0% found this document useful (0 votes)
6 views40 pages

837

The ADEMCO VISTA series installation and operation guide provides recommendations for the placement of fire and burglary detection devices to ensure proper coverage. It outlines features, installation highlights, and compatible devices for the VISTA-20P and VISTA-15P security systems, including specifics on zones, security codes, and communication methods. The document emphasizes compliance with NFPA standards and offers detailed instructions for installation and setup, ensuring effective security system operation.

Uploaded by

Abbes Benmaissa
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
6 views40 pages

837

The ADEMCO VISTA series installation and operation guide provides recommendations for the placement of fire and burglary detection devices to ensure proper coverage. It outlines features, installation highlights, and compatible devices for the VISTA-20P and VISTA-15P security systems, including specifics on zones, security codes, and communication methods. The document emphasizes compliance with NFPA standards and offers detailed instructions for installation and setup, ensuring effective security system operation.

Uploaded by

Abbes Benmaissa
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 40

ADEMCO VISTA SERIES

VISTA-20P / VISTA-20PSIA
VISTA-15P / VISTA-15PSIA
Security Systems

Installation and Operation Guide

K5305-1V7 10/08 Rev. B


RECOMMENDATIONS FOR PROPER PROTECTION
The Following Recommendations for the Location of Fire and Burglary Detection
Devices Help Provide Proper Coverage for the Protected Premises.

Recommendations For Smoke And Heat Detectors


With regard to the number and placement of smoke/heat detectors, we subscribe to the
recommendations contained in the National Fire Protection Association's (NFPA) Standard #72 noted
below.
Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms
and areas of the household as follows: For minimum protection a smoke detector should be installed
outside of each separate sleeping area, and on each additional floor of a multi-floor family living unit,
including basements. The installation of smoke detectors in kitchens, attics (finished or unfinished), or
in garages is not normally recommended.
For additional protection the NFPA recommends that you install heat or smoke detectors in the living
room, dining room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storage rooms,
basements and attached garages.
In addition, we recommend the following:
• Install a smoke detector inside every bedroom where a smoker sleeps.
• Install a smoke detector inside every bedroom where someone sleeps with the door partly or
completely closed. Smoke could be blocked by the closed door. Also, an alarm in the hallway outside
may not wake up the sleeper if the door is closed.
• Install a smoke detector inside bedrooms
where electrical appliances (such as
KITCHEN portable heaters, air conditioners or
BEDROOM BEDROOM TV ROOM KITCHEN DINING BDRM
DINING humidifiers) are used.
LIVING ROOM
BDRM • Install a smoke detector at both ends of a
BEDROOM
hallway if the hallway is more than 40
LIVING ROOM BEDROOM
feet (12 meters) long.
• Install smoke detectors in any room where
Smoke Detectors for Minimum Protection an alarm control is located, or in any room
Smoke Detectors for Additional Protection where alarm control connections to an AC
BEDROOM Heat-Activated Detectors source or phone lines are made. If
detectors are not so located, a fire within
TO
BEDROOM BR BEDROOM the room could prevent the control from
KTCHN
reporting a fire or an intrusion.
GARAGE
LVNG RM . CLOSED
DOOR THIS CONTROL COMPLIES WITH NFPA
BASEMENT REQUIREMENTS FOR TEMPORAL PULSE
floor_plan-001-V1 SOUNDING OF FIRE NOTIFICATION
APPLIANCES.

Recommendations For Proper Intrusion Protection


For proper intrusion coverage, sensors should be located at every possible point of entry to a home or
commercial premises. This would include any skylights that may be present, and the upper windows
in a multi-level building.
In addition, we recommend that radio backup be used in a security system so that alarm signals can
still be sent to the alarm monitoring station in the event that the telephone lines are out of order
(alarm signals are normally sent over the phone lines, if connected to an alarm monitoring station).

ii
Table Of Contents
Features and Installation Highlights............................................................................................................1-1
Capabilities and Functions................................................................................................................................................1-1
Compatible Devices ...........................................................................................................................................................1-2
Important Installation Highlights (Installer Please Read) .............................................................................................1-2
Mounting and Wiring the Control .................................................................................................................2-1
Installing the Control Cabinet and PC Board ..................................................................................................................2-1
Cabinet and Lock .........................................................................................................................................................2-1
Mounting the PC Board Alone (no RF Receiver) ........................................................................................................2-1
Mounting Board with RF Receiver..............................................................................................................................2-1
Auxiliary Device Current Draw Worksheet................................................................................................................2-2
AC Power, Battery, and Ground Connections ..................................................................................................................2-3
1321 Transformer.........................................................................................................................................................2-3
1361X10 Transformer ..................................................................................................................................................2-3
Battery Connections.....................................................................................................................................................2-3
Battery Saver Feature .................................................................................................................................................2-3
Earth Ground ...............................................................................................................................................................2-3
Sounder (Bell) Connections ...............................................................................................................................................2-4
Basic Connections ........................................................................................................................................................2-4
Supervised output ........................................................................................................................................................2-4
Connecting the Keypads and Other Addressable Devices ...............................................................................................2-4
Connections ..................................................................................................................................................................2-4
Supplementary Power (optional).................................................................................................................................2-4
Keypad Notes ...............................................................................................................................................................2-5
Communication Device ................................................................................................................................................2-5
(Long Range Radio) Connections.................................................................................................................................2-5
Table of Device Addresses .................................................................................................................................................2-5
Hardwire Zones and Zone Expansion ...............................................................................................................................2-6
Hardwire Zones ............................................................................................................................................................2-6
Double-Balanced Zones................................................................................................................................................2-6
Zone Doubling ..............................................................................................................................................................2-6
Smoke Detectors...........................................................................................................................................................2-6
Smoke Detector Notes..................................................................................................................................................2-7
4219/4229 Expansion Zones ........................................................................................................................................2-7
Installing the RF Receiver and Wireless Transmitter Zones ..........................................................................................2-8
Compatible Receivers...................................................................................................................................................2-8
Receiver Connections ...................................................................................................................................................2-8
RF Receiver Notes........................................................................................................................................................2-8
Installing a 5800TM Module .......................................................................................................................................2-9
Installing the Transmitters .........................................................................................................................................2-9
Transmitter Battery Life .............................................................................................................................................2-9
Installing a Keyswitch.....................................................................................................................................................2-10
Keyswitch Connections ..............................................................................................................................................2-10
Keyswitch Notes.........................................................................................................................................................2-10
Connecting Relay Modules, Powerline Carrier Devices and Output Triggers..............................................................2-11
4204/4229 Relay Modules ..........................................................................................................................................2-11
Powerline Carrier Devices .........................................................................................................................................2-11
On-Board Triggers .....................................................................................................................................................2-12
Phone Line/Phone Module, and Audio Alarm Verification (AAV) Connections............................................................2-13
Phone Line..................................................................................................................................................................2-13
4286 Phone Module....................................................................................................................................................2-13
Phone Module Problems ............................................................................................................................................2-13
Audio Alarm Verification Connections......................................................................................................................2-14
Audio Alarm Verification Connections......................................................................................................................2-15

iii
Table Of Contents

System Communication and Operation .......................................................................................................3-1


Panel Communication with Central Station ....................................................................................................................3-1
Report Code Formats.........................................................................................................................................................3-1
Ademco Contact ID® .........................................................................................................................................................3-3
Uploading/Downloading via the Internet .........................................................................................................................3-4
System Security Codes ......................................................................................................................................................3-5
Panic Keys..........................................................................................................................................................................3-7
Setting the Real-Time Clock .............................................................................................................................................3-7
Various System Trouble Displays .....................................................................................................................................3-8
Testing the System.............................................................................................................................................4-1
About Test Procedures.......................................................................................................................................................4-1
System Test........................................................................................................................................................................4-1
Checking Transmitter Enrollment (Sniffer Mode)...........................................................................................................4-1
Go/No Go Test Mode ..........................................................................................................................................................4-2
Dialer Communication Test and Periodic Test Reports...................................................................................................4-2
Automatic Standby Battery Tests.....................................................................................................................................4-2
Specifications & Accessories...........................................................................................................................5-1
Security Control.................................................................................................................................................................5-1
Compatible Devices ...........................................................................................................................................................5-1
Regulatory Agency Statements ......................................................................................................................6-1
Limitations and Warranty ...............................................................................................................................7-3

iv
S E C T I O N 1

Features and Installation Highlights


This manual applies to the following Honeywell security systems:
ADEMCO VISTA-20P/ADEMCO VISTA-20PSIA/ADEMCO VISTA-20PCN (collectively referred to as
VISTA-20P series), ADEMCO VISTA-15P/ADEMCO VISTA-15PSIA/ADEMCO VISTA-15PCN
(collectively referred to as VISTA-15P series)
Features and procedures apply to all, except where differences are noted.
SIA Installations: The VISTA-20PSIA and VISTA-15PSIA are certified SIA-compliant controls that
meet SIA specifications for False Alarm Reduction. The other controls described in this manual are
not certified as SIA compliant, but can be programmed for False Alarm Reduction. To program for
False Alarm Reduction, follow the SIA Guidelines noted in the applicable programming fields.

Capabilities and Functions


Feature/Function VISTA-20P Series VISTA-15P Series
Partitions • 2 partitions, can protect two independent VISTA-15P is not a partitioned system.
areas
• Common zone option allows either
partition to arm, while leaving a common
area (ex. lobby or foyer) disarmed for
access into the other partition.
Zones Up to 48 protection zones plus 16 keyfob Up to 32 zones plus 8 keyfob zones (zones
zones (zones 49-64) for total of 64 zones: 49-56) for total of 40 zones:
• 8 basic hardwired zones (zones 1-8) with • 6 basic hardwired zones (zone 1-6)
optional zone-doubling feature • Up to 16 additional wired zones (zones 9-
• Up to 40 additional wired zones (zones 9- 24) using up to 2 4219/4229 modules
48) using up to 5 4219/4229 modules • Up to 26 wireless transmitter zones
• Up to 40 wireless transmitter zones (5800 (5800 series; zones 9-34)
series; zones 9-48) • Up to 2 configurable zone types
• Up to 4 configurable zone types
Security Codes Up to 48 Security Codes, with separate Up to 32 Security Codes, with separate
authority levels and partition access authority levels
One-button arming Dedicated keys can arm the system. Dedicated keys can arm the system.
Schedules Up to 32; can control devices and/or auto- Up to 8; can control devices and/or auto-
arm/disarm arm/disarm
Keypad macros Up to 4; activated by wired keypads Up to 2; activated by wired keypads
Paging Up to 4 pagers; certain system conditions Up to 2 pagers; certain system conditions
can report to pagers; can use a dedicated can report to pagers; can use a dedicated
key on keypads to send a signal to a pager key on keypads to send a signal to a pager
Event Logging 100 events; display via Compass Downloader 50 events; display via Compass Downloader
software or installer/master code at Keypad software or installer/master code at Keypad
Zone descriptors Can assign for all zones (for alpha display keypads and/or 4286 Phone Module).
Bell supervision Optional, detects external sounder wiring short (when in alarm) or open (when bell is off);
causes a trouble condition, keypad display, and sends a report to the central monitoring
station, if enabled.
RF jam detection Optional, for wireless systems detects a condition that may impede proper RF reception
(i.e., jamming or other RF interference); causes keypad display, and sends a report to the
central monitoring station (if trouble reporting is enabled).
Telephone Line Built-in option can monitor the telephone line voltage and can cause a local display, or a
Monitoring display and trouble/alarm sound
Downloading via • Via Standard Phone Line: Use an IBM compatible computer, Compass downloading
Phone Line or software, and a compatible HAYES or CIA modem specified by Honeywell.
Internet • Via Internet: supports Upload/Download via the Internet/Intranet when used with an
appropriate communications device (ex. 7845i-GSM) and Compass downloading software.
This allows site maintenance independent of central station monitoring, and modification
to sites globally via the Internet.
UL NOTE: Uploading/Downloading via the Internet has not been evaluated by UL

1-1
Installation and Setup Guide
Compatible Devices
Device VISTA-20P VISTA-15P Notes
Addressable Keypads 8 8 6150 Fixed-Word Keypad, 6160 Alpha Keypad, 6150V
Fixed-Word Display Voice Keypad, 6160V Alpha
Display Voice Keypad, 6150RF Keypad/Transceiver
Touch Screen (AUI) 4 2 Touch Screen (AUI) devices are in addition to the 8
Devices addressable keypads. E.g., Symphony, 6270
4219, 4229 Zone Up to 5 for Up to 2 for Zone numbers are predefined according to the device
Expander Modules up to 40 up to 16 addresses used. See Expander Module Addresses table
exp. zones exp. zones in Wiring section and set addresses accordingly.
5800 Series Wireless Up to 40 RF Up to 26 RF Uses 5881/5883 Series Receivers/Transceivers.
zones zones
Output relays and/or Up to 16 Up to 8 Use any combination of 4204, 4229 and or Powerline
Powerline Carrier Carrier Devices.
Devices (X-10 type) Map output devices via *79 Menu mode.
On-Board Triggers 2 2 Can be used to reset 4-wire smoke detectors.
Output functions Up to 48 Up to 24 Program output functions via *80 Menu mode.
4286 Phone Module Partition 1 yes Provides access to the system via on premises or off-
only premises phones for arming, disarming, etc., plus
control of relay outputs and Powerline Carrier devices.
Audio Alarm Using AAV Using AAV Use ADEMCO UVS or Eagle Model 1250 in
Verification module module conjunction with an output trigger to permit voice
dialog between an operator at the central station and
a person at the premises. Alternatively, the AVS
system can be used to provide AAV via phone line or
AlarmNet IP/GSM (using a GSMV module).
Alarm output 12VDC, 2 12VDC, 2 Can drive the compatible sounders; steady output for
AMP output AMP output burglary/panic, or temporal pulse (3 pulses – pause –
3 pulses – pause – 3 pulses. . .) for fire. Uses current
limiting circuitry for protection.
Auxiliary Power Output See note. See note 12VDC, 600 mA maximum; uses fuse for protection.
Backup Battery See note. See note. Rechargeable (sealed lead-acid type) 12VDC, 4AH
minimum.
Long Range Radio See note. See note. Primary telephone number messages can be reported
(Communication Device) via ECP connection to various communication devices
(check compatibility/availability of specific models)
AC Power Supply See note. See note. Plug-in 120VAC transformer, 1321 (1321CN in
Canada) or, if using Powerline Carrier devices,
1361X10 Transformer Module
NOTE: All devices and accessories used in a Canadian installation must be Listed for use in Canada.

Important Installation Highlights (Installer Please Read)


• This system uses addressable keypads and Zone Expander Modules (see Table of Addresses in
Section 2. Mounting and Wiring – Wiring the Keypads and Other Addressable Devices).
• Keypads must be set for addresses 16-23 (first keypad is address 16, which is different from
previous controls) and programmed in data fields *190-*196.
• Zone Expander Modules must be set for specific addresses (07-11), based on the zone numbers used.
• 4204 Relay Modules must be set for specific addresses (12-15).
• This control will not power-up unless AC power is connected (will not power-up on battery alone).
However, once the system is powered up, it will operate on battery power in the event of AC loss.
• Relays have two programming menu modes: Use *79 Menu mode to map module addresses and
device (output) numbers. Use *80 Menu mode to define the output functions.
• This system supports programmable function keys. Use *57 Menu mode to define the function
keys.

