Technical Specifications of LT Panel & CPR

The document outlines the technical specifications for the Low Tension (LT) Panel and Control & Relay Panel for the Kumhari Urban Local Body Augmentation of Water Supply Scheme. It details standards, construction requirements, key technical particulars, testing protocols, communication features, and documentation requirements for the panels. The specifications ensure compliance with relevant standards and operational efficiency for the water supply scheme's electrical infrastructure.

Uploaded by

Jaks Jaks
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
37 views15 pages

Technical Specifications of LT Panel & CPR

The document outlines the technical specifications for the Low Tension (LT) Panel and Control & Relay Panel for the Kumhari Urban Local Body Augmentation of Water Supply Scheme. It details standards, construction requirements, key technical particulars, testing protocols, communication features, and documentation requirements for the panels. The specifications ensure compliance with relevant standards and operational efficiency for the water supply scheme's electrical infrastructure.

Uploaded by

Jaks Jaks
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 15

CLIENT: OFFICE OF CHIEF MUNICIPAL OFFICER Job No.

Page 1
URBAN LOCAL BODY, KUMHARI, DISTRICT- Calculation No. AM/CNPL/7.5MLD/ Rev. 0
DURG, CHHATTISGARH. KUM/EC/101
PROJECT: Kumhari Urban Local Body Augmentation Prepared By: Javed Akhter Date 25.03.2025
of Water Supply Scheme Checked By: Date
Technical Specification for LT Panel and Control & Relay Panel

Technical Specification for L

Kumhari Urban Local Body Augmentation of Water Supply Scheme


CLIENT: OFFICE OF CHIEF MUNICIPAL OFFICER Job No. Page 2
URBAN LOCAL BODY, KUMHARI, DISTRICT- Calculation No. AM/CNPL/7.5MLD/ Rev. 0
DURG, CHHATTISGARH. KUM/EC/101
PROJECT: Kumhari Urban Local Body Augmentation Prepared By: Javed Akhter Date 25.03.2025
of Water Supply Scheme Checked By: Date
Technical Specification for LT Panel and Control & Relay Panel

Technical Specifications for LT Panel


1. List of standard for LT panel

IS 13947 Low Voltage AC Switchgear and Control Gears Specification


IS 8623 Low Voltage AC Switchgear and Control gear assemblies
IS 4237 General requirements for AC switchgear & control gear for voltage not
exceeding- 1000V
IS 2147 Degree of protection for enclosures for low voltage switchgear and
control gear
IS 582 Methods of Chemical Testing of Leather Electrolytic Cu/Al
IS 14697 AC Electric Meters
IS 3043 Earthing
IS 2551 Danger Notice Plates
IS 2516 Circuit Breakers, voltages up to 1000 Volts
IS 375 Marking & Arrangement for Switchgear, Bus Bars, main connections
and auxiliary wiring

2. General
All the AC low voltage switchboards shall be suitable for operation with 415volts, 50 Hz.
and 3/4 wire system.

3. Construction
a. The switchboards shall be dead front totally enclosed; cubicle type suitable for
floor mounted free standing / wall mounted indoor installations. The design shall
be totally dust - tight damp-proof and vermin proof offering degree of protection
not less than IP-42 for indoor applications and IP-55 for outdoors applications.
b. Switchboards shall be comply with IEC. Separate segregated compartments shall
be provided for breakers, bus bars, cable box, wire ways, relays, instrument and
control devices. Switchboard shall be compartmentalized design and shall be
provided with hinged doors in front and back with facility for padlocking doors.
c. Floor mounted cubicles shall be provided with a 75mm high channel base frame.
Total height of the cubicle shall not exceed 2400mm, keeping in view the
operating height of top switch shall be within the limit of 1750mm & 600mm from
floor level including base channel.
d. Adequate size cable compartment should be provided for easy clamping of all the
incoming and outgoing cables irrespective of top or bottom entries.
e. The compartment doors shall be provided with continuous gasket made of
polyurethane seamless gasket for providing water tightness and preventing
ingress of dust. The gasket shall be held in position in groove provided in the
enclosure and shall be pressed all around uniformly by suitably shaped projection
of the door. All hinged door shall be earthed through tinned copper wire. Doors
CLIENT: OFFICE OF CHIEF MUNICIPAL OFFICER Job No. Page 3
URBAN LOCAL BODY, KUMHARI, DISTRICT- Calculation No. AM/CNPL/7.5MLD/ Rev. 0
DURG, CHHATTISGARH. KUM/EC/101
PROJECT: Kumhari Urban Local Body Augmentation Prepared By: Javed Akhter Date 25.03.2025
of Water Supply Scheme Checked By: Date
Technical Specification for LT Panel and Control & Relay Panel

