Lesson 11 Three Phase Transformer - Part 2
Lesson 11 Three Phase Transformer - Part 2
Three-Phase Transformers
Three-Phase Transformer
- The main use of this connection is at the substation end of the transmission line, where the
voltage is to be stepped down.
Δ-Y Connection
E L E C T R I C A L A P P A R A T U S A N D D E V I C E S
- This connection is generally employed where it is necessary to step up the voltage, for example, at
the beginning of a high-tension transmission system.
Open Delta or V-V Connection
E L E C T R I C A L A P P A R A T U S A N D D E V I C E S
- If one of the transformers of a Δ − Δ is removed and 3-phase supply is connected to the primaries
as shown in the figure, then three equal 3-phase voltages will be available at the secondary
terminals on no-load. This method of transforming 3- phase power by means of only two
transformers is called the open − Δ or V − V connection.
It is employed:
1. When the three-phase load is too small to warrant
the installation of full three-phase transformer bank.
2. When one of the transformers in a Δ − Δ bank is
disabled, so that service is continued although at
reduced capacity, till the faulty transformer is repaired
or a new one is substituted.
3. When it is anticipated that in future the load
will increase necessitating the closing of open delta.
Open Delta or V-V Connection
E L E C T R I C A L A P P A R A T U S A N D D E V I C E S
- One important point to note is that the total load that can be carried by a V − V bank is not two-
third of the capacity of a Δ − Δ bank but it is only 57.7% of it. That is a reduction of 13.4% (strictly,
13.397%) from its normal rating.
Open Delta or V-V Connection
E L E C T R I C A L A P P A R A T U S A N D D E V I C E S
- It is obvious from above that when one transformer is removed from a Δ − Δ bank.