ZONE 3 SOL & SLD
ZONE 3 SOL & SLD
M ECB1 2500AT
2500AF
3P
1-175 mm²
THHN (G) Cu. Wire
(connected ground rod)
POWERHOUSE 3
8 sets of 3-250 mm² THHN
+ 1-175 mm² THHN (G)
in 100mmØ PVC PIPE
ATS (connected to ECB)
ECB 2500AT
2500AF
3P
G
1-175 mm²
THHN (G) Cu. Wire 1.1MVA GENSET
PUMP HOUSE 3 (connected ground rod) DIESEL-TYPE,
230V, 3Ø
MDP-PH3 TRANSFER
2500AT SWITCH
2500AF 3&4
PB-PUMP 3 40AT 3P
100AF
2P 1-175 mm²
THHN (G) Cu. Wire PB-PH3 40AT
2-8.0 mm² THHN
(connected to ECB1) + 1-5.5 mm² THHN (G) 100AF
1-5.5 mm²
THHN (G) Cu. Wire 2-8.0 mm² THHN in 25 mmØ PVC PIPE 2P
+ 1-5.5 mm² THHN (G) (connected to MDP-PH3)
(connected to MDP-PH3)
in 25 mmØ PVC PIPE
(connected to MDP-PH3) 1-5.5 mm²
THHN (G) Cu. Wire
(connected to MDP-PH3)
NURSERY OFFICE PUMP HOUSE 3 DEEP WELL 5 3-30 mm² THHN DEEP WELL 6 3-30 mm² THHN
+ 1-8.0 mm² THHN (G) + 1-8.0 mm² THHN (G)
in 32 mmØ PVC PIPE in 32 mmØ PVC PIPE
8 sets of 3-250 mm² THHN (connected to MDP-PH3) (connected to MDP-PH3)
2-22 mm² THHN 3 sets of 3-175 mm² THHN 6 sets of 3-175 mm² THHN 2-8.0 mm² THHN
+ 1-8.0 mm² THHN (G) + 1-100 mm² THHN(G) + 1-38 mm² THHN (G) + 1-38 mm² THHN (G) + 1-5.5 mm² THHN (G)
in 32 mmØ PVC PIPE in 150mmØ PVC PIPE in 90 mmØ PVC PIPE in 90 mmØ PVC PIPE in 25 mmØ PVC PIPE
(connected to MDP-PH3) (connected to MDP-PH3) (connected to MDP-PH3) (connected to MDP-PH3) (connected to MDP-PH3)
CONTROL CONTROL
PANEL PANEL
PROFESSIONAL ELECTRICAL ENGINEER PROJECT TITLE: APPROVED BY: SHEET CONTENT: SHEET NO.:
ZONE 3 Single-Line Diagram 1 DESIGNED BY: REYNEN M. LOLA, REE, RME, SO2
ECO CYCEN ALWIN M. LUNAS SWINE FARM BUILDING ECO CYCEN CORPORATION
CADD BY:
CHECKED BY:
REYNEN M. LOLA, REE, RME, SO2
DP-N1 600AT
630AF
3P
1-38 mm²
THHN (G) Cu. Wire
(connected to DP5)
3-38 mm² THHN 3-80 mm² THHN 3-22 mm² THHN 3-22 mm² THHN 3-60 mm² THHN 3-22 mm² THHN 3-22 mm² THHN 3-38 mm² THHN 3-22 mm² THHN 3-22 mm² THHN 3-22 mm² THHN 3-22 mm² THHN
+ 1-8.0 mm² THHN (G) + 1-8.0 mm² THHN (G) + 1-5.5 mm² THHN (G) + 1-8.0 mm² THHN (G) + 1-8.0 mm² THHN (G) + 1-5.5 mm² THHN (G) + 1-8.0 mm² THHN (G) + 1-8.0 mm² THHN (G) + 1-5.5 mm² THHN (G) + 1-8.0 mm² THHN (G) + 1-8.0 mm² THHN (G) + 1-5.5 mm² THHN (G)
in 40 mmØ PVC PIPE in 40 mmØ PVC PIPE in 20 mmØ PVC PIPE in 40 mmØ PVC PIPE in 40 mmØ PVC PIPE in 20 mmØ PVC PIPE in 40 mmØ PVC PIPE in 40 mmØ PVC PIPE in 20 mmØ PVC PIPE in 40 mmØ PVC PIPE in 40 mmØ PVC PIPE in 20 mmØ PVC PIPE