shall be of pad locking type, whereas switchgear compartments shall be openable


only in switch OFF mode.
f. All live parts inside the switchboards shall be insulated and shall withstand a DC
test voltage.
g. 2.5 KV for 1 minute. Switchboards shall carry a warning label indicating that all
active part in the boxes may be live.
h. Sheet steel used for switchboards shall be 3mm for load bearing members and
2mm for others. Switchboards shall be readily extensible type from either side
with provision of adding vertical sections after removing of the side end covers.
i. All switchboards shall have an embossed aluminium plate describing capacities,
voltages and designated identification number.
j. After fabrication of the switchboards, the entire structure shall undergo a tank
treatment for removing dust, grease, rust etc. The switchboards then should be
powder coated with Siemens grey paint shade no. RAL-7032.
k. The bus bars shall be of high conductivity electrolytic aluminium, air insulated and
housed in a separate compartment segregated from all other compartments. Bus-
bars should have uniform cross sections with suitable capacity for carrying rated
current continuously and short circuit current for specific time duration without
overheating. All the bus bars shall be provided with colour coded heat shrinkable
sleeves.
l. The switchboard shall be provided at the bottom throughout its entire length with
adequately sized copper earth bus to carry the fault current for the same duration
as short time rating of the circuit breaker. Earth bus shall have two earthing
connection facility at its both ends of earthing conductor.
m. LV switchgear should be rated for continuous operation and with standing short
circuit capacities. These should be equipped with manually or electrically draw
out mechanism and shall be suitable for providing short circuit, overload, earth
fault protections etc. through thermo-magnetic based control system.
n. Mechanical operation indicators shall be provided to show open and closed
position of the breaker. Electrically operated breakers shall be additionally
provided with mechanical indications to show charged and discharged conditions
of the charging spring.
o. Adequate Instrument transformers, potential free contacts, connectors, auxiliary
contactors with wiring etc. are to be provided for control & monitoring including
space required. Control terminal box with adequate spare provision for future use
shall also be provided.
p. All bus-bar joints and terminal connections shall be provided with high tensile
steel bolts, spring washers and nuts to ensure good contact. Non silver plated bus-
bar joints shall be thoroughly cleaned before making joints. Setting specific torque
value for the selected hardware shall tighten all bolts.
CLIENT: OFFICE OF CHIEF MUNICIPAL OFFICER Job No. Page 4
URBAN LOCAL BODY, KUMHARI, DISTRICT- Calculation No. AM/CNPL/7.5MLD/ Rev. 0
DURG, CHHATTISGARH. KUM/EC/101
PROJECT: Kumhari Urban Local Body Augmentation Prepared By: Javed Akhter Date 25.03.2025
of Water Supply Scheme Checked By: Date
Technical Specification for LT Panel and Control & Relay Panel

q. All measuring instruments (Meters of 0.5s Class) shall be of digital electronic with
LED display compatible with SCADA. Below table presents non-exhaustive
applicable standards to which AC switchboards should conform.
4. Key technical Particulars

