Schneider Electric - Altivar-Soft-Starter-ATS480 - ATS480D17Y

The document provides a detailed product data sheet for the Altistart 480 soft starter (ATS480D17Y), which is designed for asynchronous motors with a rated operational current of 17A and a voltage range of 208 to 690V AC. It includes specifications on power supply, motor power ratings, protection features, environmental compatibility, and communication options. The product is available in stock and is intended for use in process and infrastructure applications.

Uploaded by

ryanstoner59
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
37 views12 pages

Schneider Electric - Altivar-Soft-Starter-ATS480 - ATS480D17Y

The document provides a detailed product data sheet for the Altistart 480 soft starter (ATS480D17Y), which is designed for asynchronous motors with a rated operational current of 17A and a voltage range of 208 to 690V AC. It includes specifications on power supply, motor power ratings, protection features, environmental compatibility, and communication options. The product is available in stock and is intended for use in process and infrastructure applications.

Uploaded by

ryanstoner59
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 12

Product data sheet

Specifications

Soft starter, Altistart 480, 17A, 208


to 690V AC, control supply 110 to
230V AC
ATS480D17Y

Product availability: Stock - Normally stocked in distribution


facility

Main
Range of Product Altivar Soft Starter ATS480

Product or Component Type Soft starter

Product destination Asynchronous motors

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product Specific Application Process and infrastructures

Device short name ATS480

Phase 3 phase

Utilisation category AC-3A


AC-53A

Ue power supply voltage 208...690 V - 15...10 %

power supply frequency 50...60 Hz - 20...20 %

[Ie] rated operational current Normal duty 17.0 A 104 °F (40 °C))

rated current in heavy duty 12.0 A at 104 °F (40 °C) heavy duty

Torque control True

IP Degree of Protection IP20

Motor power kW 4.0 kW 230 V in the motor supply line normal duty
2.2 kW 230 V in the motor supply line heavy duty
7.5 kW 400 V in the motor supply line normal duty
5.5 kW 400 V in the motor supply line heavy duty
7.5 kW 440 V in the motor supply line normal duty
5.5 kW 440 V in the motor supply line heavy duty
9.0 kW 500 V in the motor supply line normal duty
7.5 kW 500 V in the motor supply line heavy duty
9.0 kW 525 V in the motor supply line normal duty
7.5 kW 525 V in the motor supply line heavy duty
11.0 kW 660 V in the motor supply line normal duty
9.0 kW 660 V in the motor supply line heavy duty
15.0 kW 690 V in the motor supply line normal duty
11.0 kW 690 V in the motor supply line heavy duty
7.5 kW 230 V to the motor delta terminals normal duty
5.5 kW 230 V to the motor delta terminals heavy duty
15.0 kW 400 V to the motor delta terminals normal duty
11.0 kW 400 V to the motor delta terminals heavy duty

Maximum Horse Power Rating 3.0 hp 208 V normal duty


2.0 hp 208 V heavy duty
5.0 hp 230 V normal duty
3.0 hp 230 V heavy duty
10.0 hp 460 V normal duty
7.5 hp 460 V heavy duty
15.0 hp 575 V normal duty
10.0 hp 575 V heavy duty

Option card Communication module Profibus DP V1


Communication module Modbus TCP/EtherNet/IP
Communication module CANopen daisy chain
Communication module CANopen Sub-D
Communication module CANopen open style

Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price.

Mar 3, 2025 1
Complementary
Device connection In the motor supply line
To the motor delta terminals

[Us] control circuit voltage 110...230 V AC 50/60 Hz - 15...10 %

Apparent power 0.06 kVA

Integrated motor overload True


protection
motor thermal protection class Class 10E

Protection type Phase failure line


Integrated thermal protection motor
Thermal protection starter
Current overload motor
Underload motor
Excessive starting time, locked rotor motor
Motor phase loss motor
Line supply phase loss line
Line supply phase loss motor
Thermal protection motor

current limiting %In (5 x Ie 150…700 %


maximum)
[In] Rated current pwr loss 17.0 A
specifctn
Power loss static current 25.0 W
independent
Power loss per device current 38.0 W
dependent
Standards IEC 60947-4-2
UL 60947-4-2
IEC 60664-1

Product Certifications CE
cULus
CCC
UKCA
RCM
EAC
DNV
ABS
BV
CCS

Marking CE
CCC
UKCA
EAC
RCM
CULus

[Uc] control circuit voltage 24 V DC

Discrete input number 4

Discrete input type STOP) logic inputs, 3500 Ohm


RUN) logic inputs, 3500 Ohm
DI3) programmable as logic input, 3500 Ohm
DI4) programmable as logic input, 3500 Ohm