1-2
S E C T I O N 2

Mounting and Wiring the Control


Installing the Control Cabinet and PC Board
Cabinet and Lock 1. Mount the control cabinet to a PUSH
ON LOCK
sturdy wall in a clean, dry area, CHECK
POSITION
SNAP
UNTIL IT
IS SEATED
TAB SECURELY
which is not readily accessible to
the general public, using fasteners LOCKED
PUSH

ADEMCO

ADEMCO
or anchors (not supplied) with the
four cabinet mounting holes.
2. Remove cabinet door, then remove SNAP

cab_lock_snap-001-V0
UNLOCKED TAB
the lock knockout from the door.
Insert the key into the lock. CABINET DOOR
BOTTOM STEP 1 STEP 2

Figure 1. Installing the Cabinet Lock


3. Position the lock in the hole, making certain that the latch will make contact with the
latch bracket when the door is closed. When correctly positioned, push the lock until
the snap tabs hold it securely.
The cabinet can be secured without a lock by using 2 screws in the cover's edge.
Mounting the PC Board Before installing the cabinet's contents, remove the metal cabinet knockouts required for
Alone (no RF Receiver) wiring entry. Do not remove the knockouts after the circuit board has been installed.
1. Hang two short mounting clips (provided) on the raised cabinet tabs (see Detail B).
2. a. Insert the top of the circuit board into the slots at the top of the cabinet. Make sure
that the board rests on the correct row (see Detail A).
b. Swing the base of the board into the mounting clips and secure the board to the
cabinet with the accompanying screws (see Detail B).
CIRCUIT
BOARD CABINET

CIRCUIT
BOARD
+ +
CABINET DETAIL B
SIDE VIEW
DETAIL A OF MOUNTING
SIDE VIEW CLIPS
OF BOARD
SUPPORTING
SLOTS

MOUNTING-001-V0

Figure 2. Mounting the PC Board


Mounting Board with RF • Do not mount the cabinet on or near metal objects. This will decrease RF range and/or
Receiver block RF transmissions from wireless transmitters.
• Do not locate the cabinet in an area of high RF interference (revealed by frequent or
prolonged lighting of the LED in the receiver (random flicker is OK)
1. a. Remove the receiver board from its case, then insert the top of the board into the
slots at the top of the cabinet, as shown in Detail A in Figure 3 on the next page.
Make sure that the board rests on the correct row of tabs.
b. Swing the base of the board into the mounting clips and secure it to the cabinet
with the accompanying screws.
c. Insert the top of the control's board into the slot in the clips and position two clips
at the lower edge of the board.
d. Swing this board into place and secure it with two additional screws.
2. Insert grounding lugs (supplied with the receiver) through the top of the cabinet into
the left-hand terminals of the antenna blocks (at the upper edge of the receiver board)
and secure them to the cabinet top with the screws provided (see Detail B).
3. Insert the receiver's antennas through the top of the cabinet, into the blocks' right-
hand terminals, and tighten the screws.

2-1
Installation and Setup Guide
CABINET A B

CABINET
BOARD
RECEIVER CIRCUIT BOARD SUPPORTING
SLOTS
+ +
CIRCUIT
BOARD
MOUNTING
CLIP
CONTROL
CIRCUIT
BOARD
DETAIL A
MOUNTING SIDE VIEW
CLIP OF BOARD -
SUPPORTING SLOTS

INSTALLATION WITH RECEIVER CIRCUIT BOARD


ANTENNA
(2)

SCREW
(2)

GROUNDING
LUG
(2)

WHITE BLACK RED


MOUNTING MOUNTING MOUNTING
CLIP CLIP CLIP

NOTE
A COMBINATION OF THESE MOUNTING CLIPS HAS BEEN ANTENNA
INCLUDED IN YOUR INSTALLATION KIT. MOUNT
(2 PLACES)
USE THE APPROPRIATE CLIPS FOR MOUNTING.

IF NO RF RECEIVER IS USED, MOUNT THE PC BOARD USING DETAIL B


EITHER THE WHITE OR BLACK CLIPS, WHICHEVER ARE ANTENNA AND GROUNDING
INCLUDED IN THE CONTROL PANEL'S HARDWARE KIT. LUG INSTALLATION

pc_mount-001-V1

Figure 3. Mounting the PC Board and RF Receiver

Auxiliary Device Current Draw Worksheet


DEVICE CURRENT No. UNITS TOTAL CURRENT
6150 Fixed-Word Keypad 40mA/70mA**
6160 Alpha Keypad 40mA/150mA**
6150V Fixed-Word Display Voice Keypad 60mA/160mA**
6160V Alpha Display Voice Keypad 60mA/190mA**
8132/8142 Series AUI (Symphony) 150mA/400mA**
6270 Touch Screen Keypad 180mA/280mA**
5881/5882 RF Receiver 60mA
5883 Transceiver 80mA
4219 Zone Expander 30mA
4204 Relay Unit 15/180mA‡
4229 Zone Expander/Relay Unit 30/100mA‡
4286 Phone Module 300mA

*
(Current available from Aux. terminals = 600 mA max.)† TOTAL =
*If using hardwire devices such as PIRs, refer to the specifications for that particular unit's current draw.
** Values are for standby/alarm; alarm for keypads means armed with backlighting on and sounder on
†In UL installations, maximum current draw from the Auxiliary Output and the Alarm Output combined must not exceed 600 mA (500 mA max from Aux. Output).
‡Values are for relays OFF/relays ON.

CALIFORNIA STATE FIRE MARSHALL (CSFM) AND UL RESIDENTIAL FIRE


24-HOUR BATTERY BACKUP REQUIREMENTS
The California State Fire Marshal and UL have regulations which require that all residential fire alarm control panels must be
provided with a backup battery which has sufficient capacity to operate the panel and its attached peripheral devices for 24 hours in the
intended standby condition, followed by at least 4 minutes in the intended fire alarm signaling condition. This control panel can meet
these requirements without using a supplementary power supply, provided that the panel’s auxiliary power and bell output currents
are limited as indicated below.
OUTPUT LIMITATIONS AND CORRESPONDING REQUIRED BATTERIES
OUTPUT CURRENT LIMITATIONS BATTERY INFORMATION
Output Current Total Maximum Auxiliary Current Battery Capacity Recommended Battery
To Use (Amp/Hrs) (Yuasa Model No.)
600mA maximum total of 45mA 4AH NP4-12 (or ADEMCO 467)
auxiliary power plus bell 160mA 7AH NP7-12
output currents 200mA 8AH NP4-12 (two) ‡
425mA 14AH NP7-12 (two) ‡
500mA 17.2AH NPG18-12
‡ NOTE: Use two batteries, connected in parallel. Obtain an Ademco Battery Harness Kit SA5140-1. (Both batteries will fit inside the cabinet.)

2-2
Mounting and Wiring the Control
AC Power, Battery, and Ground Connections
1321 Transformer Connect the 1321 Transformer (1321CN in Wire Run Chart
Canada) to terminals 1 and 2 on the Distance from control Wire Size
control board. See Wire Run Chart for Up to 50 feet # 20
wire size to use. 50–100 feet # 18
• Use caution when wiring the
100-250 feet # 16
transformer to the control to guard
1
against blowing the transformer fuse
2 (the fuse is non-replaceable).
1321X10-001-V0

TO
TERMINALS
1 AND 2

• Wiring to the AC transformer must not exceed 250 feet using 16 gauge wire. The
voltage reading between terminals 1 and 2 of the control must not fall below 16.5VAC
or an “AC LOSS” message will be displayed.
• Do not plug the transformer into the AC outlet until all wiring connections to the
control are complete. As a safety precaution, always power down the control when
making such connections.
1361X10 Transformer 1. Splice one end of a 3-conductor cable 8-PIN TRIGGER CONNECTOR
1 3 4 5 6 7 8

KEY
(required if using to the wire ends of the SA4120XM-1
Powerline Carrier devices) Cable.
2. Connect the SA4120XM-1 cable plug

(YELLOW)
OUTPUT 18 (GREEN)
(ORANGE)

(PURPLE)
(BLACK)
(BLUE)
(RED)
1361X10 TRANSFORMER

to the 8-pin connector on the control


AC AC SYNC COM DATA
(see the Summary of Connections

OUTPUT 17
1 2 3 4 5

+12 AUX.
diagram for location of the 8-pin

GND (-)
AC

SYNC
AC

COM
DATA
Sy
Outnc
put Sign
TO
connector).
Com al
mon X1
Dat0
a 8-PIN
CONNECTOR SA412OXM
3. Connect the other end of the CABLE

1 3-conductor cable to the 1361X10 1 2


2 CONTROL
Transformer, as shown in Figure 4. BOARD
TERMS.
1361X10-001-V0

Canadian Installations: See


TO
TERMINALS Powerline Carrier Device section for
1 AND 2
connections to the PSC04 X-10 Interface Figure 4. 1361X10 Transformer Connections
and trigger pins.
Battery Connections 1. Place the 12-volt backup battery in the cabinet.
2. After all connections to the control are completed and AC power has been applied,
connect the red and black flying leads on the control board to the battery. Do not
BLACK
attach these leads to the battery terminals until all connections are completed.
RED
UL For UL installations and Residential fire installations, refer to the chart on page 2-2
at left for the correct battery size required to meet the mandatory standby time.
batt_conn-001-V0

CONNECT
FLYING LEADS
AFTER AC POWER
IS APPLIED

Battery Saver Feature The battery will disconnect from the system after its voltage decreases below 9VDC.
This assists the control panel in recharging the battery when AC is restored.
IMPORTANT: The panel will not power up initially on battery power only. You must
plug the transformer in first, and then connect the battery.
Earth Ground • This product has been designed and laboratory-tested to ensure its resistance to
damage from generally expected levels of lightning and electrical discharge, and does
not normally require an earth ground.
CONNECT • If an earth ground is desired for additional protection in areas of severe electrical
R D
OL
B OA PROPER
EARTH
activity, terminal 25 on the control board, or the cabinet, may be used as the ground
NTR GROUND
connection point. The following are examples of good earth grounds available at most
CO IF
25
DESIRED installations.
Metal Cold Water Pipe: Use a non-corrosive metal strap (copper is recommended) firmly
secured to the pipe to which the ground lead is electrically connected and secured.
earth_gnd-001-V0

AC Power Outlet Ground: Available from 3-prong, 120VAC power outlets only. To test
the integrity of the ground terminal, use a 3-wire circuit tester with neon lamp
indicators, such as the UL Listed Ideal Model 61-035, or equivalent, available at most
electrical supply stores.

2-3
Installation and Setup Guide
Sounder (Bell) Connections
Basic Connections Make sounder connections to alarm output terminals 3 (+) and 4 (–).
• The 12VDC sounder output activates when an alarm occurs.
3
4 • Total current drawn from this output cannot exceed 2 amps (going beyond 2 amps will
overload the power supply, or may cause the electronic circuit protecting the sounder
output to trip).
• You must install a battery, since the battery supplies this current.
ALARM OUTPUT Supervised output
10.5 - 13.5 VDC
2A MAX. spkr_conn-001-V0 1. Cut the red Bell Supervision Jumper located above terminals 2 and 3 on the PC board.
2. Connect a 2k ohm resistor across the terminals of the last sounder. See Figure 5.
3. Set field ∗91 Option Selection for Bell Supervision.
This control complies with NFPA requirements for temporal pulse sounding of fire notification
appliances. Temporal pulse sounding for a fire alarm consists of: 3 pulses – pause – 3 pulses –
pause – 3 pulses–etc..

UL TERMINALS ON
CONTROL BOARD
EXTERNAL ALARM
SOUNDER

• Use only UL Listed sounding devices for


UL installations. _
• Bell supervision is required for fire alarm 4 _
2000
ALARM
installations. OUTPUT
OBSERVE
POLARITY
OHM
EOL
• The total current drawn from the alarm TERMINALS
+
+ RESISTOR
3
output and the auxiliary power output,
combined, cannot exceed 600 mA. In
addition, the sounding device must be a
2
UL Listed audible signal appliance rated IF BELL SUPERVISION IS ENABLED
(RED JUMPER ON CONTROL BOARD IS CUT)
to operate in a 10.2-13.8 VDC voltage CONNECT A 2000 OHM RESISTOR ACROSS

sounder-001-V0
THE EXTERNAL SOUNDER AS SHOWN BY
range, and must be mounted indoors. THE DOTTED LINE.
CUT RED JUMPER ON CONTROL
BOARD TO ENABLE BELL DO NOT CONNECT THE RESISTOR AT THE
(SOUNDER) SUPERVISION. ALARM OUTPUT TERMINALS THEMSELVES!

Figure 5. Sounder Wiring (Supervised)

Connecting the Keypads and Other Addressable Devices


Connections Connect keypads and other addressable devices (4204, 4219, 4229, 4286, 5881, LRR,
etc.) to the control’s keypad terminals as shown on the Summary of Connections
4_
5+
6 IN
diagram. The system supports up to 8 keypads, which can be assigned to partitions in
7 OUT
any combination (see program fields *190-*196).
BLACK
RED
GREEN
YELLOW

AR
MED
Use the Table of Device Addresses to determine the appropriate address for each device.
RE
AD
Y

Determine wire size using the Wire Run Chart on the following page. For single 4-wire
runs, determine the current drawn by all units, then refer to the Wiring Run chart to
determine the maximum length that can be safely used for each wire size.
conn-001-V0

Supplementary Power Use supplementary power if the SUPPLEMENTARY


(optional) control’s aux. power load for all POWER SUPPLY
CONTROL TERMINAL STRIP
+ –
devices exceeds 600mA (suggested AUX. AUX. DATA DATA
– + IN OUT
UL Use a UL Listed,
power supply: AD12612). Connect 4 5 6 7
as shown in Figure 6. Be sure to
battery-backed supply for
UL installations. The battery connect the negative (–) terminal
supplies power to these on the power supply unit to
keypads in case of AC terminal 4 (AUX –) on the control.
power loss.
TO KEYPAD GRN WIRE
TO KEYPAD RED WIRE

TO KEYPAD GRN WIRE


TO KEYPAD RED WIRE
TO KEYPAD BLK WIRE

TO KEYPAD YEL WIRE

TO KEYPAD BLK WIRE

TO KEYPAD YEL WIRE

IMPORTANT:
The battery-backed power IMPORTANT: Keypads MAKE THESE
supply should have enough powered from supplies that do CONNECTIONS
power to supply the not have a backup battery will DIRECTLY TO
keypads with the UL SCREW
supp_pwr_supply-V0

required minimum standby not function if AC power is lost. TERMINALS AS


Make sure to power at least one SHOWN.
power time.
keypad in each partition from
the control’s auxiliary power
output. Figure 6. Using a Supplementary Power Supply

2-4
Mounting and Wiring the Control
Keypad Notes Set device addresses. Refer to the instructions included with the devices and set each
address according to the Table of Device Addresses.
See Keypad Programming Fields (fields *190-*196) in Section 4. Data Field
AR

RE
ME
D
Programming for details on enabling keypad addresses, assigning keypad partitions
AD

and selecting keypad sounding options.


Y

1 OF
F

2
4 MA
AW
AY
X
3
5 STA

IMPORTANT: Each keypad must be assigned a unique, predefined address, from 16 to


7 INST
TES
T
Y

ANT
6
8 CO
BYP
ASS
DE
REA
DY
9
0 CH
IME

23. The first keypad is address 16 (default = partition 1, all sounds enabled).
#

TOUCH SCREEN KEYPAD (AUI) NOTES:


• Use of AUI devices (e.g., 6270, Symphony) is independent from standard keypads and
does not affect the number of standard keypads the system can support.
• AUI devices must be set for address 1, 2, 5**, or 6** depending on which unit is
enabled in field *189. ** VISTA-20P series
• To ensure proper AUI device operation, use AUI devices with the following rev levels:
6270 series use version 1.0.9 or higher; 8132/8142 (Symphony) series use version
1.1.175 or higher.
Communication Device Connect the data in/data out terminals and voltage input terminals of the
(Long Range Radio) communication device to the control's keypad connection points.
Connections Set the device’s address to “03” following the instructions provided with the device.
• Use a compatible communication device (e.g., 7720PLUS, 7820, 7835C, or 7845C).
Wire Run Chart For Devices* Drawing Aux Power From The Control (12V+ & 12V–)
Wire TOTAL CURRENT DRAWN BY ALL DEVICES CONNECTED TO A SINGLE WIRE RUN
Size 50 mA or less 100 mA 300 mA 500 mA 600 mA
#22 900 ft (274m) 450 ft (137m) 150 ft (46m) 90 ft (27m) 75 ft (23m)
#20 1400 ft (427m) 700 ft (213m) 240 ft (73m) 140 ft (43m) 120 ft (37m)
#18 1500 ft (457m) 1100 ft (335m) 350 ft (107m) 220 ft (67m) 170 ft (52m)
#16 1500 ft (457m) 1500 ft (457m) 550 ft (168m) 350 ft (107m) 270 ft (82m)
* Includes Keypads, RF Receivers, Zone Expander/Relay Units, 4286 Phone Module, and Communication Device.
Maximum wire lengths for any device that is homerun to the control can also be determined from the Wiring Run Chart, based on the
current draw of that device alone.
The length of all wire runs for both partitions combined must not exceed 1500 feet (457m) when unshielded quad conductor cable is used
(750 feet if shielded cable is used). This restriction is due to the capacitive effect on the data lines when quad cable is used.