Sl. No Description Particulars


A Power Supply
415 V + 10%, 3
1 Voltage Phase, 4 wire, Neutral
Solidly Earthed
2 Frequency 50 Hz +/- 5%
3 Combined variation (in volts & 10% absolute sum
frequency)
B CUBICLE DATA
1 Continuous Current rating As per requirement
2 Short time rating where
3 Circuit Breaker (CB) is used as
50kA (RMS) for one sec
incomer
4 Prospective current of 50Ka
Fuse protection is used in Incomer (RMS) for the fuse clearing
time
5 Dynamic Rating where
6 CB is used as incomer 105kA (PEAK)
7 Prospective current of 105kA
Fuse Protection is used in incomer
(PEAK) as limited by fuse
8 Busbar insulation PVC Sleeve insulated
C CIRCUIT BREAKER
1 Air break spring charged
Type
stored energy type
2 Operating duty O - 3 M I N - O C - 3 M IN-OC
3 Symmetrical interrupting 50kA (RMS)
4 Short circuit rating 105kA (PEAK)
5 Short Circuit Breaking current 50kA (RMS)
6 Short time withstand 50kA (RMS) for one sec
7 No of auxiliary contacts 4NO + 4NC for Employer's use
D METERS
CLIENT: OFFICE OF CHIEF MUNICIPAL OFFICER Job No. Page 5
URBAN LOCAL BODY, KUMHARI, DISTRICT- Calculation No. AM/CNPL/7.5MLD/ Rev. 0
DURG, CHHATTISGARH. KUM/EC/101
PROJECT: Kumhari Urban Local Body Augmentation Prepared By: Javed Akhter Date 25.03.2025
of Water Supply Scheme Checked By: Date
Technical Specification for LT Panel and Control & Relay Panel

1 Accuracy class 0.5


2 Voltage Ratio 415/110 V
E CURRENT TRANSFORMERS
1 Type Cast Resin Bar Primary
2 Voltage class and frequency 650V, 50HZ
3 CT Secondary Current 1A
4 Class of insulation E or better
5 Accuracy class & burden
i For Protection 5P20 PS Class for REF
II For Metering Class 1.0, 5VA (min)
Instrument Security Factor for
iii 5
metering CT
iv Short time withstand 50kA (RMS) for 1 sec
v Dynamic withstand 105kA (PEAK)
F VOLTAGE TRANSFORMERS
1 Type Cast Resin
415 / 110V for line PT
2 Voltage Ratio
415/√3 / 110/√3V for Bus PT
3 Accuracy Class 0.5
4 Class of insulation E or better
One minute power frequency
5 2.5 KV
withstand voltage

5. Tests
All equipment shall be completely assembled, wired, adjusted and tested at the factory
as per the relevant standards.
5.1 Routine Test
The tests shall include but not necessarily be limited to the following:
a. Operation under simulated service condition to ensure accuracy of wiring,
correctness of control scheme and proper functioning of the equipment.
b. All wiring and current carrying part shall be given appropriate High Voltage Test
c. Primary current & voltages shall be applied to all instrument transformers.
d. Routine test shall be carried out on all equipment such as circuit breakers, switch -
fuse, contactors, relays, meters etc.
5.2 Type Tests
CLIENT: OFFICE OF CHIEF MUNICIPAL OFFICER Job No. Page 6
URBAN LOCAL BODY, KUMHARI, DISTRICT- Calculation No. AM/CNPL/7.5MLD/ Rev. 0
DURG, CHHATTISGARH. KUM/EC/101
PROJECT: Kumhari Urban Local Body Augmentation Prepared By: Javed Akhter Date 25.03.2025
of Water Supply Scheme Checked By: Date
Technical Specification for LT Panel and Control & Relay Panel

All the Type Tests (as per IS- 8623/IEC) should have been carried out on an identical &
similar type of switchgear for each rating involved in the project with ACB mounted in
service condition inside the switchgear panel.

Type test certificates of any equipment shall be furnished if so designed by the


purchaser/ owner. Otherwise the equipment shall have to be type tested free of charge,
to prove the design. Type test performed before five (5) years are not acceptable.

6. Communication
The components of LV Panel shall have features to communicate with SCADA over RS-485
Port. All the feeders of the LV Panel including the Incomers shall be equipped with the
features to receive the command from the SCADA for the switching and shall also provide
feedback to the SCADA about the status of the feeders.

7. Feeder Details
The Feeders details required for the project shall be outlined in Annexure-1 for Raw
Water Pumping Station, Annexure-2 for Clear Water Pumping Station.

8. APFC Requiremernt
The APFC system need to be included for the correction of power factor. The tentative
requirement shall be the correction from 0.6 to 0.95 power factor. The APFC shall be
installed within the same Bus-Bar as of LV Panel.

