837
837
VISTA-20P / VISTA-20PSIA
VISTA-15P / VISTA-15PSIA
Security Systems
ii
Table Of Contents
Features and Installation Highlights............................................................................................................1-1
Capabilities and Functions................................................................................................................................................1-1
Compatible Devices ...........................................................................................................................................................1-2
Important Installation Highlights (Installer Please Read) .............................................................................................1-2
Mounting and Wiring the Control .................................................................................................................2-1
Installing the Control Cabinet and PC Board ..................................................................................................................2-1
Cabinet and Lock .........................................................................................................................................................2-1
Mounting the PC Board Alone (no RF Receiver) ........................................................................................................2-1
Mounting Board with RF Receiver..............................................................................................................................2-1
Auxiliary Device Current Draw Worksheet................................................................................................................2-2
AC Power, Battery, and Ground Connections ..................................................................................................................2-3
1321 Transformer.........................................................................................................................................................2-3
1361X10 Transformer ..................................................................................................................................................2-3
Battery Connections.....................................................................................................................................................2-3
Battery Saver Feature .................................................................................................................................................2-3
Earth Ground ...............................................................................................................................................................2-3
Sounder (Bell) Connections ...............................................................................................................................................2-4
Basic Connections ........................................................................................................................................................2-4
Supervised output ........................................................................................................................................................2-4
Connecting the Keypads and Other Addressable Devices ...............................................................................................2-4
Connections ..................................................................................................................................................................2-4
Supplementary Power (optional).................................................................................................................................2-4
Keypad Notes ...............................................................................................................................................................2-5
Communication Device ................................................................................................................................................2-5
(Long Range Radio) Connections.................................................................................................................................2-5
Table of Device Addresses .................................................................................................................................................2-5
Hardwire Zones and Zone Expansion ...............................................................................................................................2-6
Hardwire Zones ............................................................................................................................................................2-6
Double-Balanced Zones................................................................................................................................................2-6
Zone Doubling ..............................................................................................................................................................2-6
Smoke Detectors...........................................................................................................................................................2-6
Smoke Detector Notes..................................................................................................................................................2-7
4219/4229 Expansion Zones ........................................................................................................................................2-7
Installing the RF Receiver and Wireless Transmitter Zones ..........................................................................................2-8
Compatible Receivers...................................................................................................................................................2-8
Receiver Connections ...................................................................................................................................................2-8
RF Receiver Notes........................................................................................................................................................2-8
Installing a 5800TM Module .......................................................................................................................................2-9
Installing the Transmitters .........................................................................................................................................2-9
Transmitter Battery Life .............................................................................................................................................2-9
Installing a Keyswitch.....................................................................................................................................................2-10
Keyswitch Connections ..............................................................................................................................................2-10
Keyswitch Notes.........................................................................................................................................................2-10
Connecting Relay Modules, Powerline Carrier Devices and Output Triggers..............................................................2-11
4204/4229 Relay Modules ..........................................................................................................................................2-11
Powerline Carrier Devices .........................................................................................................................................2-11
On-Board Triggers .....................................................................................................................................................2-12
Phone Line/Phone Module, and Audio Alarm Verification (AAV) Connections............................................................2-13
Phone Line..................................................................................................................................................................2-13
4286 Phone Module....................................................................................................................................................2-13
Phone Module Problems ............................................................................................................................................2-13
Audio Alarm Verification Connections......................................................................................................................2-14
Audio Alarm Verification Connections......................................................................................................................2-15
iii
Table Of Contents
iv
S E C T I O N 1
1-1
Installation and Setup Guide
Compatible Devices
Device VISTA-20P VISTA-15P Notes
Addressable Keypads 8 8 6150 Fixed-Word Keypad, 6160 Alpha Keypad, 6150V
Fixed-Word Display Voice Keypad, 6160V Alpha
Display Voice Keypad, 6150RF Keypad/Transceiver
Touch Screen (AUI) 4 2 Touch Screen (AUI) devices are in addition to the 8
Devices addressable keypads. E.g., Symphony, 6270
4219, 4229 Zone Up to 5 for Up to 2 for Zone numbers are predefined according to the device
Expander Modules up to 40 up to 16 addresses used. See Expander Module Addresses table
exp. zones exp. zones in Wiring section and set addresses accordingly.
5800 Series Wireless Up to 40 RF Up to 26 RF Uses 5881/5883 Series Receivers/Transceivers.
zones zones
Output relays and/or Up to 16 Up to 8 Use any combination of 4204, 4229 and or Powerline
Powerline Carrier Carrier Devices.
Devices (X-10 type) Map output devices via *79 Menu mode.
On-Board Triggers 2 2 Can be used to reset 4-wire smoke detectors.
Output functions Up to 48 Up to 24 Program output functions via *80 Menu mode.
4286 Phone Module Partition 1 yes Provides access to the system via on premises or off-
only premises phones for arming, disarming, etc., plus
control of relay outputs and Powerline Carrier devices.
Audio Alarm Using AAV Using AAV Use ADEMCO UVS or Eagle Model 1250 in
Verification module module conjunction with an output trigger to permit voice
dialog between an operator at the central station and
a person at the premises. Alternatively, the AVS
system can be used to provide AAV via phone line or
AlarmNet IP/GSM (using a GSMV module).
Alarm output 12VDC, 2 12VDC, 2 Can drive the compatible sounders; steady output for
AMP output AMP output burglary/panic, or temporal pulse (3 pulses – pause –
3 pulses – pause – 3 pulses. . .) for fire. Uses current
limiting circuitry for protection.
Auxiliary Power Output See note. See note 12VDC, 600 mA maximum; uses fuse for protection.
Backup Battery See note. See note. Rechargeable (sealed lead-acid type) 12VDC, 4AH
minimum.
Long Range Radio See note. See note. Primary telephone number messages can be reported
(Communication Device) via ECP connection to various communication devices
(check compatibility/availability of specific models)
AC Power Supply See note. See note. Plug-in 120VAC transformer, 1321 (1321CN in
Canada) or, if using Powerline Carrier devices,
1361X10 Transformer Module
NOTE: All devices and accessories used in a Canadian installation must be Listed for use in Canada.
1-2
S E C T I O N 2
ADEMCO
ADEMCO
or anchors (not supplied) with the
four cabinet mounting holes.
2. Remove cabinet door, then remove SNAP
cab_lock_snap-001-V0
UNLOCKED TAB
the lock knockout from the door.
Insert the key into the lock. CABINET DOOR
BOTTOM STEP 1 STEP 2
CIRCUIT
BOARD
+ +
CABINET DETAIL B
SIDE VIEW
DETAIL A OF MOUNTING
SIDE VIEW CLIPS
OF BOARD
SUPPORTING
SLOTS
MOUNTING-001-V0
2-1
Installation and Setup Guide
CABINET A B
CABINET
BOARD
RECEIVER CIRCUIT BOARD SUPPORTING
SLOTS
+ +
CIRCUIT
BOARD
MOUNTING
CLIP
CONTROL
CIRCUIT
BOARD
DETAIL A
MOUNTING SIDE VIEW
CLIP OF BOARD -
SUPPORTING SLOTS
SCREW
(2)
GROUNDING
LUG
(2)
NOTE
A COMBINATION OF THESE MOUNTING CLIPS HAS BEEN ANTENNA
INCLUDED IN YOUR INSTALLATION KIT. MOUNT
(2 PLACES)
USE THE APPROPRIATE CLIPS FOR MOUNTING.
pc_mount-001-V1
*
(Current available from Aux. terminals = 600 mA max.)† TOTAL =
*If using hardwire devices such as PIRs, refer to the specifications for that particular unit's current draw.
** Values are for standby/alarm; alarm for keypads means armed with backlighting on and sounder on
†In UL installations, maximum current draw from the Auxiliary Output and the Alarm Output combined must not exceed 600 mA (500 mA max from Aux. Output).
‡Values are for relays OFF/relays ON.