(connected to DP-N1) (connected to DP-N1) (connected to DP-N1) (connected to DP-N1) (connected to DP-N1) (connected to DP-N1) (connected to DP-N1) (connected to DP-N1) (connected to DP-N1) (connected to DP-N1) (connected to DP-N1) (connected to DP-N1)
PBL-N1U1 60AT PBHL-N1U1 80AT VCP-N1U1 CONTROL PBL-N1U2 60AT PBHL-N1U2 80AT VCP-N1U2 CONTROL PBL-N1U3 60AT PBHL-N1U3 80AT VCP-N1U3 CONTROL PBL-N1U4 60AT PBHL-N1U4 80AT VCP-N1U4 CONTROL
100AF 100AF 60AT PANEL 100AF 100AF 60AT PANEL 100AF 100AF 60AT PANEL 100AF 100AF 60AT PANEL
3P 3P 3P 3P 3P 3P 3P 3P
1-8.0 mm² 1-8.0 mm² (PROVIDED BY THE SUPPLIER) 1-8.0 mm² 1-8.0 mm² (PROVIDED BY THE SUPPLIER) 1-8.0 mm² 1-8.0 mm² (PROVIDED BY THE SUPPLIER) 1-8.0 mm² 1-8.0 mm² (PROVIDED BY THE SUPPLIER)
THHN (G) Cu. Wire THHN (G) Cu. Wire THHN (G) Cu. Wire THHN (G) Cu. Wire THHN (G) Cu. Wire THHN (G) Cu. Wire THHN (G) Cu. Wire THHN (G) Cu. Wire
(connected to DP-N1) (connected to DP-N1) (connected to DP-N1) (connected to DP-N1) (connected to DP-N1) (connected to DP-N1) (connected to DP-N1) (connected to DP-N1)
ECB 20AT
3-8.0 mm² THHN 100AF
+ 1-5.5 mm² THHN (G) 2P
in 32 mmØ PVC PIPE 1-3.5 mm²
(connected to DP-N1) THHN (G) Cu. Wire
(connected to DP-N1) 2-3.5 mm² THHN
+ 1-3.5 mm² THHN (G)
in 20mmØ PVC PIPE
SFCP-N1 CONTROL (connected to DP-N1)
40AT PANEL
M
~
Booster
(PROVIDED BY THE SUPPLIER)
Pump
1 HP, 1Ø
TO DP5
SEE DRAWING DETAILS E008
DP-N2 600AT
630AF
3P
3-38 mm² THHN 3-80 mm² THHN 3-22 mm² THHN 3-22 mm² THHN 3-60 mm² THHN 3-22 mm² THHN 3-22 mm² THHN 3-38 mm² THHN 3-22 mm² THHN 3-22 mm² THHN 3-22 mm² THHN 3-22 mm² THHN
+ 1-8.0 mm² THHN (G) + 1-8.0 mm² THHN (G) + 1-5.5 mm² THHN (G) + 1-8.0 mm² THHN (G) + 1-8.0 mm² THHN (G) + 1-5.5 mm² THHN (G) + 1-8.0 mm² THHN (G) + 1-8.0 mm² THHN (G) + 1-5.5 mm² THHN (G) + 1-8.0 mm² THHN (G) + 1-8.0 mm² THHN (G) + 1-5.5 mm² THHN (G)
in 40 mmØ PVC PIPE in 40 mmØ PVC PIPE in 20 mmØ PVC PIPE in 40 mmØ PVC PIPE in 40 mmØ PVC PIPE in 20 mmØ PVC PIPE in 40 mmØ PVC PIPE in 40 mmØ PVC PIPE in 20 mmØ PVC PIPE in 40 mmØ PVC PIPE in 40 mmØ PVC PIPE in 20 mmØ PVC PIPE
(connected to DP-N2) (connected to DP-N2) (connected to DP-N2) (connected to DP-N2) (connected to DP-N2) (connected to DP-N2) (connected to DP-N2) (connected to DP-N2) (connected to DP-N2) (connected to DP-N2) (connected to DP-N2) (connected to DP-N2)
PBL-N2U1 60AT PBHL-N2U1 80AT VCP-N2U1 CONTROL PBL-N2U2 60AT PBHL-N2U2 80AT VCP-N2U2 CONTROL PBL-N2U3 60AT PBHL-N2U3 80AT VCP-N2U3 CONTROL PBL-N2U4 60AT PBHL-N2U4 80AT VCP-N2U4 CONTROL
