication with a CP in another S7 station, the indexes of the
two corresponding data points (data point pair) must be identical on the sending and
receiving CP.
For information on the configuration, refer to the section Partner configuration with
TeleControl Basic data points. (Page 112).
CP 1243-1
94 Operating Instructions, 04/2017, C79000-G8976-C365-03
Configuration
4.10 Data points
Status identifiers
The status identifiers of the data points listed in the following tables are transferred along
with the value in each frame to the communications partner. They can be evaluated by the
communications partner.
The entries in the table row "Significance" relate to the entry in the table row "Bit status".
Bit 7 6 5 4 3 2 1 0
Flag name - NON_ Substituted LOCAL_ CARRY OVER_ RESTART ONLINE
EXISTENT FORCED RANGE
Meaning - Data point Substitute Local opera- Counted Limit value Value not Value is
does not value tor control value over- of the ana- yet updated valid
exist or S7 flow before log prepro- after start
address reading the cessing
unreachable value overshot /
undershot
Bit status (always 1 1 1 1 1 1 1
0)
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 95
Configuration
4.10 Data points
Bit 7 6 5 4 3 2 1 0
Flag name - - - LOCAL_ DISCONTI OVER_ RESTART ONLINE
FORCED NUITY RANGE
Meaning - - - Local opera- Counted Limit value of Value not yet Value is valid
tor control value over- the analog updated after
flow before prepro- start
reading the cessing over-
value shot /
undershot
Bit status (always (always (always 1 1 1 1 1
0) 0) 0)
Bit 7 6 5 4 3 2 1 0
Flag name - - SB - CY OV NT IV
substituted carry overflow not topical invalid
Meaning - - Substitute - Counted Value range Value not Value is valid
value value over- exceeded, updated
flow before analog value
reading the
value
Bit status (always (always 1 (always 1 1 1 0
0) 0) 0)
CP 1243-1
96 Operating Instructions, 04/2017, C79000-G8976-C365-03
Configuration
4.10 Data points
You can prioritize the data points in STEP 7 in the data point configuration in the "General"
tab with the "Read cycle" parameter. There you will find the two following options for input
data points:
● Fast cycle
● Normal cycle
The data points are read according to the method described below.
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 97
Configuration
4.10 Data points
Data points are configured as a static value or as an event using the "Type of transmission"
parameter (see below):
● Transfer after call: No event / static value
Static values are entered in the image memory (process image of the CP).
● Triggered: event
The values of data points configured as an event are also entered in the image memory
of the CP.
The values of events are also entered in the send buffer of the CP.
With DNP3, the value of the event is sent unsolicited to the communications partner if this
function is enabled by the master.
CP 1243-1
98 Operating Instructions, 04/2017, C79000-G8976-C365-03
Configuration
4.10 Data points
Trigger
Trigger types
Various trigger types are available for event-driven transfer:
● Threshold value trigger
The value of the data point is transferred when this reaches a certain threshold. The
threshold is calculated as the difference compared with the last stored value, refer to the
section Threshold value trigger (Page 101).
● Time trigger
The value of the data point is transferred at configurable intervals or at a specific time of
day.
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 99
Configuration
4.10 Data points
● Event trigger
The value of the data point is transferred when a configurable trigger signal is fired. As
the trigger signal, the edge change (0 → 1) of a trigger bit is evaluated that is set by the
user program. When necessary, a separate trigger bit can be configured for each data
point.
Resetting the trigger tag in the bit memory area / DB:
If the memory area of the trigger tag is in the bit memory or in a data block, the trigger tag
is reset to zero when the data point value is transferred.
Trigger
Data points are configured as a static value or as an event using the "Type of transmission"
parameter:
CP 1243-1
100 Operating Instructions, 04/2017, C79000-G8976-C365-03
Configuration
4.10 Data points
Note
Fast setting of triggers
Triggers must not be set faster than a minimum interval of 500 milliseconds. This also
applies to hardware triggers (input area).
Note
Hardware trigger
You need to reset hardware triggers via the user program
Transmission mode
The transmission mode of a frame is set in the "Trigger" tab of the data point. With the
option, you specify whether messages of events are sent immediately or following a delay:
● Immediate transfer - Spontaneous
The value is transferred immediately.
● Buffered transfer - Conditionally spontaneous
The value is transferred only when one of the following conditions is fulfilled:
– The communications partner queries the station.
– The value of another event with the transmission mode “Spontaneous" is transferred.
Note
Threshold value trigger: Calculation only after "Analog value preprocessing"
Note that the analog value preprocessing is performed before the check for a configured
threshold value and before calculating the threshold value.
This affects the value that is configured for the threshold value trigger.
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 101
Configuration
4.10 Data points
Note
No Threshold value trigger if Mean value generation is configured
If mean value generation is configured, no threshold value trigger can be configured for the
analog value event involved.
For the time sequence of the analog value preprocessing refer to the section Analog value
preprocessing (Page 103).
