Operation Manual For Recloser
Operation Manual For Recloser
No: SSIEC-SRM-V0830
SHINSUNG
HAZARDOUS VOLTAGE
CAN SHOCK, BURN,
OR CAUSE DEATH
Do not attempt to handle, install, use or
service this product before reading
instruction book
The SIREC auto circuit recloser should be installed within the design limitations as described on its
nameplate and in these instructions. Also follow your company’s safety procedures.
This recloser should not be used by itself as the sole means of isolating a high voltage circuit. For the
safety of personnel performing maintenance operations on the recloser or connecting equipment, all
components should be electrically disconnected by means of a visible break and securely grounded.
This product is intended to be operated and maintained by qualified persons thoroughly trained and
knowledgeable of the hazards involved. This publication is written only for such qualified persons and is not
intended to be substitute for adequate training and experience in the safety procedures for this device.
Detailed descriptions of standard repair procedures, safety principles, and service operations are not
included. It is important to note that this document contains some warnings and cautions against some
specific service methods that could cause personal injury to service personnel, or could-, damage
equipment or render it unsafe. These warnings and cautions do not cover every conceivable way in which
service (whether or not recommended by SHINSUNG) may be done or possible hazardous consequence
of each conceivable way, nor could SHINSUNG investigate all such ways. Anyone using service
procedures or tools, whether or not recommended by SHINSUNG, must satisfy himself thoroughly that
neither personal safety nor equipment safety will be jeopardized by the service method or tools selected.
All information contained in this manual is based on the latest product information available at the time of
printing. The right is reserved to make changes at any time without notice.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 2
2. Introduction
These instructions do not attempt to provide the user of this equipment with every possible answer to
questions which may occur in the application, operation and maintenance of the product. Also, as
improvements in parts and assemblies are made, some parts may differ in appearance than depicted in
illustrations; however, functionality will be equivalent.
Basically the SIREC vacuum reclosers and accessories are designed and constructed for outdoor
installation on the pole, and under the following conditions:
The components may vary and special protective treatment may be required where unusual conditions
are encountered:
-More high/low temperature,
-Dust and corrosive environment,
-Exposure to maritime, industrial and aggressive atmosphere.
This type recloser is a sophisticated, medium-voltage, three-phase device incorporating three vacuum
interrupters and solid insulation material. Together with the specialized control functions, the recloser will
sense an overload and automatically open. Then after a pre-set time delay, the recloser will close again. If
the overload condition still exists, the recloser will again trip and reclose. Shinsung recloser controls will
allow 3 or 4 reclosing operations before open lock-out trip. The source of the fault condition must then be
removed before normal service can be restored.
Satisfactory performance of the recloser is contingent upon correct installation, adequate maintenance
and service. Careful study of these instructions will permit the user to obtain maximum benefit from this
device.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 3
All SHINSUNG SIREC Reclosers carry out standard production (routine) tests in accordance with the
provisions of IEC 62271-111 in the factory prior to packing and shipping.
If damage is noticed when you receive products, call the carrier at once for inspection, and request an
inspection report. File a formal claim with the carrier, supported with the paid freight bill, inspection report,
and invoice. The local SHINSUNG sales representative or office should be notified
If the recloser is not to be placed in service immediately, it is essential that proper care be exercised in
handling and storage to ensure good operating conditions in the future.
(1) Check the position of the open-lock handle (green) whether it is set to the upper position as shown
below.
(2) To operate manual open, pull down the open-lock handle by hand or hook stick, and locked out not to
close electrically.
(3) To release the manual lockout, pull up the open handle to the upper position for manual close
operation.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 4
Insert the steel rod into the closing port and turn it to the clock wise.
Notice
※ Close operation shall be performed only when recloser is ‘de-energized (electrically shut-off / on
dead line)’ in order to avoid human danger from fault (over) current from the live line.
ON/OFF Indicator
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 5
1. For long time storage, recloser set should be stored indoor in dry condition. Especially Control Unit
has to be protected from water in a rainy season.
2. If it is unavoidable to store them outdoors, they should be covered with waterproof material and kept
away as high as possible from the ground in order to minimize any humid penetration from ground.
3. When "power-on" the Control Unit after long time storage, Make sure whether it is well dried and
dehumidified. Don't power-on before you are sure.
4. When the Control Cable or Power Cable is not connected at the Recloser and Control, please attach
the protective cap to the Connectors and Receptacles to prevent receptacles and connectors from the
water and humidity.
Please store the recloser with control box in a dry condition with proper humidity control to avoid the
malfunction from them.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 6
- Mounting bracket
- (Bird guard caps)-optional item
- Routine Test Reports
Site Procedure
Step 1. Required Tools preparation
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 7
Step 6. Earthing of Recloser, Control, External Transformer and Lightning Arrester into
Step 10. Remove the by-pass cable or open the by-pass switch
2. Lifting the recloser body with the upper hanger band to the pole.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 8
Step 3.2 Lifting and Mounting Recloser & External Transformer on the
Pole
For mounting on the pole, a four-point lifting is strongly recommended utilizing the Lifting Lugs in upper
side of the Recloser.
( Note 1) Take care during lifting to avoid damage to the bushings. The Recloser must not be lifted or
moved by the bushings. This may cause excessive stress on the bushings and result in the broken
bushings
( Note 2) Upon connecting the auxiliary power cable and external Potential Transformer (option), In
case the external transformer has double secondary voltage taps, do not use the higer voltage tap, for
instance, in case of 240V / 360V, 240V should input to Control Unit.
[ Recloser Handling ]
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 9
The terminal lug as optional part shall be used for connection of the main circuit cable. Depending
on the type of terminals, the termination between bushing terminal and main circuit cable(HV cabl
e) shall be properly jointed recommended as below;
In case the bushing terminal is the bolted clamping type terminal, the copper or aluminum cable shall
be inserted into no. of the copper type sleeve below, apply grease compound and compressed it
tightened, and then no. of the copper type sleeve shall be connected to the bushing bolted clamp
terminal,
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 10
In case the bushing terminal is NEMA 2-hole type terminal, the copper or aluminum cable shall be
inserted into the NEMA two-hole terminal lug as below; application is the same as case 1 above.
Before jointing HV cable termination, we recommend use/cover the bird guard caps(insulation cap) a
s an optional part on the connected terminals as below;
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 11
¶ The control hanger band is not included in the package due to the optional accessories.
Step 6. Earthing
The Recloser Tank shall always be earthed following the
local safety regulations. The earthing cable can be
connected to the earthing terminal at the upper (or bottom)
part of the Recloser with a clamp for M12 bolt. The Diameter
of the earthing terminal on the Recloser and Control is
Maximum 9 mm. The minimum diameter of earth cable is
over 2.6 mm. The Control Unit can also be earthed by
earthing terminal on the bottom part of the control cabinet to
the one earthing cable (T Connection).
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 12
2. Connect the “Control Cable” to the receptacle in the bottom of the Control Unit.
3. Connect External Transformer to Control Unit through Power Cable. To protect recloser and distribution
system, fuse cutout should be connected between recloser and External Transformer.
(Note) Earth Cable and Control Cable (including Power Cable) are recommended to be minimum 20 cm
apart from each other to prevent surge influence.
Notice
※ Check whether all cables are connected to the receptacle tightly to prevent dust or water penetration
※ The external transformer for control power supply to control unit shall be connected using the power
cable .(External power transformer is an optional item)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 13
Step 9. Energizing
1. Check if Recloser’s position indicators are correct (Open state).
2. Check if the line (main circuit) cables are connected with sufficient clearances.
5. Energize the Power Line by disconnecting the by-pass cable or opening the by-pass switch
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 14
- By pass the power line with the by-pass switch or by-pass cable
※ Control cable can be available to disconnect while ACR is connecting to power line by CT short device
and VT open protection circuit.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 15
6. Overall Features
SHINSUNG polymer Recloser utilizes vacuum interrupter as the interruption medium and solid dielectric
as the insulation medium. Also, VITR6 RTU based control is specially designed for self healing loop
system of radial and loop network.
