HLCS Velachery
HLCS Velachery
GROUND
1 FLOOR
PHARMACY 126
2 PHLEBOTOMY 96
3 CONSULTATION 102
4 ENT 103
5 CONSULTATION 102
6 CONSULTATION 102
7 FIRST OPTOMETRY/AUDIO 108
8 FLOOR CONSULTATION 108
9 PHYSIOTHEROPY 109
10 WATING/ RECEPTION AREA 320
11 Corridor-1
320
12 Corridor-2
13 OPG 60
14 TMT 111
15 ECG/PFT 96
16 CONSULTATION 99
17 DENTAL-2 114
18 DENTAL-1 150
SECOND
19 FLOOR X-RAY 120
20 CONSOLE 62
21 USG 89
22 WATING/ RECEPTION AREA 320
23 Corridor-1
295
24 Corridor-2
Preferrable Outdoor units Combination: 12HP +12HP + 12HP @ EER OF 4.2
RECOMMENDED RECOMMENDED
INDOOR UNIT TYPE AS PER OUTDOOR
INDOOR UNIT OUTDOOR UNIT
RCP UNIT IN Tr
CAPACITY (TR) IN HP
HI-wall 1
HI-wall 1
HI-wall 1
HI-wall 1
HI-wall 1
HI-wall 1
HI-wall 1
HI-wall 1
4-Way Cassette 3
4-Way Cassette, Compact
1.5
(2' X 2')
4-Way Cassette, Compact
1.5
(2' X 2')
32 26.56
HI-wall 1
HI-wall 1
HI-wall 1
HI-wall 1
HI-wall 1
HI-wall 1.5
HI-wall 1.5
HI-wall 1
HI-wall 1
4-Way Cassette 3
4-Way Cassette, Compact
1.5
(2' X 2')
4-Way Cassette, Compact
1.5
(2' X 2')
31.5 119% DIVERSITY
1 DENTAL-1 150 3 31
2 OPG 60 3 24
3 DENTAL-2 114 3 28
4 ECG/PFT 97 2 21
5 CONSULTANT ROOM 99 3 27
6 TMT 111 2 22
8 CORRIDOR 300 6 62
9 USG 89 2 20
10 CONSOLE 63 2 18
11 XRAY 120 2 22
ASSESSED
LIGHTING PROPOSED UNIT CONFIGURATION
COOLING LOAD.
LOAD (KW)
EQUIPMENT
considered
LOAD
1.0 watts / CFM/
sq.ft TR CFM TR QTY CFM
SQFT
15.1 16.0
1.5
1.0
1.0
1.0
1.0
1.0
3.0
3.0
1.0
1.0
1.5
FRESH AIR 5 CFM /
OCCUPANCY
AREA IN person + 0.06 CFM /
SL.NO DESCRIPTION ( 80 seats /
SQ.FT sq.ft & 30% extra for
sq.ft)
LEED.
1 PHARMACY 126 3 29
PHLEBOTAMY 96 3 26
2 PHYSIOTHERAPHY 124 2 23
3 CONSULTATION-01 103 3 28
4 CONSULTATION-02 103 3 28
5 OPTOMETRY/ENT 109 3 28
6 CONSULTATION-03 109 3 28
7 CONSULTATION-04 109 3 28
8 WAITING AREA 300 21 187
9 CORRIDOR 300 6 62
10 ENT 103 3 28
TOTAL
ASSESSED COOLING
LIGHTING LOAD PROPOSED UNIT CONFIGURATION
LOAD.
(KW) EQUIPMENT
considered 1.0 LOAD
watts / sq.ft TR CFM TR QTY CFM CFM/SQFT
15.5