Sheet 2 Transformers
Sheet 2 Transformers
3- A transformer has a primary winding of 800 turns and a secondary winding of 200 turns.
When the load current on the secondary is 80 A at 0.8 power factor lagging, the primary
current is 25 A at 0.707 power factor lagging. Determine graphically or otherwise the no-load
current of the transformer and its phase with respect to the voltage.
4- The no-load current of a transformer is 0.5 A at a 0.3 p.f. when supplied at 230 V, 50 Hz. The
number of turns on the primary winding is 200 Calculate:
a- The maximum value of the flux in the core.
b- The core losses.
c- The magnetizing current.
6- The equivalent circuit for a 200/400 V step up transformer has the following parameters
referred to the low voltage side.
Equivalent resistance = 0.15 Ω, equivalent reactance = 0.37 Ω, core-loss component
resistance = 600 Ω, magnetizing reactance = 300 Ω.
When the transformer is supplying a load of 10 A at power factor of 0.8 lag, calculate the
primary current and secondary terminal voltage.
7- A 1-ph, 10 kVA, 500/250 V, 50 Hz transformer has the following constants:
Reactance : primary 2 ohm, secondary 0.5 ohm
Resistance : primary 0.4 ohm, secondary 0.1 ohm
Resistance of exciting current referred to primary Ro = 1500 ohm
Reactance of exciting current referred to primary X o = 750 ohm
What would be the readings of the instruments when the transformer is connected for the
O.C. and S.C. tests?
8- Obtain the equivalent circuit of a 200/400 V, 50 Hz, 1-ph transformer from the following test
data:
O.C. Test: 200 V, 0.7 A, 70 W on LV side
S.C. Test: 15 V, 10 A, 85 W on HV side
Calculate the secondary voltage when delivering 5 kW at 0.8 power factor lagging. The
primary voltage is 200 V.
10- A 20- kVA, 2200/220 V, 50 Hz distribution transformer is tested for efficiency and regulation
as follows:
O.C. Test: 220 V 4.2 A 148 W
S.C. Test: 86 V 10.5 A 360 W
Determine:
a- Core losses.
b- Equivalent resistance referred to primary.
c- Equivalent resistance referred to secondary.
d- Equivalent reactance referred to primary.
e- Equivalent reactance referred to secondary.
f- Regulation of transformer at full load and 0.8 power factor lagging.
g- Efficiency at full load and half full load at 0.8 power factor lagging.
12- A 5 kVA, 2300/230 V, 50 Hz transformer was tested for the iron losses with normal
excitation and copper losses at full load and these were found to be 40 W and 112 W
respectively. Calculate the efficiencies of the transformer at 0.8 power factor for the
following kVA outputs:
1.25 2.5 3.75 5 6.25 7.5
Plot the efficiency vs. output curve.
13- A 600 kVA, 1-ph transformer when working at unity power factor has an efficiency of 92% at
full load and also at half full load. Determine its efficiency when it operates at unity power
factor and 60% of full load.
14- Find the all-day efficiency of a 500 kVA distribution transformer whose copper losses and
iron losses at full load are 4.5 kW and 3.5 kW respectively. During a day of 24 hours, it is
loaded as under:
No. of hours Load in kW Power factor
6 400 0.8
10 300 0.75
4 100 0.8
4 0 ----
15- Two 100 kW transformers each has a maximum efficiency of 98%. But in one the maximum
efficiency occurs at full load while in the other it occurs at half load. Each transformer is on
full load for 4 hours, on half load for 6 hours and on one-tenth load for 14 hours per day.
Determine the all-day efficiency of each transformer.
16- A 200 kVA transformer has an efficiency of 98% at full load. If the maximum efficiency
occurs at three-quarters of full load, calculate:
a- Iron and Copper losses.
b- Efficiency at half load.
Ignore the magnetizing current and assume a p.f. of 0.8 at all loads.
18- A 200 kVA, 6350/660 V, 1-phase transformer has the following winding impedances:
On no-load the transformer takes a current of 0.96 A at power factor of 0.263 lagging on
the high voltage side. Calculate:
1- The equivalent circuit parameters referred to the high voltage side. Draw the
approximate equivalent circuit.
2- The voltage regulation at full load and 0.8 power factor lagging.
3- The maximum voltage regulation at full load.
4- The efficiency of the transformer at full load and 0.8 power factor lagging.
5- The maximum efficiency at 0.8 power factor lagging.
20- Two 1-ph transformers A and B are operating in parallel and supplying a common load of
1000 kVA at 0.8 power factor lagging. The data regarding the transformers are as follows:
Transformer Rating ( kVA ) % Resistance % Reactance
A 750 3 5
B 500 2 4
Determine the loading of each transformer.
21- Two transformers A and B gave the following test results; with the low tension short-
circuited transformer A takes a current of 10 A at 200 V, the power input being 1000 W.
Similarly, B takes 30 A at 200 V, the power input being 1500 W. On open circuit, both
transformers gave a secondary voltage of 220 V when 11000 volts are applied to the
primary terminals. These transformers are connected in parallel on both high tension and
low tension sides. Calculate the current and power in each transformer when supplying a
load of 200 A at 0.8 p.f. lagging.