The circuit breaker has 6 voltage sensors, 3 CT’s and sensitive zero phase current sensors, so even for
ungrounded system, it can detect very sensitive ground fault.
Unlike conventional recloser at loop scheme, it can isolate source and load side of faulted section
before tie switch close and it also has load encroachment algorithm, automatic setting group change
functions.
It also can make loop scheme with VIT sectionalizer or with VIT reclosing sectionalizer, so it can make
many sectionalizing points than conventional recloser loop scheme with low investment.
The VIT R6 control also has directional sensitive earth fault protection, random arc (HIF) protection and
open conductor fault protection features
Recloser is self contained circuit breaker which has CTs, voltage sensors, and all the protection relay
functions. It can be installed at substation, in the middle of network and it can reduce the outage area,
outage time.
If it is used with sectionalizer or reclosing sectionalizer, it can makes many sectionalizing points, so
easily fulfill the requirement of smallest outage area.
For radial line protection, it has phase, ground, directional SEF protection functions and specially it has
high impedance random arc fault protection and open conductor fault protection based on unbalance
current ratio element.
It also has sympathetic trip restraint feature because of delayed recovery voltage during source side
fault.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 16
Sequence coordination
Complex curve
Fault indicators
Measurement
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 17
The most important functions of VITR6 control is the enhanced loop operation capabilities. The VIT R6
control can isolate the source and load side of faulted section before tie switch close without using
communication.
It can make improved recloser loop scheme and also it can make many sectionalizing points using VIT
sectionalizer or VIT reclosing sectionalizer.
The VIT R6 control can isolate the source and load side even in open conductor fault situation. The
VIT R6 control can supply more current during loop operation without sacrificing sensitivity and security
through load encroachment algorithm and it can change the setting group automatically according to the
power direction.
- Source and load side isolation of faulted section, so it eliminate the coordination problem and
unnecessary fault current impact to the healthy network during tie switch close.
- The recloser can coordinate with 2 or 3 sectionalizer and can coordinate with infinite reclosing
sectionalizer even in loop scheme.
- It has tie recloser functions and if the fault was at the zone of tie recloser, it goes to lockout without
attempting close into fault
- During open conductor fault, it can isolate both side of open conductor.
- It has load encroachment algorithm, so even the load current increased during loop operation, it
maintain sensitivity and security.
- It has two setting groups and according to the power direction, it automatically changes.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 18
VITR6 is automatic circuit recloser control and feeder remote terminal unit (RTU) for distribution
automation application.
Main functions of VITR6 are 3-phase and ground protection, auto-reclosing and RTU functions for
remote operations of recloser. VITR6 is a fully digitalized and microprocessor-based control device, so the
customers can utilize this control for the powerful function of existing recloser and distribution automation
demand at present and in the future.
- Complex curve
. Vertical multiplier
. Minimum response
Sequence coordination
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 19
Measurements
Active, reactive and apparent power for each phase and 3-phase
Power factor
Frequency
Control
Battery test
Status Monitoring
Contact inputs
- Battery status
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 20
Recording
Load profiling
Three (3) selectable setting groups ideal for loop scheme application.
MET Tester Compatibility: Since the main control cable of SIREC & VITR6 has the
same pin number as Cooper recloser, Cooper conventional control cable and MET
tester can be used at SIREC recloser and VITR6 control.
Dead Line Operation (option): Consisting of Battery, DC/DC converter and Capacitor,
it achieves dead line operability that is necessary for reconfiguration of the power
line during the line outages.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 21
Ratings
- Operating Voltage
Features
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 22
Construction
Vacuum Interrupter
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 23
7. Functional Description
The VIT recloser has all the conventional recloser functions, but also it has many enhanced functions
for self healing feeder automation system as follows;
Sensitive earth fault protection even for ungrounded system (sensitivity 100mA range)
- Automatic lockout of tie recloser if the fault is at the zone of tie recloser
- Can coordinate with sectionalizer and reclosing sectionalizer even in loop system, so more
sectionalizing points with better coordination than the conventional 5 recloser loop scheme.
- During open conductor fault, the source and load side of open conductor can be isolated.
Each shots can program the high current trip, and high current lockout.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 24
If the fault is isolated or disappear before lockout, then the sequence will be reset
In case of VIT R6 control, the lockout state should be reset before closing.
If the control is reset, then it can close automatically if one side voltage is restored.
If there is fault after manual closing, then it will go to lockout after one trip. (one short to lockout
feature)
The fast curve will be used to save the fuse or to minimize the damage of the network.
Some fast curves are extremely fast, and in this case, it maybe cannot survive during reclosing
sequence because of transformer magnetizing current. This may lead the downstream
sectionalizer to trip and lockout even during temporary fault. In this case, other fast curve which
can survive should be chosen or fast sequence only be permitted one times.
Minimum response time can be used for recloser to recloser fast curve coordination. The
minimum response time should be longer than 3cycles for series coordination
Sometimes, the series connected recloser can trip simultaneously, so for safety the number of
operations to lockout of upstream device will be more than the downstream device.
The VIT recloser has blocking timer for better series coordination. Once the recloser successfully
closed, then the blocking timer start and the fault pick up will be inhibited during blocking time.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 25
The cold load pick up functions will be sealed in when the recloser close after loss of load diversity.
Thermostatically controlled load loss load diversity after long outage, so when reenergizing the network,
there will be high cold load inrush current. The cold load pick up moves the fast curve to delay curve
and raise the minimum pick up current during the programmed time interval.
Directional zero phase current ratio (I0/I1) can improve the sensitivity
In case of 3phase 3wire system, there is very small residual current during normal operation, so
very sensitive earth fault protection will be possible using I0 or △ I0. The △ I0 is the difference
between present residual current and the background residual current
Ungrounded system
Through software calibration technique even using 3CT’s for residual current detection, 100mA
range residual current can be detected.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 26
contents. Conventional SEF protection cannot cover random arc high impedance fault. The VIT R6
control can detect random arc, and the threshold level will be the same with sensitive earth fault current.
Load encroachment feature can prevent the relay from doing fault pickup by recognizing the high load
current beyond the normal overcurrent pickup by desensitizing the overcurrent pickup of the normal
load condition if the power factor of the load does not depart from the defined normal working range.
Load encroachment feature can also be used to regulate an operation of the sympathetic tripping
avoidance element. The sympathetic tripping avoidance element also desensitizes the overcurrent
pickup of the relay to prevent miss tripping from occurring owing to the fault of the other adjacent
sections. The unbalanced or high load conditions which occur during or immediately following out-of-
section fault may cause the relay to initiate a tripping operation as the load current is over the
overcurrent pickup threshold. It may be possible to prevent overcurrent pickup by raising the
overcurrent pickup threshold. In a certain case, however, the high load current may be in excess of the
highest desensitized overcurrent pickup and relay will pickup it as the fault current. In this situation, with
the help of load encroachment element that can identify if the power factor of the load does not deviate
from the defined normal working range, it is possible to prevent the relay from doing fault pickup by
recognizing the high load current beyond the highest desensitized overcurrent pickup of the sympathetic
tripping avoidance element as the non-faulted current.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 27
Setting items
Setting Example
Figure 1. shows if the parameters above is applied and load zone is decided as figure 2.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 28
And through the Overload and Load Encroachment Pickup current, Tripping Area(hatching Area) and Non-
Tripping Area(White area) are distinguished as the following Figure.
Imaginary
Tripping Area
LEPLAR=32º
LEPLAF=30º
Non-Tripping
Area
LEPC:500A
Real
OLPC:300A
LENLAR=35º
LENLAF=45º
Note: OLPC: Over-Load pickup current, LEPC: Load Encroachment Pickup current
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 29
In case of set to “Auto 12” or “Auto 13” or “Auto 12 & Auto 13”, setting group automatically
changes according to the line condition.
