Technical Specifications of LT Panel & CPR
Technical Specifications of LT Panel & CPR
Page 1
URBAN LOCAL BODY, KUMHARI, DISTRICT- Calculation No. AM/CNPL/7.5MLD/ Rev. 0
DURG, CHHATTISGARH. KUM/EC/101
PROJECT: Kumhari Urban Local Body Augmentation Prepared By: Javed Akhter Date 25.03.2025
of Water Supply Scheme Checked By: Date
Technical Specification for LT Panel and Control & Relay Panel
2. General
All the AC low voltage switchboards shall be suitable for operation with 415volts, 50 Hz.
and 3/4 wire system.
3. Construction
a. The switchboards shall be dead front totally enclosed; cubicle type suitable for
floor mounted free standing / wall mounted indoor installations. The design shall
be totally dust - tight damp-proof and vermin proof offering degree of protection
not less than IP-42 for indoor applications and IP-55 for outdoors applications.
b. Switchboards shall be comply with IEC. Separate segregated compartments shall
be provided for breakers, bus bars, cable box, wire ways, relays, instrument and
control devices. Switchboard shall be compartmentalized design and shall be
provided with hinged doors in front and back with facility for padlocking doors.
c. Floor mounted cubicles shall be provided with a 75mm high channel base frame.
Total height of the cubicle shall not exceed 2400mm, keeping in view the
operating height of top switch shall be within the limit of 1750mm & 600mm from
floor level including base channel.
d. Adequate size cable compartment should be provided for easy clamping of all the
incoming and outgoing cables irrespective of top or bottom entries.
e. The compartment doors shall be provided with continuous gasket made of
polyurethane seamless gasket for providing water tightness and preventing
ingress of dust. The gasket shall be held in position in groove provided in the
enclosure and shall be pressed all around uniformly by suitably shaped projection
of the door. All hinged door shall be earthed through tinned copper wire. Doors
CLIENT: OFFICE OF CHIEF MUNICIPAL OFFICER Job No. Page 3
URBAN LOCAL BODY, KUMHARI, DISTRICT- Calculation No. AM/CNPL/7.5MLD/ Rev. 0
DURG, CHHATTISGARH. KUM/EC/101
PROJECT: Kumhari Urban Local Body Augmentation Prepared By: Javed Akhter Date 25.03.2025
of Water Supply Scheme Checked By: Date
Technical Specification for LT Panel and Control & Relay Panel
q. All measuring instruments (Meters of 0.5s Class) shall be of digital electronic with
LED display compatible with SCADA. Below table presents non-exhaustive
applicable standards to which AC switchboards should conform.
4. Key technical Particulars
5. Tests
All equipment shall be completely assembled, wired, adjusted and tested at the factory
as per the relevant standards.
5.1 Routine Test
The tests shall include but not necessarily be limited to the following:
a. Operation under simulated service condition to ensure accuracy of wiring,
correctness of control scheme and proper functioning of the equipment.
b. All wiring and current carrying part shall be given appropriate High Voltage Test
c. Primary current & voltages shall be applied to all instrument transformers.
d. Routine test shall be carried out on all equipment such as circuit breakers, switch -
fuse, contactors, relays, meters etc.
5.2 Type Tests
CLIENT: OFFICE OF CHIEF MUNICIPAL OFFICER Job No. Page 6
URBAN LOCAL BODY, KUMHARI, DISTRICT- Calculation No. AM/CNPL/7.5MLD/ Rev. 0
DURG, CHHATTISGARH. KUM/EC/101
PROJECT: Kumhari Urban Local Body Augmentation Prepared By: Javed Akhter Date 25.03.2025
of Water Supply Scheme Checked By: Date
Technical Specification for LT Panel and Control & Relay Panel
All the Type Tests (as per IS- 8623/IEC) should have been carried out on an identical &
similar type of switchgear for each rating involved in the project with ACB mounted in
service condition inside the switchgear panel.
6. Communication
The components of LV Panel shall have features to communicate with SCADA over RS-485
Port. All the feeders of the LV Panel including the Incomers shall be equipped with the
features to receive the command from the SCADA for the switching and shall also provide
feedback to the SCADA about the status of the feeders.
7. Feeder Details
The Feeders details required for the project shall be outlined in Annexure-1 for Raw
Water Pumping Station, Annexure-2 for Clear Water Pumping Station.
8. APFC Requiremernt
The APFC system need to be included for the correction of power factor. The tentative
requirement shall be the correction from 0.6 to 0.95 power factor. The APFC shall be
installed within the same Bus-Bar as of LV Panel.
9. Document Submittal
Bidder to submit the following documents as minimum requirement:
a. General arrangement drawing showing constructional features, space required in
front for withdrawals, power & control cable entry points etc.
b. Typical foundation plan
c. Typical control schematic
d. Bill of materials
e. Type test reports on circuit breaker
f. Technical leaflets on:
i. Circuit breaker
ii. Switch-fuse units
iii. Contactors
iv. Relays, meters, push buttons, selector switches etc.
v. Glands/terminals blocks
CLIENT: OFFICE OF CHIEF MUNICIPAL OFFICER Job No. Page 7
URBAN LOCAL BODY, KUMHARI, DISTRICT- Calculation No. AM/CNPL/7.5MLD/ Rev. 0
DURG, CHHATTISGARH. KUM/EC/101
PROJECT: Kumhari Urban Local Body Augmentation Prepared By: Javed Akhter Date 25.03.2025
of Water Supply Scheme Checked By: Date
Technical Specification for LT Panel and Control & Relay Panel
2. General Requirements
a. The switchgear boards shall have a single front, single tier, fully
compartmentalized, metal enclosed construction. comprising of a row of free-
standing floor mounted panels.