Table of Device Addresses


This Device Uses Address Reports as†† Enabled By…
RF Receiver 00 100 *56 zone programming: input device type entry
AUI 1 01 automatic if AUI enable field *189 enabled for AUI 1
AUI 2 02 automatic if AUI enable field *189 enabled for AUI 2
AUI 3 (VISTA-20P series) 05 automatic if AUI enable field *189 enabled for AUI 3
AUI 4 (VISTA-20P series) 06 automatic if AUI enable field *189 enabled for AUI 4
Communication Device (LRR) 03 103 automatic if communication device is enabled in field *29
4286 Voice Module 04 104 automatic if phone module access code field *28 enabled
Zone Expanders (4219/4229): *56 zone programming: input device type, entry 2, then:
module 1 (for zones 09 - 16) 07** 107 automatic if zone no. 9-16 set as AW type or relay assigned
module 2 (for zones 17 - 24) 08 108 automatic if zone no. 17-24 set as AW type or relay assigned
module 3 (for zones 25 - 32) 09† 109 automatic if zone no. 25-32 set as AW type or relay assigned
module 4 zones 33 - 40 10† 110 automatic if zone no. 33-40 set as AW type or relay assigned
module 5 zones 41 - 48 11† 111 automatic if zone no. 41-48 set as AW type or relay assigned
Relay Modules (4204): *79 output device programming: device address prompt:
module 1 12 112 entered at device address prompt
module 2 13 113 entered at device address prompt
module 3 14† 114 entered at device address prompt
module 4 15† 115 entered at device address prompt
Keypads: data field programming as listed below:
keypad 1 16 n/a always enabled for partition 1, all sounds enabled.
keypad 2 17 n/a data field *190
keypad 3 18 n/a data field *191
keypad 4 19 n/a data field *192
keypad 5 20 n/a data field *193
keypad 6 21 n/a data field *194
keypad 7 22 n/a data field *195
keypad 8 23 n/a data field *196
5800TM Module 28 n/a automatic
** address 07 not available if zone-doubling enabled
† 4219/4229 addresses 9-11 and 4204 addresses 14-15 apply to the VISTA-20P.
†† Addressable devices are identified by “1” plus the device address when reporting. Enter report code for zone 91 to enable addressable
device reporting (default = reports enabled). See field *199 for addressable device 3-digit/2-digit identification keypad display options.

2-5
Installation and Setup Guide
Hardwire Zones and Zone Expansion
Hardwire Zones Normally Open Zones/ N.O. EOLR Zones
1. Connect open circuit devices in parallel across the loop; for EOLR zones, connect the
EOLR across the loop wires at the last device.
2. Enable normally open/EOLR zones using Zone Programming mode, “Hardwire Type”
prompt.
Normally Closed Zones/ N.C. EOLR Zones
1. Connect closed circuit devices in series in the high (+) side of the loop; for EOLR
zones, connect the EOLR in series following the last device.
HI
LO
zones-001-V0
2. Enable normally closed/EOLR zones using Zone Programming mode, “Hardwire
Type” prompt.
End of Line Resistor (EOLR) Notes
• If the EOLR is not at the end of the loop, the zone is not properly supervised and the
system may not respond to an “open” on the zone.
• Zone 1 is intended for EOLR only.

UL For UL commercial burglar alarm installations, use EOLR zones.


Double-Balanced Zones Connect as shown below (resistor provided
(V20P only) for one device). 12 13 14

IMPORTANT: Double-balanced zones TAMPER


2k CONTACTS 2k
provide zone tamper protection, and should
be used as burglary zones only.
Do not use double-balanced zones as fire
TAMPER
2k 2k
zones. CONTACTS

zone-002-V0
2k 2k
ZONE 3 ZONE 4
Fig. 7. Typical Double Balanced Zones
Zone Doubling This feature provides two hardwired
(V20P only) normally closed zones for each standard 10 11

hardwired zone connected to the control’s


ZONE 2
terminals (but does not increase the total
3k
number of zones supported by the control). If
enabled (Zone Programming mode, ZONE 10

zone-004-V0
“Hardwire Type” prompt, option “3”), 6.2k
hardwire zones are automatically paired as Fig. 8. Typical Zone Doubling Wiring
shown in the table. Connect as shown
Zone Doubling Table
(resistors provided). Zone Paired with zone
• Do not use zone doubling for fire 2 10
zones. 3 11
4 12
NOTE: A short across the EOL (i.e., at 5 13
terminal) on either zone of a zone-doubled 6 14
pair or on a double-balanced zone causes a 7 15
tamper condition (displayed as CHECK plus 8 16
zone numbers). NOTE: Zone numbers used for zone doubling
cannot be used for anything else (ex. cannot
be used for 4219 zones)
Smoke Detectors 1. Connect up to 16 (10, if “clean me” option used) 2-wire smoke detectors across zone 1
terminals 8 (+) and 9 (-) as shown in the Summary of Connections diagram at the
TO ZONE 1 back this manual. Observe proper polarity when connecting the detectors.
TERMINALS
2. Connect an EOL resistor across the loop wires at the last detector.
3. Connect 4-wire smoke detectors (up to 16, depending on detector current draw) to
any zone from 2-8 as shown in Figure 7 (on next page).
8
2-WIRE
SMOKE 9
Power Reset: This control does not automatically reset power to 4-wire smoke
DETECTOR
detector zones, so you must use a relay (e.g., 4204, 4229), or on-board trigger to reset
5806-001-V0

HI
LO
ZONE 1 power (also required for fire verification). Do this by programming the designated
relay/trigger as zone type 54 (fire zone reset); see On-Board Trigger section for
other information.
NOTE: Maximum current on trigger 17 is 100mA.

2-6
Mounting and Wiring the Control
Smoke Detector Notes • Fire Verification (zone type 16): The control panel will “verify” a fire alarm by
resetting the smoke detectors after the first alarm trigger, and then waiting up to 90
seconds for a second alarm trigger. If the smoke detector or thermostat does not trigger
again, the control will disregard the first trigger, and no alarm signal will occur. This
feature eliminates false alarms due to electrical or physical transients.
SIA Installations: If using fire verification on zones other than zone 1, UL Fire Alarm
Listed relay accessories must be used to reset power as described in the Power Reset
paragraph above.
• The zone 1 alarm current supports only one smoke detector in the alarmed state.
• Clean Me Option: If enabled (field *174 = 1; *56 zone programming, response time
prompt = 3), certain ESL smoke detectors send “clean me” reports as appropriate. If
used, the maximum number of detectors is reduced to 10 (not standard 16). Refer to the
ESL documentation included with the smoke detector for information regarding
compatibility with the clean-me option.
• Do not use 4-wire smoke detectors on zone 1.
+ 5
RELAY
PROGRAM BLK _ + RED
AUX PWR RELAY
OUTPUT AS ZONE EOL
TERMINALS TYPE 54 POWER
(FIRE ZONE
RESET) N.O. SUPERVISION
_ 4 RELAY MODULE
N.C. A77-716B.
CONTACT OPENS USE N.O.
MOMENTARILY UPON CONTACT,
+ _ VIOLET WHICH CLOSES
FIRE ALARM RESET
WHEN POWER
4-WIRE SMOKE
OR COMBUSTION IS APPLIED.
DETECTOR
2000
OHMS
EOLR

4_wiresmk-007-V0
TO ZONE TERM. (+)
HEAT
DETECTOR
TO ZONE TERM. (_)

Figure 9a. 4-Wire Smoke Detector Using Relay for Power Reset

AUX PWR (+) 5


_
TO OUTPUT 17 (_)
BLK + RED
PROGRAM OUTPUT 17 EOL
FOR "OUT NORM POWER
LOW" = YES IN 79 MENU + N.O. SUPERVISION
MODE AND AS ZONE _ RELAY MODULE
TYPE 54 IN 4-WIRE SMOKE VIOLET A77-716B.
80 MENU MODE OR COMBUSTION USE N.O.
DETECTOR
2000 CONTACT,
OHMS WHICH CLOSES
EOLR WHEN POWER
IS APPLIED.

4_wiresmk-008-V0
TO ZONE TERM. (+)
HEAT
DETECTOR
TO ZONE TERM. (_)

Figure 9b. 4-Wire Smoke Detector Using Output 17 for Power Reset
4219/4229 Expansion 1. Connect each module to the control’s keypad terminals and set the device addresses.
Zones See the Table of Device Addresses to select an appropriate address for each module.
• VISTA-20P: Up to 40 expansion zones using up to 5 Zone Exp. Modules.
• VISTA-15P: Up to 16 expansion zones using up to 2 Zone Exp. Modules.
2. Connect sensors to the module’s loops. See Figure 8 on the following page.
• Use 1000 ohm end-of-line resistors at the end of loops connected to the 4219/4229
modules. (EOLRs used on the control terminals are 2000 ohms.)
• Expansion zones have normal response time (300–500 msec), except zone connected
to each module’s loop “A,” which can be set for fast response (10–15 msec).
3. If using relays with the 4229, connect the desired field wiring to the unit's relay contact

terminals.

2-7
Installation and Setup Guide

RELAY RELAY 4229


CONNECTOR 2 DIP SWITCH
FOR SETTING ADDRESS
AND ZONE "A" RESPONSE EITHER OR BOTH CAN BE USED TERMINALS ON
CONTROL PANEL
RELAY
1 TB2
4-PIN CONSOLE PLUG GRN DATA OUT (>)
NO C NC 4 (TERM 6)
TO CONTROL
TAMPER JUMPER POSITION
4229 IN CABINET BLK
3 (–) GROUND (TERM 4)
(NOT TAMPER) 4

ORG
BRN
GRY
3
WHT

YEL
VIO
BLK
4229 REMOTE RED
(TAMPER PROTECTED) 2 2 (+) 12VDC (TERM 5)
TB1
YEL DATA IN (<)

GND
1 1 FROM (TERM 7)
NO

NO
NC

NC
C 1 2 3 4 5 6 7 8 9 10 11 12 CONTROL

C
TERMINATE EACH
RLY RLY PROGRAMMED ZONE
2 1 REED WITH 1000 OHM (1K)
(TAMPER) END-OF-LINE RESISTOR
RELAYS OFF SWITCH (EACH ZONE'S MAX.
LOOP RESISTANCE
300 OHMS + EOL)
ZONES A B C D E F G H 4229-002-V0

Figure 10. Wiring Connections, 4219 & 4229 (4229 shown)

Installing the RF Receiver and Wireless Transmitter Zones


Compatible Receivers Use any ADEMCO 5800 Series Wireless Receivers, such as:
RF Receiver No. of Zones
5881L/5882L up to 8
5881M/5882M, up to 16
6150RF
5881H/5882H, VISTA-20P = up to 40 plus 16 buttons
5883, 6160RF VISTA-15P = up to 26 plus 8 buttons
Receiver Connections 1. Set Device Address to “00” (set all switches to the right, “off” position).
2. Mount the receiver, noting that the RF receiver can detect signals from transmitters
within a nominal range of 200 feet.
3. Connect the receiver's wire harness to the control's keypad terminals. Plug the
connector at the other end of the harness into the receiver. Refer to the installation
instructions provided with the receiver for further installation procedures regarding
antenna mounting, etc.
NOTE ANTENNAS
CIRCUIT BOARD IS MOUNTED IN (INSERT IN
CONTROL'S CABINET. GROUNDING RIGHT-HAND
LUGS (2) PROVIDED MUST BE INSERTED TERMINALS)
IN LEFT-HAND TERMINALS OF ANTENNA INSERT IN
BLOCKS AND SECURED TO CABINET. RIGHT- HAND
(SEE RECEIVER'S AND CONTROL'S TERMINALS
INSTRUCTIONS)

YELLOW
TO CONTROL'S
WIRELESS ZONE MODEL NO. IS INDICATED ON CIRCUIT BOARD
RED
BLACK
REMOTE KEYPAD
CONNECTION
NUMBERS 5882 DIP
GREEN POINTS.
LOCATION SWITCH
MOUNTING
VISTA-20P: HOLES INTERFERENCE
INDICATOR
WIRING OPENING

transmitter zones 9-48 LED


KNOCKOUT AREA
FOR SURFACE WIRING
button zones 49-64 CIRCUIT BOARD

VISTA-15P:
transmitter zones 9-34
button zones 49-56 SOCKET PLUG
TO RELEASE CIRCUIT BOARD,
REMOVE SCREWS AND
BEND BACK TABS 5881-003-V0

Figure 11. 5881/5882 RF Receiver (cover removed)


RF Receiver Notes Set the following options:
*22 RF Jam Option†
† These fields must be *24 RF House ID Code (if using wireless keypads) for each partition
enabled for Residential Fire, *67 Transmitter Low Battery Report Code†
UL Residential Burglar
*75 Transmitter Low battery restore report code†
Alarm, and UL Commercial
Burglar Alarm installations. • The receiver is supervised and a trouble report is sent (“CHECK 100” displayed) if
communication between the panel and receiver is interrupted, or if no valid RF signals
from at least one supervised transmitter are received within 12 hours.
If the receiver is mounted remotely:
• Place the RF receiver in a high, centrally located area for best reception.
• Do not locate the receiver or transmitters on or near metal objects. This will decrease
range and/or block transmissions.
• Do not locate the RF receiver in an area of high RF interference (indicated by frequent
or prolonged lighting of the LED in the receiver; random flicker is OK).
• Do not locate RF receiver closer than 10 feet from any keypads to avoid interference
from the microprocessors in those units.

2-8
Mounting and Wiring the Control
Installing a 5800TM • Use this module only if you are using one or more wireless bi-directional keypads or
Module keyfobs with a wireless Receiver; 5800TM is not necessary if using a Transceiver (e.g.,
5883).
• The 5800TM must be set to address 28 (cut red-W1 jumper).
• The 5800TM can be used in partition 1 only.
• For additional information regarding the 5800TM, refer to the 5800TM’s instructions.
1. Mount the 5800TM next to the RF receiver (between one and two feet from the
receiver’s antennas) using its accompanying mounting bracket. Do not install within
the control cabinet.
2. Connect the 5800TM to the control panel’s keypad connection terminals as shown on
the Summary of Connections diagram and set to address 28.
Installing the • Refer to the table of compatible devices at the back of this manual.
Transmitters • Supervised transmitters† send check-in signals to the receiver at 70-90 minute
intervals. If at least one check-in message is not received from each transmitter within
a 12-hour period, the “missing” transmitter number(s) and “CHECK” is displayed. (†
Hand-held transmitters, e.g., 5802, 5802CP, 5804, 5804BD, 5827, 5827BD, do not send
check-in signals.)
• To be sure reception of the transmitter's signal at the proposed mounting location is
adequate, perform a Go/No Go Test, described in the Testing the System section.
• Install transmitters in accordance with the instructions provided with each.
• Set 5827, 5827BD, 5804BD wireless keypads to the programmed House ID (field *24),
using its DIP switches (5827) or follow the instructions provided with the device.
• Use *56 or *58 Zone Programming Menu modes to program zone information and enroll
transmitters (VISTA-20P: zones 9-48, buttons 49-64; VISTA-15P: zones 9-34, buttons
49-56).
• Wireless Keys: Use Wireless Key Programming Templates section of the *58 Zone
Programming Menu mode to program zone information and enroll each button of the
wireless keys used. Once a wireless key is enrolled, it must be assigned to a user before
it becomes active. See Adding/Deleting Security Codes section for procedure.
ULC NOTE: In accordance with ULC standards, the RF supervision period for the VISTA-20PCN
and VISTA-15PCN is three hours for Fire zones (Zone Type 9 and 16) and 12 hours for all other zone
types.

UL The following transmitters are not intended for use in UL installations: 5802MN, 5802MN2, 5804,
5804BD, 5814, 5816TEMP, 5819, 5819WHS & BRS, and 5850.
The 5827BD and 5800TM can be used in UL Listed Residential Burglar installations.
Transmitter Battery Life • See Wireless Transmitter paragraph in the Limitations of This Alarm System
statement located at the end of this manual for information on transmitter battery
life.
• Some transmitters (e.g., 5802 and 5802CP) contain long-life but non-replaceable
batteries, and no battery installation is required. At the end of their life, the complete
unit must be replaced (and a new serial number enrolled by the control).
• Button-type transmitters (such as 5801, 5802, and 5802CP) should be periodically
tested for battery life.
• The 5802MN and 5804 Button Transmitters have replaceable batteries.
Do not install batteries in wireless transmitters until you are ready to enroll during
system programming. After enrolling, batteries need not be removed.