Function
If the process value deviates by the amount of the threshold value, the process value is
saved.
Two methods are used to calculate the threshold value deviation:
● Absolute method
With binary and counter values as well as with analog values with configured mean value
generation, the absolute method is used to calculate the threshold value deviation.
● Integrative method
With analog values without configured mean value generation, the integrating method is
used to calculate the threshold value deviation.
In the integration threshold value calculation, it is not the absolute value of the deviation
of the process value from the last stored value that is evaluated but rather the integrated
deviation.
Absolute method
For each binary value a check is made to determine whether the current (possibly smoothed)
value is outside the threshold value band. The current threshold value band results from the
last saved value and the amount of the configured threshold value:
● Upper limit of the threshold value band: Last saved value + threshold value
● Lower limit of the threshold value band: Last saved value - threshold value
As soon as the process value reaches the upper or lower limit of the threshold value band,
the value is saved. The newly saved value serves as the basis for calculating the new
threshold value band.
Integrative method
The integration threshold value calculation works with a cyclic comparison of the integrated
current value with the last stored value. The calculation cycle in which the two values are
compared is 500 milliseconds.
(Note: The calculation cycle must not be confused with the scan cycle of the CPU memory
areas).
The deviations of the current process value are totaled in each calculation cycle. The trigger
is set only when the totaled value reaches the configured value of the threshold value trigger
and a new process value is entered in the send buffer.
The method is explained based on the following example in which a threshold value of 2.0 is
configured.
CP 1243-1
102 Operating Instructions, 04/2017, C79000-G8976-C365-03
Configuration
4.10 Data points
Table 4- 7 Example of the integration calculation of a threshold value configured with 2.0
Time [s] Process value Current process Absolute deviation Integrated devia-
(calculation cycle) stored in the value from the stored tion
send buffer value
0 20.0 20.0 0 0
0.5 20.3 +0.3 0.3
1.0 19.8 -0.2 0.1
1.5 20.2 +0.2 0.3
2.0 20.5 +0.5 0.8
2.5 20.3 +0.3 1.1
3.0 20.4 +0.4 1.5
3.5 20.5 20.5 +0.5 2.0
4.0 20.4 -0.1 -0.1
4.5 20.1 -0.4 -0.5
5.0 19.9 -0.6 -1.1
5.5 20.1 -0.4 -1.5
6.0 19.9 19.9 -0.6 -2.1
With the changes in the process value shown in the example, the threshold value trigger
configured with 2.0 fires twice:
● At the time 3.5 s: The value of the integrated deviation is at 2.0. The new process value
stored in the send buffer is 20.5.
● At the time 6.0 s: The value of the integrated deviation is at 2.1. The new process value
stored in the send buffer is 19.9.
In this example, if a deviation of the process value of approximately 0.5 should fire the
trigger, then with the behavior of the process value shown here a threshold value of
approximately 1.5 ... 2.5 would need to be configured.
Note
Restrictions due to configured triggers
The analog value preprocessing options "Fault suppression time", "Limit value calculation"
and "smoothing" are not performed if no threshold value trigger is configured for the relevant
data point.. In these cases, the read process value of the data point is entered in the image
memory of the CP before the preprocessing cycle of the threshold value calculation (500 ms)
elapses.
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 103
Configuration
4.10 Data points
CP 1243-1
104 Operating Instructions, 04/2017, C79000-G8976-C365-03
Configuration
4.10 Data points
The 500 millisecond cycle is started by the integrative threshold value calculation. In this
cycle, the values are saved even when the following preprocessing options are enabled:
● Unipolar transfer
● Fault suppression time
● Limit value calculation
● Smoothing
Note
Restricted preprocessing options if mean value generation is configured
If you configure mean value generation for an analog value event, the following
preprocessing options are not available:
• Unipolar transfer
• Fault suppression time
• Smoothing
Function
With this parameter, acquired analog values are transferred as mean values.
If mean value generation is active, it makes sense to configure a time trigger..
The current values of an analog data point are read in a 100 millisecond cycle and totaled.
The number of read values per time unit depends on the read cycle of the CPU and the CPU
scan cycle of the CP.
The mean value is calculated from the accumulated values as soon as the transfer is
triggered by a trigger. Following this, the accumulation starts again so that the next mean
value can be calculated.
The mean value can also be calculated if the transmission of the analog value message is
triggered by a request from the communications partner. The duration of the mean value
calculation period is then the time from the last transmission (for example triggered by the
trigger) to the time of the request. Once again, the accumulation restarts so that the next
mean value can be calculated.
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 105
Configuration
4.10 Data points
The calculation of a new mean value is then started. If the analog value remains in the
overflow or underflow range, one of the two values named is again saved as an invalid mean
value and sent when the next message is triggered.