Setting group automatically changes from Normal Group(SG1) to Alternate Group1(SG2) or vice
versa according to the current direction, voltage condition and power flow setting on front panel. It
can used for VIT LOOP and TIE mode.
In close state, when the reverse power flow is detected, it changes from current working group set
to opposite group set.
In open state, setting group is changed according the voltage condition and power flow setting on
front panel.
SG1 : when source(ABC) side voltage is sensed and load(RST) side voltage is not sensed.
SG2 : when source(RST) side voltage is sensed and load(ABC) side voltage is not sensed.
SG1 : when source(RST) side voltage is sensed and load(ABC) side voltage is not sensed.
SG2 : when source(ABC) side voltage is sensed and load(RST) side voltage is not sensed.
Setting group automatically changes from Normal Group(SG1) to Alternate Group2(SG3) or vice
versa according to the load current. It can used for VIT TIE mode.
When operating in VIT TIE mode, if the load current is increased over than pre-set current after
close(automatic closing by VIT function), it changes from Normal Group(SG1) to Alternate
Group2(SG3) after pre-set delay time.
After changing to Alternate Group2(SG3), if the load current is decreased below than pre-set
current, it changes to Normal Group(SG1) after pre-set delay time.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 30
SG1: setting group 1 is used for normal radial operation. The power direction should be set after
installation for directional protection. The setting group 1 can be changed to setting group 3
automatically if the load current continuously higher than the automatic setting group change level
and also if the load current reduced below the automatic change level, then setting group will be
reset from SG3 to SG1.
SG2: Setting group 2 is used for the reverse connected recloser during loop operation and
generally the operation current will be lower than SG1. The power direction should be set reverse
with SG1.If the load side voltage appear first after tie recloser close, then the setting group change
from SG1 to SG2. If the line is maintained and if the configuration be returned to normal state,
then the setting group will be change again from SG2 to SG1.
SG3: Setting group 3 is used for the recloser of healthy network and generally the operation
current will be higher than SG1 because it has to supply more currents during loop operation.
The VIT R6 control has load encroachment algorithm, so at the instant of tie closing, even the
load current increase than the operation current, it can avoid mis-tripping, if the load currents are
higher than change over current, the setting groups can be changed from SG1 to SG3
automatically. If the currents are reduced lower than change over current, the setting group will be
changed again from SG3 to SG1.
If many reclosers should be coordinated, even to use minimum response time, different number
of shots to lockout, still it is not easy to coordinate. The VIT R6 control has special fault block
functions, so once the reclosers are trip simultaneously, then the upstream recloser close
successfully without fault, then the fault block function will be engaged. So, the downstream
recloser only responses to the fault without additional simultaneous trip of upstream recloser.
The conventional recloser cannot isolate load side of faulted section so when the tie recloser
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 31
close, there is coordination problems of many series connected protection device and cannot
avoid unnecessary fault impact to the network because the fault still not isolated before tie switch
close. If the load side of fault cannot be isolated, then the tie switch, mid-point switch should be
circuit breaker, because during tie or mid-point switch close, the fault should be cleared by the
switch. The VIT R6 control can isolate the load side of fault before tie switch close through the
voltage counting which same with the number of shots to lockout of the upstream device and if
there is no voltage restoration before tie switch close.
It monitors the operation of upstream device through the loss of voltage counting and voltage
restoration time.
If will open after one or two voltage counting, if it is set to two counts open, then during
temporary fault, it maintain close position.
If there is two count sectionalizer at the downstream, the voltage count should be one.
The control make voltage counts and check the reclosing interval of back up device through
voltage restoration. If the conditions are met and if the outage is extended, then the recloser
will be open and lockout before tie recloser close. If the conditions are not met and if the
outage is extended, then the recloser will be open, but it will close again when voltage is
restored through tie recloser close
Tie recloser monitor the both side upstream reclosers, and if the voltage counts, reclosing
interval condition are met and if the outage extended, then it will go to lockout, so it will not
close into faulted network.
The tie recloser will close after successful close timing and if there is still fault, then it will
open and lockout. If there is no fault, then it will recover to normal sequence according to the
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 32
stetting group.
VIT recloser and VIT sectionalizer scheme can make 5~8 sectionalizing points, (5recloser scheme can
make 3 sections), the coordination time is fast, the sectionalizer will not close into fault, so it is best
suited for urban network of solidly grounded system.
Close Timer
The close timer should be longer than the fault clearing time of back up C.B or recloser
After close, lockout timer will start and if the voltage lost again (Backup trip again because of
fault), then it will be open and lockout. If the lockout out timer (which is longer than back up
clearing time ) is successfully finished, then the blocking timer will start during total coordination
time (normally close time of tie switch) to prevent unnecessary current, voltage counting.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 33
If the back-up open again before close timer finished, it will go to lockout while maintain open
position
If the load side voltage is restored after tie switch close, it will change the setting group and will
close. If use the VIT recloser and VIT reclosing sectionalizer, then it can make infinite
sectionalizing points but compared with VIT sectionalizer scheme, the reclosing sectionalizer
open and close more times than sectionalizer, and it has a chance to close into fault during the
sequence. But if the system is resistance grounded or ungrounded, the damage from close into
fault will be very small, so it will be the best solution for long rural network with impedance
grounded system or ungrounded system.
7.15 Sensitive earth fault, high impedance fault and open conductor fault
The SEF, HIF and open conductor fault protection is the difficult challenge for the protection engineer.
The ground fault has a tendency to be high impedance because of asphalt, concrete pavement, but
many researches are focused to develop monitoring device at the substation. But detection of the small
earth fault at the substation has a limitation and also the isolation is very difficult because it means the
whole outage of the feeder. The best way is for recloser and sectionalizers have the protection functions
of SEF, HIF and open conductor, then it can have more sensitivity and can isolate the section, because
the outage is just at limited area. In the VIT self healing system, the sectionalizer can clear the ground
fault by itself up to maximum load current (630A) and during the open conductor fault, the both side of
broken conductor can be isolated without sequential operation of recloser.
The delay time of open conductor protection should be longer than any other protection element and if
the broken conductor make considerable unbalance current, then it can be isolated positively through
unbalance current ratio element I2/I1 or △I2/I1. But if broken conductor occurs at small branch line and
so there is no detectable unbalance current ratio, then it should be protected by SEF or HIF.
The 3 phase 3 wire system can realize sensitive earth fault protection, because the normal residual
current is very small. So, I0 or △I0 with directional protection can achieve SEF, HIF protection. The SEF
and HIF can use the same threshold level, but the HIF algorithm differs in the random arc phenomena
The 3 phase 4wire system is very difficult to get sensitive earth fault protection, because there is
phase to ground load during normal operation, and it makes zero phase current.
To reduce the ground pickup lower than max. phase current, then it should use directional protection to
avoid mis-tripping during source side fault and to give more sensitivity, the zero phase current ratio
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 34
element I0/I1 or △I0/I1 are used in VIT recloser and VIT sectionalizer.
The radial network can use the VIT sectionalizer or VIT reclosing sectionalizer to clear directly the SEF,
HIF, open conductor fault, but in the loop network the SEF, HIF should be cleared by recloser through
sequential operation to isolate the both side of fault, but in case of open conductor, the recloser, LBS all
together can isolate the open conductor fault.
In case recloser is tripped, recloser will block the close operation under the out of preset value.
If the recloser is tripped by under/over voltage condition, single-shot reclosing function is activated after
voltage returns to normal. After reclosing, if the recloser is tripped again by under/over voltage condition
within preset reset time, recloser goes to lockout.
In case recloser is tripped, recloser will block (selectable) the close operation under the out of preset
value.