5- A transformer used only for electrical isolation between two circuits has turns ratio which
is
a- more than unity b- less than unity
c- equal to unity d- more than 0.5
6- If 110% of normal voltage and 110% of normal frequency is applied to a transformer, the
percent change of eddy current loss is
a- 10% b- 20% c- 25% d- 21%
7- A transformer has two 2400 V primary coils and two 240 V secondary coils. By proper
connection of the windings, the transformation ratio that can be obtained is
a- 10 b- 5 c- 20 d – all the above
8- A single phase, 2200/200 V transformer takes 1 A at LT side on no-load at power factor of
0.385 lagging, the iron losses are
a- 167 W b- 77 W c- 88 W d- 98 W
9- Neglecting resistance, at constant flux density, the power required per kg to magnetize the
iron core of the transformer is 0.8 W at 25 Hz and 2.04 W at 60 Hz. The power required per
kg at 100 Hz is
a- 3.8 W b- 3.63 W c- 3.4 W d- 5.2 W
13- High leakage impedance transformers are used for applications such as
a- power distribution b- electric toys
c- arc welding d- fluorescent lamps
14- A transformer 2000 kVA, 250 Hz is to operate at 50 Hz, its kVA rating should be revised to
a- 400 kVA b- 10000 kVA c- 2000 kVA d- can not be revised
16- Transfer of electric power from primary to secondary in a transformer takes place
a- electrically b- electromagnetically
c- magnetically d- none of these
23- A ferrite core has less eddy current loss than an iron core because ferrites have
a- Lower permeability b- high hysteresis
c- alnico as the main constituent d- high resistance
c- leading d- leading
25- The zero voltage regulation of a transformer occurs at a power factor of:
a- Unity b- lagging
c- leading d- leading
26- A transformer is connected to a constant voltage source. If the supply frequency decreases,
magnetic flux in the core will
a- increase b- decrease c- remain unchanged d- none of these
28- The efficiency of an auto-transformer for the same output compared to a two winding
transformer is
a- greater b- lesser c- poor d- none of these
30- During parallel operation of transformers, incorrect polarity will result in:
a- open circuit b- dead short circuit c- regeneration power
d- power factor of transformer will be different from that of the load
31- A 10 kVA, 400/200 V single phase transformer with 10 % impedance draws a steady short
circuit current of:
a- 50 A b- 150 A c- 250 A d- 350 A
37- While performing short circuit test on a transformer the applied voltage magnitude is kept
constant but the frequency is increased. The short circuit current will
a- increase b- decrease c- remain the same d- none of the above
38- A transformer has a hysteresis loss of 30 W at 240 V, 60 Hz. The hysteresis loss at 200 V, 50
Hz will be
a- 20.8 W b- 25 W c- 30 W d- 36 W
39- In a transformer the exciting current will be in phase quadrature with the applied voltage
provided
a- only the leakage impedance drop is ignored
b- only the core loss is ignored
c- both the leakage impedance drop and the core loss are ignored
d- only no-load copper loss is ignored
40- The magnetizing impedance of a transformer is determined by
a- short circuit test b- open circuit test
c- both open circuit and short circuit tests d- none of these
41- A transformer is to be tested at full load conditions while consuming only losses from the
supply. The test is
a- Load test b- open circuit and short circuit tests
c- back to back test d- none of these
42- In a transformer operating at constant voltage if the input frequency increases the core loss
will
a- Increase b- decrease c- remain constant
b- increase as the square of the frequency
43- is the resistance of the primary winding of a transformer. The turns ratio in terms of
primary to secondary is . The equivalent resistance of the primary referred to secondary is
a- b- c- d - none of these
44- If are the induced emf and the terminal voltage in the secondary winding during
load, the voltage regulation of the transformer is given by
a- b- c- d-
45- One transformer has leakage impedance of (1+j4) Ω and (3+j4) Ω for its primary and
secondary windings respectively. The transformer has
a- low voltage primary b- high voltage primary
c- medium voltage primary d- none of the above
46- A single phase transformer has its maximum efficiency at 60 % of full load. At full load the
copper loss will be
a- equal to core loss b- less than core loss
c- more than core loss d- zero
47- The flux in a magnetic core is alternating sinusoidally at a frequency of 600 Hz. The
maximum flux density is 2 T and the eddy current loss is 15 watt. If the frequency is raised
to 800 Hz and the maximum flux density is reduced to 1.5 T, the eddy current loss will be
a- The same b- reduced to half
c- doubled d- increased by 50 %
Answers
1- b 2- a 3- c 4- a 5- c
6- d 7- d 8- b 9- b 10- a
11- d 12- b 13- c 14- a 15- d
16- b 17- b 18- c 19- d 20-d
21- b 22- d 23-d 24- b 25- d
26- a 27- d 28- a 29- e 30- b
31- c 32- a 33- c 34- b 35- a
36- c 37- b 38- b 39- b 40- b
41- c 42- a 43- c 44- a 45- a
46- c 47- a 48- b