2-2
Mounting and Wiring the Control
AC Power, Battery, and Ground Connections
1321 Transformer Connect the 1321 Transformer (1321CN in Wire Run Chart
Canada) to terminals 1 and 2 on the Distance from control Wire Size
control board. See Wire Run Chart for Up to 50 feet # 20
wire size to use. 50–100 feet # 18
• Use caution when wiring the
100-250 feet # 16
transformer to the control to guard
1
against blowing the transformer fuse
2 (the fuse is non-replaceable).
1321X10-001-V0
TO
TERMINALS
1 AND 2
• Wiring to the AC transformer must not exceed 250 feet using 16 gauge wire. The
voltage reading between terminals 1 and 2 of the control must not fall below 16.5VAC
or an “AC LOSS” message will be displayed.
• Do not plug the transformer into the AC outlet until all wiring connections to the
control are complete. As a safety precaution, always power down the control when
making such connections.
1361X10 Transformer 1. Splice one end of a 3-conductor cable 8-PIN TRIGGER CONNECTOR
1 3 4 5 6 7 8
KEY
(required if using to the wire ends of the SA4120XM-1
Powerline Carrier devices) Cable.
2. Connect the SA4120XM-1 cable plug
(YELLOW)
OUTPUT 18 (GREEN)
(ORANGE)
(PURPLE)
(BLACK)
(BLUE)
(RED)
1361X10 TRANSFORMER
OUTPUT 17
1 2 3 4 5
+12 AUX.
diagram for location of the 8-pin
GND (-)
AC
SYNC
AC
COM
DATA
Sy
Outnc
put Sign
TO
connector).
Com al
mon X1
Dat0
a 8-PIN
CONNECTOR SA412OXM
3. Connect the other end of the CABLE
CONNECT
FLYING LEADS
AFTER AC POWER
IS APPLIED
Battery Saver Feature The battery will disconnect from the system after its voltage decreases below 9VDC.
This assists the control panel in recharging the battery when AC is restored.
IMPORTANT: The panel will not power up initially on battery power only. You must
plug the transformer in first, and then connect the battery.
Earth Ground • This product has been designed and laboratory-tested to ensure its resistance to
damage from generally expected levels of lightning and electrical discharge, and does
not normally require an earth ground.
CONNECT • If an earth ground is desired for additional protection in areas of severe electrical
R D
OL
B OA PROPER
EARTH
activity, terminal 25 on the control board, or the cabinet, may be used as the ground
NTR GROUND
connection point. The following are examples of good earth grounds available at most
CO IF
25
DESIRED installations.
Metal Cold Water Pipe: Use a non-corrosive metal strap (copper is recommended) firmly
secured to the pipe to which the ground lead is electrically connected and secured.
earth_gnd-001-V0
AC Power Outlet Ground: Available from 3-prong, 120VAC power outlets only. To test
the integrity of the ground terminal, use a 3-wire circuit tester with neon lamp
indicators, such as the UL Listed Ideal Model 61-035, or equivalent, available at most
electrical supply stores.
2-3
Installation and Setup Guide
Sounder (Bell) Connections
Basic Connections Make sounder connections to alarm output terminals 3 (+) and 4 (–).
• The 12VDC sounder output activates when an alarm occurs.
3
4 • Total current drawn from this output cannot exceed 2 amps (going beyond 2 amps will
overload the power supply, or may cause the electronic circuit protecting the sounder
output to trip).
• You must install a battery, since the battery supplies this current.
ALARM OUTPUT Supervised output
10.5 - 13.5 VDC
2A MAX. spkr_conn-001-V0 1. Cut the red Bell Supervision Jumper located above terminals 2 and 3 on the PC board.
2. Connect a 2k ohm resistor across the terminals of the last sounder. See Figure 5.
3. Set field ∗91 Option Selection for Bell Supervision.
This control complies with NFPA requirements for temporal pulse sounding of fire notification
appliances. Temporal pulse sounding for a fire alarm consists of: 3 pulses – pause – 3 pulses –
pause – 3 pulses–etc..
UL TERMINALS ON
CONTROL BOARD
EXTERNAL ALARM
SOUNDER
sounder-001-V0
THE EXTERNAL SOUNDER AS SHOWN BY
range, and must be mounted indoors. THE DOTTED LINE.
CUT RED JUMPER ON CONTROL
BOARD TO ENABLE BELL DO NOT CONNECT THE RESISTOR AT THE
(SOUNDER) SUPERVISION. ALARM OUTPUT TERMINALS THEMSELVES!
AR
MED
Use the Table of Device Addresses to determine the appropriate address for each device.
RE
AD
Y
Determine wire size using the Wire Run Chart on the following page. For single 4-wire
runs, determine the current drawn by all units, then refer to the Wiring Run chart to
determine the maximum length that can be safely used for each wire size.
conn-001-V0
IMPORTANT:
The battery-backed power IMPORTANT: Keypads MAKE THESE
supply should have enough powered from supplies that do CONNECTIONS
power to supply the not have a backup battery will DIRECTLY TO
keypads with the UL SCREW
supp_pwr_supply-V0
2-4
Mounting and Wiring the Control
Keypad Notes Set device addresses. Refer to the instructions included with the devices and set each
address according to the Table of Device Addresses.
See Keypad Programming Fields (fields *190-*196) in Section 4. Data Field
AR
RE
ME
D
Programming for details on enabling keypad addresses, assigning keypad partitions
AD
1 OF
F
2
4 MA
AW
AY
X
3
5 STA
ANT
6
8 CO
BYP
ASS
DE
REA
DY
9
0 CH
IME
23. The first keypad is address 16 (default = partition 1, all sounds enabled).
#
2-5
Installation and Setup Guide
Hardwire Zones and Zone Expansion
Hardwire Zones Normally Open Zones/ N.O. EOLR Zones
1. Connect open circuit devices in parallel across the loop; for EOLR zones, connect the
EOLR across the loop wires at the last device.
2. Enable normally open/EOLR zones using Zone Programming mode, “Hardwire Type”
prompt.
Normally Closed Zones/ N.C. EOLR Zones
1. Connect closed circuit devices in series in the high (+) side of the loop; for EOLR
zones, connect the EOLR in series following the last device.
HI
LO
zones-001-V0
2. Enable normally closed/EOLR zones using Zone Programming mode, “Hardwire
Type” prompt.
End of Line Resistor (EOLR) Notes
• If the EOLR is not at the end of the loop, the zone is not properly supervised and the
system may not respond to an “open” on the zone.
• Zone 1 is intended for EOLR only.
zone-002-V0
2k 2k
ZONE 3 ZONE 4
Fig. 7. Typical Double Balanced Zones
Zone Doubling This feature provides two hardwired
(V20P only) normally closed zones for each standard 10 11
zone-004-V0
“Hardwire Type” prompt, option “3”), 6.2k
hardwire zones are automatically paired as Fig. 8. Typical Zone Doubling Wiring
shown in the table. Connect as shown
Zone Doubling Table
(resistors provided). Zone Paired with zone
• Do not use zone doubling for fire 2 10
zones. 3 11
4 12
NOTE: A short across the EOL (i.e., at 5 13
terminal) on either zone of a zone-doubled 6 14
pair or on a double-balanced zone causes a 7 15
tamper condition (displayed as CHECK plus 8 16
zone numbers). NOTE: Zone numbers used for zone doubling
cannot be used for anything else (ex. cannot
be used for 4219 zones)
Smoke Detectors 1. Connect up to 16 (10, if “clean me” option used) 2-wire smoke detectors across zone 1
terminals 8 (+) and 9 (-) as shown in the Summary of Connections diagram at the
TO ZONE 1 back this manual. Observe proper polarity when connecting the detectors.
TERMINALS
2. Connect an EOL resistor across the loop wires at the last detector.
3. Connect 4-wire smoke detectors (up to 16, depending on detector current draw) to
any zone from 2-8 as shown in Figure 7 (on next page).
8
2-WIRE
SMOKE 9
Power Reset: This control does not automatically reset power to 4-wire smoke
DETECTOR
detector zones, so you must use a relay (e.g., 4204, 4229), or on-board trigger to reset
5806-001-V0
HI
LO
ZONE 1 power (also required for fire verification). Do this by programming the designated
relay/trigger as zone type 54 (fire zone reset); see On-Board Trigger section for
other information.
NOTE: Maximum current on trigger 17 is 100mA.