If the recloser is tripped by under/over frequency condition, single-shot reclosing function is activated
after frequency returns to normal. After reclosing, if the recloser is tripped again by under/over frequency
condition within preset reset time, recloser goes to lockout.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 35
8. Technical Data
Ratings
Environmental
Test Standards
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 36
Power Circuit
ANSI/IEEE C 37.90.1(1989)
IEEE C37.90.2(1995)
Opto-isolation : 2,000Vrms
Delay time setting (10~500ms) for each contact input to suppress bouncing
Signals
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 37
- Recloser Trip
- Recloser Closing
- Battery Test
- Modem On/Off
- Spare 1
Max. current 10 A
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 38
Signals
- Ia : A-phase current
- Ib : B-phase current
- Ic : C-Phase current
- In : Neutral current
Signals
- Va : A-phase voltage
- Vb : B-phase voltage
- Vc : C-Phase voltage
- Vr : R-phase voltage
- Vs : S-phase voltage
- Vt : T-Phase voltage
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 39
8.3 Measurements
Current
RMS (A) & Phase angle (o) Ia, Ib, Ic, In, Ig
600~12,000A : ±3%
Voltage
RMS (V) & Phase angle (o) Va, Vb, Vc, Vr, Vs, Vt
Power
Accuracy ±1%
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 40
Power factor
Lead/lag display
Accuracy ±2%
Frequency
Accuracy ±0.02Hz
Energy
Accuracy ±2%
Harmonics
Total harmonic distortion (THD, %) Ia, Ib, Ic, Va, Vb, Vc, Vr, Vs, Vt
Ia, Ib, Ic, Pa, Pb, Pc, P3ph, Qa, Qb, Qc, Q3ph
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 41
Va, Vb, Vc
8.4 Recording
- Resolution: 1ms
- These event reports contain date, time, current, voltage, relay element, opto-isolated input,
and output contact information.
- Up to fifty 20- cycle reports are stored in non-volatile memory. If more reports are
triggered, the newest event report overwrites the oldest event report.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 42
- These event reports contain date, time, fault current magnitude and shot count information
- The control stores the latest 300 events of the fault events report in non-volatile memory.
If the report fills up, newer rows overwrite the oldest rows in the report.
The control adds lines in the SER report for a change of state of a programmable condition. The
SER lists data and time-stamped lines of information each time when a programmed condition
changes state. The control stores the latest 4000 lines of the SER report in non-volatile memory. If
the report fills up, newer rows overwrite the oldest rows in the report.
Load Profile time interval can be set to any one of 5, 10, 15, 30 and 60 minutes. And load profile can
be selected any of the following load profile items up to twenty. Load profile data can be stored for 110
days of 15 minutes, in case 20 items are fully activated.
8.4.3 Counters
8.5 Communications
Physical Layer
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 43
Class assignable for each object type. (single point, double points, measured point)
Events display
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 44
Measurements display
HANDLE LOCK
Lockout information Load Side, Source Side, Bump Prevention, Loss of Voltage
Serial port
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 45
DSP
Remote communication
Self-diagnosis
Analog/Digital conversion
Memory
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 46
VITR6’s enclosure is constructed for normal operation under the high/low temperature and humid
environments by adopting duplicate external covers with air gap. Swing panel within enclosure will enhance
operational safety. No need to open swing door to operate/ manipulate VITR6. Behind swing panel
batteries, modem, analog modules and other parts are installed.
(CAUTION)
1) When mounting on electric pole, always utilize the lifting lugs and mounting accessories.
2) In connection of control and power cables, please make sure of correct insertion and
close adherence. Install the cable-fixing band at every 1 meter and reserve the enough curvature
radiuses to prevent direct load on the receptacles.
3) Grounding conductor of the enclosure should be fixed with some distance from the
control cable.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 47
Swing
Panel
Document
Door
Door Switch
Locking
Device Fuse for Outlet
NFB (No Fuse Breaker)
AC PowerOutlet
For Auxiliary AC Power
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 48
VITR6
Relay
Battery
Charger
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 49
9.2.1 Battery
There are two 12 Vdc sealed rechargeable batteries to back up external AC power loss and to supply
power of 24 Vdc. Battery condition can be checked by measuring battery voltage, charging current and
discharging current. A fully charged 18 Ah battery supplies the trip and control power for 10 to 24 hours
depending on ambient temperature and load. It takes approximately 24 hours to fully charge the battery
from a complete discharge state.
When battery capacity drops down to a threshold level voltage, 23V (temperature-compensated voltage
level), the VITR6 shifts to sleep mode.
It is normally expected 5 years of life span, but recommended to replace every 3 years according to the
operational environments. When replacing the batteries, be sure to confirm to the battery specifications.
(Caution) When testing the voltage of battery using voltage meter, be careful not to contact each
terminal and not to make it short-circuited.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 50
It is unnecessary to power on to LCD and other LED’s while the enclosure door is not opened for local
operation. The main control function module gets door status information from this switch. Therefore, when
the enclosure door is closed, VITR6 is designed to disconnect the power supply to LCD and LED’s to save
battery or external AC power. This status is also monitored remotely and can be used to acknowledge local
maintenance and for security purpose.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 51
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 52
On the panel, there are LED’s indicating Recloser’s status, functional buttons and LED’s, operational
buttons and LED’s, LCD manipulation buttons, and a RS232 port for maintenance.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 53
Display Part
- LCD (liquid crystal display) : Shows the Status, Measurement, Settings and More
- Operation Button : use 6 buttons (Up, Down, Left, Right, MENU/ESC, ENTER)
- BATTERY TROUBLE
Battery test is done automatically every day(12:00 PM) or done manually by pressing BA
TTERY TEST button.
- CONTROL ENABLED
Show the status of CPU. In normal state, green light blinks. If a problem occurs on the
CPU, stop blinking or light off.
- HANDLE LOCK
- AUX1
- SEF/HIF: sensitive earth fault / High impedance fault overcurrent element trip.
- BUMP PREVENTION
LED is lit when recloser is locked out at open state by bump prevention feature.
Loop mode has bump prevention feature. When the close timer is running, if the voltages
are alive from both source and load side, there should be prohibited the switch from being
closed to prevent unnecessary bumping between two networks by having the switch gone t
o lockout and getting the closer timer reset. If the condition that there exist voltages on bo
th sides is ended, the lockout state is automatically reset, the close timer starts again and
the switch is closed after close time ended.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 54
- LOSS OF VOLTAGE
Light is on when recloser is opened and locked out by loss of voltage lockout feature.
- UVR: LED is lit when the recloser is opened and locked out through UVR feature. (under c
onsideration)
- OVR: LED is lit when the recloser is opened and locked out through OVR feature. (under c
onsideration)
- OPEN CONDUCTOR: LED is lit when the recloser is opened and locked out by open cond
uctor fault protection feature.
- SPARE1
- Setting Group
The sticker was posted on the bottom of the control swing panel that describes the setting
group status according to the lamp on/off as below;
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 55
Setting value and status data & fault can be updated or recorded through LCD display and function keys
on Operation Control Panel. All the information is displayed on LCD in the tree view manner. The figure
following represents the main menu of Recloser. LCD Screen is to facilitate manual programming of control
unit and for viewing data such as settings, events, fault records and measurements. The LCD shall
preferably switch off when not in use and activated by pressing the appropriate key such as panel ON/OFF
switch. Default LCD screen display shall be selectable from PC.
In the right area of LCD (4 lines 20 characters), there are six(6) buttons for manipulating the LCD menus
and data input and output. These setting buttons have no relations with other buttons in the local front
panel such as REMOTE ENABLED pushbutton (Local/Remote) and BUTTON LOCK pushbutton
(Unlock/Lock). So even if Remote Button or Lock Button is activated (ON), you can still operate the setting
buttons. They have functions as below.
10.2.2 MENU/ESC
1. You can switch between main menu screen and initial mode screen.
2. You can return to higher category from a lower category in menu and initial mode.
3. You can cancel new setting value and return to the previous setting value.
10.2.3 ENTER
By this button,
1. You can move to a lower category from a category in any mode. When you are in the Initial Mode, by
pressing this button, you can move to sub-initial screen (Current & Voltage, Current & Voltage Angle,
Internal Power, MVA and MW & MVAR screen) from main Initial screen (Recloser Status and Current
& Voltage screen).