2-9
Installation and Setup Guide
Installing a Keyswitch
Keyswitch Connections 1. Connect the 4146 keyswitch's normally open momentary switch to a zone’s (2-8)
terminals. Remove the 2000 ohm EOL resistor if connected across the selected zone.
2. Using a standard keypad cable as shown:
Connect the yellow and white keyswitch wires to trigger connector pin 3 (+12V).
Connect the Red and Green LED wires to the appropriate output 17/output 18
trigger connector pins.
3. Connect a 2000 ohm EOL resistor across the momentary switch.
4. You can wire an optional closed-circuit tamper switch (model 112) in series with the
zone. If the switchplate is then removed from the wall, the tamper will open,
disabling keyswitch operation until the system is next disarmed from the keypad.
If the tamper is opened when the system is armed, an alarm will occur.
8-PIN TRIGGER CONNECTOR
1 3 4 5 6 7 8

KEY

(GREEN)
OUTPUT 17 (YELLOW)

(RED)

OUTPUT 18
+12 AUX.
STANDARD
4146 KEYSWITCH
KEYPAD
CABLE (ARMED)
RED
YELLOW

(READY)
GREEN
WHITE

820 820
ohms ohms

BLACK

RED
TAMPER
SWITCH (N. C.)
BROWN BROWN
11

TYPICAL ZONE
ON CONTROL LOCK
BOARD SWITCH (N. O.)
BLUE BLUE
10

00-trigcon-004-V1
EOLR
(use appropriate value)

Figure 12. Keyswitch Wiring Connections


Keyswitch Notes
UL A UL Listed keyswitch is required for fire installations and UL commercial and residential
burglar alarm installations. The Ademco 4146 keyswitch is UL Listed.
If a keyswitch is used on:
• an installation that transmits opening and closing signals, the keyswitch zone must be programmed
to send opening and closing signals.
• a UL commercial burglar alarm installation, the keyswitch’s tamper switch must be connected in to
the alarm system. This tamper switch zone must also be programmed for Zone Type 05 – Trouble
by Day / Alarm by Night.
• a fire alarm installation, the keyswitch must be located next to an alphanumeric display keypad.

• Use 4146 keyswitch or any N.O. keyswitch.


• Use only one keyswitch per partition.
• When using a keyswitch, the zone it is connected to is no longer available for use as a
protective zone.
• Use *56 Menu mode to program the keyswitch zone and assign it zone type 77.
• Use *80 Menu mode to program the LED functions: program outputs 17 and 18 for
system operation zone type 78 (red LED) and 79 (green LED) as appropriate (see
Output Device Programming section).

2-10
Mounting and Wiring the Control

Connecting Relay Modules, Powerline Carrier Devices and Output Triggers


4204/4229 Relay Modules 1. Mount either remotely or in the control panel.
2. Connect each module to the control’s keypad terminals and set the device addresses
as previously described in the Connecting Keypads and Other Addressable
Device section. Use the connector harness supplied with the module. Use standard
4-conductor twisted cable for long wiring runs.
VISTA-20P: Up to 16 relays (if no powerline carrier devices are used)
VISTA-15P: Up to 8 relays (if no powerline carrier devices are used)
3. Connect the desired field wiring to the unit's relay contact terminals.
4204 RELAY C

10 11 12
4 NC
DIP SWITCH TYPICAL
FOR SETTING DEVICE ADDRESS (SHOWN "OFF") NO
AND ENABLING/DISABLING TAMPER C

9
RELAY

UL 3 NC

8
COVER TAMPER (REED) SWITCH
For UL installation

7
NO
C

6
4-PIN TOUCHPAD PLUG RELAY
requirements, refer to the
2 NC

5
Installation Instructions for EITHER OR BOTH NO

4
the 4204. CAN BE USED
C

3
RELAY
TB1
1

2
NC

1
13 14 15 16 NO

YEL DATA IN TB2


FROM CONTROL
BLK
(–) GROUND
GRN DATA OUT
TO CONTROL
RED
(+) 12V 4204_conn-1-V0

Figure 13. 4204 Connections to Control


• Supervision: 4204 and 4229 modules are supervised against removal. The module’s
device address is displayed as follows if a module is disconnected from the control’s
terminals, or if the module cover is removed and the tamper jumper is installed:
Alpha: CHECK xx Wire Expansion
FAULT xx Wire Expansion
ALARM xx Wire Expansion
Fixed-Glass: lxx (or 91 if field *199 set for 2-digit display)
where “xx is the module’s address.
• If communication/tamper failure occurs on a device with zones wired to it, all zones on
the device will be displayed in their respective partitions.
Powerline Carrier 1. Install the powerline carrier devices according to the instructions included with each.
Devices VISTA-20P: Up to 16 devices (if no relays are used)
VISTA-15P: Up to 8 devices (if no relays are used)
UL Powerline Carrier
2. Use Programming Mode to enter the device house ID in data field*27, and enter the
unit code using *79 Output Device menu Mode.
devices and the 1361X10
Transformer are not UL 3. See connections diagram in the AC Wiring section for connecting the 1361X10
Listed for fire or burglary transformer to the triggers.
functions and are intended • You must use a 1361X10 Transformer instead of the 1321 Transformer.
for home automation. • The 1361X10 Transformer provides AC power to the control panel, and also supplies
signals from the control panel through the premises AC wiring to the Powerline
Carrier devices (which are plugged into AC outlets). You can then make devices that
are plugged into Powerline Carrier devices perform various functions in response to
commands you enter at the security system keypads.
Canada: Use the PSC04 Powerline Interface as shown below.
8-PIN TRIGGER CONNECTOR
1 3 4 5 6 7 8
KEY

(GREEN)
(BLUE)

(BLACK)
(RED)

(YELLOW)

(PURPLE)
(ORANGE)

X-10 PSC04
POWERLINE INTERFACE
OUTPUT 18
OUTPUT 17

+12 AUX.
GND (-)

SYNC
COM
DATA

1234

SA4120XM-1 CABLE
SYNC
BLK
MODULAR PHONE CORD (not supplied)
1 - BLACK
GRN
2 - RED
COM
3 - GREEN
4 - YELLOW
RED
DATA
YEL

Figure 14. PSC04 Powerline Interface Connections

2-11
Installation and Setup Guide
On-Board Triggers Connect field wiring to the desired trigger pin on the 8-pin trigger connector centrally
located above the terminal strip.
• If using 1361X10 transformer and powerline carrier devices, use the SA4120XM-1
cable (part of 4120TR Trigger Cable). See Wiring the AC Transformer section for
transformer connections.
• If only using the on-board triggers, you can use a 4-wire cable (N4632-4, supplied
with the control) as shown below.
8-PIN TRIGGER CONNECTOR
8-PIN TRIGGER CONNECTOR
1 3 4 5 6 7 8

KEY
1 3 4 5 6 7 8

KEY

(GREEN)
OUTPUT 17 (YELLOW)

(RED)
(BLACK)
(GREEN)

(BLACK)
(YELLOW)

(PURPLE)
(BLUE)
(ORANGE)
(RED)

OUTPUT 18
OUTPUT 18
OUTPUT 17

+12 AUX.
+12 AUX.

GND (-)
GND (-)

SYNC
COM
DATA

4-WIRE
SA412OXM-1
CABLE
CABLE
00-trigcon-003-V1 00-trigcon-005-V2

Figure 15a. On-Board Trigger Connector Figure 15b. On-Board Trigger Connector
with SA4120XM-1 Cable for Use With with 4-Wire Cable for Trigger Use Only
1361X10 Transformer

• Trigger outputs are normally high, and go low upon programmed condition.
• The outputs can be programmed for inverted operation (normally low, go high) using
*79 Menu mode.
• Program these triggers using *80/*81 Menu modes as you would for any other relay
output.
• When using these outputs, note:
pin 1 = output number 17 (trigger 1):
15 ohms to ground when closed (output low), open when off (output high, normal
default); can be used to reset smoke detector power (must set “output normal low
= yes” in *79 Menu mode, and set for zone type 54, fire zone reset, in *80 Menu
mode); or can support 12V relay module (e.g., Altronix AX-RBS) that draws less
than 100mA
pin 5 = output number 18 (trigger 2):
100 ohms to ground when closed (output low); open when off (output high,
normal default); or can support 12V relay module that draws less than 20mA

UL If on-board triggers are used, the wiring between the control unit and the UL Listed device must
be run in conduit, be no more than 3 feet apart and have no intervening barriers or walls.

2-12
Mounting and Wiring the Control

Phone Line/Phone Module, and Audio Alarm Verification (AAV) Connections


Phone Line Connect incoming phone line and handset wiring to the main terminal block (via an
RJ31X jack) as shown in the Summary of Connections diagram at the back of this
manual.
Wire colors represent the colors of the cable to the RJ31X jack.
4286 Phone Module 1. Make 12V (+) and (–) and data in and data out connections from the phone module to
the control, using the connector cable supplied with the phone module, then insert
the keyed connector at the other end of the connector cable into the header on the
phone module.
2. Connect Phone Module terminals as shown below. Use an RJ31X jack with a direct-
connect cord and make all connections exactly as shown.
3. Caller ID Units: If a Caller ID unit is being used, connect the unit directly to the
“Handset” terminals (21 & 22) on the control, as shown.
Compatibility: 4286 Phone INCOMING GROUND
Modules must have HANDSET TELCO LINE

{
{
software version WA4286-
TERMINALS
15.1 or higher (refer to the ON CONTROL
21 22 23 24 25 TO EARTH GROUND (COLD WATER PIPE, ETC.)
label on the square 4286 INCOMING TELCO LINE
CALLER ID

GREEN (TIP)

RED (RING)
microprocessor chip).

RING
TIP
UNIT DIRECT
CONNECT

(RING)
CORD

(TIP)
IMPORTANT NOTE FOR TIP
EXISTING INSTALLATIONS: RJ31X
RING
JACK
UL The 4286 modules
EXISTING WIRES
CONNECTED TO THE
"HANDSET" TERMINALS ON CA38A PREMISES ANSWERING
IN
are UL Listed only for use CONTROL MUST BE MOVED PLUG
CANADA
MACHINE AND PHONES
FROM THERE TO TERMINALS
on residential fire and UL 3 AND 4 ON THE 4286.
ANSWERING
residential burglar alarm

BROWN (T)
MACHINE

GREY (R)
installations.
4286 VIP MODULE
12345 6 7

LOUDER

*
VOLUME
KEYED
HEADER * NOTE: IF THE TELEPHONE HAS BUILT-IN CALLER ID,
THE CALLER ID FUNCTION MAY NOT WORK .

UNUSED
4286 TERMINAL ASSIGNMENTS
YELLOW: TO DATA OUT (term. 7) TO CONTROL
1 - TIP
CONNECTOR
NO CONNECTION
RED: TO AUX (+) (term. 5)
PANEL
TERMINALS
}
2 - RING
PHONE INPUT
3 - TIP
}

4286_cntrl-001-V1
WITH FLYING BLACK: TO AUX. GROUND (–) (term.4) USED FOR PHONE OUTPUT
GREEN: TO DATA IN (term. 6) 4 - RING
LEADS KEYPAD
5 - NO CONNECTION
CONNECTIONS
6-
7- } AUDIO OUT

Figure 16. 4286 Phone Module Wiring Connections


• Only one phone module can be used and it can only be connected to partition 1.
• The phone lines must be in service for the phone module to function, even when
accessing the system from an on-premises phone.
• If you are also using an Audio Alarm Verification (AAV) unit, refer to Audio Alarm
Verification (AAV) section for special wiring connections.
CAUTION: To reduce the risk of fire, use only No. 26 AWG or larger telecommunication
line cord for phone line connections.
Phone Module Problems If no touch tones are produced following access to the security system from on-premises
(this problem may arise in rare cases), it may be necessary to reverse the wires connected
to terminals 3 and 4 on the phone module and the wires connected to terminals (21) &
(22) on the control. The wiring diagram shows the wiring connections that will provide
proper operation in most cases.
Connection to the incoming telco line via a RJ31X jack and direct-connect cord, as shown,
is essential, even if the system is not connected to a central station. The 4286 will not
function if this is not done and an error signal (fast busy signal) will occur when trying to
access the system via the phone.
The house phone lines (gray and brown wires) must be wired to the phone module
terminals; not to the control terminals. Otherwise, an error signal (fast busy signal) will
occur when trying to access the system from an on-premises phone.

2-13
Installation and Setup Guide
Audio Alarm Verification Using the UVS System with UVCM Module
Connections The UVS system provides audio alarm verification via the phone line.
(UVS System) • Refer to the connection diagrams below. One diagram shows connections when a 4286
Phone Module is used, the other shows connections when the 4286 is not used.
• Connections use one of the on-board triggers.
• Set field *91 for AAV and program the appropriate output (output 17 or 18) using *80
Menu mode: select zone type 60 and output action 1 (close for 2 seconds).
• For voice session monitoring, connect an EOLR zone to UVCM module terminals 6 & 7,
and program the zone as zone type 81 (*56 Menu mode).
E.g., Using output 18 for the trigger, program an output function in *80 Menu mode as:
ZT = 60, P = 0, Action = 1, Device = 18
• Suggested AAV Module: ADEMCO UVS (shown) or Eagle 1250

UL UL installations using the AAV feature must use the ADEMCO UVCM module (part of the
ADEMCO UVS system).

TRIGGER
5 CONNECTOR

OUTPUT 18
EARTH
ZONE GROUND

CONTROL TERMINALS
AUXILIARY 4 5 21 22 23 24 25
AUDIO LEVEL
ADJUSTMENT GND
TRIM POT

+12VDC
EOL

UVCM RING
29 30 31 32 33 34

MODULE TIP

RED (R)

GREEN (T)

GREY (R) RJ31X


BROWN (T)
NOTE:
REFER TO UVCM MODULE
INSTRUCTIONS FOR
CONNECTIONS TO AUDIO
10 11

OPTIONAL
SPEAKERS AND MICROPHONE.
MONITORING ZONE
1 2 3 4 5 6 7 8
SWITCH BANK 2

CONNECTION
(USE ZONE TYPE 81)
9

SWITCH SWITCH TO
8

BANK 1 BANK 2 PREMISES


HANDSET
7

1 = ON
ON

1 = OFF
2 = OFF 2 = ON INCOMING
6

3 = OFF 3 = OFF PHONE LINE


FALLING VOICE TRIG
5

4 = OFF 4 = ON
SWITCH BANK 1
1 2 3 4 5 6 7 8

5 = OFF 5 = ON
4

6 = OFF 6 = ON
7 = ON
3

7 = OFF
8 = ON 8 = ON
2

GND

aav_uvcm-003-V0
ON

+12VDC IN
1

Figure 17a. Connection of AAV Unit When Not Using a 4286 Phone Module
TRIGGER
5 CONNECTOR
OUTPUT 18

EARTH
ZONE GROUND

CONTROL TERMINALS
AUXILIARY 4 5 21 22 23 24 25
AUDIO LEVEL
ADJUSTMENT
GND

+12VDC

TRIM POT
EOL

UVCM RING
29 30 31 32 33 34

RING
MODULE TIP
TIP

RED (R)

GREEN (T)

GREY (R) RJ31X


OPTIONAL
BROWN (T)
MONITORING
ZONE
NOTE: CONNECTION
REFER TO UVCM MODULE (USE ZONE
10 11

INSTRUCTIONS FOR TYPE 81)


CONNECTIONS TO AUDIO
1 2 3 4 5 6 7 8
SWITCH BANK 2

SPEAKERS AND MICROPHONE.