2-6
Mounting and Wiring the Control
Smoke Detector Notes • Fire Verification (zone type 16): The control panel will “verify” a fire alarm by
resetting the smoke detectors after the first alarm trigger, and then waiting up to 90
seconds for a second alarm trigger. If the smoke detector or thermostat does not trigger
again, the control will disregard the first trigger, and no alarm signal will occur. This
feature eliminates false alarms due to electrical or physical transients.
SIA Installations: If using fire verification on zones other than zone 1, UL Fire Alarm
Listed relay accessories must be used to reset power as described in the Power Reset
paragraph above.
• The zone 1 alarm current supports only one smoke detector in the alarmed state.
• Clean Me Option: If enabled (field *174 = 1; *56 zone programming, response time
prompt = 3), certain ESL smoke detectors send “clean me” reports as appropriate. If
used, the maximum number of detectors is reduced to 10 (not standard 16). Refer to the
ESL documentation included with the smoke detector for information regarding
compatibility with the clean-me option.
• Do not use 4-wire smoke detectors on zone 1.
+ 5
RELAY
PROGRAM BLK _ + RED
AUX PWR RELAY
OUTPUT AS ZONE EOL
TERMINALS TYPE 54 POWER
(FIRE ZONE
RESET) N.O. SUPERVISION
_ 4 RELAY MODULE
N.C. A77-716B.
CONTACT OPENS USE N.O.
MOMENTARILY UPON CONTACT,
+ _ VIOLET WHICH CLOSES
FIRE ALARM RESET
WHEN POWER
4-WIRE SMOKE
OR COMBUSTION IS APPLIED.
DETECTOR
2000
OHMS
EOLR
4_wiresmk-007-V0
TO ZONE TERM. (+)
HEAT
DETECTOR
TO ZONE TERM. (_)
Figure 9a. 4-Wire Smoke Detector Using Relay for Power Reset
4_wiresmk-008-V0
TO ZONE TERM. (+)
HEAT
DETECTOR
TO ZONE TERM. (_)
Figure 9b. 4-Wire Smoke Detector Using Output 17 for Power Reset
4219/4229 Expansion 1. Connect each module to the control’s keypad terminals and set the device addresses.
Zones See the Table of Device Addresses to select an appropriate address for each module.
• VISTA-20P: Up to 40 expansion zones using up to 5 Zone Exp. Modules.
• VISTA-15P: Up to 16 expansion zones using up to 2 Zone Exp. Modules.
2. Connect sensors to the module’s loops. See Figure 8 on the following page.
• Use 1000 ohm end-of-line resistors at the end of loops connected to the 4219/4229
modules. (EOLRs used on the control terminals are 2000 ohms.)
• Expansion zones have normal response time (300–500 msec), except zone connected
to each module’s loop “A,” which can be set for fast response (10–15 msec).
3. If using relays with the 4229, connect the desired field wiring to the unit's relay contact
➞
terminals.
➞
2-7
Installation and Setup Guide
ORG
BRN
GRY
3
WHT
YEL
VIO
BLK
4229 REMOTE RED
(TAMPER PROTECTED) 2 2 (+) 12VDC (TERM 5)
TB1
YEL DATA IN (<)
GND
1 1 FROM (TERM 7)
NO
NO
NC
NC
C 1 2 3 4 5 6 7 8 9 10 11 12 CONTROL
C
TERMINATE EACH
RLY RLY PROGRAMMED ZONE
2 1 REED WITH 1000 OHM (1K)
(TAMPER) END-OF-LINE RESISTOR
RELAYS OFF SWITCH (EACH ZONE'S MAX.
LOOP RESISTANCE
300 OHMS + EOL)
ZONES A B C D E F G H 4229-002-V0
YELLOW
TO CONTROL'S
WIRELESS ZONE MODEL NO. IS INDICATED ON CIRCUIT BOARD
RED
BLACK
REMOTE KEYPAD
CONNECTION
NUMBERS 5882 DIP
GREEN POINTS.
LOCATION SWITCH
MOUNTING
VISTA-20P: HOLES INTERFERENCE
INDICATOR
WIRING OPENING
VISTA-15P:
transmitter zones 9-34
button zones 49-56 SOCKET PLUG
TO RELEASE CIRCUIT BOARD,
REMOVE SCREWS AND
BEND BACK TABS 5881-003-V0
2-8
Mounting and Wiring the Control
Installing a 5800TM • Use this module only if you are using one or more wireless bi-directional keypads or
Module keyfobs with a wireless Receiver; 5800TM is not necessary if using a Transceiver (e.g.,
5883).
• The 5800TM must be set to address 28 (cut red-W1 jumper).
• The 5800TM can be used in partition 1 only.
• For additional information regarding the 5800TM, refer to the 5800TM’s instructions.
1. Mount the 5800TM next to the RF receiver (between one and two feet from the
receiver’s antennas) using its accompanying mounting bracket. Do not install within
the control cabinet.
2. Connect the 5800TM to the control panel’s keypad connection terminals as shown on
the Summary of Connections diagram and set to address 28.
Installing the • Refer to the table of compatible devices at the back of this manual.
Transmitters • Supervised transmitters† send check-in signals to the receiver at 70-90 minute
intervals. If at least one check-in message is not received from each transmitter within
a 12-hour period, the “missing” transmitter number(s) and “CHECK” is displayed. (†
Hand-held transmitters, e.g., 5802, 5802CP, 5804, 5804BD, 5827, 5827BD, do not send
check-in signals.)
• To be sure reception of the transmitter's signal at the proposed mounting location is
adequate, perform a Go/No Go Test, described in the Testing the System section.
• Install transmitters in accordance with the instructions provided with each.
• Set 5827, 5827BD, 5804BD wireless keypads to the programmed House ID (field *24),
using its DIP switches (5827) or follow the instructions provided with the device.
• Use *56 or *58 Zone Programming Menu modes to program zone information and enroll
transmitters (VISTA-20P: zones 9-48, buttons 49-64; VISTA-15P: zones 9-34, buttons
49-56).
• Wireless Keys: Use Wireless Key Programming Templates section of the *58 Zone
Programming Menu mode to program zone information and enroll each button of the
wireless keys used. Once a wireless key is enrolled, it must be assigned to a user before
it becomes active. See Adding/Deleting Security Codes section for procedure.
ULC NOTE: In accordance with ULC standards, the RF supervision period for the VISTA-20PCN
and VISTA-15PCN is three hours for Fire zones (Zone Type 9 and 16) and 12 hours for all other zone
types.
UL The following transmitters are not intended for use in UL installations: 5802MN, 5802MN2, 5804,
5804BD, 5814, 5816TEMP, 5819, 5819WHS & BRS, and 5850.
The 5827BD and 5800TM can be used in UL Listed Residential Burglar installations.
Transmitter Battery Life • See Wireless Transmitter paragraph in the Limitations of This Alarm System
statement located at the end of this manual for information on transmitter battery
life.
• Some transmitters (e.g., 5802 and 5802CP) contain long-life but non-replaceable
batteries, and no battery installation is required. At the end of their life, the complete
unit must be replaced (and a new serial number enrolled by the control).
• Button-type transmitters (such as 5801, 5802, and 5802CP) should be periodically
tested for battery life.
• The 5802MN and 5804 Button Transmitters have replaceable batteries.
Do not install batteries in wireless transmitters until you are ready to enroll during
system programming. After enrolling, batteries need not be removed.
2-9
Installation and Setup Guide
Installing a Keyswitch
Keyswitch Connections 1. Connect the 4146 keyswitch's normally open momentary switch to a zone’s (2-8)
terminals. Remove the 2000 ohm EOL resistor if connected across the selected zone.
2. Using a standard keypad cable as shown:
Connect the yellow and white keyswitch wires to trigger connector pin 3 (+12V).
Connect the Red and Green LED wires to the appropriate output 17/output 18
trigger connector pins.
3. Connect a 2000 ohm EOL resistor across the momentary switch.
4. You can wire an optional closed-circuit tamper switch (model 112) in series with the
zone. If the switchplate is then removed from the wall, the tamper will open,
disabling keyswitch operation until the system is next disarmed from the keypad.