100AF 100AF 60AT PANEL 100AF 100AF 60AT PANEL 100AF 100AF 60AT PANEL 100AF 100AF 60AT PANEL
3P 3P 3P 3P 3P 3P 3P 3P
1-8.0 mm² 1-8.0 mm² (PROVIDED BY THE SUPPLIER) 1-8.0 mm² 1-8.0 mm² (PROVIDED BY THE SUPPLIER) 1-8.0 mm² 1-8.0 mm² (PROVIDED BY THE SUPPLIER) 1-8.0 mm² 1-8.0 mm² (PROVIDED BY THE SUPPLIER)
THHN (G) Cu. Wire THHN (G) Cu. Wire THHN (G) Cu. Wire THHN (G) Cu. Wire THHN (G) Cu. Wire THHN (G) Cu. Wire THHN (G) Cu. Wire THHN (G) Cu. Wire
(connected to DP-N2) (connected to DP-N2) (connected to DP-N2) (connected to DP-N2) (connected to DP-N2) (connected to DP-N2) (connected to DP-N2) (connected to DP-N2)
ECB 20AT
3-8.0 mm² THHN 100AF
+ 1-5.5 mm² THHN (G) 2P
in 32 mmØ PVC PIPE 1-3.5 mm²
(connected to DP-N1) THHN (G) Cu. Wire
(connected to DP-N1) 2-3.5 mm² THHN
+ 1-3.5 mm² THHN (G)
in 20mmØ PVC PIPE
SFCP-N2 CONTROL (connected to DP-N1)
40AT PANEL
M
~
Booster
(PROVIDED BY THE SUPPLIER)
Pump
1 HP, 1Ø
ZONE 3
E-009 Single-Line Diagram 2
01 01 SCALE: NTS
PROFESSIONAL ELECTRICAL ENGINEER PROJECT TITLE: APPROVED BY: SHEET CONTENT: SHEET NO.:
ZONE 3 Single-Line Diagram 2 DESIGNED BY: REYNEN M. LOLA, REE, RME, SO2
ECO CYCEN ALWIN M. LUNAS SWINE FARM BUILDING ECO CYCEN CORPORATION
CADD BY:
CHECKED BY:
REYNEN M. LOLA, REE, RME, SO2
DP-F1 600AT
630AF
3P
FARROWING 1 (UNIT 1) FARROWING 1 (UNIT 2) FARROWING 1 (UNIT 3) FARROWING 1 (UNIT 4) FARROWING 1 (UNIT 5)
3-22 mm² THHN 3-22 mm² THHN 3-22 mm² THHN 3-22 mm² THHN 3-22 mm² THHN 3-22 mm² THHN 3-22 mm² THHN 3-22 mm² THHN 3-22 mm² THHN 3-30 mm² THHN 3-22 mm² THHN 3-22 mm² THHN 3-30 mm² THHN 3-30 mm² THHN 3-22 mm² THHN
+ 1-8.0 mm² THHN (G) + 1-8.0 mm² THHN (G) + 1-8.0 mm² THHN (G) + 1-8.0 mm² THHN (G) + 1-8.0 mm² THHN (G) + 1-8.0 mm² THHN (G) + 1-8.0 mm² THHN (G) + 1-8.0 mm² THHN (G) + 1-8.0 mm² THHN (G) + 1-8.0 mm² THHN (G) + 1-8.0 mm² THHN (G) + 1-8.0 mm² THHN (G) + 1-8.0 mm² THHN (G) + 1-8.0 mm² THHN (G) + 1-8.0 mm² THHN (G)
in 40 mmØ PVC PIPE in 40 mmØ PVC PIPE in 40 mmØ PVC PIPE in 40 mmØ PVC PIPE in 40 mmØ PVC PIPE in 40 mmØ PVC PIPE in 40 mmØ PVC PIPE in 40 mmØ PVC PIPE in 40 mmØ PVC PIPE in 40 mmØ PVC PIPE in 40 mmØ PVC PIPE in 40 mmØ PVC PIPE in 40 mmØ PVC PIPE in 40 mmØ PVC PIPE in 40 mmØ PVC PIPE
(connected to DP-F1) (connected to DP-F1) (connected to DP-F1) (connected to DP-F1) (connected to DP-F1) (connected to DP-F1) (connected to DP-F1) (connected to DP-F1) (connected to DP-F1) (connected to DP-F1) (connected to DP-F1) (connected to DP-F1) (connected to DP-F1) (connected to DP-F1) (connected to DP-F1)