9

SWITCH SWITCH TO
8

BANK 1 BANK 2 PREMISES


HANDSET
7
ON

1 = OFF 1 = ON
2 = OFF 2 = ON
6

INCOMING
3 = OFF 3 = OFF PHONE LINE
FALLING VOICE TRIG
5

4 = OFF 4 = ON
1 2 3 4 5 6 7 8
SWITCH BANK 1

4286
5 = OFF 5 = ON
4

6 = OFF 6 = ON
7 = ON 4
3

7 = OFF
8 = ON 8 = ON
3
2

GND
aav_uvcm-004-V1
ON

+12VDC IN
1

Figure 17b. Connection of AAV Unit When Using a 4286 Phone Module

2-14
Mounting and Wiring the Control
Audio Alarm Verification Using the AVS System with AVS Module and AVST Remote Stations
Connections The AVS system provides audio alarm verification via the phone line or via AlarmNet if
(AVS System) the GSMV module is used as the communication device.
Refer to the instructions included with the AVS system for installation procedures. The
following is a summary.
Mounting the AVS Base Unit
As shipped, the AVS Base unit board
comes pre-mounted on its mounting
bracket, which is designed to mount
inside the control cabinet. SECURE
WITH TWO (2)
Refer to the diagram at right. SELF-TAP SCREWS
(SUPPLIED)
a. Position the mounting plate/PC
board assembly in the bottom of
the control’s cabinet. CABINET
SYSTEM TIE-WRAP
b. Slide the mounting plate to the BATTERY LOOP

right so that the plate’s left-hand


ON

ON 4 5
2 3
1
3 4
1 2

tang slides under the cabinet’s tie- TANG


BENEATH
MOUNTING
wrap loop. PLATE
c. Secure the assembly to the cabinet SLIDE ASSEMBLY TO RIGHT UNTIL
using the two self-tapping screws TANG SLIPS UNDER CABINET LOOP
AVS-003-V0

provided.
BATTERY NOTE: When using a 7AH battery, mount the battery vertically on the
bottom left-hand side of the cabinet, with the terminals facing down and right (negative
terminal closest to the PC board bracket).
Wiring the AVS to the Control
The AVS Base unit board has several terminal blocks for making connections to remote
stations, telephone lines, and to the control panel. The AVS base unit connects to the
control’s ECP terminals, with all other ECP devices connecting to the AVS base unit ECP
terminals. See the diagram on the next page for specific wiring connections.
IMPORTANT: The AVS should be the only ECP device connected to the control’s
ECP terminals. Connect all other ECP devices (keypads, expander modules, etc.) to
the ECP terminals on the AVS board.
Connecting an Optional GSMV Module
a. If using a GSMV module for 2-way voice operation, install the module according to its
instructions. NOTE: The module must be mounted within three feet of the control.
b. Connect the audio cable from the GSMV module to the Audio connector on the AVS
board. The audio cable is supplied with the GSMV module.
c. Complete all other GSMV wiring following the instructions included with that
module.
The following summarizes the programming steps for AVS operation (refer to the
Programming Guide for details of the AVS Quick Command options):
a. Install the AVS module according to its instructions.
b. Use one of the control’s AVS Quick Program commands as follows :
• installer code + [#] + 03: enable AVS operation without panel sounds on the AVST
• installer code + [#] + 04: enable AVS operation and enable panel sounds on the
AVST speaker
c. Use data field ∗55 Dynamic Signaling Priority to select the desired reporting paths.

2-15
Installation and Setup Guide

TIP

4
5
6
3
RING
TIP RJ31X

7
2
RING INCOMING

8
TELCO
PREMISES
PHONES
DIRECT
CONNECT
CORD

VISTA SERIES RESIDENTIAL CONTROL


KEYPAD

GRN

BRN
RED

GRY
TRIGGER HEADER
1 2 3 4 5 6 7 8

(EARTH GND
INCOMING
HANDSET PHONE LINE
ECP TERMINALS

(RING)

(RING)
(TIP)

(TIP)
DATA DATA
GND AUX IN OUT

AVST STATION

IMPORTANT:
GRN

SPEAKERS
RED
BLK

YEL
LED DO NOT CONNECT ANY OTHER
ECP DEVICES TO PANEL.
VOLUME / ID
USE AVS BASE UNIT ECP
BUTTON TERMINALS FOR OTHER ECP DEVICES.
SUPPLIED HARNESS

AAV
DATA
YEL
AUDIO
GRN
GND
KEYPAD BLK
RED +VDC

MIC

FOR EXTERNAL ANTENNA

50 OHM, MMCX ONLY

AUDIO CABLE

TB 1
1
Honeywell
2
RSSI
MODE 1
MODE 2
WEB
GPPS
GSM

3
4
5
6
7
8
9
10
11
AVS BASE UNIT
(200 FT. MAX)

LED
GSMV
(OPTIONAL)
PROGRAM MODE PHONE
CALLBACK MODE DIP SW GRY
RING
ON ON DEVICE ADDRESS HANDSET
(ADDRESS 8 BRN
1 2 3 4 1 2 3 4 5
TIP
SHOWN)
PANEL TRIGGER
MODE TIP
NOT INCOMING
NORMAL MODE USED PHONE LINE
RING
BASE UNIT AUDIO CONNECTOR
DEVICE ADDRESS
AAV PANEL ECP
VISTA-15P = 8 RED BLK GRN YEL RED BLK GRN YEL RED BLK GRN YEL

ON

1 2 3 4 5
BATTERY
TO ALL
VISTA-20P = 11 OTHER ECP
DEVICES
ON

1 2 3 4 5

AVS-001-V0

Figure 18. Connections for the AVS System

2-16
S E C T I O N 3

System Communication and Operation


Panel Communication with Central Station
This system accommodates several formats for reporting alarms and other system conditions to the Central
Station. The process of a successful transmission consists of both the method of communication between the
control panel and the Central Station receiver; and the actual way the information is sent and displayed at
the Central Station.
When the panel calls the Central Station receiver, it waits to hear a “handshake” frequency from the receiver
to confirm that the receiver is on-line and ready to receive its message. Once the panel hears the handshake
it is programmed to listen for, it sends its message. The panel then waits for a “kissoff” frequency from the
receiver acknowledging that the message was received and understood.
If the handshake frequency is not given or is not understood by the panel, the panel will not send its
message. Once the handshake frequency is received and understood by the panel, the panel sends its
message. If there is an error in the transmission (the receiver does not receive a “valid” message), the kissoff
frequency is not given by the Central Station receiver.
The panel makes a total of eight attempts to the primary telephone number and eight attempts to the
secondary telephone number (if programmed) to get a valid message through. If the panel is not successful
after its numerous attempts, the keypad displays COMM. FAILURE (on alpha keypads) or FC (on fixed-
word keypads).

Report Code Formats


The following chart indicates the types of (handshake/kissoff) frequencies that the panel supports and the
different formats that can be sent with each.
FORMAT HANDSHAKE TRANSMITS DATA KISSOFF TRANSMIT TIME
Low Speed 1400 Hz 1900Hz (10PPS) 1400 Hz Under 15 secs
3+1, 4+1, 4+2 (Standard report)
Sescoa/Rad 2300 Hz 1800Hz (20PPS) 2300 Hz Under 10 secs
3+1, 4+1, 4+2 (Standard report)
Express 1400–2300 Hz DTMF (10 cps) 1400 Hz Under 3 secs
4+2
Contact ID 1400–2300 Hz DTMF (10 cps) 1400 Hz Under 3 secs

The following table describes each format in greater detail.


FORMAT TYPE DESCRIPTION
3+1 and 4+1 Comprises a 3- (or 4-) digit subscriber number and a single-digit report
Standard Formats code (e.g., Alarm, Trouble, Restore, Open, Close, etc).
3+1 and 4+1 Comprises a 3- (or 4-) digit subscriber number and a two-digit report code.
Expanded Formats The first digit is displayed on the first line. On the second line, it is repeated
3 (or 4) times and is followed by the second digit. This is the “expanded”
digit.
4+2 Format Comprises a 4-digit subscriber number and 2-digit report code.
ADEMCO Contact ID Comprises a 4- or 10-digit subscriber number (depending on format
Reporting Format selected), 1-digit event qualifier (“new” or “restore”), 3-digit event code, and
3-digit zone number, user number, or system status number (see the
following page).

3-1
Installation and Setup Guide

The following table lists codes for reports sent in different formats:
Code for Code for
Type of 3+1/4+1 3+1/4+1 Code for
Report Standard Expanded 4+2
Alarm SSS(S) A SSS(S) A SSSS AZ
AAA(A) Z
Trouble SSS(S) T SSS(S) T SSSS Tt
TTT(T) t
Bypass SSS(S) B SSS(S) B SSSS Bb
BBB(B) b
AC Loss SSS(S) E SSS(S) E SSSS EAC
EEE(E) AC
Low Batt SSS(S) L SSS(S) L SSSS LLB
LLL(L) LB
Open SSS(S) O SSS(S) O SSSS OU
OOO(O) U
Close SSS(S) C SSS(S) C SSSS CU
CCC(C) U
Test SSS(S) G SSS(S) G SSSS Gg
GGG(G)g
Restore SSS(S) R SSS(S) R SSSS RZ
Alarm RRR(R) Z
AC Restore SSS(S) RA SSS(S) RA SSSSRA Ac
RARARA(RA)Ac
LoBat Res. SSS(S) RL SSS(S) RL SSSS RLLB
RLRLRL(RL)LB
Trouble Res. SSS(S) RT SSS(S) RT SSSS RTt
RTRTRT (RT)t
Bypass Res. SSS(S) RB SSS(S) RB SSSS RBb
RBRBRB (RB)b

Where:
SSS or SSSS = Subscriber ID C= Close Code–1st Digit
A= Alarm Code–1st digit U= User Number (in hex)
Z= Typically Zone Number*–2nd digit Gg = Test Code (1st & 2nd digits)
Tt = Trouble Code (1st & 2nd digits) R= Restore Code (Alarm)
Bb = Bypass Code (1st & 2nd digits) RTt = Restore Code (Trbl) 1st & 2nd digits
EAC = AC Loss Code (1st & 2nd digits) RBb = Restore Code (Byps) 1st & 2nd digits
LLB = Low Battery Code (1st & 2nd digits) RAAC = Restore Code (AC) 1st & 2nd digits
O = Open Code–1st Digit RLLB = Restore Code (Bat) 1st & 2nd digits
*Zone numbers for: ✱ & #, or B = 99; 1 + ✱, or A = 95; 3 + #, or C = 96; Duress = 92

3-2
System Communication

Ademco Contact ID®


The Ademco Contact ID® Reporting Format comprises the following:
4-digit or 10-digit subscriber number (depending on format selected).
1-digit event qualifier (“new” or “restore”).
3-digit event code.
2-digit Partition No.
3-digit zone number, user number, or system status number (see the following page).
Ademco Contact ID® Reporting takes the following format: CCCC(CCCCCC) Q EEE GG ZZZ
where: CCCC(CCCCCC) =Customer (subscriber) ID
Q = Event qualifier, where: E = new event , and R = restore
EEE = Event code (3 hexadecimal digits)
Note: For a complete list of event codes, refer to the central office
receiver manual.
GG = Partition Number (system messages show “00”)
ZZZ = Zone/contact ID number reporting the alarm, or user number for
open/close reports. System status messages (AC Loss, Walk Test, etc.)
contain zeroes in the ZZZ location.
TABLE OF CONTACT ID EVENT CODES
(some event codes may not apply to certain control panels)

Code Definition Code Definition


110 Fire Alarm 381 RF Sensor Supervision
121 Duress 382 Supervision Auxiliary Wire Zone
122 Alarm, 24-hour Silent 383 RF Sensor Tamper
123 Alarm, 24-hour Audible 384 RF Sensor Low-battery
131 Alarm, Perimeter 393 Clean Me
132 Alarm, Interior 401 Disarmed, Armed AWAY, Armed
134 Alarm, Entry/Exit MAXIMUM
135 Alarm, Day/Night 403 Schedule Arm/Disarm AWAY
137 Alarm, Tamper 406 Cancel by User
143 Alarm, Expansion Module 407 Remote Arm/Disarm (Downloading)
145 ECP Module cover tamper 408 Quick Arm AWAY
146 Silent Burglary 409 Keyswitch Arm/Disarm AWAY
150 Alarm, 24-Hour Auxiliary/Monitor zone 441 Disarmed/Armed STAY/INSTANT,
162 Carbon Monoxide Quick-Arm STAY/INSTANT
301 AC Power 442 Keyswitch Arm/Disarm STAY
302 Low System Battery/Battery Test Fail 459 Recent Closing
305 System Reset (Log only) 570 Bypass
321 Bell/Siren Trouble 601 Manually Triggered Dialer Test
333 Trouble, Expansion Mod. Supervision 602 Periodic Test
341 Trouble, ECP Cover Tamper 606 AAV to Follow
344 RF Receiver Jam 607 Walk Test Entered/Exited
351 Telco Line Fault 623 Event Log 80% Full
353 Long Range Radio Trouble 625 Real-Time Clock was Changed (log only)
373 Fire Loop Trouble 627 Program Mode Entry (log only)
374 Exit Error Alarm 628 Program Mode Exit (log only)
380 Global Trouble, Trouble Day/Night 642 Latch Key (log only)
750 - Reserved for Configurable Zone Type
789 report codes (check with central station
when using these codes)

3-3
Installation and Setup Guide

Uploading/Downloading via the Internet


UL: Up/downloading via the Internet has not been evaluated by UL.
This control, when used with a compatible Internet/Intranet Communication Device, supports
upload/download programming capability via the Internet using the AlarmNet network or, depending on
the communication module used, a Private local area network (Intranet). This allows site maintenance
independent of central station monitoring, and modification to sites globally via the Internet. Depending on
the module used, Internet connection from the protected premises is either via high speed (broadband)
cable or phone service, or via the GSM/GPRS digital cellular network (GSM modules).
Refer to the instructions provided with the communication module for information regarding its
installation, programming, and registration. The System Requirements table below lists two sets of system
requirements, depending upon whether you intend to communicate over the Internet or whether you are
communicating over a Private LAN (Intranet).
Compatible Communication Modules: The following modules support Internet uploading/downloading,
but future modules may also provide Internet upload/download support; refer to the module’s instructions
for compatibility. Compatible Modules: 7845i-ent, 7845i-GSM, 7845GSM
System Requirements
Internet Communication Intranet (Private LAN) Communication, if applicable*
At the Installation Site: At the Installation Site:
• Appropriate Internet Communication Module • Internet/Intranet Communication Module
• 7720P Programmer • 7720P Programmer
• Broadband Internet Access (for wired modules) • Ethernet Network Connection
• Broadband (Cable/DSL) Modem (for wired modules) • IP compatible Control Panel
• Broadband (Cable/DSL) Router (for wired modules if At the Downloading Office:
connecting more than one device to the Internet)
• 7810iR-ent IP Receiver
• IP compatible Control Panel • Internal Router
At the Downloading Office: • Computer(s) running the following software:
• Broadband Internet Access - Compass Downloading Software version that supports
• Broadband (Cable/DSL) Modem IP upload/download for this control.
• Broadband (Cable/DSL) Router (optional, if connecting - Compass Connect Data Server Application
more than one device to the Internet) - Compass Connect Control Server Application
• Computer running Compass Downloading Software * see module’s instructions for applicability for LAN usage
version that supports Internet upload/download for this (ex. 7845i-ent supports LAN)
control. NOTE: Compass, the Compass Connect Data Server, and
the Compass Connect Control Server applications may all
be installed on the same computer if desired. If they are
installed on one computer, the computer must have a fixed
IP Address.

To set up the control panel, do the following:


1. Connect the module to the control panel’s ECP (keypad) terminals.
2. Internet Users: For wired modules, connect the module to the Internet via a cable/DSL modem and router.
Intranet Users: Connect the module to the Intranet (LAN) via the appropriate Ethernet connection.
3. Enable the module as a Long Range Radio in the control panel (programming field *29) to enable alarm
reporting and module supervision.
4. Set the module for address 3.
5. Program the module as required using the module’s programming methods (ex. 7720P programmer).
6. Register the module with AlarmNet. The module must be registered before downloading or alarm
reporting can take place.
To perform upload/download functions:
1. Connect the computer to the Internet and start the Compass downloading software.
2. Open the control’s account, then select the Communications function and click the Connect button.
3. At the Connect screen, check that the control’s MAC address is entered and the TCP/IP checkbox is
checked.
4. Click Connect. The Internet connection to the control is made automatically via AlarmNet.
5. Once connected, use the Compass downloading software as normal to perform upload/download functions.