9. Document Submittal
Bidder to submit the following documents as minimum requirement:
a. General arrangement drawing showing constructional features, space required in
front for withdrawals, power & control cable entry points etc.
b. Typical foundation plan
c. Typical control schematic
d. Bill of materials
e. Type test reports on circuit breaker
f. Technical leaflets on:
i. Circuit breaker
ii. Switch-fuse units
iii. Contactors
iv. Relays, meters, push buttons, selector switches etc.
v. Glands/terminals blocks
CLIENT: OFFICE OF CHIEF MUNICIPAL OFFICER Job No. Page 7
URBAN LOCAL BODY, KUMHARI, DISTRICT- Calculation No. AM/CNPL/7.5MLD/ Rev. 0
DURG, CHHATTISGARH. KUM/EC/101
PROJECT: Kumhari Urban Local Body Augmentation Prepared By: Javed Akhter Date 25.03.2025
of Water Supply Scheme Checked By: Date
Technical Specification for LT Panel and Control & Relay Panel

Technical Specifications for Control and Relay Panel


1. List of standards for Control and Relay panel

IS 722 Ac electrical meters


Direct acting indicating analogue electrical
IS 1248
measurement and accessories
Degree of protection provided by enclosures for low
IS/IEC: 60947
voltage switchgear and control gear.
IS: 6005 Code of practice for phosphating of iron and steel.
IEC: 61850 Communication Standard for Numerical relays
IEC: 61131-3 Automation Standard for Numerical relays
AC contactors for voltages above 1000 volts and upto
IS: 9046
and including 11000 Volts.
IS: 13703 Low voltage fuses
Guide for uniform system of marking and identification
IS: 11353
of conductors and apparatus terminals.
IEC: 60947-7-1 Terminal blocks for copper conductors
IS :513 (2008) Cold Rolled Low Carbon Steel Sheets and Strips

2. General Requirements
a. The switchgear boards shall have a single front, single tier, fully
compartmentalized, metal enclosed construction. comprising of a row of free-
standing floor mounted panels.
b. As a minimum, 2 mm (14SWG) sheet steel shall be used for all front and rear
doors and covers. Gland plate and load bearing component sheet minimum
thickness to be 3 mm. Wherever required, stiffeners shall be provided to increase
stiffness of large size doors and covers.
c. The panel shall be totally enclosed and vermin-proof. If necessary, openings for
natural ventilation shall be provided. These shall be provided with wire mesh
having opening less than 1mm. The enclosure shall have complete protection
against approach to live parts. The enclosure shall have IP4X protection as per IEC
529.
d. All openings, covers and doors shall be provided with suitable neoprene gaskets.
e. The panel shall be provided with front access with hinged doors and rear access
with bolted cover.
CLIENT: OFFICE OF CHIEF MUNICIPAL OFFICER Job No. Page 8
URBAN LOCAL BODY, KUMHARI, DISTRICT- Calculation No. AM/CNPL/7.5MLD/ Rev. 0
DURG, CHHATTISGARH. KUM/EC/101
PROJECT: Kumhari Urban Local Body Augmentation Prepared By: Javed Akhter Date 25.03.2025
of Water Supply Scheme Checked By: Date
Technical Specification for LT Panel and Control & Relay Panel

f. All relays, metering, and control components shall be mounted on the panel front
only. All terminals shall be shrouded with plastic covers to prevent accidental
contact.
g. The panels shall be provided with space heaters to prevent moisture
condensation.
h. The panel shall be suitable for installation on panel supporting frame of 3-4 mm
thickness, to be supplied by others. The panels shall be suitable for tack welding,
directly to this frame.
i. All analogue instruments shall be of square pattern, 96X96 mm, flush mounted
type. Measuring instruments shall be provided. The accuracy class for all
instruments shall be 1.0. Digital instruments shall also be acceptable.
j. The switchboard shall be Powder Coated & finished with shade RAL-7032. The
switchboard shall comprise of the equipment / components listed below in BOM.
k. All routine & acceptance tests shall be carried out at manufacturer’s work in
presence of project in charge, Consultant or Owner representative.
l. All Relays should be numerical type (Integral relays along with RS 485 / MODBUS
RTO Protocol). All relays and switch gears status has to be communicated to
common PLC SCADA to monitor and control the system.