If the tamper is opened when the system is armed, an alarm will occur.
8-PIN TRIGGER CONNECTOR
1 3 4 5 6 7 8
KEY
(GREEN)
OUTPUT 17 (YELLOW)
(RED)
OUTPUT 18
+12 AUX.
STANDARD
4146 KEYSWITCH
KEYPAD
CABLE (ARMED)
RED
YELLOW
(READY)
GREEN
WHITE
820 820
ohms ohms
BLACK
RED
TAMPER
SWITCH (N. C.)
BROWN BROWN
11
TYPICAL ZONE
ON CONTROL LOCK
BOARD SWITCH (N. O.)
BLUE BLUE
10
00-trigcon-004-V1
EOLR
(use appropriate value)
2-10
Mounting and Wiring the Control
10 11 12
4 NC
DIP SWITCH TYPICAL
FOR SETTING DEVICE ADDRESS (SHOWN "OFF") NO
AND ENABLING/DISABLING TAMPER C
9
RELAY
UL 3 NC
8
COVER TAMPER (REED) SWITCH
For UL installation
7
NO
C
6
4-PIN TOUCHPAD PLUG RELAY
requirements, refer to the
2 NC
5
Installation Instructions for EITHER OR BOTH NO
4
the 4204. CAN BE USED
C
3
RELAY
TB1
1
2
NC
1
13 14 15 16 NO
(GREEN)
(BLUE)
(BLACK)
(RED)
(YELLOW)
(PURPLE)
(ORANGE)
X-10 PSC04
POWERLINE INTERFACE
OUTPUT 18
OUTPUT 17
+12 AUX.
GND (-)
SYNC
COM
DATA
1234
SA4120XM-1 CABLE
SYNC
BLK
MODULAR PHONE CORD (not supplied)
1 - BLACK
GRN
2 - RED
COM
3 - GREEN
4 - YELLOW
RED
DATA
YEL
2-11
Installation and Setup Guide
On-Board Triggers Connect field wiring to the desired trigger pin on the 8-pin trigger connector centrally
located above the terminal strip.
• If using 1361X10 transformer and powerline carrier devices, use the SA4120XM-1
cable (part of 4120TR Trigger Cable). See Wiring the AC Transformer section for
transformer connections.
• If only using the on-board triggers, you can use a 4-wire cable (N4632-4, supplied
with the control) as shown below.
8-PIN TRIGGER CONNECTOR
8-PIN TRIGGER CONNECTOR
1 3 4 5 6 7 8
KEY
1 3 4 5 6 7 8
KEY
(GREEN)
OUTPUT 17 (YELLOW)
(RED)
(BLACK)
(GREEN)
(BLACK)
(YELLOW)
(PURPLE)
(BLUE)
(ORANGE)
(RED)
OUTPUT 18
OUTPUT 18
OUTPUT 17
+12 AUX.
+12 AUX.
GND (-)
GND (-)
SYNC
COM
DATA
4-WIRE
SA412OXM-1
CABLE
CABLE
00-trigcon-003-V1 00-trigcon-005-V2
Figure 15a. On-Board Trigger Connector Figure 15b. On-Board Trigger Connector
with SA4120XM-1 Cable for Use With with 4-Wire Cable for Trigger Use Only
1361X10 Transformer
• Trigger outputs are normally high, and go low upon programmed condition.
• The outputs can be programmed for inverted operation (normally low, go high) using
*79 Menu mode.
• Program these triggers using *80/*81 Menu modes as you would for any other relay
output.
• When using these outputs, note:
pin 1 = output number 17 (trigger 1):
15 ohms to ground when closed (output low), open when off (output high, normal
default); can be used to reset smoke detector power (must set “output normal low
= yes” in *79 Menu mode, and set for zone type 54, fire zone reset, in *80 Menu
mode); or can support 12V relay module (e.g., Altronix AX-RBS) that draws less
than 100mA
pin 5 = output number 18 (trigger 2):
100 ohms to ground when closed (output low); open when off (output high,
normal default); or can support 12V relay module that draws less than 20mA
UL If on-board triggers are used, the wiring between the control unit and the UL Listed device must
be run in conduit, be no more than 3 feet apart and have no intervening barriers or walls.
2-12
Mounting and Wiring the Control
{
{
software version WA4286-
TERMINALS
15.1 or higher (refer to the ON CONTROL
21 22 23 24 25 TO EARTH GROUND (COLD WATER PIPE, ETC.)
label on the square 4286 INCOMING TELCO LINE
CALLER ID
GREEN (TIP)
RED (RING)
microprocessor chip).
RING
TIP
UNIT DIRECT
CONNECT
(RING)
CORD
(TIP)
IMPORTANT NOTE FOR TIP
EXISTING INSTALLATIONS: RJ31X
RING
JACK
UL The 4286 modules
EXISTING WIRES
CONNECTED TO THE
"HANDSET" TERMINALS ON CA38A PREMISES ANSWERING
IN
are UL Listed only for use CONTROL MUST BE MOVED PLUG
CANADA
MACHINE AND PHONES
FROM THERE TO TERMINALS
on residential fire and UL 3 AND 4 ON THE 4286.
ANSWERING
residential burglar alarm
BROWN (T)
MACHINE
GREY (R)
installations.
4286 VIP MODULE
12345 6 7
LOUDER
*
VOLUME
KEYED
HEADER * NOTE: IF THE TELEPHONE HAS BUILT-IN CALLER ID,
THE CALLER ID FUNCTION MAY NOT WORK .
UNUSED
4286 TERMINAL ASSIGNMENTS
YELLOW: TO DATA OUT (term. 7) TO CONTROL
1 - TIP
CONNECTOR
NO CONNECTION
RED: TO AUX (+) (term. 5)
PANEL
TERMINALS
}
2 - RING
PHONE INPUT
3 - TIP
}
4286_cntrl-001-V1
WITH FLYING BLACK: TO AUX. GROUND (–) (term.4) USED FOR PHONE OUTPUT
GREEN: TO DATA IN (term. 6) 4 - RING
LEADS KEYPAD
5 - NO CONNECTION
CONNECTIONS
6-
7- } AUDIO OUT
2-13
Installation and Setup Guide
Audio Alarm Verification Using the UVS System with UVCM Module
Connections The UVS system provides audio alarm verification via the phone line.
(UVS System) • Refer to the connection diagrams below. One diagram shows connections when a 4286
Phone Module is used, the other shows connections when the 4286 is not used.
• Connections use one of the on-board triggers.
• Set field *91 for AAV and program the appropriate output (output 17 or 18) using *80
Menu mode: select zone type 60 and output action 1 (close for 2 seconds).
• For voice session monitoring, connect an EOLR zone to UVCM module terminals 6 & 7,
and program the zone as zone type 81 (*56 Menu mode).
E.g., Using output 18 for the trigger, program an output function in *80 Menu mode as:
ZT = 60, P = 0, Action = 1, Device = 18
• Suggested AAV Module: ADEMCO UVS (shown) or Eagle 1250
UL UL installations using the AAV feature must use the ADEMCO UVCM module (part of the
ADEMCO UVS system).
TRIGGER
5 CONNECTOR
OUTPUT 18
EARTH
ZONE GROUND
CONTROL TERMINALS
AUXILIARY 4 5 21 22 23 24 25
AUDIO LEVEL
ADJUSTMENT GND
TRIM POT
+12VDC
EOL
UVCM RING
29 30 31 32 33 34
MODULE TIP
RED (R)
GREEN (T)
OPTIONAL
SPEAKERS AND MICROPHONE.
