MHT-1202
MHT-1202
CONTROLLER
MHT 1202
APPLICATIONS
Process industries
Lab Testing equipment
Testing Chambers
HVAC & Refrigeration industries
Mechanical Dimensions
Body Dimensions
MHT 1202
°C
Temperature
R1
90.5
101
R2
Humidity %RH
SET ENT
101 2.5 54
92
www.multispanindia.com Page01
TECHNICAL DATA
S1 : RTD, PT 100/3W Sensor
Input
S2 : Humidity Sensor (RH-100)
Input Output
Input S1 : RTD, PT 100/3W Sensor Relays 2 Nos
S2 : Humidity Sensor (RH-100) Relay Type 1C/O (NO-C-NC)
Range 0.0 to 400.0°C Rating 5A, 230V AC / 30V DC
0.0 to 100.0% RH
Resolution 0.1 %
Accuracy ± 1% of FSD
Display LED & Keys
Upper 4 Digit 7 seg 0.36”Red LED
ADC Resolution 10 Bit Display
Lower 4 Digit 7 seg 0.36” White LED
Sample Time 600 msec
Key SET, INC, DEC, ENT
CJC Error ± 2°C
LED Indication R1, R2
Sensor Open PT 100 & RH 100
Sensor Burnout Current 1.10uA
Communication
CMRR >120 dB ( Typical )
Type RS 485
Max Voltage 20V DC
Protocol MODBUS RTU
Response Time 675mS
2400 , 4800 , 9600 ,
Baud Rate 19200 , 38400
2500 VRMS Isolation as per
Isolation UL 1577
Auxiliary Power Supply
Power Supply 100 to 270V AC, 50/60Hz
Note :
Burden 4VA Accurate sensing of humidity is subject to
proper mounting of humidity sensor as per
application area. Please consult our support
engineers if needed.
Mechanical Characteristics
Mounting Type Panel Mount
Dimension (HxWxD) mm 101 x 101 x 54
Panel Cutout (HxW) mm 92 x 92
Front Polycarbonate (PC)
Material
Enclosure ABS
Terminal Screw Size M3.5
Screw Torque (N.m) 0.5
Wire Guage (AWG) 26-14
Unpacked : 200
Weight (Approx) gms
Packed : 230
Accessories 1 Pair of Mounting Clamps
Page03