Note
Fault suppression time > 0 configured
If you have configured an error suppression time and then enable mean value generation,
the value of the error suppression time is grayed out but no longer used. If mean value
generation is enabled, the error suppression time is set to 0 (zero) internally.
Unipolar transfer
Restrictions
Unipolar transfer cannot be configured at the same time as mean value generation. Enabling
unipolar transfer has no effect when mean value generation is activated.
Function
With unipolar transfer, negative values are corrected to zero. This can be desirable if values
from the underrange should not be transferred as real measured values.
Exception: With process data from input modules, the value -32768 / 8000h for wire break of
a live zero input is transferred.
With a software input, on the other hand, all values lower than zero are corrected to zero.
Restrictions
The fault suppression time cannot be configured at the same time as mean value generation.
A configured value has no effect when mean value generation is activated.
Function
A typical use case for this parameter is the suppression of peak current values when starting
up powerful motors that would otherwise be signaled to the control center as a disruption.
The transmission of an analog value in the overflow (7FFFh) or underflow range (8000h) is
suppressed for the specified time. The value 7FFFH or 8000H is only sent after the fault
suppression time has elapsed, if it is still pending.
If the value returns to the measuring range before the fault suppression time elapses, the
current value is transferred.
CP 1243-1
106 Operating Instructions, 04/2017, C79000-G8976-C365-03
Configuration
4.10 Data points
Input modules
The suppression is adjusted to analog values that are acquired directly by the S7 analog
input modules as raw values. These modules return the specified values for the overflow or
underflow range for all input ranges (also for live zero inputs).
An analog value in the overflow range (32767 / 7FFFh) or underflow range (-32768 / 8000h)
is not transferred for the duration of the fault suppression time. This also applies to live zero
inputs. The value in the overflow/underflow range is only sent after the fault suppression time
has elapsed, if it is still pending.
Smoothing factor
Restrictions
The smoothing factor cannot be configured at the same time as mean value generation. A
configured value has no effect when mean value generation is activated.
Function
Analog values that fluctuate quickly can be evened out using the smoothing function.
The smoothing factors are calculated according to the following formula as with S7 analog
input modules.
where
yn = smoothed value in the current cycle
xn = value acquired in the current cycle n
k = smoothing factor
The following values can be configured for the module as the smoothing factor.
● 1 = No smoothing
● 4 = Weak smoothing
● 32 = Medium smoothing
● 64 = Strong smoothing
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 107
Configuration
4.10 Data points
Function
In these two input boxes, you can set a limit value in the direction of the start of the
measuring range or in the direction of the end of the measuring range. You can also
evaluate the limit values, for example as the start or end of the measuring range.
CP 1243-1
108 Operating Instructions, 04/2017, C79000-G8976-C365-03
Configuration
4.10 Data points
Range Raw value (16 bits) of the PLC tag Module output [mA] Measuring
Decimal Hexadecimal 0 .. 20 -20 .. +20 4 .. 20 range [%]
Note
Evaluation of the value even when the option is disabled
If you enable one or both options and configure a value and then disable the option later, the
grayed out value is nevertheless evaluated.
To disable the two options, delete the previously configured values limit values from the input
boxes and then disable the relevant option.
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 109
Configuration
4.10 Data points
The parameters can be configured for the following data point types:
● DNP3
Binary Command Output
● IEC
Single command
Configuration
The data point types allow receipt of a command with the following control information
(control code):
● LATCH_ON / LATCH_OFF
or
● PULSE_ON
When the byte "Control Code" is received with the function "PULSE_ON" information sent
with it by the master "Count", "On-time" and "Off-time" is evaluated and compared to the
object parameters "Max. pulse duration", "Pulse duration replacement time" and "Max.
number of pulses" (see below).
The following control codes sent by the master station are evaluated.
Parameter
CP 1243-1
110 Operating Instructions, 04/2017, C79000-G8976-C365-03
Configuration
4.10 Data points
Default: 0
Explanation: Monitors the number of pulses sent by the master station (Count). If the
number of pulses received from the master station exceeds the value con-
figured here, the command is rejected.
If you enter 0 (zero), the monitoring is disabled.
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 111
Configuration
4.10 Data points
CP 1243-1
112 Operating Instructions, 04/2017, C79000-G8976-C365-03
Configuration
4.11 Messages
4.11 Messages
Configuring e-mails
If important events occur, the CP can send e-mails to a communications partner.
For the requirements for using e-mails, see section E-mail configuration (Page 69).
You configure the e-mail in STEP 7 in the editor for the data point and message
configuration. You can find this using the project tree:
Project > directory of the relevant station > Local modules > CP
For the view in STEP 7, refer to the section Data point configuration (Page 82).
General functions of the message editor such as copying or column settings correspond to
those of the data point editor.
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 113
Configuration
4.11 Messages
"Message parameter"
Here you configure the recipient, the subject and the text of the message.
"Trigger"
In the "Trigger" parameter group you configure triggering for sending the message and other
parameters.