PBL-F1U1 60AT PBHL-F1U1 60AT VCP-F1U1 CONTROL PBL-F1U2 60AT PBHL-F1U2 60AT VCP-F1U2 CONTROL PBL-F1U3 60AT PBHL-F1U3 60AT VCP-F1U3 CONTROL PBL-F1U4 60AT PBHL-F1U4 60AT VCP-F1U4 CONTROL PBL-F1U5 60AT PBHL-F1U5 60AT VCP-F1U5 CONTROL
100AF 100AF 60AT PANEL 100AF 100AF 60AT PANEL 100AF 100AF 60AT PANEL 100AF 100AF 60AT PANEL 100AF 100AF 60AT PANEL
3P 3P 3P 3P 3P 3P 3P 3P 3P 3P
1-8.0 mm² 1-8.0 mm² (PROVIDED BY THE SUPPLIER) 1-8.0 mm² 1-8.0 mm² (PROVIDED BY THE SUPPLIER) 1-8.0 mm² 1-8.0 mm² (PROVIDED BY THE SUPPLIER) 1-8.0 mm² 1-8.0 mm² (PROVIDED BY THE SUPPLIER) 1-8.0 mm² 1-8.0 mm² (PROVIDED BY THE SUPPLIER)
THHN (G) Cu. Wire THHN (G) Cu. Wire THHN (G) Cu. Wire THHN (G) Cu. Wire THHN (G) Cu. Wire THHN (G) Cu. Wire THHN (G) Cu. Wire THHN (G) Cu. Wire THHN (G) Cu. Wire THHN (G) Cu. Wire
(connected to DP-F1) (connected to DP-F1) (connected to DP-F1) (connected to DP-F1) (connected to DP-F1) (connected to DP-F1) (connected to DP-F1) (connected to DP-F1) (connected to DP-F1) (connected to DP-F1)
ECB 20AT
3-8.0 mm² THHN 100AF
+ 1-5.5 mm² THHN (G) 2P
in 32 mmØ PVC PIPE 1-3.5 mm²
(connected to DP-F1) THHN (G) Cu. Wire
(connected to DP-F1) 2-3.5 mm² THHN
+ 1-3.5 mm² THHN (G)
in 20mmØ PVC PIPE
SFCP-F1 CONTROL (connected to DP-F1)
40AT PANEL
M
~
Booster
(PROVIDED BY THE SUPPLIER)
Pump
1 HP, 1Ø
TO MDP-PH3
SEE DRAWING DETAILS E008
DP-F2 600AT
630AF
3P
FARROWING 2 (UNIT 1) FARROWING 2 (UNIT 2) FARROWING 2 (UNIT 3) FARROWING 2 (UNIT 4) FARROWING 2 (UNIT 5)
3-22 mm² THHN 3-22 mm² THHN 3-22 mm² THHN 3-22 mm² THHN 3-22 mm² THHN 3-22 mm² THHN 3-22 mm² THHN 3-22 mm² THHN 3-22 mm² THHN 3-30 mm² THHN 3-22 mm² THHN 3-22 mm² THHN 3-30 mm² THHN 3-30 mm² THHN 3-22 mm² THHN
+ 1-8.0 mm² THHN (G) + 1-8.0 mm² THHN (G) + 1-8.0 mm² THHN (G) + 1-8.0 mm² THHN (G) + 1-8.0 mm² THHN (G) + 1-8.0 mm² THHN (G) + 1-8.0 mm² THHN (G) + 1-8.0 mm² THHN (G) + 1-8.0 mm² THHN (G) + 1-8.0 mm² THHN (G) + 1-8.0 mm² THHN (G) + 1-8.0 mm² THHN (G) + 1-8.0 mm² THHN (G) + 1-8.0 mm² THHN (G) + 1-8.0 mm² THHN (G)
in 40 mmØ PVC PIPE in 40 mmØ PVC PIPE in 40 mmØ PVC PIPE in 40 mmØ PVC PIPE in 40 mmØ PVC PIPE in 40 mmØ PVC PIPE in 40 mmØ PVC PIPE in 40 mmØ PVC PIPE in 40 mmØ PVC PIPE in 40 mmØ PVC PIPE in 40 mmØ PVC PIPE in 40 mmØ PVC PIPE in 40 mmØ PVC PIPE in 40 mmØ PVC PIPE in 40 mmØ PVC PIPE