Input compatibility STOP discrete input level 1 PLC IEC 61131-2


RUN discrete input level 1 PLC IEC 61131-2
DI3 discrete input level 1 PLC IEC 61131-2
DI4 discrete input level 1 PLC IEC 61131-2

Discrete input logic Programmable digital input < 5 V

Relay output number 3

Relay output type Relay outputs R1A 1 NO


Relay outputs R1B 1 NO
Relay outputs RIC NO/NC programmable

Minimum switching current 100 mA 12 V DC relay outputs

2 Mar 3, 2025
Maximum switching current Relay outputs 2 A 250 V AC
Relay outputs 2 A 30 V DC

Discrete output number 2

Discrete output type DQ1) programmable digital output <= 30 V


DQ2) programmable digital output <= 30 V

Output compatibility Open collector level 1 PLC IEC 65A-68

Analogue input number 1

Analogue input type AI1/PTC PTC/Pt 100 temperature probe


PTC2 PTC/Pt 100 temperature probe
PTC3 PTC/Pt 100 temperature probe

Analogue output number 1

Analogue output type Current output AQ1 0...20 mA or 0...10 V 500 Ohm

Communication Port Protocol Modbus serial

Connector Type 1 RJ45

Communication data link Serial

Physical interface 2-wire RS 485

Transmission Rate 1200...256000 bit/s

Transmission frame RTU

Data format 8 bits, configurable odd, even or no parity

Type of polarization No impedance Modbus serial

Number of addresses 0…227 Modbus serial

Method of access Slave Modbus serial

Function Available External bypass control


Pre-heating
Smoke extraction
Multi-motor cascade
Second motor set
User management
Ports and services hardening
Security event logging
Cybersecure firmware update
Single direction

Display screen available True

Operating position Vertical +/- 10 degree

Height 10.8 in (275.0 mm)

Width 6.3 in (160.0 mm)

Depth 8.0 in (203.0 mm)

Net Weight 10.8 lb(US) (4.9 kg)

Environment
Electromagnetic compatibility Conducted and radiated emissions level A conforming to IEC 60947-4-2
Conducted and radiated emissions with bypass level B conforming to IEC 60947-4-2
Damped oscillating waves level 3 conforming to IEC 61000-4-12
Electrostatic discharge level 3 conforming to IEC 61000-4-11
Immunity to electrical transients level 4 conforming to IEC 61000-4-4
Immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3
Voltage/current impulse level 3 conforming to IEC 61000-4-5

pollution degree Level 3

[Uimp] rated impulse withstand 6 kV


voltage
[Ui] Rated Insulation Voltage 690 V

Mar 3, 2025 3
Environmental class (during Class 3C3 according to IEC 60721-3-3
operation) Class 3S2 according to IEC 60721-3-3

Relative humidity 0…95 % without condensation or dripping water IEC 60068-2-3

Ambient air temperature for 104…140 °F (40…60 °C) (with current derating of 2 % per °C)
operation 5…104 °F (-15…40 °C) (without derating)

Ambient Air Temperature for -13…158 °F (-25…70 °C)


Storage
Operating altitude <= 3280.84 ft (1000 m) without derating
> 3280.84...13123.36 ft (> 1000...4000 m) with current derating 1 % per 100 m

Maximum deflection under 1.5 mm at 2...13 Hz


vibratory load (during operation)
Maximum deflection under 1.75 mm at 2...9 Hz
vibratory load (during storage)
Maximum deflection under 1.75 mm at 2...9 Hz
vibratory load (during transport)
Maximum acceleration under 10 m/s² at 13...200 Hz
vibrational stress (during
operation)
Maximum acceleration under 15 m/s² at 200...500 Hz
vibratory load (during storage) 10 m/s² at 9...200 Hz

Maximum acceleration under 15 m/s² at 200...500 Hz


vibratory load (during transport) 10 m/s² at 9...200 Hz

Maximum acceleration under 150 m/s² at 11 ms


shock impact (during operation)
Maximum acceleration under 100 m/s² at 11 ms
shock load (during storage)
Maximum acceleration under 100 m/s² at 11 ms
shock load (during transport)

Ordering and shipping details


Category US1CP1G22588

Discount Schedule CP1G

GTIN 3606481088994

Returnability Yes

Country of origin ID

Packing Units
Unit Type of Package 1 PCE

Number of Units in Package 1 1

Package 1 Height 11.69 in (29.700 cm)

Package 1 Width 10.63 in (27.000 cm)

Package 1 Length 14.37 in (36.500 cm)

Package 1 Weight 13.558 lb(US) (6.150 kg)

Unit Type of Package 2 S06

Number of Units in Package 2 8

Package 2 Height 29.53 in (75.000 cm)

Package 2 Width 23.62 in (60.000 cm)

Package 2 Length 31.50 in (80.000 cm)

Package 2 Weight 138.450 lb(US) (62.800 kg)

4 Mar 3, 2025
Environmental Data

Schneider Electric aims to achieve Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity
via our ongoing “Use Better, Use Longer, Use Again” campaign to extend product lifetimes and recyclability.