● E-mail trigger
Specifies the event for which the sending of the e-mail is triggered.
– Use PLC tag
For the trigger signal to send the e-mail, the edge change (0 → 1) of the trigger bit
"PLC tag for trigger" is evaluated that is set by the user program. When necessary, a
separate trigger bit can be configured for each e-mail. For information on the trigger
bit, see below.
– CPU changes to STOP
– CPU changes to RUN
– Connection to a partner interrupted
Triggers the sending of the e-mail when the connection to a partner is interrupted.
– Connection to a partner established
Triggers the sending of the e-mail when the connection returns.
Following triggers only with TeleControl Basic:
– Connection establishment to partner failed
Triggers the sending of the e-mail when the connection to a partner could not be
established.
– Teleservice session started
– Teleservice session ended
● PLC tag for trigger
PLC tag for the e-mail trigger "Use PLC tag"
If the memory area of the trigger bit is in the bit memory or in a data block, the trigger bit
is reset to zero when the e-mail is sent.
● Enable identifier for processing status
If the option is enabled, every attempt to send returns a status with information about the
processing status of the sent message.
The status is written to the "PLC tag for processing status". If there are problems
delivering messages, you can determine the status via the Web server of the CPU by
displaying the value of the PLC tag there.
For the significance of the status output in hexadecimal, refer to the section Processing
status of e-mails (Page 126).
CP 1243-1
114 Operating Instructions, 04/2017, C79000-G8976-C365-03
Configuration
4.12 Access to the Web server
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 115
Configuration
4.12 Access to the Web server
CP 1243-1
116 Operating Instructions, 04/2017, C79000-G8976-C365-03
Program blocks 5
5.1 Program blocks for OUC
Note
Different program block versions
Note that in STEP 7 you cannot use different versions of a program block in a station.
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 117
Program blocks
5.1 Program blocks for OUC
CP 1243-1
118 Operating Instructions, 04/2017, C79000-G8976-C365-03
Program blocks
5.2 Changing the IP address during runtime
Note
Connection abort
If an existing connection is aborted by the communications partner or due to disturbances on
the network, the connection must also be terminated by calling TDISCON. Make sure that
you take this into account in your programming.
Note
Changing the IP parameters with a dynamic IP address
Note the effects of program-controlled changes to the IP parameters if the CP obtains a
dynamic IP address from the Internet service provider: In this case, the CP can no longer be
reached by communications partners.
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 119
Program blocks
5.2 Changing the IP address during runtime
Apart from the address parameters of the CP, with T_CONFIG the address parameters of
DNS servers (IF_CONF_DNS) and NTP servers (IF_CONF_NTP) can also be changed
program controlled.
Depending on the STEP 7 version, the following program blocks and system data types can
be used:
● STEP 7 Basic ≥ V14
T_CONFIG
Along with:
– IF_CONF_V4
– IF_CONF_NTP
– IF_CONF_V6
– IF_CONF_DNS
● STEP 7 Basic ≤ V14
TC_CONFIG
Along with:
– IF_CONF_V4
You will find detailed information on programming the blocks in the STEP 7 information
system.
Requirements - CP programming
To be able to change the IP parameters program controlled the option "IP address is set
directly at the device" must be enabled in the configuration of the IP address of the Ethernet
interface of the CP.
CP 1243-1
120 Operating Instructions, 04/2017, C79000-G8976-C365-03
Diagnostics and upkeep 6
6.1 Diagnostics options
The following diagnostics options are available.
STEP 7: Diagnostics functions in the "Online > Online and diagnostics" menu
Using the online functions, you can read diagnostics information from the CP from an
engineering station on which the project with the CP is stored.
If you want to operate online diagnostics with the station via the CP, you need to activate the
online functions in the parameter group "Communication types" see the section
Communication types (Page 45).
"Diagnostics" group
Here, you can obtain the following static information on the selected module:
● General information on the module
General information on the module
● Diagnostics status
Information on the diagnostics status
● Ethernet interface
Address and statistical information
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 121
Diagnostics and upkeep
6.1 Diagnostics options
"Functions" group
● Saving service data
The function serves for logging of internal processes is situations in which you cannot
eliminate unexpected or unwanted behavior of the module yourself.
The log file is created with the "Save service data" button. The data is saved in a file with
the format "*.dmp" that can be evaluated by the Siemens hotline.
SNMP
For information on the functions, refer to the section SNMP (Page 125).
CP 1243-1
122 Operating Instructions, 04/2017, C79000-G8976-C365-03
Diagnostics and upkeep
6.2 Online security diagnostics via port 8448
See also
Settings for online security diagnostics and downloading to station with the firewall activated
(Page 68)
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 123
Diagnostics and upkeep
6.3 Online functions and TeleService
Note
Transmission time with TeleService
Note that transferring larger amounts of data via WAN (Internet) can take a very long time.
If there are disruptions or interruptions of the transmission path this can lead to the data
transmission being aborted.