2. You can select a certain setting value you want to manage, where you can change the value with
pressing LEFT, RIGHT, UP, DOWN buttons.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 56
10.2.6 UP ARROW
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 57
10.3.1 CLOSE
Press this button when you close Recloser manually. Then red light is on to indicate that Recloser is
closed. Close action signal is transmitted to the main body of circuit breaker on pushing the CLOSE button
and fault detecting action is ready on completing the close action.
In case of manual close, cold load pickup action precedes the normal fault detection function if cold load
pickup scheme is enabled and if the load current is over the overcurrent pickup level, and unless the fault
current is detected the set sequences of phase/ground will be followed to prepare the basic operations.
With set a delay, the operator can push the CLOSE button and then keep a safe distance away from the
Recloser before the VITR6 transmits a close signal. With a set delay, light flashes on and off during the
delay time, indicating a pending close. This pending close can be aborted by pushing CLOSE again or by
pushing TRIP button. This delay setting is available through setting menu.
10.3.2 TRIP
Press this button to open the Recloser manually and take the control to the lockout state. Then green light
is on to indicate that Recloser is open. Open action signal is transmitted to the main body of circuit breaker
on pushing the TRIP button and fault detecting action is suppressed on completing the open action, then
the switch to be locked out. When the lock function is engaged, the TRIP operator control can still trip the
Recloser by TRIP free function. With set a delay, the operator can push TRIP button and then keep a safe
distance away from the Recloser before the VITR6 transmits a trip signal. With a set delay, lights flashes on
and off during the delay time, indicating a pending open. This pending open can be aborted by pushing
TRIP button again or by pressing CLOSE button. This delay setting is available through setting menu.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 58
These buttons are to enable or disable significant functions in running the Recloser. Press the buttons and
make the respective LEDs on to enable each function. These buttons are toggled between enable and
disable
PROTECTION ENABLED button is used to halt the fault detection operation temporarily. It enables or
disables phase fault detection and ground fault detection functions, simultaneously. PROTECTION
ENABLED operator control pushbutton is pressed and LED illuminates, protection enabled. Pushbutton is
pressed again and LED doesn’t illuminate, protection disabled.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 59
RECLOSE ENABLED button enables or disables the reclosing function. In disable mode, the Recloser is
locked out right after the 1st trip. RECLOSE ENABLED operator control pushbutton is pressed and LED
illuminates, auto reclosing enabled. Pushbutton is pressed again and LED doesn’t illuminate, auto reclosing
disabled.
GROUND ENABLED button enables or disables ground fault detection function only. GROUND
ENABLED operator control pushbutton is pressed and LED illuminates, ground enabled. Pushbutton is
pressed again and LED doesn’t illuminate, ground disabled.
SEF/HIF ENABLED button enables or disables sensitive earth fault / high impedance fault detection
function. SEF/HIF ENABLED operator control pushbutton is pressed and LED illuminates, SEF/HIF
enabled. Pushbutton is pressed again and LED doesn’t illuminate, SEF/HIF disabled.
To decide the control position to remote, push this button and make the LED on. REMOTE ENABLED
operator control pushbutton is pressed and LED illuminates, remote control enabled. Pushbutton is pressed
again and LED doesn’t illuminate, remote control disabled.
VITR6 carry out the close or trip action after set time. For example, if close and trip delay time is set
with10 seconds, and then VITR6 carry out the close or trip action after 10 seconds. Close or trip LED is
repeated blinking during the delay time.
This button is used to block closing of the Recloser locally or remotely while doing maintenance work or
repair work. HOT LINE TAG operator control pushbutton is pressed and LED illuminates, hot line tag set
and closing action is prohibited. Pushbutton is pressed again and LED doesn’t illuminate, hot line tag reset.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 60
Press this button for 3 seconds, if you use to radial normal close mode.
Press this button for 3 seconds, if you use to loop normal close mode.
Press this button for 3 seconds, if you use to loop normal open mode.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 61
Fault indicators show the fault information through the LED lamp. It has two kinds of reset mode; manual
and auto. Manual option retains the fault indication without
external command once a fault has been detected. In this
mode operators should do command action for reset,
locally manipulating the FI reset(Target Reset) button or
remotely sending a command, to extinguish these LED’s.
Manual FI mode is for the operator’s acknowledgement
purpose. On the other hand, auto option turns the lamp off
automatically after a fault on detecting the normal current.
These LEDs indicate on which state the Recloser operates. There are 3 states the Recloser operates and
the reclosing control is in one and only one of those 3
states at any time which are reset state and reclose cycle
state and lockout state. When in a given state, the
corresponding LED illuminates. Automatic reclose only
takes place when control is in the reclose cycle state.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 62
10.6 Others
WAKE-UP: Wake up the VITR6 if Operation Control Panel is dark. The unit put itself to sleep after an
extended outage. After the unit wakes up, the
Panel illuminates. This button is also used to
turn on the VITR6 after the battery has been
installed by sealing the battery. The VITR6
wakes up automatically from an extended
outage when 220 VAC power returns to the unit.
LAMP TEST: Illuminate all front-panel LEDs for 3 seconds for LED test.
TARGET RESET: Clear trip-latched target fault indication LEDs (A, B, C, GROUND, SEF, FAST, HIGH,
DELAY, VOLTAGE)
Manual Mode is to check the battery by pressing the BATTERY TEST button on Panel.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 63
[Side of R6 Relay]
- VOLT-IN: Measurement voltage input terminal, total 6 voltage (3 for source side, 3 for load side)
are input via voltage sensor. When the main circuit voltage is 13.2kV in connecting to the control,
each phase has about 0.85Vac.
- CURR-IN: Measurement Current input terminal. Each phase has 1/1,000A that comes from the
main circuit.
- DI_IN: It is a input terminal of the door open of the control box, recloser’s status(main circuit
close/open, manual handle lock), remote control command et.
- AUX_TB: It is a auxiliary terminal block interconnecting to controller. It provides the input/output
terminal of modem power, Aux digital output contact.
- DO: It is a output terminal of control Power(24~36dc), and close, Trip Sign
- SM_IN : Connected with SMPS for charging. When inputting external power, SMPS supplies
36Vdc / 4A capacity to the control. It is used for battery charging, control power, and mode power.
SMPS has a wide input voltage range of 85V to 264Vac to provide stable power to the control
under any external power adverse conditions.
- TR_IN: It is to connect the transformer for driving. When external power is input, Trans supplies
AC24V / 200VA power to the control. It is used only for driving and it is separated from the control
power and does not affect the control function. When both SM_IN and TR_IN are input with normal
voltage, control determines whether the external power is normal and the AC PWR lamp is turned
on.
- DCM: Output port for driving the magnetic actuator mechanism of reclosing body
- Battery: Input terminal f the battery. After the checking the polarity, replace the battery or
maintenance.
- Debug port(Rs-232/Male): It is a RS-232 serial port on the front panel to connect laptop computer
for local command, setting and configuration.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 64
- SCADA port(Rs-232/Male): It is a RS-232 serial port on the side of relay to connect the modem for
SCADA communication. If either port of Debug port or SCADA port fails, it can be used by
changing each other in the internal setting menu of LCD.
- 485 port: It is a RS-485 port on the side of relay for connecting the modem with RS485 interface
for SCADA communication. The communication port setting is available via LCD display of the
control front panel.
- - Ethernet: It is an Ethernet port on the side of relay for connecting the modem with RJ45 interface
for SCADA communication. The communication port setting is available via LCD display of the
control front panel.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 65
10.8 Others
- Communication cable inlet: A cable gland at the bottom of the control box is available for the channel of
the communication cable, which a cable grand has the protection of IP66 as following specification.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 66
10.8.3 Battery:
Two 12V batteries are connected in series for 24Vdc.
