Belimo EV..F BAC Datasheet En-Gb

The EV..F+BAC is a characterized control valve designed for sensor-operated flow rate or power control in closed water systems, featuring a power and energy-monitoring function. It operates on a nominal voltage of AC/DC 24 V and supports various communication protocols including BACnet and Modbus, with options for cloud connectivity. The device is suitable for modulating control of air-handling and heating systems, with adjustable flow rates and integrated temperature and glycol monitoring capabilities.

Uploaded by

wathaifi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
25 views13 pages

Belimo EV..F BAC Datasheet En-Gb

The EV..F+BAC is a characterized control valve designed for sensor-operated flow rate or power control in closed water systems, featuring a power and energy-monitoring function. It operates on a nominal voltage of AC/DC 24 V and supports various communication protocols including BACnet and Modbus, with options for cloud connectivity. The device is suitable for modulating control of air-handling and heating systems, with adjustable flow rates and integrated temperature and glycol monitoring capabilities.

Uploaded by

wathaifi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 13

Technical data sheet EV..

F+BAC

Characterised control valve with sensor-


operated flow rate or power control, power and
energy-monitoring function, 2-way, Flange,
PN 16 (Energy Valve)

• Nominal voltage AC/DC 24 V


• Control modulating, communicative, hybrid,
Cloud
• For closed water systems
• For modulating control of air-handling and
heating systems on the water side
• Ethernet 10/100 Mbit/s, TCP/IP, integrated
web server
• Communication via BACnet, Modbus, Belimo
Picture may differ from product
MP-Bus or conventional control
• optional Belimo Cloud connection
• Glycol monitoring

Type Overview

Type DN V'nom V'nom V'nom Kvs theor. PN


[l/s] [l/min] [m³/h] [m³/h]
EV065F+BAC 65 8 480 28.8 50 16
EV080F+BAC 80 11 660 39.6 75 16
EV100F+BAC 100 20 1200 72 127 16
EV125F+BAC 125 31 1860 111.6 195 16
EV150F+BAC 150 45 2700 162 254 16
Kvs theor.: theoretical Kvs value for pressure drop calculation

Technical data

Electrical data Nominal voltage AC/DC 24 V


Nominal voltage frequency 50/60 Hz
Nominal voltage range AC 19.2...28.8 V / DC 21.6...28.8 V
Power consumption in operation 7W
Power consumption in rest position 5W
Power consumption for wire sizing 6 VA (DN 65, 80)
11 VA (DN 100, 125, 150)
Connection supply / control Cable 1 m, 6x 0.75 mm²
Connection Ethernet RJ45 socket
Parallel operation Yes (note the performance data)

Data bus communication Communicative control BACnet/IP, BACnet MS/TP


Modbus TCP, Modbus RTU
MP-Bus
Cloud
Number of nodes BACnet / Modbus see interface description
MP-Bus max. 8

Functional data Operating range Y 2...10 V


Input impedance 100 kΩ
Operating range Y variable 0.5...10 V
Position feedback U 2...10 V
Position feedback U note Max. 1 mA
Position feedback U variable 0...10 V
0.5...10 V
Sound power level motor 45 dB(A)

www.belimo.com EV..F+BAC • en-gb • 2025-03-26 • Subject to change 1 / 13


Technical data sheet EV..F+BAC

Functional data V'max adjustable 30...100% of V'nom


Control accuracy ±5% (of 25...100% V'nom) @ 20°C / Glycol 0%
vol.
Control accuracy note ±10% (of 25...100% V'nom) @ -10...120°C /
Glycol 0...50% vol.
Min. controllable flow 1% of V'nom
Configuration via integrated web server / ZTH EU
Fluid Water, water with glycol up to max. 50% vol.
Fluid temperature -10...120°C [14...248°F]
Close-off pressure ∆ps 690 kPa
Differential pressure Δpmax 340kPa
Flow characteristic equal percentage (VDI/VDE 2173), optimised
in the opening range
Flow characteristic note switchable to linear (VDI/VDE 2173)
Leakage rate air-bubble tight, leakage rate A (EN 12266-1)
Pipe connection Flange
according to EN 1092-2
Installation orientation upright to horizontal (in relation to the
spindle)
Servicing maintenance-free
Manual override with push-button, can be locked