Procedure:
1. Connect the ES to the network.
2. Open the relevant STEP 7 project on the ES.
3. Select the CP or the CPU of the station whose CP you want to update with new firmware.
4. Enable the online functions using the "Connect online" icon.
5. In the "Connect online" dialog, go to the Choose the entry "TeleService via telecontrol" in
the "Type of PG/PC interface" drop-down list.
6. In the "PG/PC interface" drop-down list select the entry "TeleService board".
7. In the table select the CP if it is not already selected.
The path both via the CP or the CPU is possible.
8. Click on the icon next to the "PG/PC interface" drop-down list.
The "Establish remote connection via telecontrol" dialog box opens.
9. Make the necessary entries in this dialog (see below) and click on "Connect".
CP 1243-1
124 Operating Instructions, 04/2017, C79000-G8976-C365-03
Diagnostics and upkeep
6.4 SNMP
● Authentication ...
– Teleservice user name and password
Here, enter the data for the TeleService user that you configured in STEP 7 in the
global Security settings, see also section Configuration of the TeleService access
(Page 80).
6.4 SNMP
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 125
Diagnostics and upkeep
6.5 Processing status of e-mails
Configuration
For information on the configuration, refer to:
● With security functions disabled (SNMPv1): SNMP (Page 53)
● With security functions enabled (SNMPv1 / SNMPv3): SNMP (Page 70)
CP 1243-1
126 Operating Instructions, 04/2017, C79000-G8976-C365-03
Diagnostics and upkeep
6.5 Processing status of e-mails
Status Meaning
0000 Transfer completed free of errors
82xx Other error message from the e-mail server
Apart from the leading "8", the message corresponds to the three-digit error number of the
SMTP protocol.
8401 No channel available. Possible cause: There is already an e-mail connection via the CP. A
second connection cannot be set up at the same time.
8403 No TCP/IP connection could be established to the SMTP server.
8405 The SMTP server has denied the login request.
8406 An internal SSL error or a problem with the structure of the certificate was detected by the
SMTP client.
8407 Request to use SSL was denied.
8408 The client could not obtain a socket for creating a TCP/IP connection to the mail server.
8409 It is not possible to write via the connection. Possible cause: The communications partner
reset the connection or the connection aborted.
8410 It is not possible to read via the connection. Possible cause: The communications partner
terminated the connection or the connection was aborted.
8411 Sending the e-mail failed. Cause: There was not enough memory space for sending.
8412 The configured DNS server could not resolve specified domain name.
8413 Due to an internal error in the DNS subsystem, the domain name could not be resolved.
8414 An empty character string was specified as the domain name.
8415 An internal error occurred in the cURL module. Execution was aborted.
8416 An internal error occurred in the SMTP module. Execution was aborted.
8417 Requests to SMTP on a channel already being used or invalid channel ID. Execution was
aborted.
8418 Sending the e-mail was aborted. Possible cause: Execution time exceeded.
8419 The channel was interrupted and cannot be used before the connection is terminated.
8420 Certificate chain from the server could not be verified with the root certificate of the CP.
8421 Internal error occurred. Execution was stopped.
8450 Action not executed: Mailbox not available / unreachable. Try again later.
84xx Other error message from the e-mail server
Apart from the leading "8", the message corresponds to the three-digit error number of the
SMTP protocol.
8500 Syntax error: Command unknown.
This also includes the error of having a command chain that is too long. The cause may be
that the e-mail server does not support the LOGIN authentication method.
Try sending e-mails without authentication (no user name).
8501 Syntax error. Check the following configuration data:
Alarm configuration > E-mail data (Content):
• Recipient address ("To" or "Cc").
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 127
Diagnostics and upkeep
6.5 Processing status of e-mails
Status Meaning
8502 Syntax error. Check the following configuration data:
Alarm configuration > E-mail data (Content):
• Email address (sender)
8535 SMTP authentication incomplete. Check the "User name" and "Password" parameters in
the CP configuration.
8550 SMTP server cannot be reached. You have no access rights. Check the following configu-
ration data:
• CP configuration > E-mail configuration:
– User name
– Password
– Email address (sender)
• Alarm configuration > E-mail data (Content):
– Recipient address ("To" or "Cc").
8554 Transfer failed
85xx Other error message from the e-mail server
Apart from the leading "8", the message corresponds to the three-digit error number of the
SMTP protocol.
CP 1243-1
128 Operating Instructions, 04/2017, C79000-G8976-C365-03
Diagnostics and upkeep
6.6 Downloading firmware
Note
Effects on the retentive memory of the CPU
• If you use a SIMATIC memory card to install the firmware file, the retentive memory is
retained.
• If you use the Web server or the online functions to install the firmware file, retentive
memory is lost.
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 129
Diagnostics and upkeep
6.6 Downloading firmware
4. In the parameter group "General", select the "Enable Web server for this interface"
option.