- TYPE: Sealed lead-acid type
- Standard: 12V/18Ah *2ea in series connection
- Size(Based on 1 battery): (L)181*(W)76*(H)167
- Weight(Based on 1 battery): 5.66Kg
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 67
[LRS-150-36]
- Specification:
* Note the spec are applicable for the rating marked in red.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 68
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 69
This factor is only for manufacturer’s reference value, not for user’s setting
※ Not required set PT ratio since the factory calibration was based on the line voltage.
This factor is only for manufacturer’s reference value, not for user’s setting.
Nominal voltage 6 – 63 kV 11
-. Set the control input AC voltage for control power supply (based on 100%).
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 70
1. If it is set to Yes, it is able to be adjustable to reset the fault indicator in the range of the self-holding
※ The automatic reset shall trigger when it is the close condition, non-fault and normal voltage for
Thermal use same method with thermal energy increase/decrease, Rolling use calculation by 5 minuts
step counting
Stored Load Profile can be used for analysis by season and timeline
- Instantaneous Ia, Ib, Ic, In, Va, Vb, Vc, Vr, Vs, Vt
- Frequency
Can select storage periods by setting time, 95 days profile can be stored in case selecting 30
minutes
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 71
VITL6 control can store 20 cycles of fault wave when fault occurred. Can choose point of saving fault
wave
For example if required for 10sec delay, set 500 at 50 Hz or 600 at 60Hz system
Must set as “AUTO” when operation mode Loop normal open, Loop normal close.
If the measured value after the battery test is below the dead voltage, it is a battery failure.
After the initial test according to the Start Hour, Start Minute,
the test is conducted at the time interval set in the Test Period.
Bat Drop Capacity / Dead Voltage 18 ~ 24 23.0V
-. In case of AC power loss, it is to protect the battery from the deep discharge. When it goes below
the setting value, the relay power is automatically cut off until AC power is supplied
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 72
-. In a open status, it is to inhibit the close operation when the voltage angle difference of source
side and load side goes is out of setting range under the condition of the between the high and
You can use the desired digital input point by changing the 6th trip and 7th close of the internal terminal
-. You can set the delay time and reset time for over current alarm
-. Over current is detected, controller will send alarm to the SCADA master
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 73
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 74
Delay-Ground
-. The time multiplier setting shifts a curve in time, by the set multiplier.
Delay-Negative
EM Reset Yes/No No
-. After the fault occurs, it is to choose the function of the returning time of the
relay where it is installed on the load side before trip operation.
Min.Resp. 0 ~ 1500Cycle 0
-. Curves can trip no faster than the Min. response time setting.
Phase OFF, 1 ~ 5 2
Ground OFF, 1 ~ 5 2
Netative OFF, 1 ~ 5 1
-. After the fault occurs, when reclosing sequence, it operates as the fast curve according to the
preset count.
Phase OFF, 1 ~ 5 4
Ground OFF, 1 ~ 5 4
SEF OFF, 1 ~ 5 4
Negative OFF, 1 ~ 5 1
-. It goes to lockout when it reaches to the preset fault current count according to the
type of the fault pickups.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 75
Delay2 0 ~ 16000Cycle 0
-. When the high current occurs more than the multiple of the preset pickup(Min
Phase
phase, ground), it will be tripped after preset time(delay) regardless the setting of
Ground
TCC curve.
* Setting available in 3 sections for details. .
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 76
High current trip setting is available to set phase and ground individually, and its setting consists
of three levels that can be able to be individual setting.
Multi1~3
These settings determine the current threshold for high current tripping.
Example:
If Multi1=15 and Pickup current = 100A for ground, then current threshold for high current
tripping level1 of the ground operates at a value equal to: 15*100A=1500A
Delay1~3
To set the intentional time delay for high current tripping each level.
Activate SH1~5
To set tripping shot for high current tripping. Activate SH1~5 settings determine the shot number
to trip for high current tripping during sequence operation.
Example:
If Activate SH2 and SH3 = ON, High current tripping can be achieved during the 2nd and 3rd trip.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 77
High current lockout setting is available to set phase and ground individually, its setting is not
related to the high current trip.
Multiplier
Multiplier setting determines the current threshold for high current lockout.
Example:
If Multiplier=20 and Pickup current = 400A for the phase, then current threshold for high
current lockout of the phase operates at a value equal to: 20*400A=8,000A
Activate
Example:
If Activate=3 and fault current ≥ setting current of the high current lockout, the R6 control goes to
lockout(79LO) after the 3rd trip operation.
Delay 0 ~ 999999.00Cycle 0
-. Condition: The recloser is open or Control is in the lockout state
or reclosing is disabled.
Loss Load Diversity In case of the condition above, the function of the loss load diversity is
activated for the preset time.
Note that the cold load pickup function is not applicable during the time
above.
Delay 0 ~ 999999.00Cycle OFF
Force Time -. Return back to the preset minimum pick-up current after close
operation.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 78
Phase Yes/No No
Ground Yes/No No
SEF Yes/No No
Yes : If the cold load pickup scheme is active, the phase current threshold for
Restore Min. Trip
over current detection is forced back to the regular Min. trip-phase level when
the preceding Restore min. trips-time limit tines out.
No : If the cold load pickup scheme is active, the phase current threshold for
overcurrent detection can only return back to its regular Min.
Coordination Yes/No No
The Sequence coordination setting keeps R6 Control in step with a downstream recloser control,
preventing the overreaching R6 Control Fast curve elements from tripping for faults beyond the
downstream recloser.
Sequence coordination advances the operations counter each time the following sequence occurs.
Precedence Yes/No No
Yes : If the ground fault current is above the Min. trip-ground level at the time of trip, the operations to
lockout follows Operations to lockout-ground.
if ground fault current is below the Min. trip-ground level and phase fault current is above the Min. trip-
phase level at the time of trip. the determination to go to lockout is controlled by Operation to lockout-
phase.
No : If ground fault current is above the min trip-ground level and phase fault current is below the Min
trip-phase level at the time of trip the determination to go to lockout is controlled by Operations to
lockout-ground.
If phase fault current is above the Min trip-phase at the time of trip, the determination to go to lockout is
controlled by Operations to lockout-phase.
Enabled Yes/No No
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 79
Po.Lo.Ang.For 0 ~ 90 20D
Ne.Lo.Ang.For 0 ~ (-)90 -56D
Po.Lo.Ang.Rev 0 ~ 90 54D
Direction No/Forward/Reverse No
Phase Max.Torq-Ang 0 ~ 359 0
Ang Width 10 ~ (±)170 (±)90De
Direction No/Forward/Reverse No
3V0 Pickup 2 ~ 100 10.0%
Ground
Max.Torq-Ang 0 ~ 359 0
Ang Width 10 ~ (±)170 (±)90De
Enabled No/Forward/Reverse No
3V0 Pickup 2 ~ 100 10.0%
SEF
Max.Torq-Ang 0 ~ 359 0
Ang Width 10 ~ (±)170 (±)90De
Reverse power elements and directionally supervised over-current elements are employed.
The directional supervision of the phase overcurrent element is made up of two components.
One is the use of positive sequence voltage polarized phase elements to detect three phase
faults. The second is zero sequence voltage polarized directional element used to detect
unbalanced faults.
Following figure is a diagram of positive sequence element. For zero sequence element, it is similar to
this.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 80
The settings such as MTA(Maximum Torque Angle), TAW(Torque Angle Width) are related closely to
the distribution system configuration and its grounding system. So it is hard to suggest guideline or
setting procedure.
1 Tuning works are necessary from site, because maximum torque angle is different according to
ground connection (un-ground, Peterson coli, high resistance ground).
2 Maximum torque angel is 135℃ at resistance ground, 180℃ at Peterson coil, 270℃ at un-ground.
3 If arc current is small and intermittent, must use HIF protection function because SEF protection
function is applied to continuous arc current.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 81
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 82
11.3.1 Count
Item Range Default
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 83
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 84
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 85
You can use the PC program by connecting to a PC through the corresponding port. Use Speed as the
same as PC program.