Temperature measurement Measuring accuracy absolute temperature ± 0.35°C @ 10°C (Pt1000 EN60751 Class B)
± 0.6°C @ 60°C (Pt1000 EN60751 Class B)
Measuring accuracy differential temperature ±0.18 K @ ΔT = 10 K
±0.23 K @ ΔT = 20 K

Flow measurement Measuring principle Ultrasonic volumetric flow measurement


Measuring accuracy flow ±2% (of 25...100% V'nom) @ 20°C / glycol 0%
vol.
Measuring accuracy flow note ±6% (of 25...100% V'nom) @ -10...120°C /
glycol 0...50% vol.
Min. flow measurement 0.5% of V'nom

Glycol monitoring Measurement display glycol 0...40% or >40%


Measuring accuracy glycolmonitoring ±4% (0...40%)

Safety data Protection class IEC/EN III, Safety Extra-Low Voltage (SELV)
Degree of protection IEC/EN IP40
IP54 when using protective cap or protective
grommet for RJ45 socket
Pressure equipment directive CE according to 2014/68/EU
EMC CE according to 2014/30/EU
Type of action Type 1
Rated impulse voltage supply / control 0.8 kV
Pollution degree 3
Ambient humidity Max. 95% RH, non-condensing
Ambient temperature -30...50°C [-22...122°F]
Storage temperature -40...80°C [-40...176°F]

Materials Valve body EN-GJL-250 (GG 25)


Flow measuring pipe EN-GJL-250 (GG 25), with protective paint
Closing element Stainless steel AISI 316

www.belimo.com EV..F+BAC • en-gb • 2025-03-26 • Subject to change 2 / 13


Technical data sheet EV..F+BAC
Technical data

Materials Spindle Stainless steel AISI 304


Spindle seal EPDM
Seat PTFE, O-ring Viton
Immersion sleeve Stainless steel AISI 316

Safety notes

• This device has been designed for use in stationary heating, ventilation and air-conditioning
systems and must not be used outside the specified field of application, especially in aircraft
or in any other airborne means of transport.
• Outdoor application: only possible in case that no (sea) water, snow, ice, insolation or
aggressive gases interfere directly with the device and that it is ensured that the ambient
conditions remain within the thresholds according to the data sheet at any time.
• Only authorised specialists may carry out installation. All applicable legal or institutional
installation regulations must be complied with during installation.
• The device contains electrical and electronic components and must not be disposed of as
household refuse. All locally valid regulations and requirements must be observed.

Product features

Operating mode The HVAC performance device is comprised of four components: characterised control valve
(CCV), measuring pipe with flow sensor, temperature sensors and the actuator itself. The
adjusted maximum flow (V'max) is assigned to the maximum control signal DDC (typically 10
V / 100%). Alternatively, the control signal DDC can be assigned to the valve opening angle or
to the power required on the heat exchanger (see power control). The HVAC performance
device can be controlled via communicative or analogue signals. The fluid is detected by the
sensor in the measuring pipe and is applied as the flow value. The measured value is
balanced with the setpoint. The actuator corrects the deviation by changing the valve
position. The angle of rotation α varies according to the differential pressure through the
control element (see flow curves).

Flow rate curves

www.belimo.com EV..F+BAC • en-gb • 2025-03-26 • Subject to change 3 / 13


Technical data sheet EV..F+BAC

Transmission behaviour HE Heat exchanger transmission behaviour


Depending on the construction, temperature spread, fluid characteristics and hydronic circuit,
the power Q is not proportional to the water volumetric flow V' (Curve 1). With the classical
type of temperature control, an attempt is made to maintain the control signal Y proportional
to the power Q (Curve 2). This is achieved by means of an equal-percentage flow characteristic
(Curve 3).

Power control Alternatively, the control signal DDC can be assigned to the output power required at the heat
exchanger.
Depending on the water temperature and air conditions, the Energy Valve ensures the
amount of water V' required to achieve the desired power.