5. With a CPU version V4.0 or higher, create a user in the user administration with the
required rights.
You need to assign the right to perform firmware updates in the access level.
The procedure for establishing a connection to the Web server depends on whether you
have enabled or disabled the "Allow access only using HTTPS" option in the "General"
parameter group:
● Connection establishment with HTTP
Procedure if the "Allow access only using HTTPS" option is disabled
● Connection establishment with HTTPS
Procedure if the "Allow access only using HTTPS" option is enabled
These two variants are described in the following sections.
Requirement: The new firmware file is stored on your engineering station.
You will find the requirements for access to the Web server of the CPU (permitted Web
browser) and the description of the procedure in the STEP 7 information system under the
keyword "Information about the Web server".
CP 1243-1
130 Operating Instructions, 04/2017, C79000-G8976-C365-03
Diagnostics and upkeep
6.6 Downloading firmware
Loading firmware
1. Log in on the start page of the Web server as a user with the necessary rights.
Use the user data configured in the user administration of the Web server of the CPU.
2. After logging in, select the entry "Module status" in the navigation panel of the Web
server.
3. Select the CP in the module list.
4. Select the "Firmware" tab lower down in the window.
5. Browse for the firmware file on your PC using the "Browse..." button and download the file
to the station using the "Run update" button.
Note
Closing the Web server
If you close the Web server during the firmware update, you cannot change the operating
status of the CPU to RUN. In this case you need to turn the CPU off and on again to change
the CPU to the operating status RUN.
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 131
Diagnostics and upkeep
6.7 Module replacement
Module replacement
CAUTION
Read the system manual "S7-1200 Programmable Controller"
Prior to installation, connecting up and commissioning, read the relevant sections in the
system manual "S7-1200 Programmable Controller" (refer to the documentation in the
Appendix).
When installing and connecting up, keep to the procedures described in the system manual
"S7-1200 Programmable Controller".
Make sure that the power supply is turned off when installing/uninstalling the devices.
The STEP -7 project data of the CP is stored on the local CPU. If there is a fault on the
device, this allows simple replacement of the CP without needing to download the project
data to the station again.
When the station starts up again, the new CP reads the project data from the CPU.
CP 1243-1
132 Operating Instructions, 04/2017, C79000-G8976-C365-03
Technical data 7
7.1 Technical specifications of the CP 1243-1
Technical specifications
Article number 6GK7 243-1BX30-0XE0
Attachment to Industrial Ethernet
Quantity 1
Design RJ-45 jack
Properties 100BASE-TX, IEEE 802.3-2005, half duplex/full duplex, autocrossover, autonego-
tiation, galvanically isolated
Transmission speed 10/100 Mbps
Permitted cable lengths (Ethernet) (Alternative combinations per length range) *
0 ... 55 m • Max. 55 m IE TP Torsion Cable with IE FC RJ45 Plug 180
• Max. 45 m IE TP Torsion Cable with IE FC RJ45 + 10 m TP Cord via
IE FC RJ45 Outlet
0 ... 85 m • Max. 85 m IE FC TP Marine/Trailing/Flexible/FRNC/Festoon/Food Cable with
IE FC RJ45 Plug 180
• Max. 75 m IE FC TP Marine/Trailing/Flexible/FRNC/Festoon/Food Cable +
10 m TP Cord via IE FC RJ45 Outlet
0 ... 100 m • Max. 100 m IE FC TP Standard Cable with IE FC RJ45 Plug 180
• Max. 90 m IE FC TP Standard Cable + 10 m TP Cord via IE FC RJ45 Outlet
Electrical data
Power supply From the S7-1200 backplane bus 5 VDC
Current consumption (typical) From the S7-1200 backplane bus 250 mA
Effective power loss (typical) From the S7-1200 backplane bus 1.25 W
Permitted ambient conditions
Ambient temperature During operation with the rack in- -20 °C to +70 °C
stalled horizontally
During operation with the rack in- -20 °C to +60 °C
stalled vertically
During storage -40 ℃ to +70 ℃
During transportation -40 ℃ to +70 ℃
Relative humidity During operation ≤ 95 % at 25 °C, no condensation
Design, dimensions and weight
Module format Compact module for S7-1200, single width
Degree of protection IP20
Weight 122 g
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 133
Technical data
7.2 Pinout of the Ethernet interface
Technical specifications
Dimensions (W x H x D) 30 x 110 x 75 mm
Installation options Standard DIN rail
Switch panel
Product functions **
CP 1243-1
134 Operating Instructions, 04/2017, C79000-G8976-C365-03
Approvals A
Approvals issued
Note
Issued approvals on the type plate of the device
The specified approvals apply only when the corresponding mark is printed on the product.
You can check which of the following approvals have been granted for your product by the
markings on the type plate.