-. It is to set the waiting time of the receiving/sending the data during SCADA
communication.
* DCD Timeout: Data Carrier Detect. If the modem send the carrier signal, it means it
* RTS Preamble: After sending the data from the controller, it is to set the waiting
* RTS Postamble: After completing the data from the controller, it is to maintain the
transmitting(RTS) time.
* CTS Checkout: It is the waiting time for modem’s CTS signal. The modem data
IP 192.168.010.095 0~255
RTU IP Address
SUB 255.255.255.000 0~255
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 86
-. Mode: For IEC60870-5-101, to set the unbalance and balance same as SCADA’s settings.
-. Size Address: Select the size of link address, and set it same as SCADA’s setting.
-. Confirm Timeout: To set the waiting time for the response,
-. Max Retiries: To set the re-try count when it has no response..
-. ASDU Size: To select the seize of the ASDU Address, and set it same as SCAD’s setting.
-. COT Size: To select the size of the cause of transmission, and set it same as SCADA’s setting
-. IOA size: To select the size of Information Object Address, and set it same as SCADA’s setting.
ASDU Address 00003 0~65535
Sector
SBO Timeout 010sec 10~60
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 87
-. SBO Timeout: It is the Select Before Operation, which is to set the limit time for operate.
-. Event Mode: To select whether to save the latest data or the changed value .
-. Analog Input: Reserve the start address of Analog Input Point IOA
Time Setting
Level 2 Reading only Setting items but can write Config items “0000”
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 88
Level 3 Reading and writing for Setting items and Config items “0000”
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 89
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 90
APPENDIX 1: TC-Curves
100
CLEARING TIME
CURVE:A,B,C,D,E
CURVE SHOWN IS
THE 1.0×MULTIPLIER CURVE.
AVERAGE CLEARING TIME
VARIATIONS ±10% or 0.01 SECONDS
10
.
TIME(SECONDS)
0.1
D B
A
0.01
100 1000 10000
CURRENT(PERCENTAGE OF MINIMUM TRIP)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 91
1000
CLEARING TIME
CURVE:K,L,M,N
CURVE SHOWN IS
THE 1.0×MULTIPLIER CURVE.
AVERAGE CLEARING TIME
VARIATIONS ±10% or 0.01 SECONDS
100
10
.
TIME(SECONDS)
N M
0.1
0.01
100 1000 10000
CURRENT(PERCENTAGE OF MINIMUM TRIP)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 92
1000
CLEARING TIME
CURVE:P,R,T,V
CURVE SHOWN IS
THE 1.0×MULTIPLIER CURVE.
AVERAGE CLEARING TIME
VARIATIONS ±10% or 0.01 SECONDS
100
10
.
TIME(SECONDS)
1
V
T
0.1
R
0.01
100 1000 10000
CURRENT(PERCENTAGE OF MINIMUM TRIP)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 93
1000
CLEARING TIME
CURVE:W,Y,Z
CURVE SHOWN IS
THE 1.0×MULTIPLIER CURVE.
AVERAGE CLEARING TIME
VARIATIONS ±10% or 0.01 SECONDS
100
10
.
TIME(SECONDS)
0.1
0.01
100 1000 10000
CURRENT(PERCENTAGE OF MINIMUM TRIP)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 94
100
CLEARING TIME
CURVE:1,2,3,4,5
CURVE SHOWN IS
THE 1.0×MULTIPLIER CURVE.
AVERAGE CLEARING TIME
VARIATIONS ±10% or 0.01 SECONDS
10
TIME(SECONDS)
1 3
0.1
5
1
0.01
100 1000 10000
CURRENT(PERCENTAGE OF MINIMUM TRIP)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 95
100
CLEARING TIME
CURVE:6,7,8,8*,9
CURVE SHOWN IS
THE 1.0×MULTIPLIER CURVE.
7 AVERAGE CLEARING TIME
VARIATIONS ±10% or 0.01 SECONDS
10
9
TIME(SECONDS)
8*
0.1
0.01
100 1000 10000
CURRENT(PERCENTAGE OF MINIMUM TRIP)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 96
100
CLEARING TIME
CURVE:11,13,14,15,16,18
CURVE SHOWN IS
THE 1.0×MULTIPLIER CURVE.
AVERAGE CLEARING TIME
VARIATIONS ±10% or 0.01 SECONDS
10 11
TIME(SECONDS)
18
14
13
16
0.1
15
0.01
100 1000 10000
CURRENT(PERCENTAGE OF MINIMUM TRIP)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 97
100
CLEARING TIME
RECLOSER CLEARING TIME
CURVE:A,B,C,D,E
CURVE:N1,N2,N3,N4
CURVE SHOWN IS
THE 1.0×MULTIPLIER CURVE.
AVERAGE CLEARING TIME
VARIATIONS ±10% or 0.01 SECONDS
10
TIME(SECONDS)
N2 N3
N4
0.1
N1
0.01
100 1000 10000
CURRENT(PERCENTAGE OF MINIMUM TRIP)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 98
US1
100
RESPONSE TIME
CURVE : US1
AVERAGE RESPONSE TIME
VARIATIONS ±10% or 0.01
SECONDS
10
15
10
TIME(SECONDS)
1
5
0.1 0.5
0.01
100 1000 10000
CURRENT(PERCENTAGE OF MINIMUM TRIP)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 99
US2
1000
RESPONSE TIME
CURVE : US2
AVERAGE RESPONSE TIME
VARIATIONS ±10% or 0.01
SECONDS
100
10
TIME(SECONDS)
15
10
1 5
0.1 0.5
0.01
100 1000 10000
CURRENT(PERCENTAGE OF MINIMUM TRIP)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 100
US3
1000
RESPONSE TIME
CURVE : US3
AVERAGE RESPONSE TIME
VARIATIONS ±10% or 0.01
SECONDS
100
10
TIME(SECONDS)
15
1
10
0.1 1
0.5
0.01
100 1000 10000
CURRENT(PERCENTAGE OF MINIMUM TRIP)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 101
US4
1000
RESPONSE TIME
CURVE : US4
AVERAGE RESPONSE TIME
VARIATIONS ±10% or 0.01
SECONDS
100
10
TIME(SECONDS)
1
1
10
0.1
0.5
0.01
100 1000 10000
CURRENT(PERCENTAGE OF MINIMUM TRIP)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 102
US5
100
RESPONSE TIME
CURVE : US5
AVERAGE RESPONSE TIME
VARIATIONS ±10% or 0.01
SECONDS
10
TIME(SECONDS)
1
1
10
0.1
0.5
0.01
100 1000 10000
CURRENT(PERCENTAGE OF MINIMUM TRIP)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 103
IEC1
100
RESPONSE TIME
CURVE : IEC1
AVERAGE RESPONSE TIME
VARIATIONS ±10% or 0.01
SECONDS
10
1
TIME(SECONDS)
0.5
1
0.2
0.1
0.05
0.1
0.01
100 1000 10000
CURRENT(PERCENTAGE OF MINIMUM TRIP)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 104
IEC2
1000
RESPONSE TIME
CURVE : IEC2
AVERAGE RESPONSE TIME
VARIATIONS ±10% or 0.01
SECONDS
100
10
TIME(SECONDS)
0.5
0.2
0.1
0.1
0.05
0.01
100 1000 10000
CURRENT(PERCENTAGE OF MINIMUM TRIP)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 105
IEC3
1000
RESPONSE TIME
CURVE : IEC3
AVERAGE RESPONSE TIME
VARIATIONS ±10% or 0.01
SECONDS
100
10
TIME(SECONDS)
0.1 0.5
0.2
0.1
0.01 0.05
100 1000 10000
CURRENT(PERCENTAGE OF MINIMUM TRIP)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 106
IEC4
10000
RESPONSE TIME
CURVE : IEC4
AVERAGE RESPONSE TIME
VARIATIONS ±10% or 0.01
SECONDS
1000
100
TIME(SECONDS)
10
0.5
0.2
1
0.1
0.05
0.1
0.01
100 1000 10000
CURRENT(PERCENTAGE OF MINIMUM TRIP)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 107
IEC5
100
RESPONSE TIME
CURVE : IEC5
AVERAGE RESPONSE TIME
VARIATIONS ±10% or 0.01
SECONDS
10
TIME(SECONDS)
0.5
0.1
0.2
0.1
0.05
0.01
100 1000 10000
CURRENT(PERCENTAGE OF MINIMUM TRIP)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 108
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 109
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 110
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 111
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 112
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 113
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 114
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 115
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 116
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 117
0:Normal 1:Fail
5,000 times
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 118
0: Undefine(CS:0,OS:0)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 119
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 120
0:Normal 1:Fail
5,000 times
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 121
on : enable
3004 Hot Line Tag En/Dis Command on / off
off : disable
on : enable
3005 Protection En/Dis Command on / off
off : disable
on : Alt. Group