3-4
System Operation

System Security Codes


The systems provides one Installer code, one System Master code, plus a set of other user codes intended
for other users of the system. These codes can each be assigned one of 5 authority levels, which determine
the functions each code can perform as listed in the table below.
VISTA-20P: Provides 48 security codes (plus Installer code), including one System Master code, two
Partition Master codes, and 45 general user codes.
VISTA-15P: Provides 32 security codes (plus Installer code), including one System Master code and 31
general user codes.
Authority Levels (can be assigned to users 03-49 only; users 1 and 2 cannot be changed)
Level User No. Functions
Installer 01 (default=4112) perform all security functions except can disarm only if used to arm; can
enter program mode; can change System Master code; cannot assign any other user
codes
System 02 (default 1234) only one system master code per system; can perform all security
Master functions, add/delete users in either partition, change system master code, view event
log, set system clock, program keypad macro, program scheduled events, activate output
devices (triggers/relays)
Partition P1 = 03 VISTA-20P. Same as Master, except add/delete users limited to assigned partition
Master P2 = 33 only, (these users can be assigned different authority levels, if desired; any user can be
(default) assigned the partition master authority level)
0-User 03-49 (V20P) perform security functions (arm, disarm, etc.) only; cannot add/delete users, view event
03-33 (V15P) log, set system clock or program scheduled events
1-Arm Only see “user” arm system only
2-Guest see “user” can disarm the system only if it was used to arm the system
3-Duress see “user” performs security functions, but also silently sends a duress message to the central
station; reports as duress code user number.
4-Partition see “user” VISTA-20P. See Partition Master paragraph above; used to assign other user numbers
Master as partition masters

Refer to the user guide for detailed procedures on adding/deleting security codes and changing user
attributes.
The following is a brief description of how to add user codes.
Changing the System Master code...
Using Installer code: Installer code + [8] + 02 + new code
Using current System Master code: System Master code + [8] + 02 + new code + new code again
Adding a User Code: Master code + [8] + 2-digit user no. + user’s code
Deleting a User Code: Master code + [8] + 2-digit user no. + [#] [0]
Assigning Attributes: Master code + [8] + 2-digit user no. + [#] [attribute no.] + value
Attributes: Values
1 = Authority Level 0-4 (see Authority Level table above)
2 = Access Group 0-8 (0 = not assigned to a group)
3 = Active Partition(s) 1, 2, 3 (common)
for this user; Enter partitions consecutively if more than one and press [#] to
end the entries.
4 = RF Zone No. Assigns user number to button type zone for arm/disarm
(keyfob must be enrolled in system first; see Wireless Key
Templates section).
5 = Open/Close Paging 1 for yes, 0 for no

3-5
Installation and Setup Guide

Keypad Functions
The following is a brief list of system commands. For detailed information concerning system functions,
refer to the User's Manual. For Touch Screen style keypad users, refer to the separate Touch Screen
keypad (AUI) User’s Guide.
Voice Keypads
The 6150V/6160V Voice Keypads provide the following features:
• Message Center, which lets the user record and playback one message.
• Voice Status, which can announce system status by using the STATUS key.
• Voice Chime, which can alert users to the opening of doors/windows while the system is disarmed.
Refer to the User Guide for specific procedures for activating and using these features.
Keypad Commands
Function Description
Silence Burglary Pressing any key will silence the keypad sounder for 10 seconds. Disarming the system
Alarms (security code + OFF) silences both keypad and external sounders.
Silence Fire or Carbon Press the OFF [1] key to silence the keypad sounder and, for fire alarms, the external
Monoxide Alarms sounder. The detector sounding stops when the contaminated air is cleared from the
detector; see the detector’s instructions for further information.
Quick Arm If enabled (field ∗21), you can press [#] in place of the system's security code, plus the
desired arming key (Away, Stay, Instant, Maximum)
Single-Button arming If programmed (*57 Function Key menu mode), lettered keys A-D can be used for arming,
using options 3-AWAY, 4-STAY, 5-NIGHT-STAY, or 6-Step-Arming
If used, no security code is required to arm the system.
Alarm Memory When the system is disarmed, any zones that were in an alarm condition during the armed
period will be displayed. To clear this display, simply repeat the disarm sequence (enter
the security code and press the OFF key) again.
Arming Away Enter code + AWAY [2] or simply press appropriate lettered key on the keypads (see
“Single-Button Arming” above). If the “Auto-Stay Arm” feature is enabled (field *84) and
the entry/exit door is not opened and closed within the programmed exit delay time, the
system will automatically arm in STAY mode if armed from a wired keypad (non-RF
device). If the door is opened and closed within the exit delay period, the system arms in
AWAY mode.
Arming Stay Enter code + STAY [3] or simply press appropriate key on the keypads (see “Single-Button
Arming” above). See “Arming Away” above for Auto-Stay arming feature.
Arming Night-Stay Enter code + STAY [3] + STAY [3] or simply press appropriate key on the keypads (see
“Single-Button Arming” above).
Arming Instant Enter code + INSTANT [7].
Arming Maximum Enter code + MAXIMUM [4] or simply press appropriate lettered key on the keypads (see
“Single-Button Arming” above).
Disarming Enter code + OFF [1]. If entry delay or an alarm is active, you do not need to press OFF.
Bypassing Zones Enter code + BYPASS [6] + zone number(s).
Forced (Quick) Bypass To automatically bypass all faulted zones, use the “Quick Bypass” method. Enter code +
BYPASS + [#], then wait for all open zones to be displayed. Arm when display indicates
“ZONE BYPASSED” and “READY TO ARM”.
Chime Mode Enter code + CHIME [9]. To turn chime off, enter code + CHIME again.
Activate Output If relay outputs (via a 4204, or 4229), or Powerline Carrier devices are used, two keypad
Devices entries available to the user are included. If programmed, these entries can be used to
manually activate or deactivate the device(s) for starting or stopping some action, such as
turning lights on or off, etc. These keypad entries are:
[Security Code] + # + 7 + [2-digit Device #] activates (starts) that device.
[Security Code] + # + 8 + [2-digit Device #] deactivates (stops) that device.

3-6
System Operation
SUMMARY OF ARMING MODES
Arming Mode Features for Each Arming Mode
Exit Delay Entry Delay Perimeter Armed Interior Armed
AWAY Yes Yes Yes Yes
STAY Yes Yes Yes No
NIGHT-STAY Yes Yes Yes only those zones
listed in Night-
Stay zone list
INSTANT Yes No Yes No
MAXIMUM Yes No Yes Yes

Panic Keys
There are three Panic keys (A, B, and C) that, if programmed, can be used to manually initiate alarms and
send a report to the central station.
Each key can be programmed for 24-hour Silent, 24-hour Audible, Fire, or Personal Emergency responses.
The programmed Panic response is activated when the appropriate key is pressed for at least 2 seconds.
The Panic keys are identified by the system as follows:
Keys Displayed as Zone
∗/1)
[A] (∗ 95
∗/#)
[B] (∗ 99
[C] (3/#) 96
IMPORTANT: For a Silent panic function (if programmed) to be of practical value, you must program a
report code for the zone and the system must be connected to a central station.

Setting the Real-Time Clock


IMPORTANT: The Real-Time Clock must be set before the end of the installation.
NOTE: All partitions must be disarmed before time/date can be set.
Set the time and date by doing the following:
1. +[#] + [6] [3] Alpha Display:

(Master Code) DISARMED


READY TO ARM

2. Press [∗] when the time/date is displayed.


TIME/DATE SAT
A cursor appears under the first digit of the hour.
04:04PM 10/17/00
To move cursor ahead, press [∗]. To go back, press [#].
Current time display
• Enter the 2-digit hour setting.
• Enter the 2-digit minute setting.
TIME/DATE SAT
• Press [1] for PM or [2] for AM.
04:04P2000/10/17
• Enter the last two digits of the current year. Time/date editing display
• Enter the 2-digit month setting.
• Enter the 2-digit day setting.
3. To exit, press [∗] when cursor is at the last digit, or wait 30 seconds.

3-7
Installation and Setup Guide

Various System Trouble Displays


Alpha Display Fixed Disp. Meaning
ALARM CANCELED CA will appear if an exit or interior zone contained a fault during closing at the
time the Exit Delay ended (e.g., exit door left open), but the system was
disarmed during the Entry Delay time. The alarm sounder and keypad sound
continuously, but stop when the system is disarmed. No message will be
transmitted to the central station.
EXIT ALARM EA appears when Exit Delay ends if an exit or interior zone contained a fault
during closing. The alarm sounder and keypad sound continuously until the
system is disarmed (or timeout occurs). An “Exit Alarm” message is sent to the
central station. Also results if an alarm from an exit or interior zone occurs
within 2 minutes after the end of an Exit Delay.
CHECK CHECK indicates that a problem exists with the displayed zone(s) and requires
attention.
ALARM 1xx 1xx indicates that communication between control and a zone expander or wireless
FAULT 1xx 1xx receiver is interrupted, where “xx” is the device address. Check the wiring and
CHECK 1xx 1xx DIP switch settings on the units.
91 If field *199 is set to “1,” all ECP module problems are displayed as “91.”
If there are wireless sensors in the system, the Check condition may also be
caused by some change in the environment that prevents the receiver from
receiving signals from a particular sensor.
SYSTEM LO BAT BAT with no zone number indicates that the system's standby battery is weak.
LO BAT BAT with a zone number and a once-per-minute beeping at the keypad indicates
that a low-battery condition exists in the wireless sensor displayed (zone “00”
indicates a wireless keypad). If the battery is not replaced within 30 days, a
“CHECK” display may occur.
NOTE: Some wireless sensors contain a non-replaceable long-life battery which
requires replacement of the entire unit at the end of battery life (e.g., Nos.
5802, 5802CP).
TELCO FAULT 94 Telephone Line Failure, indicates that a monitored telephone line (if
programmed in field *92) has been cut or disconnected. Depending on how the
system was programmed, the keypad may also produce a trouble sound, and
the external sounder may be activated. Silence by entering installer code +
OFF.
Busy-Standby dl If this remains displayed for more than 1 minute, the system is disabled.
Modem Comm CC The system is in communication with the central station for change of function
or status verification.
no display no display Power Failure
If there is no keypad display at all and the LEDs are unlit, operating power
(AC and battery) for the system has stopped and the system is inoperative.
If the message “AC LOSS” (Alpha display keypads) or “NO AC” (Fixed-Word
display keypads) is displayed, the keypad is operating on battery power only.
If the battery standby capacity is used up during a prolonged AC power outage,
the control's power will shut down to minimize deep discharge of the battery.
Comm. Failure FC A communication failure has occurred.
Open Circuit 0C The keypad is not receiving signals from the control; sees an open circuit.
Long Rng Trbl bF Backup LRR communication failure.
Bell Failure 70 Bell supervision failure.
RCVR Jam 90 RF jam detected.
KEYPAD LOW BAT 00 BAT Wireless keypad low battery.
Phone Okay Cd The dialer test has been successful (CID code 601).
Dialer Off d0 The dialer is disabled.
Test in Progress dd Walk test mode is active(CID code 607).
Upload Completed dC The upload or download session was completed.
Upload Failed dF The upload or download session failed before completion.

3-8
S E C T I O N 4

Testing the System


About Test Procedures
After the installation is complete, you should perform the following tests:
System Test: Checks that all zones have been installed properly and the system responds to faults.
Dialer Test: Checks that the phone connection to the central station is working properly.
Go/No Go Test: Checks that transmissions can be received from transmitters. Should be performed
before permanently mounting transmitters.
RF Sniffer Mode: Checks that RF transmitter serial numbers have been properly enrolled.
Battery Tests: Automatic battery tests are performed by the system.

System Test
NOTE: Test mode can be entered from any keypad. However, faulted zones appear only on those keypads
assigned to the partition to which the zone is assigned (i.e., partition 1 zones appear only on partition 1
keypads, etc.). To see another partition’s faulted zones, view a keypad assigned to that partition or use the
GOTO command (code +[∗] + partition number 0-3, where 0 is the keypad’s home partition).
With the system in the disarmed state, check that all zones are intact (not faulted). Doors and windows
with contacts should be closed, PIRs should be covered (use a cloth to mask them temporarily if necessary).
If a “NOT READY” message is displayed, press [∗] to display the faulted zone(s). Restore faulted zone(s) if
necessary, so that the “READY” message is displayed.
1. Enter Installer Code + 5 [TEST] , then press “0” at the prompt to start Walk Test mode.
1=DIAL, 0=WALK (no special display on Fixed-Word keypads)

The following will be displayed on the initiating keypad and a Contact ID report will be sent (code 607):
TEST IN PROGRESS (“dd” displayed on Fixed-Word Display Keypads)

2. Upon entering the system test mode, the outside sounder should sound for 1 second.
If the backup battery is discharged or missing, the sounder may not turn on and a “LOW BATTERY”
report will be transmitted with a “TEST” report.
The keypad will beep about every 30 seconds as a reminder that the system is in the Test mode.
NOTE: Wireless motion detectors (Passive Infrared units) will send signals out only if they have been
inactive for 3 minutes (conserves battery life).
3. Test all sensors using the procedure described in the User’s Guide “Testing the System” section.
4. After checking sensors, turn off the test mode by entering installer code + OFF.
NOTE: Test mode automatically ends after 4 hours. During the final 5 minutes (after 3 hours 55
minutes of Test mode), the keypad emits a double-beep every 30 seconds to alert that the end of Test
mode is nearing.

Checking Transmitter Enrollment (Sniffer Mode)


Use this mode to verify that all transmitters have been properly programmed. Make sure both partitions
are disarmed before trying to enter this mode, since this is a system-wide command.
1. From a keypad in partition 1, press [Installer code] + [#] + 3.
NOTE: If the communicator is in the process of sending a report to the central station, the system will
not go into the Sniffer mode. If so, wait a few minutes, and try again.
The keypads in both partitions will display all zone numbers of wireless units (in both partitions)
programmed into the system. Fault each transmitter in turn, causing each one to send a signal. As the
system receives a signal from each of the transmitters, the zone number of that transmitter disappears
from the display.
2. After all transmitters have been checked, exit the sniffer mode by keying [Installer code] + OFF.
IMPORTANT: Sniffer mode does not automatically expire. You must manually exit Sniffer mode (by
entering [Installer code] + OFF) to return to normal operation.

4-1
Installation and Setup Guide

NOTES: • All BR type units must physically be activated to clear the display.
• When one button of a transmitter (RF, UR, or BR) is activated, all zones assigned to other
buttons on that transmitter are cleared from the display. This also applies to 5816 and
5817 transmitters, which have multiple loops (zones).
• Any transmitter that is not “enrolled” will not turn off its zone number.

Go/No Go Test Mode


The Go/No Go Test verifies adequate RF signal strength from the proposed transmitter location, and allow
you to reorient or relocate transmitters if necessary, before mounting the transmitters permanently. This
mode is similar to the Transmitter Test mode, except that the wireless receiver gain is reduced. This will
enable you to make sure that the RF signal from each transmitter is received with sufficient signal
amplitude when the system is in the normal operating mode.
1. Enter [Installer code] + [#] + 4 from the partition being tested. For multi-partition systems, repeat this
test for each partition.
2. After you have placed transmitters in their desired locations and the approximate length of wire to be
run to sensors is connected to the transmitter's screw terminals (if used), fault each transmitter. Do not
conduct this test with your hand wrapped around the transmitter, as this will cause inaccurate results.
a. The keypad will beep three times to indicate signal reception and display the zone number.
b. If the keypad does not beep, you should reorient or move the transmitter to another location.
Usually a few inches in either direction is all that is required.
4. If each transmitter produces the proper keypad response when it is faulted, you can then permanently
mount each of the transmitters according to the instructions provided with them.
5. Exit the Go/No Go Test mode by entering: [any user code (partition-specific)] + OFF.