MONITORING ZONE
1 2 3 4 5 6 7 8
SWITCH BANK 2
CONNECTION
(USE ZONE TYPE 81)
9
SWITCH SWITCH TO
8
1 = ON
ON
1 = OFF
2 = OFF 2 = ON INCOMING
6
4 = OFF 4 = ON
SWITCH BANK 1
1 2 3 4 5 6 7 8
5 = OFF 5 = ON
4
6 = OFF 6 = ON
7 = ON
3
7 = OFF
8 = ON 8 = ON
2
GND
aav_uvcm-003-V0
ON
+12VDC IN
1
Figure 17a. Connection of AAV Unit When Not Using a 4286 Phone Module
TRIGGER
5 CONNECTOR
OUTPUT 18
EARTH
ZONE GROUND
CONTROL TERMINALS
AUXILIARY 4 5 21 22 23 24 25
AUDIO LEVEL
ADJUSTMENT
GND
+12VDC
TRIM POT
EOL
UVCM RING
29 30 31 32 33 34
RING
MODULE TIP
TIP
RED (R)
GREEN (T)
SWITCH SWITCH TO
8
1 = OFF 1 = ON
2 = OFF 2 = ON
6
INCOMING
3 = OFF 3 = OFF PHONE LINE
FALLING VOICE TRIG
5
4 = OFF 4 = ON
1 2 3 4 5 6 7 8
SWITCH BANK 1
4286
5 = OFF 5 = ON
4
6 = OFF 6 = ON
7 = ON 4
3
7 = OFF
8 = ON 8 = ON
3
2
GND
aav_uvcm-004-V1
ON
+12VDC IN
1
Figure 17b. Connection of AAV Unit When Using a 4286 Phone Module
2-14
Mounting and Wiring the Control
Audio Alarm Verification Using the AVS System with AVS Module and AVST Remote Stations
Connections The AVS system provides audio alarm verification via the phone line or via AlarmNet if
(AVS System) the GSMV module is used as the communication device.
Refer to the instructions included with the AVS system for installation procedures. The
following is a summary.
Mounting the AVS Base Unit
As shipped, the AVS Base unit board
comes pre-mounted on its mounting
bracket, which is designed to mount
inside the control cabinet. SECURE
WITH TWO (2)
Refer to the diagram at right. SELF-TAP SCREWS
(SUPPLIED)
a. Position the mounting plate/PC
board assembly in the bottom of
the control’s cabinet. CABINET
SYSTEM TIE-WRAP
b. Slide the mounting plate to the BATTERY LOOP
ON 4 5
2 3
1
3 4
1 2
provided.
BATTERY NOTE: When using a 7AH battery, mount the battery vertically on the
bottom left-hand side of the cabinet, with the terminals facing down and right (negative
terminal closest to the PC board bracket).
Wiring the AVS to the Control
The AVS Base unit board has several terminal blocks for making connections to remote
stations, telephone lines, and to the control panel. The AVS base unit connects to the
control’s ECP terminals, with all other ECP devices connecting to the AVS base unit ECP
terminals. See the diagram on the next page for specific wiring connections.
IMPORTANT: The AVS should be the only ECP device connected to the control’s
ECP terminals. Connect all other ECP devices (keypads, expander modules, etc.) to
the ECP terminals on the AVS board.
Connecting an Optional GSMV Module
a. If using a GSMV module for 2-way voice operation, install the module according to its
instructions. NOTE: The module must be mounted within three feet of the control.
b. Connect the audio cable from the GSMV module to the Audio connector on the AVS
board. The audio cable is supplied with the GSMV module.
c. Complete all other GSMV wiring following the instructions included with that
module.
The following summarizes the programming steps for AVS operation (refer to the
Programming Guide for details of the AVS Quick Command options):
a. Install the AVS module according to its instructions.
b. Use one of the control’s AVS Quick Program commands as follows :
• installer code + [#] + 03: enable AVS operation without panel sounds on the AVST
• installer code + [#] + 04: enable AVS operation and enable panel sounds on the
AVST speaker
c. Use data field ∗55 Dynamic Signaling Priority to select the desired reporting paths.
2-15
Installation and Setup Guide
TIP
4
5
6
3
RING
TIP RJ31X
7
2
RING INCOMING
8
TELCO
PREMISES
PHONES
DIRECT
CONNECT
CORD
GRN
BRN
RED
GRY
TRIGGER HEADER
1 2 3 4 5 6 7 8
(EARTH GND
INCOMING
HANDSET PHONE LINE
ECP TERMINALS
(RING)
(RING)
(TIP)
(TIP)
DATA DATA
GND AUX IN OUT
AVST STATION
IMPORTANT:
GRN
SPEAKERS
RED
BLK
YEL
LED DO NOT CONNECT ANY OTHER
ECP DEVICES TO PANEL.
VOLUME / ID
USE AVS BASE UNIT ECP
BUTTON TERMINALS FOR OTHER ECP DEVICES.
SUPPLIED HARNESS
AAV
DATA
YEL
AUDIO
GRN
GND
KEYPAD BLK
RED +VDC
MIC
AUDIO CABLE
TB 1
1
Honeywell
2
RSSI
MODE 1
MODE 2
WEB
GPPS
GSM
3
4
5
6
7
8
9
10
11
AVS BASE UNIT
(200 FT. MAX)
LED
GSMV
(OPTIONAL)
PROGRAM MODE PHONE
CALLBACK MODE DIP SW GRY
RING
ON ON DEVICE ADDRESS HANDSET
(ADDRESS 8 BRN
1 2 3 4 1 2 3 4 5
TIP
SHOWN)
PANEL TRIGGER
MODE TIP
NOT INCOMING
NORMAL MODE USED PHONE LINE
RING
BASE UNIT AUDIO CONNECTOR
DEVICE ADDRESS
AAV PANEL ECP
VISTA-15P = 8 RED BLK GRN YEL RED BLK GRN YEL RED BLK GRN YEL
ON
1 2 3 4 5
BATTERY
TO ALL
VISTA-20P = 11 OTHER ECP
DEVICES
ON
1 2 3 4 5
AVS-001-V0
2-16
S E C T I O N 3
3-1
Installation and Setup Guide
The following table lists codes for reports sent in different formats:
Code for Code for
Type of 3+1/4+1 3+1/4+1 Code for
Report Standard Expanded 4+2
Alarm SSS(S) A SSS(S) A SSSS AZ
AAA(A) Z
Trouble SSS(S) T SSS(S) T SSSS Tt
TTT(T) t
Bypass SSS(S) B SSS(S) B SSSS Bb
BBB(B) b
AC Loss SSS(S) E SSS(S) E SSSS EAC
EEE(E) AC
Low Batt SSS(S) L SSS(S) L SSSS LLB
LLL(L) LB
Open SSS(S) O SSS(S) O SSSS OU
OOO(O) U
Close SSS(S) C SSS(S) C SSSS CU
CCC(C) U
Test SSS(S) G SSS(S) G SSSS Gg
GGG(G)g
Restore SSS(S) R SSS(S) R SSSS RZ
Alarm RRR(R) Z
AC Restore SSS(S) RA SSS(S) RA SSSSRA Ac
RARARA(RA)Ac
LoBat Res. SSS(S) RL SSS(S) RL SSSS RLLB
RLRLRL(RL)LB
Trouble Res. SSS(S) RT SSS(S) RT SSSS RTt
RTRTRT (RT)t
Bypass Res. SSS(S) RB SSS(S) RB SSSS RBb
RBRBRB (RB)b
Where:
SSS or SSSS = Subscriber ID C= Close Code–1st Digit
A= Alarm Code–1st digit U= User Number (in hex)
Z= Typically Zone Number*–2nd digit Gg = Test Code (1st & 2nd digits)
Tt = Trouble Code (1st & 2nd digits) R= Restore Code (Alarm)
Bb = Bypass Code (1st & 2nd digits) RTt = Restore Code (Trbl) 1st & 2nd digits
EAC = AC Loss Code (1st & 2nd digits) RBb = Restore Code (Byps) 1st & 2nd digits
LLB = Low Battery Code (1st & 2nd digits) RAAC = Restore Code (AC) 1st & 2nd digits
O = Open Code–1st Digit RLLB = Restore Code (Bat) 1st & 2nd digits
*Zone numbers for: ✱ & #, or B = 99; 1 + ✱, or A = 95; 3 + #, or C = 96; Duress = 92
3-2
System Communication
3-3
Installation and Setup Guide
3-4
System Operation
Refer to the user guide for detailed procedures on adding/deleting security codes and changing user
attributes.
The following is a brief description of how to add user codes.
Changing the System Master code...