3. Auxiliary Wiring and Terminals


a. Inside the cubicles, the wiring for control, signaling, protection and instrument
circuits shall be done with BIS approval, PVC insulated, flame retardant type, and
copper conductor wire. The insulation grade shall be 650 V. The wiring shall be
routed through flexible conduits.
b. Each wire shall be identified at both ends by correctly sized PVC ferrules, shorting
links shall be provided for all CT terminals.
c. CT secondary wiring shall be done with 2.5 sq.mm copper conductors. Other
control wiring may be with 1.5 sq.mm copper conductors.

4. Metering panel
a. As per local metering code, plant end (as per SLD) metering arrangement is
required for measurement of solar energy supplied by Solar generating stations.
b. The meters shall have to be of 0.5/1.0 class accuracy in line with the Good Utility
Practices. The Main Meter (MFM) shall be located at the cubicle and shall
measure current & voltage from same current and potential transformer at
different cores.

5. Numerical relay
a. Circuit breaker feeders (with protection function as per requirement) shall be
provided with communicable numerical relays (IED, i.e. Intelligent Electronic
CLIENT: OFFICE OF CHIEF MUNICIPAL OFFICER Job No. Page 9
URBAN LOCAL BODY, KUMHARI, DISTRICT- Calculation No. AM/CNPL/7.5MLD/ Rev. 0
DURG, CHHATTISGARH. KUM/EC/101
PROJECT: Kumhari Urban Local Body Augmentation Prepared By: Javed Akhter Date 25.03.2025
of Water Supply Scheme Checked By: Date
Technical Specification for LT Panel and Control & Relay Panel

Device) complying with IEC-61850, having protection, control, and monitoring


features.
i. Numerical relay with breaker feedback protection: Modbus RS485.
ii. MFM / TVM shall be Modbus RS485.
b. These relays shall be networked and suitably interfaced with the SCADA system
for dynamic SLD display, status monitoring, measurements, event / alarm
displays, reports, etc.
c. Feasibility needs to be checked for the existing system to be interfaced with the
SCADA system of the new project.
d. Disturbance Record waveforms, event records & alarms shall be stored in Non-
volatile memory and failure of control supply shall not result in deletion of any of
these data Relays shall have event recording feature, recording of abnormalities
and operating parameters with time stamping.
e. All CT & VT terminals on the relays shall be of fixed type suitable for connection of
ring type lugs to avoid any hazard due to loose connection leading to CT open
circuit.
f. Relays shall have at least two sets or groups of two different sets of adaptable
settings. Relays shall have multiple IEC / ANSI programmable characteristics.

6. EARTHING AND EARTHING DEVICES


a. Copper / galvanized steel earthing bus shall be provided at the bottom and shall
extend throughout the length of each switch board. It shall be bolted/ welded to
the framework of each panel at the bottom and shall extend both side for
connecting with Employer’s earthing system.
b. The earth bus shall have sufficient cross section to carry the momentary short
circuit and short time fault currents to earth as indicated under switchgear
parameters without exceeding the allowable temperature rise.
c. Suitable arrangement shall be provided at each end of the earth bus for bolting to
Employer's earthing conductors. All joint splices to the earth bus shall be made
through at least two bolts and taps by proper lug and bolt connection.
d. VT and CT secondary neutral point earthing shall be at one place only on the
terminal block. Such earthing shall be made through links so that earthing of one
secondary circuit may be removed without disturbing the earthing of other
circuits.

7. PAINTING
a. Paint shade shall be RAL 7032.

8. CONTROL SUPPLY AND SPACE HEATER SUPPLY


a. Each panel shall be provided at least two (02) Nos of aux. supply viz., DC Supply
from the Power Pack and the raw power from the LT Panel.
CLIENT: OFFICE OF CHIEF MUNICIPAL OFFICER Job No. Page 10
URBAN LOCAL BODY, KUMHARI, DISTRICT- Calculation No. AM/CNPL/7.5MLD/ Rev. 0
DURG, CHHATTISGARH. KUM/EC/101
PROJECT: Kumhari Urban Local Body Augmentation Prepared By: Javed Akhter Date 25.03.2025
of Water Supply Scheme Checked By: Date
Technical Specification for LT Panel and Control & Relay Panel

b. Suitable rated 230V single phase AC supply feeder per switchboard / Switchboard
section for space heater supply. Bidder shall provide necessary switch and fuse to
receive, isolate and distribute to each panel.