Maximum controllable power on heat exchanger in power control mode:

Control characteristics The specially configured control parameters in connection with the precise velocity sensor
ensure a stable quality of control. They are, however, not suitable for rapid control processes,
i.e. for domestic water control.

Power control
Q'nom is the maximum possible power output on the heat exchanger.

Q'max is the maximum power output on the heat exchanger which has been set with the
highest control signal DDC. Q'max can be set between 1% and 100% of Q'nom.

Q'min 0% (non-variable).

www.belimo.com EV..F+BAC • en-gb • 2025-03-26 • Subject to change 4 / 13


Technical data sheet EV..F+BAC

Flow control
V'nom is the maximum possible flow.

V'max is the maximum flow rate which has been set with the highest control signal. V'max can
be set between 30% and 100% of V'nom.

Creep flow suppression Given the very low flow speed in the opening point, this can no longer be measured by the
sensor within the required tolerance. This range is overridden electronically.

Opening valve
The valve remains closed until the flow required by the control signal DDC corresponds to 1%
of V'nom. The control along the flow characteristic is active after this value has been
exceeded.

Closing valve
The control along the flow characteristic is active up to the required flow rate of 1% of V'nom.
Once the level falls below this value, the flow rate is maintained at 1% of V'nom. If the level
falls below the flow rate of 0.5% of V'nom required by the control signal DDC, then the valve
will close.

Configurable device The factory settings cover the most common applications. Single parameters can be modified
with Belimo Assistant 2 or ZTH EU.

www.belimo.com EV..F+BAC • en-gb • 2025-03-26 • Subject to change 5 / 13


Technical data sheet EV..F+BAC

Communication The configuration can be carried out through the integrated web server (RJ45 connection to
the web browser) or by communicative means.
Additional information regarding the integrated web server can be found in the separate
documentation.

"Peer to Peer" connection


http://belimo.local:8080
The Notebook must be set to "DHCP".
Make sure that only one network connection
is active.

Standard IP address:
http://192.168.0.10:8080
Static IP address

Password (read-only):
User name: «guest»
Password: «guest»

Control signal inversion This can be inverted in cases of control with an analogue control signal DDC. The inversion
causes the reversal of the standard behaviour, i.e. at a control signal DDC of 0%, regulation is
to V'max or Q'max, and the valve is closed at a control signal DDC of 100%.

Hydronic balancing Via the integrated web server, the maximum flow rate (equivalent to 100% requirement) can
be adjusted on the device itself, simply and reliably, in a few steps. If the device is integrated
in the management system, then the balancing can be handled directly by the management
system.

Delta-T manager If a heating or cooling register is operated with a differential temperature that is too low and
thus with a flow rate that is too high, this will not result in an increased power output.
Nevertheless, heating or cooling machines must provide the energy at a lower degree of
efficiency. This means, that pumps circulate too much water and increase energy
consumption unnecessarily.
With the aid of the Energy Valve, it is simple to discover that operation is being carried out at
a differential temperature that is too low, resulting in the inefficient use of energy.
Necessary setting adjustments can now be carried out quickly and easily at any time. The
integrated differential temperature limiting offers the user the possibility of defining a low
limit value. The Energy Valve limits the flow rate automatically to prevent the level from falling
below this value.
The settings of the Delta-T manager can be made either directly on the web server or via the
Belimo Cloud a direct analysis of the Delta-T behavior is carried out by Belimo experts.