b. As a minimum, 2 mm (14SWG) sheet steel shall be used for all front and rear
doors and covers. Gland plate and load bearing component sheet minimum
thickness to be 3 mm. Wherever required, stiffeners shall be provided to increase
stiffness of large size doors and covers.
c. The panel shall be totally enclosed and vermin-proof. If necessary, openings for
natural ventilation shall be provided. These shall be provided with wire mesh
having opening less than 1mm. The enclosure shall have complete protection
against approach to live parts. The enclosure shall have IP4X protection as per IEC
529.
d. All openings, covers and doors shall be provided with suitable neoprene gaskets.
e. The panel shall be provided with front access with hinged doors and rear access
with bolted cover.
CLIENT: OFFICE OF CHIEF MUNICIPAL OFFICER Job No. Page 8
URBAN LOCAL BODY, KUMHARI, DISTRICT- Calculation No. AM/CNPL/7.5MLD/ Rev. 0
DURG, CHHATTISGARH. KUM/EC/101
PROJECT: Kumhari Urban Local Body Augmentation Prepared By: Javed Akhter Date 25.03.2025
of Water Supply Scheme Checked By: Date
Technical Specification for LT Panel and Control & Relay Panel
f. All relays, metering, and control components shall be mounted on the panel front
only. All terminals shall be shrouded with plastic covers to prevent accidental
contact.
g. The panels shall be provided with space heaters to prevent moisture
condensation.
h. The panel shall be suitable for installation on panel supporting frame of 3-4 mm
thickness, to be supplied by others. The panels shall be suitable for tack welding,
directly to this frame.
i. All analogue instruments shall be of square pattern, 96X96 mm, flush mounted
type. Measuring instruments shall be provided. The accuracy class for all
instruments shall be 1.0. Digital instruments shall also be acceptable.
j. The switchboard shall be Powder Coated & finished with shade RAL-7032. The
switchboard shall comprise of the equipment / components listed below in BOM.
k. All routine & acceptance tests shall be carried out at manufacturer’s work in
presence of project in charge, Consultant or Owner representative.
l. All Relays should be numerical type (Integral relays along with RS 485 / MODBUS
RTO Protocol). All relays and switch gears status has to be communicated to
common PLC SCADA to monitor and control the system.
4. Metering panel
a. As per local metering code, plant end (as per SLD) metering arrangement is
required for measurement of solar energy supplied by Solar generating stations.
b. The meters shall have to be of 0.5/1.0 class accuracy in line with the Good Utility
Practices. The Main Meter (MFM) shall be located at the cubicle and shall
measure current & voltage from same current and potential transformer at
different cores.
5. Numerical relay
a. Circuit breaker feeders (with protection function as per requirement) shall be
provided with communicable numerical relays (IED, i.e. Intelligent Electronic
CLIENT: OFFICE OF CHIEF MUNICIPAL OFFICER Job No. Page 9
URBAN LOCAL BODY, KUMHARI, DISTRICT- Calculation No. AM/CNPL/7.5MLD/ Rev. 0
DURG, CHHATTISGARH. KUM/EC/101
PROJECT: Kumhari Urban Local Body Augmentation Prepared By: Javed Akhter Date 25.03.2025
of Water Supply Scheme Checked By: Date
Technical Specification for LT Panel and Control & Relay Panel
7. PAINTING
a. Paint shade shall be RAL 7032.
b. Suitable rated 230V single phase AC supply feeder per switchboard / Switchboard
section for space heater supply. Bidder shall provide necessary switch and fuse to
receive, isolate and distribute to each panel.
9. SPACE HEATER
a. A 230V single phase 50 Hz AC plug point shall be provided in the interior of each
cubicle with ON-OFF switch for connection of hand lamp.
b. Each panel shall be equipped with thermostatically controlled space heater(s),
suitably located in breaker and cable compartments to prevent condensation
within the enclosure. The space heater shall be connected to 230V single phase
AC auxiliary supply available in the panel, through switches and fuses provided
separately for each panel.
10. TEST
a. ROUTINE TESTS
i. All acceptance and routine tests as per the specification and relevant
standards shall be carried out. Charges for these shall be deemed to be
included in the equipment price.
ii. An indicative list of tests / checks is to be provided by the manufacturer in
a detailed Quality Plan indicating the practice and procedure along with
relevant supporting documents.
LT Console Panel shall comprise of 1 No. Incomer and 7 Nos. Output feeders to power the
Actuators for valve operation.
Each console panel shall be equipped with the PLC to receive the commands and execute the
designated task as per the operation programming. The feedback signal of the console panel
shall be fed to the SCADA for the real-time monitoring.
Sl.No Rating in
. Motor Purpose KW Qty. Feeder Reqd. Unit Remarks
1 Actuators 3.1 25 12W+13S Nos.
CLIENT: OFFICE OF CHIEF MUNICIPAL OFFICER Job No. Page 15
URBAN LOCAL BODY, KUMHARI, DISTRICT- Calculation No. AM/CNPL/7.5MLD/ Rev. 0
DURG, CHHATTISGARH. KUM/EC/101
PROJECT: Kumhari Urban Local Body Augmentation Prepared By: Javed Akhter Date 25.03.2025
of Water Supply Scheme Checked By: Date
Technical Specification for LT Panel and Control & Relay Panel