Dialer Communication Test and Periodic Test Reports


1. Enter Installer Code + 5 [TEST], then press “1” at the prompt to start the Dialer Test (checks phone line
integrity only; does not confirm report transmissions).
1=DIAL, 0=WALK (no special display on Fixed-Word keypads)

The following will be displayed (accompanied by 2 beeps) if test is successful:


PHONE OKAY (“Cd” displayed on Fixed-Word Display Keypads)

A Contact ID report will also be sent (code 601)


If the dialer test is unsuccessful, “COMM FAILURE” (or FC) is displayed.
2. Enter Installer code + OFF to clear the display and exit.
Automatic Periodic Test Report
The system can be set to automatically send test reports (enabled in field *64; Contact ID code 602) at
specified intervals. Frequency of the reports is set in Scheduling mode (event 11) or by the following key
commands: installer code + [#] + 0 + 0 = test report sent every 24 hours
installer code + [#] + 0 + 1 = test report sent once per week
installer code + [#] + 0 + 2 = test report sent every 28 days
Each mode sets schedule 32 (VISTA-20P) or schedule 08 (VISTA-15P) to the selected repeat option; the first
test report is sent 12 hours after command.
To ensure that test reports are sent at the times expected, set the Real-Time Clock to the proper time
before entering the test report schedule command.
Automatic Standby Battery Tests
1. An automatic test is conducted every 3 minutes to ensure that a standby battery is present and
properly connected. If a battery is not present or is not properly connected, a “LOW BATTERY”
message is displayed and, if so programmed, will be reported to the central station.
2. A battery capacity test is automatically conducted for 2 minutes every 4 hours, beginning 4 hours after
exiting the Programming mode or after powering up the system. In addition, entry into the Test mode
will also cause a battery capacity test to be initiated. If the battery cannot sustain a load, a “Low
Battery” message is displayed and, if so programmed, will be reported to the central station.

4-2
S E C T I O N 5

Specifications & Accessories


Security Control
1. Physical: 12-1/2” W x 14-1/2” H x 3” D (318mm x 368mm x 76mm)
2. Electrical:
VOLTAGE INPUT: 16.5VAC from plug-in 25VA transformer, ADEMCO 1321 (in U.S.A.)
RECHARGEABLE BACKUP BATTERY: 12VDC, 4AH (sealed lead acid type). Charging
Voltage: 13.8VDC.
ALARM SOUNDER: 12V, 2.0 Amp output can drive 12V BELLS or can drive one or two
702 (series connected) self-contained 20-watt sirens. Do not connect
two 702s in parallel.
AUXILIARY POWER OUTPUT: 12VDC, 600mA max.
NOTE: For UL installations, Alarm Sounder plus Auxiliary Power currents should
not exceed 600mA total.

FUSE: Battery (3A) No. 90–12


3. Communication:
FORMAT SUPPORTED:
ADEMCO Express: 10 characters/sec, DTMF (TouchTone) Data Tones,
1400/2300Hz ACK, 1400Hz KISSOFF.
ADEMCO Low Speed: 10 pulses/sec, 1900Hz Data Tone, 1400Hz ACK/KISSOFF.
Radionics/SESCOA: 20 pulses/sec, 1800Hz Data Tone, 2300Hz ACK/KISSOFF.
Can report 0-9, B-F
Ademco Contact ID 10 characters/sec., DTMF (TouchTone) Data Tones,
1400/2300Hz ACK, 1400Hz KISSOFF.
LINE SEIZE: Double Pole
RINGER EQUIVALENCE: 0.1B
FCC REGISTRATION No.: 5GBUSA-44003-AL-E
4. Maximum Zone Resistance: Zones 1–8 = 300 ohms excluding EOLR standard zones

Compatible Devices
Keypads: 6150 Fixed-Word Keypad, 6160 Alpha Keypad, 6150V and
6160V Voice Keypads, 6270 Touch Screen Keypad,
Symphony Advanced User Interface
Wireless Receivers: 5881L/5882L: accepts up to 8 transmitters
5881M/5882M: accepts up to 16 transmitters
5881H/5882H: accepts up to system maximum transmitters
5800TM Transmitter Module (used with Wireless 2-Way Keypads)
5883 Transceiver: accepts up to system maximum transmitters
6150RF Keypad/Transceiver: accepts up to system max. transmitters
Zone Expansion: 4219 WIRED EXPANSION MODULE
4229 WIRED EXPANSION/RELAY MODULE
Relay Module: 4204 RELAY MODULE
Phone Modules: 4286VIP PHONE MODULE
Long Range Radio 7845GSM, 7845i-GSM
(Communication Device)

5-1
Installation and Setup Guide

2-Wire Smoke Detector:


Detector Type System Sensor Model No.
Photoelectric w/heat sensor, direct wire 2300TB
Photoelectric, direct wire 2400
Photoelectric w/heat sensor, direct wire 2400TH
Photoelectric 2451 w/B401B base
Photoelectric w/heat sensor 2451TH w/B401B base
Ionization, direct wire 1400
Ionization 1451 w/B401B base
Photoelectric duct detector 2451 w/DH400 base
Ionization duct detector 1451D w/DH400 base H
Low-profile, Photoelectric, w/135°F thermal 2100T
Low-profile, Ionization type, direct wire 1100
Transformers: 1321: 16.5VAC, 25VA Plug-In Transformer (No. 1321CN in Canada)
1361X10: 16.5VAC, 40VA Powerline Carrier device Interface AC Transformer
Sounders: AB12M 10” Motorized Bell & Box
1011BE12M 10” Motorized Bell & Box
702 Outdoor Siren
719 2-Channel Siren
713 High Power Speaker
746 Indoor Speaker
747 Indoor Siren
747PD Two-Tone Piezo Dynamic Indoor Siren
747UL Indoor Siren
748 Dual Tone Siren
749 Speaker/Horn
744 Siren Driver
745X3 Voice Siren Driver
705-820, 5-inch Round Speaker
713 Speaker
WAVE Speaker
WAVE2 Two-Tone Siren
WAVE2PD Two-Tone Piezo Dynamic Siren
5800WAVE Wireless Siren
System Sensor PA400B (beige)/; PA400R (red) Indoor Piezo Sounder

5-2
S E C T I O N 6

Regulatory Agency Statements


“FEDERAL COMMUNICATIONS COMMISSION (FCC) Part 15 STATEMENT”
This equipment has been tested to FCC requirements and has been found acceptable for use. The FCC requires the following statement for
your information:
This equipment generates and uses radio frequency energy and if not installed and used properly, that is, in strict accordance with the
manufacturer’s instructions, may cause interference to radio and television reception. It has been type tested and found to comply with the
limits for a Class B computing device in accordance with the specifications in Part 15 of FCC Rules, which are designed to provide reasonable
protection against such interference in a residential installation. However, there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause interference to radio or television reception, which can be determined by turning the equipment off
and on, the user is encouraged to try to correct the interference by one or more of the following measures:
• If using an indoor antenna, have a quality outdoor antenna installed.
• Reorient the receiving antenna until interference is reduced or eliminated.
• Move the receiver away from the control/communicator.
• Move the antenna leads away from any wire runs to the control/communicator.
• Plug the control/communicator into a different outlet so that it and the receiver are on different branch circuits.
If necessary, the user should consult the dealer or an experienced radio/television technician for additional suggestions.
The user or installer may find the following booklet prepared by the Federal Communications Commission helpful: “Interference Handbook”
This booklet is available from the U.S. Government Printing Office, Washington, DC 20402.
The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User’s Manual.
Unauthorized changes or modifications could void the user’s authority to operate the equipment.

TELEPHONE/MODEM INTERFACE
FCC Part 68
This equipment complies with Part 68 of the FCC rules. On the front cover of this equipment is a label that contains the FCC registration
number and Ringer Equivalence Number (REN). You must provide this information to the telephone company when requested.
This equipment uses the following USOC jack: RJ31X
This equipment may not be used on telephone-company-provided coin service. Connection to party lines is subject to state tariffs. This
equipment is hearing-aid compatible.
Industry Canada
NOTICE: The Industry Canada Label identifies certified equipment. This certification means that the equipment meets telecommunications
network protective, operational and safety requirements as prescribed in the appropriate Terminal Equipment Technical Requirements
document(s). The Department does not guarantee the equipment will operate to the user’s satisfaction.
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications
company. The equipment must also be installed using an acceptable method of connection. The customer should be aware that compliance with
the above conditions may not prevent degradation of service in some situations.
Repairs to certified equipment should be coordinated by a representative designated by the supplier. Any repairs or alterations made by the
user to this equipment, or equipment malfunctions, may give the telecommunications company to request the user to disconnect the equipment.
Users should ensure for their own protection that the electrical ground connections of the power utility, telephone lines and internal metallic
water pipe system, if present, are connected together, This precaution may be particularly important in rural areas.
Caution: Users should not attempt to make such connections themselves but should contact appropriate electric inspection authority, or
electrician, as appropriate.
Ringer Equivalence Number Notice:
The Ringer Equivalence Number (REN) assigned to each terminal device provides an indication of the maximum number of terminals
allowed to be connected to a telephone interface. The termination on an interface may consist of any combination of devices subject only to the
requirement that the sum of the Ringer Equivalence Numbers of all the devices does not exceed 5.

Industrie Canada
AVIS: l’étiquette d’Industrie Canada identifie le matériel homologué. Cette étiquette certifie que le matériel est conforme aux normes de
protection, d’exploitation et de sécurité des réseaux de télécommunications, comme le prescrivent les documents concernant les exigences
techniques relatives au matériel terminal. Le Ministère n’assure toutefois pas que le matériel fonctionnera à la satisfaction de l’utilisateur.
Avant d’installer ce matériel, l’utilisateur doit s’assurer qu’il est permis de le raccorder aux installations de l’enterprise locale de
télécommunication. Le matériel doit également être installé en suivant une méthode acceptée da raccordement. L’abonné ne doit pas oublier
qu’il est possible que la conformité aux conditions énoncées ci-dessus n’empêche pas la dégradation du service dans certaines situations.
Les réparations de matériel nomologué doivent être coordonnées par un représentant désigné par le fournisseur. L’entreprise de
télécommunications peut demander à l’utilisateur da débrancher un appareil à la suite de réparations ou de modifications effectuées par
l’utilisateur ou à cause de mauvais fonctionnement.
Pour sa propre protection, l’utilisateur doit s’assurer que tous les fils de mise à la terre de la source d’energie électrique, de lignes téléphoniques
et des canalisations d’eau métalliques, s’il y en a, sont raccordés ensemble. Cette précaution est particulièrement importante dans les régions
rurales.
Avertissement : L’utilisateur ne doit pas tenter de faire ces raccordements lui-même; il doit avoir racours à un service d’inspection des
installations électriques, ou à un électricien, selon le cas.
AVIS : L’indice d’équivalence de la sonnerie (IES) assigné à chaque dispositif terminal indique le nombre maximal de terminaux qui
peuvent être raccordés à une interface. La terminaison d’une interface téléphonique peut consister en une combinaison de quelques dispositifs,
à la seule condition que la somme d’indices d’équivalence de la sonnerie de tous les dispositifs n’excède pas 5.

6-1
Installation and Setup Guide

UL NOTICES
1. Entry Delay No. 1 and No. 2 (fields ∗35, ∗36) cannot be greater than 30 seconds for UL Residential
Burglar Alarm installations, and entry delay plus dial delay should not exceed 1 minute. For UL
Commercial Burglar Alarm installations, total entry delay may not exceed 45 seconds.
2. For UL Commercial Burglar Alarm and UL Residential Burglar Alarm installations with line
security, total exit delay time must not exceed 60 seconds.
3. The maximum number of reports per armed period (field ∗93) must be set to “0” (unlimited) for UL
installations.
4. Periodic testing (see scheduling mode) must be at least every 24 hours.
5. Alarm Sounder plus Auxiliary Power currents must not exceed 600mA total for UL installations
(Aux power 500mA max.).
6. All partitions must be owned and managed by the same person(s).
7. All partitions must be part of one building at one street address.
8. If used, the audible alarm device(s) must be placed where it/they can be heard by all partitions.
9. For UL commercial burglar alarm installations the control unit must be protected from
unauthorized access. The tamper switch installed to protect the control unit enclosure door is
suitable for this purpose.
10. Remote downloading without an alarm company technician on-site (unattended downloading) is not
permissible for UL installations.
11. Auto-disarming is not a UL Listed feature.
12. As SIA limits for delay of alarm reporting and sounding can exceed UL limits for commercial and
residential applications, the following UL requirements per UL681 are provided:
The maximum time that a control unit shall be programmed to delay the transmission of a signal to
a remote monitoring location, or to delay the energizing of a local alarm sounding device to permit
the alarm system user to enter and disarm the system, or to arm the system and exit shall not
exceed:
a) 60 seconds for a system with standard line security or encrypted line security,
b) 120 seconds for a system without standard line security or encrypted line security, or
c) 120 seconds for a system that does not transmit an alarm signal to a remote monitoring location.
13. This control is not intended for bank safe and vault applications.

SIA Quick Reference Guide


1. *31 Single Alarm Sounding per Zone: If “0” selected, “alarm sounding per zone” will be the same as
the “number of reports in armed period” set in field *93 (1 if one report, 2 if 2 reports, unlimited for
zones in zone list 7).
2. *34 Exit Delay: Minimum exit delay is 45 seconds.
3. *35/*36 Entry Delay 1 and 2: Minimum entry delay is 30 seconds.
4. *37 Audible Exit Warning: Feature always enabled; field does not exist.
5. *39 Power Up in Previous State: Must be “1,” power up in previous state.
6. *40 PABX Access Code or Call Waiting Disable: If call waiting is used, call waiting disable option
in field *91 must be set.
7. *50 Burglary Dial Delay: Delay must be a minimum of 30 seconds.
8. *59 Exit Error Alarm Report Code: Always enabled.
9 *68 Cancel Report Code: Default is “code enabled.”
10. *69 Recent Closing Report Code: Always enabled.
11. *91 Option Selection: Exit Delay option should be enabled. If call waiting is used, Call Waiting
Disable must be set to “1” (enabled).
12. *93 No. reports in Armed Period: Must be set for 1 or 2 report pairs.
13. Cross zone timer programming is set in field ∗85; cross zone pairs are assigned in zone list 4 using
∗81 Zone List mode.
14. Duress code is assigned by using the “add a user code” procedure found in the User Guide. Enable
Duress code reporting by programming zone 92 using ∗56 Zone Programming mode.
15. Fire alarm verification is a built-in system feature when a zone is programmed for zone type 16.

6-2
S E C T I O N 7

Limitations and Warranty


WARNING
THE LIMITATIONS OF THIS ALARM SYSTEM
While this System is an advanced design security system, it does not offer guaranteed protection against burglary, fire or
other emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a
variety of reasons. For example:
• Intruders may gain access through unprotected openings or have the technical sophistication to bypass an alarm sensor
or disconnect an alarm warning device.
• Intrusion detectors (e.g., passive infrared detectors), smoke detectors, and many other sensing devices will not work
without power. Battery-operated devices will not work without batteries, with dead batteries, or if the batteries are not
put in properly. Devices powered solely by AC will not work if their AC power supply is cut off for any reason, however
briefly.
• Signals sent by wireless transmitters may be blocked or reflected by metal before they reach the alarm receiver. Even if
the signal path has been recently checked during a weekly test, blockage can occur if a metal object is moved into the
path.
• A user may not be able to reach a panic or emergency button quickly enough.
• While smoke detectors have played a key role in reducing residential fire deaths in the United States, they may not
activate or provide early warning for a variety of reasons in as many as 35% of all fires, according to data published by
the Federal Emergency Management Agency. Some of the reasons smoke detectors used in conjunction with this System
may not work are as follows. Smoke detectors may have been improperly installed and positioned. Smoke detectors may
not sense fires that start where smoke cannot reach the detectors, such as in chimneys, in walls, or roofs, or on the other
side of closed doors. Smoke detectors also may not sense a fire on another level of a residence or building. A second floor
detector, for example, may not sense a first floor or basement fire. Finally, smoke detectors have sensing limitations. No
smoke detector can sense every kind of fire every time. In general, detectors may not always warn about fires caused by
carelessness and safety hazards like smoking in bed, violent explosions, escaping gas, improper storage of flammable
materials, overloaded electrical circuits, children playing with matches, or arson. Depending on the nature of the fire
and/or location of the smoke detectors, the detector, even if it operates as anticipated, may not provide sufficient warning
to allow all occupants to escape in time to prevent injury or death.
• Passive Infrared Motion Detectors can only detect intrusion within the designed ranges as diagrammed in their
installation manual. Passive Infrared Detectors do not provide volumetric area protection. They do create multiple
beams of protection, and intrusion can only be detected in unobstructed areas covered by those beams. They cannot
detect motion or intrusion that takes place behind walls, ceilings, floors, closed doors, glass partitions, glass doors, or
windows. Mechanical tampering, masking, painting or spraying of any material on the mirrors, windows or any part of
the optical system can reduce their detection ability. Passive Infrared Detectors sense changes in temperature; however,
as the ambient temperature of the protected area approaches the temperature range of 90° to 105°F (32° to 40°C), the
detection performance can decrease.
• Alarm warning devices such as sirens, bells or horns may not alert people or wake up sleepers if they are located on the
other side of closed or partly open doors. If warning devices are located on a different level of the residence from the
bedrooms, then they are less likely to waken or alert people inside the bedrooms. Even persons who are awake may not
hear the warning if the alarm is muffled by noise from a stereo, radio, air conditioner or other appliance, or by passing
traffic. Finally, alarm warning devices, however loud, may not warn hearing-impaired people.
• Telephone lines needed to transmit alarm signals from a premises to a central monitoring station may be out of service
or temporarily out of service. Telephone lines are also subject to compromise by sophisticated intruders.
• Even if the system responds to the emergency as intended, however, occupants may have insufficient time to protect
themselves from the emergency situation. In the case of a monitored alarm system, authorities may not respond
appropriately.
• This equipment, like other electrical devices, is subject to component failure. Even though this equipment is designed to
last as long as 10 years, the electronic components could fail at any time.
The most common cause of an alarm system not functioning when an intrusion or fire occurs is inadequate maintenance.
This alarm system should be tested weekly to make sure all sensors and transmitters are working properly. The security
keypad (and remote keypad) should be tested as well.
Wireless transmitters (used in some systems) are designed to provide long battery life under normal operating conditions.
Longevity of batteries may be as much as 4 to 7 years, depending on the environment, usage, and the specific wireless device
being used. External factors such as humidity, high or low temperatures, as well as large swings in temperature, may all
reduce the actual battery life in a given installation. This wireless system, however, can identify a true low-battery
situation, thus allowing time to arrange a change of battery to maintain protection for that given point within the system.
Installing an alarm system may make the owner eligible for a lower insurance rate, but an alarm system is not a substitute
for insurance. Homeowners, property owners and renters should continue to act prudently in protecting themselves and
continue to insure their lives and property.
We continue to develop new and improved protection devices. Users of alarm systems owe it to themselves and their loved
ones to learn about these developments.