The CP has the following approvals and meets the following standards:
EC declaration of conformity
The CP meets the requirements and safety objectives of the following EU directives and it
complies with the harmonized European standards (EN) for programmable logic controllers
which are published in the official documentation of the European Union.
● 2014/34/EU (ATEX explosion protection directive)
Directive of the European Parliament and the Council of 26 Febrary 2014 on the
approximation of the laws of the Member States concerning equipment and protective
systems intended for use in potentially explosive atmospheres, official journal of the EU
L96, 29/03/2014, pages. 309-356
● 2014/30/EU (EMC)
EMC directive of the European Parliament and of the Council of February 26, 2014 on the
approximation of the laws of the member states relating to electromagnetic compatibility.;
official journal of the EU L96, 29/03/2014, pages. 79-106
● 2011/65/EU (RoHS)
Directive of the European Parliament and of the Council of 8 June 2011 on the restriction
of the use of certain hazardous substances in electrical and electronic equipment
The EC Declaration of Conformity is available for all responsible authorities at:
Siemens Aktiengesellschaft
Division Process Industries and Drives
Process Automation
DE-76181 Karlsruhe
Germany
You will find the EC Declaration of Conformity for this product on the Internet at the following
address:
Link: (https://support.industry.siemens.com/cs/ww/en/ps/15922/cert) > "EC Declaration of
Conformity"
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 135
Approvals
IECEx
The CP meets the requirements of explosion protection according to IECEx.
IECEx classification: Ex nA IIC T4 Gc
IECEx certificate: IECEx DEK 14.0088X
The CP meets the requirements of the following standards:
● EN 60079-0
Hazardous areas - Part 0: Equipment - General requirements
● EN 60079-15
Explosive atmospheres - Part 15: Equipment protection by type of protection 'n'
You can see the current versions of the standards in the IECEx certificate that you will find
on the Internet at the following address:
Link: (https://support.industry.siemens.com/cs/ww/en/ps/15922/cert)
The conditions must be met for the safe deployment of the CP according to the section
Notices on use in hazardous areas according to IECEx / ATEX (Page 32).
You should also note the information in the document "Use of subassemblies/modules in a
Zone 2 Hazardous Area" that you will find on the Internet at the following address:
Link: (https://support.industry.siemens.com/cs/ww/en/view/78381013)
ATEX
The product meets the requirements of the EC directive:2014/34/EC "Equipment and
Protective Devices for Use in Potentially Explosive Atmospheres".
ATEX approval: II 3 G Ex nA IIC T4 Gc
Type Examination Certificate: KEMA 10ATEX0166 X
Relevant standards:
● EN 60079-0:2006: Potentially explosive atmosphere - general requirements
● EN 60079-15:2005: Electrical apparatus for explosive gas atmospheres; type of
protection 'n'
The device is suitable for use in environments with pollution degree 2.
The device is suitable for use only in environments that meet the following conditions:
● Class I, Division 2, Group A, B, C, D and areas where there is no risk of explosion
● Class I, Zone 2, Group IIC and areas where there is no risk of explosion
WARNING
Installation guidelines
The product meets the requirements if you keep to the following during installation and
operation:
• The notes in the section Important notes on using the device (Page 31)
• The installation instructions in the document /1/ (Page 141)
CP 1243-1
136 Operating Instructions, 04/2017, C79000-G8976-C365-03
Approvals
Note the conditions for the safe deployment of the CP according to the section Link:
(https://support.industry.siemens.com/cs/ww/en/ps/15922/cert).
You should also note the information in the document "Use of subassemblies/modules in a
Zone 2 Hazardous Area" that you will find on the Internet at the following address:
Link: (https://support.industry.siemens.com/cs/ww/en/view/78381013)
c(UL)us
Applied standards:
● Underwriters Laboratories, Inc.: UL 61010-1 (Safety Requirements for Electrical
Equipment for Measurement, Control, and Laboratory Use - Part 1: General
Requirements)
● IEC/UL 61010-2-201 (Safety requirements for electrical equipment for measurement,
control and laboratory use. Particular requirements for control equipment)
● Canadian Standards Association: CSA C22.2 No. 142 (Process Control Equipment)
File Number: E223122
FM
Factory Mutual Approval Standard Class Number 3600, 3611, 3810, ANSI/ISA-61010-1
Equipment rating:
Class I, Division 2, Group A, B, C, D, Temperature Class T4A, Ta = 60 °C
Class I, Zone 2, Group IIC, Temperature Class T4, Ta = 60 °C
Report Number: 3049779, 3049925
Note the conditions for the safe deployment of the CP according to the section Notices on
use in hazardous areas according to FM (Page 33).
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 137
Approvals
Australia - RCM
The CP meets the requirements of the AS/NZS 2064 standards (Class A).
Current approvals
SIMATIC NET products are regularly submitted to the relevant authorities and approval
centers for approvals relating to specific markets and applications.