(connected to DP-F2) (connected to DP-F2) (connected to DP-F2) (connected to DP-F2) (connected to DP-F2) (connected to DP-F2) (connected to DP-F2) (connected to DP-F2) (connected to DP-F2) (connected to DP-F2) (connected to DP-F2) (connected to DP-F2) (connected to DP-F2) (connected to DP-F2) (connected to DP-F2)
PBL-F2U1 60AT PBHL-F2U1 60AT VCP-F2U1 CONTROL PBL-F2U2 60AT PBHL-F2U2 60AT VCP-F2U2 CONTROL PBL-F2U3 60AT PBHL-F2U3 60AT VCP-F2U3 CONTROL PBL-F2U4 60AT PBHL-F2U4 60AT VCP-F2U4 CONTROL PBL-F2U5 60AT PBHL-F2U5 60AT VCP-F2U5 CONTROL
100AF 100AF 60AT PANEL 100AF 100AF 60AT PANEL 100AF 100AF 60AT PANEL 100AF 100AF 60AT PANEL 100AF 100AF 60AT PANEL
3P 3P 3P 3P 3P 3P 3P 3P 3P 3P
1-8.0 mm² 1-8.0 mm² (PROVIDED BY THE SUPPLIER) 1-8.0 mm² 1-8.0 mm² (PROVIDED BY THE SUPPLIER) 1-8.0 mm² 1-8.0 mm² (PROVIDED BY THE SUPPLIER) 1-8.0 mm² 1-8.0 mm² (PROVIDED BY THE SUPPLIER) 1-8.0 mm² 1-8.0 mm² (PROVIDED BY THE SUPPLIER)
THHN (G) Cu. Wire THHN (G) Cu. Wire THHN (G) Cu. Wire THHN (G) Cu. Wire THHN (G) Cu. Wire THHN (G) Cu. Wire THHN (G) Cu. Wire THHN (G) Cu. Wire THHN (G) Cu. Wire THHN (G) Cu. Wire
(connected to DP-F2) (connected to DP-F2) (connected to DP-F2) (connected to DP-F2) (connected to DP-F2) (connected to DP-F2) (connected to DP-F2) (connected to DP-F2) (connected to DP-F2) (connected to DP-F2)
ECB 20AT
3-8.0 mm² THHN 100AF
+ 1-5.5 mm² THHN (G) 2P
in 32 mmØ PVC PIPE 1-3.5 mm²
(connected to DP-F2) THHN (G) Cu. Wire
(connected to DP-F2) 2-3.5 mm² THHN
+ 1-3.5 mm² THHN (G)
in 20mmØ PVC PIPE
SFCP-F2 CONTROL (connected to DP-F2)
40AT PANEL
M
~
Booster
(PROVIDED BY THE SUPPLIER)
Pump
1 HP, 1Ø
ZONE 3
E-010 Single-Line Diagram 3
01 01 SCALE: NTS
PROFESSIONAL ELECTRICAL ENGINEER PROJECT TITLE: APPROVED BY: SHEET CONTENT: SHEET NO.:
ZONE 3 Single-Line Diagram 3 DESIGNED BY: REYNEN M. LOLA, REE, RME, SO2
ECO CYCEN ALWIN M. LUNAS SWINE FARM BUILDING ECO CYCEN CORPORATION
CADD BY:
CHECKED BY:
REYNEN M. LOLA, REE, RME, SO2
PROFESSIONAL ELECTRICAL ENGINEER PROJECT TITLE: APPROVED BY: SHEET CONTENT: SHEET NO.:
ZONE 3 Schedule of Loads & Computations 1 DESIGNED BY: REYNEN M. LOLA, REE, RME, SO2
ECO CYCEN ALWIN M. LUNAS SWINE FARM BUILDING ECO CYCEN CORPORATION
CADD BY:
CHECKED BY:
REYNEN M. LOLA, REE, RME, SO2
PROFESSIONAL ELECTRICAL ENGINEER PROJECT TITLE: APPROVED BY: SHEET CONTENT: SHEET NO.:
ZONE 3 Schedule of Loads & Computations 2 DESIGNED BY: REYNEN M. LOLA, REE, RME, SO2
ECO CYCEN ALWIN M. LUNAS SWINE FARM BUILDING ECO CYCEN CORPORATION
CADD BY:
CHECKED BY:
REYNEN M. LOLA, REE, RME, SO2