Environmental Data explained

How we assess product sustainability

Environmental footprint

Carbon footprint (kg CO2 eq, Total Life cycle) 2115

Environmental Disclosure Product Environmental Profile

Use Better

Materials and Substances

Packaging made with recycled cardboard Yes

Packaging without single use plastic No

SCIP Number 411029a0-6a52-4ec9-8a30-b0c07e93ba50

China RoHS Regulation China RoHS declaration

WARNING: This product can expose you to chemicals


including: Lead and lead compounds, which is known to
California proposition 65 the State of California to cause cancer and birth defects
or other reproductive harm. For more information go to
www.P65Warnings.ca.gov

Use Again

Repack and remanufacture

Circularity Profile End of Life Information

The product must be disposed on European Union


WEEE markets following specific waste collection and never end
up in rubbish bins.

Take-back No

Mar 3, 2025 5
Product data sheet ATS480D17Y

Dimensions Drawings

Dimensions

Front, Side and Rear View

6 Mar 3, 2025
Product data sheet ATS480D17Y

Connections and Schema

Power Connections

(1) : Mains side


(2) : Motor side
1/L1, 3/L2, 5/L3 : Mains supply inputs
2/T1, 4/T2, 6/T3 : Outputs to motor
A2, B2, C2 : Soft starter bypass

Mar 3, 2025 7
Product data sheet ATS480D17Y

Connection in line, with line contactor, no bypass, type 1 or 2 coordination, non -


reversing, 2-wire or 3-wire control

(1) : Installation of additional fast-acting fuses to upgrade to type 2 coordination according to IEC 60947–4–2.
(2) : Take into account the electrical characteristics of the relays (Control Terminal Characteristics).
(3) : The transformer must supply 110...230 VAC +10% — 15%, 50/60Hz.
(4) : RUN and STOP Management (3-wire control).
(5) : RUN and STOP Management (2-wire control).

8 Mar 3, 2025
Product data sheet ATS480D17Y

Connection in line, with line and bypass contactor, freewheel or controlled stop, type 1 or
2 coordination, non reversing, 2-wire or 3-wire

(1) : Installation of additional fast-acting fuses to upgrade to type 2 coordination according to IEC 60947–4–2.
(2) : Take into account the electrical characteristics of the relays (Control Terminal Characteristics).
(3) : The transformer must supply 110...230 VAC +10% – 15%, 50/60Hz.
(4) : Take into account the electrical characteristics of the relays, especially when connecting to high rating contactor
(Control Terminal Characteristics).
(5) : RUN and STOP Management (3-wire control).
(6) : RUN and STOP Management (2-wire control).
(7) : PC or PLC control

Mar 3, 2025 9
Product data sheet ATS480D17Y

Connection inside the delta, with line and bypass contactor, type 1 and 2 coordination,
non reversing, 2 wire or 3 wire

(1) : Installation of additional fast-acting fuses to upgrade to type 2 coordination according to IEC 60947–4–2.
(2) : Take into account the electrical characteristics of the relays (Control Terminal Characteristics).
(3) : The transformer must supply 110...230 VAC +10% – 15%, 50/60Hz.
(4) : Take into account the electrical characteristics of the relays, especially when connecting to high rating contactor
(Control Terminal Characteristics).
(5) : RUN and STOP Management (3-wire control).
(6) : RUN and STOP Management (2-wire control).
(7) : PC or PLC control

10 Mar 3, 2025
Product data sheet ATS480D17Y

Control block wiring diagram

(1) : Control power supply 110-230 VAC


(2) : External supply 24 VDC
(3) : 2 Wires PTC/PT100
R1A, R1C, R3A, R3C : Sequence relay
R2A, R2C : End of start
STOP, RUN, DI3, DI4 : Digital inputs
AQ1 : Analogue output
PTC1/AI1, PTC2, PTC3 : PTC or PT100 connection
DQ1, DQ2, DQ+ : Digital outputs

Mar 3, 2025 11
Product data sheet ATS480D17Y

Mounting and Clearance

Mounting Position

12 Mar 3, 2025