Using Installer code: Installer code + [8] + 02 + new code
Using current System Master code: System Master code + [8] + 02 + new code + new code again
Adding a User Code: Master code + [8] + 2-digit user no. + user’s code
Deleting a User Code: Master code + [8] + 2-digit user no. + [#] [0]
Assigning Attributes: Master code + [8] + 2-digit user no. + [#] [attribute no.] + value
Attributes: Values
1 = Authority Level 0-4 (see Authority Level table above)
2 = Access Group 0-8 (0 = not assigned to a group)
3 = Active Partition(s) 1, 2, 3 (common)
for this user; Enter partitions consecutively if more than one and press [#] to
end the entries.
4 = RF Zone No. Assigns user number to button type zone for arm/disarm
(keyfob must be enrolled in system first; see Wireless Key
Templates section).
5 = Open/Close Paging 1 for yes, 0 for no
3-5
Installation and Setup Guide
Keypad Functions
The following is a brief list of system commands. For detailed information concerning system functions,
refer to the User's Manual. For Touch Screen style keypad users, refer to the separate Touch Screen
keypad (AUI) User’s Guide.
Voice Keypads
The 6150V/6160V Voice Keypads provide the following features:
• Message Center, which lets the user record and playback one message.
• Voice Status, which can announce system status by using the STATUS key.
• Voice Chime, which can alert users to the opening of doors/windows while the system is disarmed.
Refer to the User Guide for specific procedures for activating and using these features.
Keypad Commands
Function Description
Silence Burglary Pressing any key will silence the keypad sounder for 10 seconds. Disarming the system
Alarms (security code + OFF) silences both keypad and external sounders.
Silence Fire or Carbon Press the OFF [1] key to silence the keypad sounder and, for fire alarms, the external
Monoxide Alarms sounder. The detector sounding stops when the contaminated air is cleared from the
detector; see the detector’s instructions for further information.
Quick Arm If enabled (field ∗21), you can press [#] in place of the system's security code, plus the
desired arming key (Away, Stay, Instant, Maximum)
Single-Button arming If programmed (*57 Function Key menu mode), lettered keys A-D can be used for arming,
using options 3-AWAY, 4-STAY, 5-NIGHT-STAY, or 6-Step-Arming
If used, no security code is required to arm the system.
Alarm Memory When the system is disarmed, any zones that were in an alarm condition during the armed
period will be displayed. To clear this display, simply repeat the disarm sequence (enter
the security code and press the OFF key) again.
Arming Away Enter code + AWAY [2] or simply press appropriate lettered key on the keypads (see
“Single-Button Arming” above). If the “Auto-Stay Arm” feature is enabled (field *84) and
the entry/exit door is not opened and closed within the programmed exit delay time, the
system will automatically arm in STAY mode if armed from a wired keypad (non-RF
device). If the door is opened and closed within the exit delay period, the system arms in
AWAY mode.
Arming Stay Enter code + STAY [3] or simply press appropriate key on the keypads (see “Single-Button
Arming” above). See “Arming Away” above for Auto-Stay arming feature.
Arming Night-Stay Enter code + STAY [3] + STAY [3] or simply press appropriate key on the keypads (see
“Single-Button Arming” above).
Arming Instant Enter code + INSTANT [7].
Arming Maximum Enter code + MAXIMUM [4] or simply press appropriate lettered key on the keypads (see
“Single-Button Arming” above).
Disarming Enter code + OFF [1]. If entry delay or an alarm is active, you do not need to press OFF.
Bypassing Zones Enter code + BYPASS [6] + zone number(s).
Forced (Quick) Bypass To automatically bypass all faulted zones, use the “Quick Bypass” method. Enter code +
BYPASS + [#], then wait for all open zones to be displayed. Arm when display indicates
“ZONE BYPASSED” and “READY TO ARM”.
Chime Mode Enter code + CHIME [9]. To turn chime off, enter code + CHIME again.
Activate Output If relay outputs (via a 4204, or 4229), or Powerline Carrier devices are used, two keypad
Devices entries available to the user are included. If programmed, these entries can be used to
manually activate or deactivate the device(s) for starting or stopping some action, such as
turning lights on or off, etc. These keypad entries are:
[Security Code] + # + 7 + [2-digit Device #] activates (starts) that device.
[Security Code] + # + 8 + [2-digit Device #] deactivates (stops) that device.
3-6
System Operation
SUMMARY OF ARMING MODES
Arming Mode Features for Each Arming Mode
Exit Delay Entry Delay Perimeter Armed Interior Armed
AWAY Yes Yes Yes Yes
STAY Yes Yes Yes No
NIGHT-STAY Yes Yes Yes only those zones
listed in Night-
Stay zone list
INSTANT Yes No Yes No
MAXIMUM Yes No Yes Yes
Panic Keys
There are three Panic keys (A, B, and C) that, if programmed, can be used to manually initiate alarms and
send a report to the central station.
Each key can be programmed for 24-hour Silent, 24-hour Audible, Fire, or Personal Emergency responses.
The programmed Panic response is activated when the appropriate key is pressed for at least 2 seconds.
The Panic keys are identified by the system as follows:
Keys Displayed as Zone
∗/1)
[A] (∗ 95
∗/#)
[B] (∗ 99
[C] (3/#) 96
IMPORTANT: For a Silent panic function (if programmed) to be of practical value, you must program a
report code for the zone and the system must be connected to a central station.
3-7
Installation and Setup Guide
3-8
S E C T I O N 4
System Test
NOTE: Test mode can be entered from any keypad. However, faulted zones appear only on those keypads
assigned to the partition to which the zone is assigned (i.e., partition 1 zones appear only on partition 1
keypads, etc.). To see another partition’s faulted zones, view a keypad assigned to that partition or use the
GOTO command (code +[∗] + partition number 0-3, where 0 is the keypad’s home partition).
With the system in the disarmed state, check that all zones are intact (not faulted). Doors and windows
with contacts should be closed, PIRs should be covered (use a cloth to mask them temporarily if necessary).
If a “NOT READY” message is displayed, press [∗] to display the faulted zone(s). Restore faulted zone(s) if
necessary, so that the “READY” message is displayed.
1. Enter Installer Code + 5 [TEST] , then press “0” at the prompt to start Walk Test mode.
1=DIAL, 0=WALK (no special display on Fixed-Word keypads)
The following will be displayed on the initiating keypad and a Contact ID report will be sent (code 607):
TEST IN PROGRESS (“dd” displayed on Fixed-Word Display Keypads)
2. Upon entering the system test mode, the outside sounder should sound for 1 second.
If the backup battery is discharged or missing, the sounder may not turn on and a “LOW BATTERY”
report will be transmitted with a “TEST” report.
The keypad will beep about every 30 seconds as a reminder that the system is in the Test mode.
NOTE: Wireless motion detectors (Passive Infrared units) will send signals out only if they have been
inactive for 3 minutes (conserves battery life).
3. Test all sensors using the procedure described in the User’s Guide “Testing the System” section.
4. After checking sensors, turn off the test mode by entering installer code + OFF.
NOTE: Test mode automatically ends after 4 hours. During the final 5 minutes (after 3 hours 55
minutes of Test mode), the keypad emits a double-beep every 30 seconds to alert that the end of Test
mode is nearing.
4-1
Installation and Setup Guide
NOTES: • All BR type units must physically be activated to clear the display.
• When one button of a transmitter (RF, UR, or BR) is activated, all zones assigned to other
buttons on that transmitter are cleared from the display. This also applies to 5816 and
5817 transmitters, which have multiple loops (zones).
• Any transmitter that is not “enrolled” will not turn off its zone number.