Power output of the heating or cooling


registers 1
Diff. temperature between supply and return
2
Loss zone (heating or cooling register
saturation) 3
Adjustable minimum differential temperature
4

Combination analogue - communicative With conventional control by means of an analogue control signal DDC, the integrated web
(hybrid mode) server, BACnet, Modbus or MP-Bus can be used for the communicative position feedback.

www.belimo.com EV..F+BAC • en-gb • 2025-03-26 • Subject to change 6 / 13


Technical data sheet EV..F+BAC
Product features

Power and energy monitoring function The HVAC performance device is equipped with two temperature sensors. One sensor (T2) is
integrated in the measuring pipe, the second sensor (T1) is included with the system,
prewired, and must be installed in the water circuit on site. The sensors are used to record the
fluid temperature of the supply and return lines of the consumer (heating/cooling coil). As the
water quantity is also known, thanks to the flow measurement integrated in the system, the
power released from the consumer can be calculated. Furthermore, the heating/cooling
energy is also determined automatically by means of the evaluation of the power over time.
The current data, e.g. temperatures, volumetric flow volumes, exchanger energy
consumption etc. can be recorded and accessed at any time by means of web browsers or
communication.

Data recording The recorded data (integrated data recording for 13 months) can be used for the optimisation
of the overall system and for the determination of the performance of the consumer (heating/
cooling coil).
Download csv files through web browser.

Belimo Cloud Additional services are available if the Energy Valve is connected to the Belimo Cloud: for
instance, several devices may be managed via Internet. Also, Belimo experts may help analyse
the delta-T behaviour or provide written reports about the Energy Valve performance. Under
certain conditions, the product warranty according to the applicable Terms and Conditions of
Sale may be prolonged. The "Terms of Use for Belimo Cloud Services" in their currently valid
version apply to the use of Belimo Cloud services. Further details may be found under
[www.belimo.com/ext-warranty]

Glycol monitoring Glycol monitoring measures the actual glycol content, which is necessary for safe operation
and optimised heat exchange.

Manual override Manual override with push-button possible (the gear train is disengaged for as long as the
button is pressed or remains locked).

High functional safety The actuator is overload protected, requires no limit switches and automatically stops when
the end stop is reached.

Accessories

Tools Description Type


Service tool, with ZIP-USB function, for configurable and communicative ZTH EU
Belimo actuators, VAV controller and HVAC performance devices
Connecting cable 5 m, A: RJ11 6/4 ZTH EU, B: 6-pin for connection to ZK1-GEN
service socket
Electrical accessories Description Type
Grommet for RJ connection module, Multipack 50 pcs. Z-STRJ.1
Stem heater flange F05 (30 W) ZR24-F05

Electrical installation

Supply from isolating transformer.


Parallel connection of other actuators possible. Observe the performance data.
The wiring of the line for BACnet MS/TP / Modbus RTU is to be carried out in accordance with
applicable RS-485 regulations.
Modbus / BACnet: Supply and communication are not galvanically isolated. COM and ground
of the devices must be connected to each other.

www.belimo.com EV..F+BAC • en-gb • 2025-03-26 • Subject to change 7 / 13


Technical data sheet EV..F+BAC
Electrical installation

Wire colours: Functions:


1 = black C1 = D- (wire 6)
2 = red C2 = D+ (wire 7)
3 = white
5 = orange
6 = pink
7 = grey

BACnet MS/TP / Modbus RTU

BACnet/IP / Modbus TCP

Optional connection via RJ45


(direct connection to notebook /
connection via Intranet or
Internet) for access to the
integrated web server

www.belimo.com EV..F+BAC • en-gb • 2025-03-26 • Subject to change 8 / 13


Technical data sheet EV..F+BAC

Further electrical installations

Functions with specific parameters (configuration necessary)

Override control and limiting with DC 24 V with relay contacts (with conventional control or hybrid mode)

1) Position control
2) Flow control
3) Power control

BACnet MS/TP / Modbus RTU with analogue setpoint (hybrid mode) BACnet/IP / Modbus TCP with analogue setpoint (hybrid mode)

MP-Bus, supply via 3-wire connection MP-Bus via 2-wire connection, local power supply

Max. 8 additional MP-Bus nodes

www.belimo.com EV..F+BAC • en-gb • 2025-03-26 • Subject to change 9 / 13


Technical data sheet EV..F+BAC
Further electrical installations

Functions with specific parameters (configuration necessary)

MP-Bus with analogue setpoint (hybrid mode)

Operating controls and indicators

2 LED display green

Off: No power supply or wiring error


On: In operation
Flickering: Internal communication (valve/sensor)

3 Push-button and LED display yellow

On: Adaptation or synchronisation process active


Press button: Triggers angle-of-rotation adaptation, followed by standard mode

4 Manual override button

Press button: Gear train disengages, motor stops, manual override possible
Release button: Gear train engages, standard mode

5 Service plug
For connecting configuration and service tools

Installation notes

Permissible installation orientation The ball valve can be installed upright to horizontal. The ball valve may not be installed in a
hanging position, i.e. with the spindle pointing downwards.