If you require a list of the current approvals for individual devices, consult your Siemens
contact or check the Internet pages of Siemens Industry Online Support:
Link: (https://support.industry.siemens.com/cs/ww/en/ps/15922/cert)
CP 1243-1
138 Operating Instructions, 04/2017, C79000-G8976-C365-03
Dimension drawings B
Note
All dimensions in the drawings of the CP are in millimeters.
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 139
Dimension drawings
CP 1243-1
140 Operating Instructions, 04/2017, C79000-G8976-C365-03
Documentation references C
Where to find Siemens documentation
● Article numbers
You will find the article numbers for the Siemens products of relevance here in the
following catalogs:
– SIMATIC NET - Industrial Communication / Industrial Identification, catalog IK PI
– SIMATIC - Products for Totally Integrated Automation and Micro Automation, catalog
ST 70
You can request the catalogs and additional information from your Siemens
representative. You will also find the product information in the Siemens Industry Mall at
the following address:
Link: (https://mall.industry.siemens.com)
● Manuals on the Internet
You will find SIMATIC NET manuals on the Internet pages of Siemens Industry Online
Support:
Link: (https://support.industry.siemens.com/cs/ww/en/ps/15247/man)
Go to the required product in the product tree and make the following settings:
Entry type “Manuals”
● Manuals on the data medium
You will find manuals of SIMATIC NET products on the data medium that ships with many
of the SIMATIC NET products.
/1/
SIMATIC
S7-1200 Programmable Controller
System Manual
Siemens AG
Current release at the following address:
Link: (https://support.industry.siemens.com/cs/ww/en/ps/13683/man)
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 141
Documentation references
/2/
SIMATIC NET
CP 1243-1
Operating Instructions
Siemens AG
Link: (https://support.industry.siemens.com/cs/ww/en/view/103948898)
/3/
SIMATIC NET
TeleControl Server Basic (Version V3)
Operating Instructions
Siemens AG
Link: (https://support.industry.siemens.com/cs/ww/en/ps/15918/man)
/4/
SIMATIC NET
Industrial Ethernet Security
Security basics and applications
Configuration manual
Siemens AG
Link: (https://support.industry.siemens.com/cs/ww/en/ps/15326/man)
/5/
SIMATIC NET
Diagnostics and configuration with SNMP
Diagnostics manual
Siemens AG
Link: (https://support.industry.siemens.com/cs/ww/en/ps/15392/man)
CP 1243-1
142 Operating Instructions, 04/2017, C79000-G8976-C365-03
Index
A G
Abbreviations/acronyms, 4 Gateway, 79
Article number, 3 Glossary, 6
C H
Conditional spontaneous, 100, 101 Hardware product version, 3
Connection resources, 15
CPU firmware, 23
Cross references (PDF), 5 I
IEC addressing, 41
Image memory, 98
D
Importing a certificate - e-mail, 70
Data buffering, 16 Instructions (OUC), 117
Data point configuration, 82 Internet connections, 42
Data point type, 89 Inter-station communication, 94
Dimensions, 35 IP address - program-controlled change, 119
Disposal, 6 IP address (master), 41
DNP3 addressing, 41 IP configuration
DNP3 implementation level, 65 IPv4, IPv6, 12
DNP3 master, addressing via the Internet, 21 IP_CONF_V4, 119
DNS server, 42
DNS server - program-controlled change, 119
L
Logging server, 73
E
E-mail
Configuration, 113 M
Programming (OUC), 117
MAC address, 3
Quantity, 16
MIB, 125
Encryption, 11
Mirroring, 92
Ethernet interface
Assignment, 134
Events, 98
N
NTP, 43
F NTP (secure), 43
NTP server - program-controlled change, 119
Firewall, 14
IPsec tunnel,
Firmware version, 3
Forced image mode, 98
Frame memory, 16, 98
O
Online diagnostics, 46, 121
Online functions, 13, 121
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03 143
Index
U
P Unsolicited, 100, 101
Passive VPN connection establishment, 79
PG/OP connections, 16
Port 8448, 123 V
Process image, 98
Virtual IP address, 57
Product name, 4
VPN, 16, 42, 74
PUT/GET, 16
W
R
Web server, 115
Recycling, 6
Redundant DNP3 master, addressing, 22
Replacing a module, 132
Reset trigger bit, 99
S
S7 connections
Enable, 46
Resources, 16
Safety notices, 31
Security, 13
Security diagnostics without port 102, 123
Send buffer, 16, 98
Service & Support, 6
SIMATIC NET glossary, 6
SMS
Programming (OUC), 117
SMTPS, 69
SNMP, 13, 53, 125
SNMPv3, 15, 70
SSL/TLS, 69
STARTTLS, 69
Static values, 98
STEP 7 - version, 23
SYSLOG, 80
T
T_CONFIG, 119
TC_CONFIG, 119
TeleService, 13
Time stamp, 90
CP 1243-1
144 Operating Instructions, 04/2017, C79000-G8976-C365-03