4-2
S E C T I O N 5
Compatible Devices
Keypads: 6150 Fixed-Word Keypad, 6160 Alpha Keypad, 6150V and
6160V Voice Keypads, 6270 Touch Screen Keypad,
Symphony Advanced User Interface
Wireless Receivers: 5881L/5882L: accepts up to 8 transmitters
5881M/5882M: accepts up to 16 transmitters
5881H/5882H: accepts up to system maximum transmitters
5800TM Transmitter Module (used with Wireless 2-Way Keypads)
5883 Transceiver: accepts up to system maximum transmitters
6150RF Keypad/Transceiver: accepts up to system max. transmitters
Zone Expansion: 4219 WIRED EXPANSION MODULE
4229 WIRED EXPANSION/RELAY MODULE
Relay Module: 4204 RELAY MODULE
Phone Modules: 4286VIP PHONE MODULE
Long Range Radio 7845GSM, 7845i-GSM
(Communication Device)
5-1
Installation and Setup Guide
5-2
S E C T I O N 6
TELEPHONE/MODEM INTERFACE
FCC Part 68
This equipment complies with Part 68 of the FCC rules. On the front cover of this equipment is a label that contains the FCC registration
number and Ringer Equivalence Number (REN). You must provide this information to the telephone company when requested.
This equipment uses the following USOC jack: RJ31X
This equipment may not be used on telephone-company-provided coin service. Connection to party lines is subject to state tariffs. This
equipment is hearing-aid compatible.
Industry Canada
NOTICE: The Industry Canada Label identifies certified equipment. This certification means that the equipment meets telecommunications
network protective, operational and safety requirements as prescribed in the appropriate Terminal Equipment Technical Requirements
document(s). The Department does not guarantee the equipment will operate to the user’s satisfaction.
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications
company. The equipment must also be installed using an acceptable method of connection. The customer should be aware that compliance with
the above conditions may not prevent degradation of service in some situations.
Repairs to certified equipment should be coordinated by a representative designated by the supplier. Any repairs or alterations made by the
user to this equipment, or equipment malfunctions, may give the telecommunications company to request the user to disconnect the equipment.
Users should ensure for their own protection that the electrical ground connections of the power utility, telephone lines and internal metallic
water pipe system, if present, are connected together, This precaution may be particularly important in rural areas.
Caution: Users should not attempt to make such connections themselves but should contact appropriate electric inspection authority, or
electrician, as appropriate.
Ringer Equivalence Number Notice:
The Ringer Equivalence Number (REN) assigned to each terminal device provides an indication of the maximum number of terminals
allowed to be connected to a telephone interface. The termination on an interface may consist of any combination of devices subject only to the
requirement that the sum of the Ringer Equivalence Numbers of all the devices does not exceed 5.
Industrie Canada
AVIS: l’étiquette d’Industrie Canada identifie le matériel homologué. Cette étiquette certifie que le matériel est conforme aux normes de
protection, d’exploitation et de sécurité des réseaux de télécommunications, comme le prescrivent les documents concernant les exigences
techniques relatives au matériel terminal. Le Ministère n’assure toutefois pas que le matériel fonctionnera à la satisfaction de l’utilisateur.
Avant d’installer ce matériel, l’utilisateur doit s’assurer qu’il est permis de le raccorder aux installations de l’enterprise locale de
télécommunication. Le matériel doit également être installé en suivant une méthode acceptée da raccordement. L’abonné ne doit pas oublier
qu’il est possible que la conformité aux conditions énoncées ci-dessus n’empêche pas la dégradation du service dans certaines situations.
Les réparations de matériel nomologué doivent être coordonnées par un représentant désigné par le fournisseur. L’entreprise de
télécommunications peut demander à l’utilisateur da débrancher un appareil à la suite de réparations ou de modifications effectuées par
l’utilisateur ou à cause de mauvais fonctionnement.
Pour sa propre protection, l’utilisateur doit s’assurer que tous les fils de mise à la terre de la source d’energie électrique, de lignes téléphoniques
et des canalisations d’eau métalliques, s’il y en a, sont raccordés ensemble. Cette précaution est particulièrement importante dans les régions
rurales.
Avertissement : L’utilisateur ne doit pas tenter de faire ces raccordements lui-même; il doit avoir racours à un service d’inspection des
installations électriques, ou à un électricien, selon le cas.
AVIS : L’indice d’équivalence de la sonnerie (IES) assigné à chaque dispositif terminal indique le nombre maximal de terminaux qui
peuvent être raccordés à une interface. La terminaison d’une interface téléphonique peut consister en une combinaison de quelques dispositifs,
à la seule condition que la somme d’indices d’équivalence de la sonnerie de tous les dispositifs n’excède pas 5.
6-1
Installation and Setup Guide
UL NOTICES
1. Entry Delay No. 1 and No. 2 (fields ∗35, ∗36) cannot be greater than 30 seconds for UL Residential
Burglar Alarm installations, and entry delay plus dial delay should not exceed 1 minute. For UL
Commercial Burglar Alarm installations, total entry delay may not exceed 45 seconds.
2. For UL Commercial Burglar Alarm and UL Residential Burglar Alarm installations with line
security, total exit delay time must not exceed 60 seconds.
3. The maximum number of reports per armed period (field ∗93) must be set to “0” (unlimited) for UL
installations.
4. Periodic testing (see scheduling mode) must be at least every 24 hours.
5. Alarm Sounder plus Auxiliary Power currents must not exceed 600mA total for UL installations
(Aux power 500mA max.).
6. All partitions must be owned and managed by the same person(s).
7. All partitions must be part of one building at one street address.
8. If used, the audible alarm device(s) must be placed where it/they can be heard by all partitions.
9. For UL commercial burglar alarm installations the control unit must be protected from
unauthorized access. The tamper switch installed to protect the control unit enclosure door is
suitable for this purpose.
10. Remote downloading without an alarm company technician on-site (unattended downloading) is not
permissible for UL installations.
11. Auto-disarming is not a UL Listed feature.
12. As SIA limits for delay of alarm reporting and sounding can exceed UL limits for commercial and
residential applications, the following UL requirements per UL681 are provided:
The maximum time that a control unit shall be programmed to delay the transmission of a signal to
a remote monitoring location, or to delay the energizing of a local alarm sounding device to permit
the alarm system user to enter and disarm the system, or to arm the system and exit shall not
exceed:
a) 60 seconds for a system with standard line security or encrypted line security,
b) 120 seconds for a system without standard line security or encrypted line security, or
c) 120 seconds for a system that does not transmit an alarm signal to a remote monitoring location.