9. SPACE HEATER
a. A 230V single phase 50 Hz AC plug point shall be provided in the interior of each
cubicle with ON-OFF switch for connection of hand lamp.
b. Each panel shall be equipped with thermostatically controlled space heater(s),
suitably located in breaker and cable compartments to prevent condensation
within the enclosure. The space heater shall be connected to 230V single phase
AC auxiliary supply available in the panel, through switches and fuses provided
separately for each panel.

10. TEST
a. ROUTINE TESTS
i. All acceptance and routine tests as per the specification and relevant
standards shall be carried out. Charges for these shall be deemed to be
included in the equipment price.
ii. An indicative list of tests / checks is to be provided by the manufacturer in
a detailed Quality Plan indicating the practice and procedure along with
relevant supporting documents.

11. Document Submittal


Bidder to submit the following documents as minimum requirement:
a. Detailed GA drawing of the Control and Relay Panel
b. Detailed filled in technical datasheet of the C&R panel.
c. Detailed schematic diagram including Metering, protection, interconnection,
Indication etc.
d. Detailed bill of materials
e. Installation & maintenance manual.
f. Manufacturer quality plan
g. All type and routine test reports.

12. Key technical particulars

Sr. Description Particular


No
A SYSTEM PARAMETERS
1 Nominal System voltage 33kV
2 Highest System voltage 36kV
CLIENT: OFFICE OF CHIEF MUNICIPAL OFFICER Job No. Page 11
URBAN LOCAL BODY, KUMHARI, DISTRICT- Calculation No. AM/CNPL/7.5MLD/ Rev. 0
DURG, CHHATTISGARH. KUM/EC/101
PROJECT: Kumhari Urban Local Body Augmentation Prepared By: Javed Akhter Date 25.03.2025
of Water Supply Scheme Checked By: Date
Technical Specification for LT Panel and Control & Relay Panel

3 Rated Frequency 50Hz


4 Number of phases/ poles Three
5 System neutral earthing Solidly Earthed
B One minute power frequency withstand voltage
1 for Type tests 70kV
2 for Routine tests 70kV
1.2/50 microsecond Impulse
3 170kV (peak)
withstand voltage
4 Minimum system fault level 25kA for 1 Sec.
Short time rating for bus bars,
ckt. breakers, current
5 25kA for 1 Sec.
transformers and swgr.
assembly.
6 Dynamic withstand rating 63kA(peak)
7 Control supply voltage 24V DC/230V AC
8 Maximum ambient air 500C
temperature
C SWGR. CUBICLE CONSTRUCTIONAL REQUIREMENTS
1 Cable entry Bottom
2 Earthing conductor Galvanized steel strip
D METERING
1 Secondary Current 5A / 1A
2 Class of Insulation Class E or better
Adequate for the relays and devices
3 Rated output of each
connected,
4 Accuracy class
Class 5P20 / 5P10 for other
Protection
protection CTs;
0.5 (For MFM)
Metering
CLIENT: OFFICE OF CHIEF MUNICIPAL OFFICER Job No. Page 12
URBAN LOCAL BODY, KUMHARI, DISTRICT- Calculation No. AM/CNPL/7.5MLD/ Rev. 0
DURG, CHHATTISGARH. KUM/EC/101
PROJECT: Kumhari Urban Local Body Augmentation Prepared By: Javed Akhter Date 25.03.2025
of Water Supply Scheme Checked By: Date
Technical Specification for LT Panel and Control & Relay Panel

ANNEXURE-1: FEEDER REQUIREMENT FOR RAW WATER PUMPING STATION:


Sl.No Rating in
. Motor Purpose KW Qty. Feeder Reqd. Unit Remarks
1 Raw Water Pump 65 4 2W+2S Nos.
2 Dewatering Pump 7.5 5 2W+2S+1 (Spare) Nos.
3 Actuators 3.1 7 5W+2 (Spare) Nos.
4 EOT Cranes 5 6 5W+1 (Spare) Nos.
5 Station Lighting 3 1 1W Nos. 32A TPN
6 Transformer & Breaker Aux. Supply 2 2 1W+1 (Spare) Nos. 16A TPN
7 Maintenance Load (Incidental) 20 2 1W+1 (Spare) Nos. 32A TPN
8 Power Supply to PLC Panel 32A (TPN) 1 1 Nos.
9 Power supply to UPS (Future) 32A (TPN) 1 1 Nos. These shall be
10 Spare 63A TPN Feeder (Future) 63A (TPN) 1 1 Nos. clubbed as per
11 Spare 32A TPN Feeder (Future) 32A (TPN) 4 4 Nos. suitability.
12 Spare 16A TPN Feeder (Future) 32A (TPN) 4 4 Nos.
CLIENT: OFFICE OF CHIEF MUNICIPAL OFFICER Job No. Page 13
URBAN LOCAL BODY, KUMHARI, DISTRICT- Calculation No. AM/CNPL/7.5MLD/ Rev. 0
DURG, CHHATTISGARH. KUM/EC/101
PROJECT: Kumhari Urban Local Body Augmentation Prepared By: Javed Akhter Date 25.03.2025
of Water Supply Scheme Checked By: Date
Technical Specification for LT Panel and Control & Relay Panel

ANNEXURE-2: FEEDER REQUIREMENT FOR CLEAR WATER PUMPING STATION:


Sl.No Rating in
. Motor Purpose KW Qty. Feeder Reqd. Unit Remarks
1 Clear Water Pump 75 4 2W+2S Nos.
2 Air Blower 9.3 3 1W+1S+1 (Spare) Nos.
3 Wash Water Pump 9.3 2 1W+1S Nos.
4 Recirculation Pump 15 2 1W+1S Nos.
Feed Pump 1.2 3 1W+1S+1 (Spare)
Circular Thickener Tank 3.2 1 1W
Centrifuge Pump 22 2 1W+1S
Flash Mixer / Clarifloccator / Plate Settler 7.6 6 3W+2S+1 (Spare)
Lime / Alum / PE / Poly Dosing Pump 1.2 7 3W+3S+1 (Spare)
Lime / Alum / PE / Poly Agitator 2.2 7 3W+3S+1 (Spare)
Actuator 3.1 6 5W+1 (Spare)
EOT Cranes 5 6 5W+1 (Spare)
5 Station Lighting 5 1 1W Nos.
6 Transformer & Breaker Aux. Supply 2 2 1W+1 (Spare) Nos.
7 Maintenance Load (Incidental) 20 2 1W+1 (Spare) Nos.
8 Power Supply to PLC Panel 32A (TPN) 1 1 Nos.
9 Power supply to UPS (Future) 32A (TPN) 1 1 Nos. These shall be
10 Spare 63A TPN Feeder (Future) 63A (TPN) 1 1 Nos. clubbed as per
11 Spare 32A TPN Feeder (Future) 32A (TPN) 6 6 Nos. suitability.
12 Spare 16A TPN Feeder (Future) 32A (TPN) 6 6 Nos.
CLIENT: OFFICE OF CHIEF MUNICIPAL OFFICER Job No. Page 14
URBAN LOCAL BODY, KUMHARI, DISTRICT- Calculation No. AM/CNPL/7.5MLD/ Rev. 0
DURG, CHHATTISGARH. KUM/EC/101
PROJECT: Kumhari Urban Local Body Augmentation Prepared By: Javed Akhter Date 25.03.2025
of Water Supply Scheme Checked By: Date
Technical Specification for LT Panel and Control & Relay Panel

ANNEXURE-3: CONSOLE PANEL REQUIREMENT FOR FILTER BED ACTUATORS:

LT Console Panel shall comprise of 1 No. Incomer and 7 Nos. Output feeders to power the
Actuators for valve operation.
Each console panel shall be equipped with the PLC to receive the commands and execute the
designated task as per the operation programming. The feedback signal of the console panel
shall be fed to the SCADA for the real-time monitoring.
Sl.No Rating in
. Motor Purpose KW Qty. Feeder Reqd. Unit Remarks
1 Actuators 3.1 25 12W+13S Nos.
CLIENT: OFFICE OF CHIEF MUNICIPAL OFFICER Job No. Page 15
URBAN LOCAL BODY, KUMHARI, DISTRICT- Calculation No. AM/CNPL/7.5MLD/ Rev. 0
DURG, CHHATTISGARH. KUM/EC/101
PROJECT: Kumhari Urban Local Body Augmentation Prepared By: Javed Akhter Date 25.03.2025
of Water Supply Scheme Checked By: Date
Technical Specification for LT Panel and Control & Relay Panel