3006 Alternate Group Setting Command on / off
off : Nor. Group
on : enable
3008 Reclose En/Dis Command on / off
off : disable
on : enable
3009 Ground En/Dis Command on / off
off : disable
on : enable
3013 SEF/HIF En/Dis Command on / off
off : disable
on : enable
3014 Close/Trip delay time En/Dis Command on / off
off : disable
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 122
on : enable
3019 Dummy CB1 Command on / off
off : disable
on : enable
3020 Dummy CB2 Command on / off
off : disable
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 123
on : Close
4001 Recloser Open / Close Command on / off
off : Open
on : enable
4003 Hot Line Tag En/Dis Command on / off
off : disable
on : enable
4004 Protection En/Dis Command on / off
off : disable
on : Alt. Group
4005 Alternate Group Setting Command on / off
off : Nor. Group
on : enable
4007 Reclose En/Dis Command on / off
off : disable
on : enable
4008 Ground En/Dis Command on / off
off : disable
on : enable
4012 SEF/HIF En/Dis Command on / off
off : disable
on : enable
4013 Close/Trip delay time En/Dis Command on / off
off : disable
4014 ABC->RST for Power Flow Command on / off on : ABC -> RST
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 124
on : enable
4017 Dummy CB1 Command on / off
off : disable
on : enable
4018 Dummy CB2 Command on / off
off : disable
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 125
Analog Input
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 126
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 127
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 128
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 129
Word Bit
No. Description
(Recloser)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 130
Word Bit
No. Description
(Recloser)
22 51N1TCD Over current element torque control for delay curve (ground)
23 51N1TCF Over current element torque control for fast curve (ground)
33 51P1TCD Over current element torque control for delay curve (phase)
34 51P1TCF Over current element torque control for fast curve (phase)
Over current element torque control for delay curve (negative sequence
43 51Q1TCD
current)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 131
Word Bit
No. Description
(Recloser)
44 51Q1TCF Over current element torque control for fast curve (negative sequence current)
45 51Q1TD Trip by negative sequence current pickup with delay curve operation
46 51Q1TF Trip by negative sequence current pickup with fast curve operation
47 51TCD Over current element torque control with VIT sequence operation
49 79ARS Auto reset for VIT (VAND1 and !FLTT and !52A), rese time = 60s fix
51 79CLS Close power supervision (power source is sufficient for close opration)
57 79FRS Forced reset after count for VIT (VAND1 and 52A), reset time = 10min. fix
59 79LO1 Lockout by manual trip, handle lock, trip fail, close fail
65 79LO8 Lockout by voltage count or open ductor function for tie mode
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 132
Word Bit
No. Description
(Recloser)
67 79NCRS N.C mode reset for VIT (VAND1 and !FLTT and 52A), rese time = 180s fix
N.O mode reset for VIT (VAND1 and !FLTT and !52A and N.O mode),
68 79NORS
rese time = 180s fix
73 79OIXLT
84 ABF 2-phase fault ( A and B phase) - use for fault location calculation
86 AGF Single phase fault (A phase) - use for fault location calculation
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 133
Word Bit
No. Description
(Recloser)
93 BCF 2-phase fault ( B and C phase) - use for fault location calculation
94 BGF Single phase fault (B phase) - use for fault location calculation
96 CAF 2-phase fault ( A and C phase) - use for fault location calculation
99 CF Close fail
100 CGF Single phase fault (C phase) - use for fault location calculation
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 134
Word Bit
No. Description
(Recloser)
115 DCM DC power was charged to the capacitor with sufficient voltage
DC power was charged to the capacitor with sufficient voltage for close-
116 DCMC
operation
DC power was charged to the capacitor with sufficient voltage for trip-
117 DCMT
operation
120 DI13 Reset command for VIT sequence by external input signal in T/B
121 DOBT Battery load test by push-button or remote command or automatic schedule
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 135
Word Bit
No. Description
(Recloser)
139 FCP
142 GASLOW Gas low alarm (for SF6 gas insulated recloser)
143 HANDLELOCK Manual Locking handle status [ Logical 1: Lock, Logical 0: Unlock ]
148 LOCKTRIP Lockout trip (command trip, push-button trip, UVTRIP, OVTRIP, 81T)
149 MLRS Manual reset for VIT sequence (lockout state -> reset state)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 136
Word Bit
No. Description
(Recloser)
152 MRS Reset for VIT seqeunce when close by manual operating handle
159 NOCN Voltage count reaches to preset upstream count for tie mode
164 OCCL Wating for close after open conductor trip (radial normal colse mode)
165 OCCP Automatic close pulse after open conductor trip (radial normal colse mode)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 137
Word Bit
No. Description
(Recloser)
177 OPFB Operating circuit (drive circuit for close and open operation) fuse blown
183 OVCN Voltage count reaches to preset upstream count for normal close mode
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 138
Word Bit
No. Description
(Recloser)
199 RSCL Wating for close after reset in initializing seqeunce of VIT
210 SH0 Shot number 0 for reclose seqeunce (from reset state to 1st trip)
211 SH1 Shot number 1 for reclose seqeunce (from 1st reclose to 2nd trip)
212 SH2 Shot number 2 for reclose seqeunce (from 2nd reclose to 3rd trip)
213 SH3 Shot number 3 for reclose seqeunce (from 3rd reclose to 4th trip)
214 SH4 Shot number 4 for reclose seqeunce (from 4th reclose to 5th trip)
217 SV11T Cold load pickup natural reset time-out for SEF
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 139
Word Bit
No. Description
(Recloser)
221 SV5T Forced reset timer is time-out for cold load pickup (restore minimum pickup)
223 SV7T Cold load pickup natural reset timer is time-out for phase
225 SV9T Cold load pickup natural reset timer is time-out for ground
233 TR3 Trip by voltage count within CLT(close lockout time) after close
239 UNBC Unbalance current pickup (I2/I1) for open conductor protection
240 UNBV Unbalance voltage pickup (V0/V1) for open conductor protection
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 140
Word Bit
No. Description
(Recloser)
249 V1A1 Source side positive sequence voltage is over than level1 (35%)
250 V1A2 Source side positive sequence voltage is over than level2 (40%)
251 V1R1 Load side positive sequence voltage is over than level1 (35%)
252 V1R2 Load side positive sequence voltage is over than level2 (40%)
253 V2A1 Source side negative sequence voltage is over than level1 (35%)
254 V2A2 Source side negative sequence voltage is over than level2 (40%)
255 V2R1 Load side negative sequence voltage is over than level1 (35%)
256 V2R2 Load side negative sequence voltage is over than level2 (40%)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 141
Word Bit
No. Description
(Recloser)
277 PICKUPABC Over current alarm with time delay (A & B & C)
278 PICKUPABCN Over current alarm with time delay (A & B & C & N)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 142
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 143
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 144
SHINSUNG
Industrial Electric Co., Ltd.