Un-Control Systems Engineering
Un-Control Systems Engineering
" #
x
y C 0 (12.115b)
xN
Thus, the system type has been increased, and we can use the characteristic equation
associated with Eq. (12.115a) to design K and Ke to yield the desired transient response.
Realize, we now have an additional pole to place. The effect on the transient response of any
closed-loop zeros in the final design must also be taken into consideration. One possible
assumption is that the closed-loop zeros will be the same as those of the open-loop plant.
This assumption, which of course must be checked, suggests placing higher-order poles at
the closed-loop zero locations. Let us demonstrate with an example.
Example 12.10
y 1 0x (12.116b)
a. Design a controller without integral control to yield a 10% overshoot and a settling time
of 0.5 second. Evaluate the steady-state error for a unit step input.
b. Repeat the design of Part a using integral control. Evaluate the steady-state error for a
unit step input.
SOLUTION:
a. Using the requirements for settling time and percent overshoot, we find that the
desired characteristic polynomial is
Since the plant is represented in phase-variable form, the characteristic polynomial for the
controlled plant with state-variable feedback is
s2 5 k2 s 3 k 1 12.118
K k1 k2 180:1 11 12.119
WEBC12 10/29/2014 8:56:40 Page 686
From Eqs. (12.3), the controlled plant with state-variable feedback represented in phase-
variable form is
0 1 0
x_ A BKx Br x r (12.120a)
183:1 16 1
y Cx 1 0x (12.120b)
Using Eq. (7.96), we find that the steady-state error for a step input is
e ∞ 1C A BK 1 B
" # 1" #
0 1 0
1 1 0
183:1 16 1
0:995 12.121
Using Eq. (3.73) and the plant of Eqs. (12.116), we find that the transfer function of
the plant is G s 1= s2 5s 3. The desired characteristic polynomial for the closed-
loop integral-controlled system is shown in Eq. (12.117). Since the plant has no zeros, we
assume no zeros for the closed-loop system and augment Eq. (12.117) with a third pole,
s 100, which has a real part greater than five times that of the desired dominant second-
order poles. The desired third-order closed-loop system characteristic polynomial is
s3 5 k 2 s2 3 k1 s K e 12.124
k 1 1780:1 (12.125a)
k2 111 (12.125b)
k e 18;310 (12.125c)
12.8 Steady-State Error Design via Integral Control 687
Substituting these values into Eqs. (12.122) yields this closed-loop integral-controlled
system:
2 3 2 32 3 2 3
x_ 1 0 1 0 x1 0
6 7 4 5 4
4 x_ 2 5 1783:1 116 18;310 x2 0 5 r
5 4 (12.126a)
x_ N 1 0 0 xN 1
2 3
x
1
y 1 0 0 x2 5
4 (12.126b)
xN
In order to check our assumption for the zero, we now apply Eq. (3.73) to
Eqs. (12.126) and find the closed-loop transfer function to be
18;310
T s 12.127
s3 116s2 1783:1s 18;310
Since the transfer function matches our design, we have the desired transient response.
Now let us find the steady-state error for a unit step input. Applying Eq. (7.96) to
Eqs. (12.126), we obtain
2 3 12 3
0 1 0 0
6 7 6 7
e ∞ 1 1 0 0 4 1783:1 116 18;310 5 4 0 5 0 12.128
1 0 0 1
to yield a step response with 10% overshoot, a peak time of 2 seconds, and zero
steady-state error.
Now that we have designed controllers and observers for transient response and
steady-state error, we summarize the chapter with a case study demonstrating the design
process.