13. This control is not intended for bank safe and vault applications.
6-2
S E C T I O N 7
7-3
Installation and Setup Guide
– INDEX –
1321 ......................................... 1-2, 2-3 Cabinet ............................................2-1 MODel 112 ....................................2-10
1321 AC Transformer .................... 2-11 CALIFORNIA STATE FIRE Modem ............................................3-8
1361X10 ................. 2-3, 2-11, 2-12, 5-2 MARSHALL.................................2-2 Momentary Switch .........................2-10
3+1 and 4+1 Standard Formats ....... 3-1 Caller ID Unit ................................. 2-13
4204 ....1-2, 2-2, 2-5, 2-6, 2-11, 3-6, 5-1 Charging Voltage .............................5-1 On-Board Triggers .........................2-14
4219 ......1-1, 1-2, 2-2, 2-5, 2-7, 2-8, 5-1 Chime Mode ....................................3-6 Output Relays ..................................1-2
4229 .1-1, 1-2, 2-2, 2-5, 2-6, 2-7, 2-8, 2- Clean Me Option..............................2-7
11, 3-6, 5-1 Communication.........................3-1, 5-1 Panic Keys.......................................3-7
4285 .............................................. 2-14 Contact ID Reporting .......................5-1 Periodic Test Reports ......................4-2
4286 .............................................. 2-14 CSFM ..............................................2-2 Phone Line ....................................2-13
5800 Series Transmitters................. 2-9 Phone Module.1-1, 2-2, 2-5, 2-13, 2-14,
5800TM .................................... 2-9, 5-1 Device Address ...............2-5, 2-11, 3-8 5-1
5801 ................................................ 2-9 Dialer Communication Test..............4-2 Power Failure...................................3-8
5802 ......................................... 2-9, 3-8 DIP Switches. ..................................2-9 Power Supply.....................2-2, 2-4, 7-6
5802CP .................................... 2-9, 3-8 Disarming ........................................3-6 Powerline Carrier Devices1-2, 2-11, 3-6
5827 ................................................ 2-9 Double-Balanced .............................2-6 PSC04 Powerline Interface ............2-11
5827BD ........................................... 2-9
5881 ......................................... 2-2, 2-8 Enrolling ..........................................2-9 Relay Modules ........................1-2, 2-11
7720PLUS or 7820 .......................... 1-2 Entry Delay...............................3-7, 3-8 Report Code ....................................3-1
EOLR .......................................2-6, 5-1 Report Code Formats ......................3-1
AC Power Supply ............................ 1-2 Exit Delay .................................3-7, 3-8 Response Time................................ 2-7
AC Transformer ............... 2-3, 2-12, 5-2 Exit Error Alarm ...............................3-8 RF House ID Code...........................2-8
Ademco Contact ID.......................... 3-3 Expansion Zones .............................2-7 RF Interference................................2-8
Alarm Output ............................ 2-2, 2-4 RF jam detection..............................1-1
Arming Away ................................... 3-6 Fast Busy Signal............................ 2-13 RF Jam Option.................................2-8
Arming Instant ................................. 3-6 FCC.................................................6-1 RF Receiver............2-1, 2-2, 2-5, 2-8, 3
Arming Modes ................................. 3-7 RJ31X Jack ...................................2-13
Arming Stay..................................... 3-6 Go/No Go Test Mode.......................4-2
Audio Alarm Verification (AAV) ...... 2-13 SA4120XM-1 Cable .........................2-3
AUI .................................................. 2-5 Handshake ......................................3-1 Security Codes .........................1-1, 3-5
Authority Levels ............................... 3-5 Hardwired Zones .............................1-1 Silent Burglary ....................................3
Auxiliary Output ............................... 2-2 HAYES Modem ...............................1-1 Silent Panic......................................3-7
House ID .........................................2-9 Sniffer Mode ....................................4-1
Backup Battery ................................ 1-2 Ideal Model 61–035 .........................2-3 Sounder Connections ......................2-4
Battery Life ...................................... 2-9 Supplementary Power......................2-4
Battery Tests ............................ 4-1, 4-2 Installer Code ...........................4-1, 4-2 System Communication ...................3-1
Bell Supervision............................... 2-4 System Test.....................................4-1
Bell Supervision Jumper .................. 2-4 Keypad Addresses...........................2-5
Bypassing Zones ............................. 3-6 Keyswitch .................................. 2-10, 3 Tamper Switch........................2-10, 6-2
Kissoff..............................................3-1 Telco Line ..................................2-13, 3
Telephone Line Monitoring...............1-1
Lock.................................................2-1 Test Mode.................................4-1, 4-2
Long Range Radio................2-5, 3, 5-1 Trigger outputs...............................2-12
Low Battery Message ......................4-2 Trouble Displays .......................3-7, 3-8
Verify Operation...............................2-7
7-4
24-HR BATTERY STANDBY REQUIRED FOR 8-PIN CONNECTOR
BATTERY FUSE FOR COMPLETE ADEMCO No. 4219 4-WIRE SMOKE DETECTOR CONNECTIONS
FIRE INSTALLATIONS. USE 12V, 17.2AH USED FOR 1361X10 +
INFORMATION, WIRED EXPANSION MODULE 5
BATTERY FOR 600mA AUX POWER. SEE 3A FOR REPLACEMENT, TRANSFORMER
USE SAME VALUE SEE INSTRUCTIONS (8 ADD'L EOLR WIRED ZONES)
INSTRUCTIONS. CONNECTIONS AND FOR SET UNIT’S AUX PWR RELAY
(e.g. ADEMCO No. 90-12) K5305-1V5 -AND/OR- PROGRAM RELAY _
ON-BOARD TRIGGERS OR LATER. ADEMCO No. 4229 DIP SWITCH OUTPUT BLK + RED
AS ZONE TYPE 54
BATTERY CAPACITY FOR EMERGENCY SEE INSTRUCTIONS. FOR DEVICE TERMINALS (FIRE ZONE RESET)
WIRED EXPANSION/RELAY MODULE EOL
BURGLARY STANDBY USE AT LEAST 4 HRS BLK (8 ADD'L EOLR WIRED ZONES PLUS 2 ADDRESSES _ 4 POWER
1 2 3 4 5 6 7 8 (USE SA4120XM-1 N.O. SUPERVISION
RED OUTPUT RELAYS) 7 - 15 N.C.
CABLE) OR RELAY MODULE
-AND/OR- SEE CONTACT OPENS MOMENTARILY A77-716B.
CHARGING VOLTAGE
BLACK SYNC GRN INSTRUCTIONS. UPON FIRE ALARM RESET
BATTERY ADEMCO No. 4204 RELAY MODULE USE N.O.
13.8VDC. MAXIMUM 12V, 4AH FLYING LEADS YEL (4 OUTPUT RELAYS) CONTACT,
COM TO
OPTIONAL
CHARGING CURRENT + FOR BATTERY VIOLET WHICH CLOSES
RED TRANS. TO OUTPUT 17 +
650mA. CONNECTION DATA PROGRAM OUTPUT 17 FOR _ WHEN POWER
AND/OR
GND
SET "OUT NORM LOW" = YES IN 4-WIRE SMOKE IS APPLIED.
+ ADEMCO 5881* Type RECEIVER’S 79 MENU MODE AND AS ZONE OR COMBUSTION 2000
(TRIG. 1)
(TRIG. 2)
TYPE 54 IN 80 MENU MODE DETECTOR OHMS
+12 AUX
SEALED LEAD-ACID TYPE. RF RECEIVER DIP SWITCH MAX. CURRENT = 100 mA EOLR
OUTPUT 17
OUTPUT 18
BATTERY NORMALLY NEED NOT BE
LO
HI
LO
LO
HI
HI
HI
HI
HI
LO
HI
HI
LO
LO
LO
LO
▲
+
HANDSET INCOMING
}
USE 1361X10 TRANSFORMER EARTH
INTERFACE IN PLACE OF 1321 OR AUX. POWER PHONE LINE GROUND
1321CN WHEN POWER LINE CARRIER OUTPUT TELEPHONE WIRING SEE
DEVICES ARE BEING USED. (SEE 10.5-13.8VDC (VIA RJ31X* JACK AND DIRECT INSTRUCTIONS
INSTRUCTIONS FOR CONNECTIONS) TO 110VAC 600mA MAX. CONNECT CORD) FOR PROPER
UNSWITCHED (500mA MAX. GROUNDING
*CA38A IN CANADA DOC LOAD NO.: 3
OUTLET (24HR) FOR UL
THIS EQUIPMENT SHOULD BE INSTALLED INSTALLATIONS) FOR CONNECTION OF OPTIONAL 4286 VIP MODULES
IN ACCORDANCE WITH THE NATIONAL TO PHONE TERMINALS, SEE INSTRUCTIONS.
ZONE 7
ZONE 8
ZONE 1
VISTA-20P ONLY
ZONE 2
ZONE 3
ZONE 4
ZONE 5
ZONE 6
BLK
RED: KEYPAD PWR ( + )
DESCRIBING PROPER INSTALLATION, USAGE, INCLUDING CURRENT (IN BOTH NO. 5GBUSA-44003-AL-E RINGER EQUIVALENCE: 0.1B.
OPERATION,TESTING, MAINTENANCE, AUX POWER) STEADY PARTITIONS) AND • MAXIMUM LOOP RESISTANCE: (EACH ZONE) 300 OHMS (PLUS EOLR)
EVACUATION PLANNING AND REPAIR FOR BURGLARY/PANIC, ALL OTHER DEVICES REMOTE • RESPONSE, ZONES 1-8: 10, 350, OR 700 MSEC (PROGRAMMABLE)
SERVICE IS TO BE PROVIDED WITH THIS TEMPORAL PULSE DRAWING POWER KEYPADS 12 13 14
AND OTHER • MAXIMUM NUMBER OF 2-WIRE SMOKE DETECTORS ON ZONE 1 IS 16;
EQUIPMENT. SOUNDING FOR FIRE. FROM TERMS 4 & 5 DETECTORS MUST HAVE COMPATIBILITY IDENTIFIER AS "A".
7-5
WARRANTY INFORMATION
For the latest warranty information, please go to:
www.honeywell.com/security/hsc/resources/wa
www.honeywell.com/security
ÊK5305-1V7/Š
K5305-1V7 10/08 Rev. B