Installation location in return Installation in the return is recommended.

www.belimo.com EV..F+BAC • en-gb • 2025-03-26 • Subject to change 10 / 13


Technical data sheet EV..F+BAC

Water quality requirements The water quality requirements specified in VDI 2035 must be adhered to.
Belimo valves are regulating devices. For the valves to function correctly in the long term, they
must be kept free from particle debris (e.g. welding beads during installation work). The
installation of a suitable strainer is recommended.

Spindle heater In cold water applications and warm humid ambient air, condensation can be caused in the
actuators. This can lead to corrosion in the gear train of the actuator and a breakdown of the
actuator. In such applications, the use of a spindle heater is recommended.
The spindle heater must only be activated when the system is in operation because it does not
have a temperature controller.

Servicing Ball valves, rotary actuators and sensors are maintenance-free.


Before any service work on the control element is carried out, it is essential to isolate the
rotary actuator from the power supply (by unplugging the electrical cable if necessary). Any
pumps in the part of the piping system concerned must also be switched off and the
appropriate slide valves closed (allow all components to cool down first if necessary and
always reduce the system pressure to ambient pressure level).
The system must not be returned to service until the ball valve and the rotary actuator have
been correctly reassembled in accordance with the instructions and the pipeline has been
refilled by professionally trained personnel.

Flow direction The direction of flow, specified by an arrow on the housing, is to be complied with, since
otherwise the flow rate will be measured incorrectly.

Inlet section A flow calming section or inlet section in the direction of flow must be maintained in front of
the flow sensor to achieve the specified measuring accuracy. Its dimensions should be at least
5x DN.

www.belimo.com EV..F+BAC • en-gb • 2025-03-26 • Subject to change 11 / 13


Technical data sheet EV..F+BAC
Installation notes

Mounting of immersion sleeve and The valve is equipped with two temperature sensors:
temperature sensor • T2: One sensor is already installed in the valve unit.
• T1: The second sensor must be mounted at the installation site ahead of the consumer (valve
in the return line; recommended) or after the consumer (valve in the supply line). The
immersion sleeve required is supplied with the valve unit.

The temperature sensor is already wired with the valve.

Note
The cable between valve unit and temperature sensor may not be either shortened or
lengthened.

Split installation The valve-actuator combination may be mounted separately from the flow sensor. The
direction of flow of both components must be observed.

General notes

Minimum differential pressure (pressure The minimum required differential pressure (pressure drop through the valve) for achieving
drop) the desired flow V'max can be calculated with the aid of the theoretical Kvs value (see type
overview) and the below-mentioned formula. The calculated value is dependent on the
required maximum flow V'max. Higher differential pressures are compensated for
automatically by the valve.

Formula

Example (DN 100 with the desired maximum flow rate = 50% V'nom)

Behaviour in case of sensor failure In case of a flow sensor error, the Energy Valve will switch from either power or flow control
to position control (Delta-T manger will be deactivated).
Once the error disappears, the Energy Valve will switch back to the normal control setting
(Delta-T manager activated)

www.belimo.com EV..F+BAC • en-gb • 2025-03-26 • Subject to change 12 / 13


Technical data sheet EV..F+BAC

Dimensions

If Y <180 mm, the extension of the hand crank must be demounted as necessary.

Further documentation

• Tool connections
• BACnet Interface description
• Modbus Interface description
• Description Data-Pool Values
• Overview MP Cooperation Partners
• MP Glossary
• Introduction to MP-Bus Technology
• General notes for project planning
• Instruction Webserver

www.belimo.com EV..F+BAC • en-gb • 2025-03-26 • Subject to change 13 / 13