7-3
Installation and Setup Guide

– INDEX –
1321 ......................................... 1-2, 2-3 Cabinet ............................................2-1 MODel 112 ....................................2-10
1321 AC Transformer .................... 2-11 CALIFORNIA STATE FIRE Modem ............................................3-8
1361X10 ................. 2-3, 2-11, 2-12, 5-2 MARSHALL.................................2-2 Momentary Switch .........................2-10
3+1 and 4+1 Standard Formats ....... 3-1 Caller ID Unit ................................. 2-13
4204 ....1-2, 2-2, 2-5, 2-6, 2-11, 3-6, 5-1 Charging Voltage .............................5-1 On-Board Triggers .........................2-14
4219 ......1-1, 1-2, 2-2, 2-5, 2-7, 2-8, 5-1 Chime Mode ....................................3-6 Output Relays ..................................1-2
4229 .1-1, 1-2, 2-2, 2-5, 2-6, 2-7, 2-8, 2- Clean Me Option..............................2-7
11, 3-6, 5-1 Communication.........................3-1, 5-1 Panic Keys.......................................3-7
4285 .............................................. 2-14 Contact ID Reporting .......................5-1 Periodic Test Reports ......................4-2
4286 .............................................. 2-14 CSFM ..............................................2-2 Phone Line ....................................2-13
5800 Series Transmitters................. 2-9 Phone Module.1-1, 2-2, 2-5, 2-13, 2-14,
5800TM .................................... 2-9, 5-1 Device Address ...............2-5, 2-11, 3-8 5-1
5801 ................................................ 2-9 Dialer Communication Test..............4-2 Power Failure...................................3-8
5802 ......................................... 2-9, 3-8 DIP Switches. ..................................2-9 Power Supply.....................2-2, 2-4, 7-6
5802CP .................................... 2-9, 3-8 Disarming ........................................3-6 Powerline Carrier Devices1-2, 2-11, 3-6
5827 ................................................ 2-9 Double-Balanced .............................2-6 PSC04 Powerline Interface ............2-11
5827BD ........................................... 2-9
5881 ......................................... 2-2, 2-8 Enrolling ..........................................2-9 Relay Modules ........................1-2, 2-11
7720PLUS or 7820 .......................... 1-2 Entry Delay...............................3-7, 3-8 Report Code ....................................3-1
EOLR .......................................2-6, 5-1 Report Code Formats ......................3-1
AC Power Supply ............................ 1-2 Exit Delay .................................3-7, 3-8 Response Time................................ 2-7
AC Transformer ............... 2-3, 2-12, 5-2 Exit Error Alarm ...............................3-8 RF House ID Code...........................2-8
Ademco Contact ID.......................... 3-3 Expansion Zones .............................2-7 RF Interference................................2-8
Alarm Output ............................ 2-2, 2-4 RF jam detection..............................1-1
Arming Away ................................... 3-6 Fast Busy Signal............................ 2-13 RF Jam Option.................................2-8
Arming Instant ................................. 3-6 FCC.................................................6-1 RF Receiver............2-1, 2-2, 2-5, 2-8, 3
Arming Modes ................................. 3-7 RJ31X Jack ...................................2-13
Arming Stay..................................... 3-6 Go/No Go Test Mode.......................4-2
Audio Alarm Verification (AAV) ...... 2-13 SA4120XM-1 Cable .........................2-3
AUI .................................................. 2-5 Handshake ......................................3-1 Security Codes .........................1-1, 3-5
Authority Levels ............................... 3-5 Hardwired Zones .............................1-1 Silent Burglary ....................................3
Auxiliary Output ............................... 2-2 HAYES Modem ...............................1-1 Silent Panic......................................3-7
House ID .........................................2-9 Sniffer Mode ....................................4-1
Backup Battery ................................ 1-2 Ideal Model 61–035 .........................2-3 Sounder Connections ......................2-4
Battery Life ...................................... 2-9 Supplementary Power......................2-4
Battery Tests ............................ 4-1, 4-2 Installer Code ...........................4-1, 4-2 System Communication ...................3-1
Bell Supervision............................... 2-4 System Test.....................................4-1
Bell Supervision Jumper .................. 2-4 Keypad Addresses...........................2-5
Bypassing Zones ............................. 3-6 Keyswitch .................................. 2-10, 3 Tamper Switch........................2-10, 6-2
Kissoff..............................................3-1 Telco Line ..................................2-13, 3
Telephone Line Monitoring...............1-1
Lock.................................................2-1 Test Mode.................................4-1, 4-2
Long Range Radio................2-5, 3, 5-1 Trigger outputs...............................2-12
Low Battery Message ......................4-2 Trouble Displays .......................3-7, 3-8

UL.............................2-2, 2-4, 2-11, 5-1

Verify Operation...............................2-7

Wire Run Chart .........................2-4, 2-5


Worksheet .......................................2-2

Zone Doubling .................................2-6

7-4
24-HR BATTERY STANDBY REQUIRED FOR 8-PIN CONNECTOR
BATTERY FUSE FOR COMPLETE ADEMCO No. 4219 4-WIRE SMOKE DETECTOR CONNECTIONS
FIRE INSTALLATIONS. USE 12V, 17.2AH USED FOR 1361X10 +
INFORMATION, WIRED EXPANSION MODULE 5
BATTERY FOR 600mA AUX POWER. SEE 3A FOR REPLACEMENT, TRANSFORMER
USE SAME VALUE SEE INSTRUCTIONS (8 ADD'L EOLR WIRED ZONES)
INSTRUCTIONS. CONNECTIONS AND FOR SET UNIT’S AUX PWR RELAY
(e.g. ADEMCO No. 90-12) K5305-1V5 -AND/OR- PROGRAM RELAY _
ON-BOARD TRIGGERS OR LATER. ADEMCO No. 4229 DIP SWITCH OUTPUT BLK + RED
AS ZONE TYPE 54
BATTERY CAPACITY FOR EMERGENCY SEE INSTRUCTIONS. FOR DEVICE TERMINALS (FIRE ZONE RESET)
WIRED EXPANSION/RELAY MODULE EOL
BURGLARY STANDBY USE AT LEAST 4 HRS BLK (8 ADD'L EOLR WIRED ZONES PLUS 2 ADDRESSES _ 4 POWER
1 2 3 4 5 6 7 8 (USE SA4120XM-1 N.O. SUPERVISION
RED OUTPUT RELAYS) 7 - 15 N.C.
CABLE) OR RELAY MODULE
-AND/OR- SEE CONTACT OPENS MOMENTARILY A77-716B.
CHARGING VOLTAGE
– BLACK SYNC GRN INSTRUCTIONS. UPON FIRE ALARM RESET
BATTERY ADEMCO No. 4204 RELAY MODULE USE N.O.
13.8VDC. MAXIMUM 12V, 4AH FLYING LEADS YEL (4 OUTPUT RELAYS) CONTACT,
COM TO

OPTIONAL
CHARGING CURRENT + FOR BATTERY VIOLET WHICH CLOSES
RED TRANS. TO OUTPUT 17 +
650mA. CONNECTION DATA PROGRAM OUTPUT 17 FOR _ WHEN POWER
AND/OR

GND
SET "OUT NORM LOW" = YES IN 4-WIRE SMOKE IS APPLIED.
+ – ADEMCO 5881* Type RECEIVER’S 79 MENU MODE AND AS ZONE OR COMBUSTION 2000

(TRIG. 1)
(TRIG. 2)
TYPE 54 IN 80 MENU MODE DETECTOR OHMS

+12 AUX
SEALED LEAD-ACID TYPE. RF RECEIVER DIP SWITCH MAX. CURRENT = 100 mA EOLR

OUTPUT 17
OUTPUT 18
BATTERY NORMALLY NEED NOT BE

FOR UP TO 40 ADDITIONAL ZONES


BLK WIRELESS ZONES FOR DEVICE (UP TO 16 DETECTORS

( FROM EITHER OR BOTH GROUPS)


TO TERM 4 BLK
REPLACED FOR AT LEAST 3 YRS. ADDRESS PLUS EOL MODULE)
TO TERM 5 RED RED 5881L: UP TO 8
RED JUMPER 5881M: UP TO 16 OF “0”. TO ZONE TERM. ( +)
TO DETERMINE TOTAL STANDBY LOAD TO TERM 6 GRN HEAT
CUT FOR BELL SUPERVISION. GRN 5881H: UP TO 56 SEE DETECTOR
ON BATTERY, ADD 100mA TO TOTAL OF TO TERM 7 YEL INSTRUCTIONS. TO ZONE TERM. ( _)
ALSO, CONNECT 2000 OHM RESISTOR YEL *5882 IN CANADA
AUX. POWER OUTPUT AND REMOTE DIRECTLY ACROSS SOUNDER.
KEYPAD CURRENTS.

USE UL LISTED LIMITED ENERGY 10 14 17


CABLE FOR ALL CONNECTIONS
1 2 3 4 5 6 7 8 9 11 12 13 15 16 18 19 20 21 22 23 24 25
CLASS 2 PLUG-IN TRANSFORMER
16.5VAC, 25VA

LO
HI
LO

LO
HI
HI

HI
HI

HI
LO
HI

HI
LO
LO

LO
LO

(e.g. ADEMCO No. 1321). TIP RING TIP RING


(USE No. 1321CN IN CANADA) (BROWN) (GRAY) (GREEN) (RED)

}
}


– +
HANDSET INCOMING

}
USE 1361X10 TRANSFORMER EARTH
INTERFACE IN PLACE OF 1321 OR AUX. POWER PHONE LINE GROUND
1321CN WHEN POWER LINE CARRIER OUTPUT TELEPHONE WIRING SEE
DEVICES ARE BEING USED. (SEE 10.5-13.8VDC (VIA RJ31X* JACK AND DIRECT INSTRUCTIONS
INSTRUCTIONS FOR CONNECTIONS) TO 110VAC 600mA MAX. CONNECT CORD) FOR PROPER
UNSWITCHED (500mA MAX. GROUNDING
*CA38A IN CANADA DOC LOAD NO.: 3
OUTLET (24HR) FOR UL
THIS EQUIPMENT SHOULD BE INSTALLED INSTALLATIONS) FOR CONNECTION OF OPTIONAL 4286 VIP MODULES
IN ACCORDANCE WITH THE NATIONAL TO PHONE TERMINALS, SEE INSTRUCTIONS.
ZONE 7
ZONE 8

ZONE 1
VISTA-20P ONLY

ZONE 2
ZONE 3
ZONE 4
ZONE 5
ZONE 6

FIRE PROTECTION ASSOCIATION'S ALL OUTPUTS


STANDARD 72, CHAPTER 11 (NATIONAL ARE POWER WARNING:TO PREVENT RISK OF SHOCK, DISCONNECT

BLACK: KEYPAD GROUND (- ) RETURN


FIRE PROTECTION ASSOCIATION, + – LIMITED. TELEPHONE LINE AT TELCO JACK BEFORE SERVICING
BATTERY-MARCH PARK, QUINCY,MA ALARM OUTPUT 2000 2000 2000 2000 2000 2000 2000 2000 THIS UNIT.
02169). 10.5–13.8VDC, 2A MAX. NOTE: OHMS OHMS OHMS OHMS OHMS OHMS OHMS OHMS
PRINTED INFORMATION (600mA MAX. FOR UL KEYPAD (S) EOLR EOLR EOLR EOLR EOLR EOLR EOLR EOLR COMPLIES WITH FCC RULES, PART 68. FCC REGISTRATION

GREEN: DATA IN FROM KEYPAD


YELLOW: KEYPAD DATA OUT

BLK
RED: KEYPAD PWR ( + )
DESCRIBING PROPER INSTALLATION, USAGE, INCLUDING CURRENT (IN BOTH NO. 5GBUSA-44003-AL-E RINGER EQUIVALENCE: 0.1B.
OPERATION,TESTING, MAINTENANCE, AUX POWER) STEADY PARTITIONS) AND • MAXIMUM LOOP RESISTANCE: (EACH ZONE) 300 OHMS (PLUS EOLR)
EVACUATION PLANNING AND REPAIR FOR BURGLARY/PANIC, ALL OTHER DEVICES REMOTE • RESPONSE, ZONES 1-8: 10, 350, OR 700 MSEC (PROGRAMMABLE)
SERVICE IS TO BE PROVIDED WITH THIS TEMPORAL PULSE DRAWING POWER KEYPADS 12 13 14
AND OTHER • MAXIMUM NUMBER OF 2-WIRE SMOKE DETECTORS ON ZONE 1 IS 16;
EQUIPMENT. SOUNDING FOR FIRE. FROM TERMS 4 & 5 DETECTORS MUST HAVE COMPATIBILITY IDENTIFIER AS "A".

CAN BE USED FOR 2-WIRE SMOKE DETECTORS


CAN USE ADEMCO No. 702 MUST BE INCLUDED ADDRESSABLE
SIREN, OR 12V BELL). IN AUX CURRENT DEVICES
SEE INSTRUCTIONS. DRAIN CALCULATIONS. (e.g. 5800TM, POWER SHUTDOWN NOTE:
4286, LRR,
2k ZONE
2k

CONNECTION OF THE FIRE ALARM SYSTEM SHUTS DOWN


PAIRS

Figure 17. Summary of Connections


SIGNAL TO A FIRE ALARM 4219, 4229, SENSOR DETECTION
10 11
HEADQUARTERS OR A CENTRAL STATION 4204, 5881) PROCESSING IF CONTROL'S
2 / 10
SHALL BE PERMITTED ONLY WITH THE WEEKLY TESTING IS REQUIRED TO ENSURE VOLTAGE DROPS BELOW 9.6V.
REMOTE KEYPADS 3 / 11
PERMISSION OF THE LOCAL AUTHORITY PROPER OPERATION OF THIS SYSTEM. CAN USE 6150 OR 6160 ZONE 2 4 / 12
HAVING JURISDICTION. THE BURGLAR IN ADDITION, THIS SYSTEM MUST BE ALL DEVICES AND
KEYPADS. LOCAL 5 / 13
2k
2k

ALARM SIGNAL SHALL NOT BE CHECKED BY A QUALIFIED TECHNICIAN ACCESSORIES USED IN A


PROGRAMMING 3k 6 / 14
CONNECTED TO A POLICE EMERGENCY AT LEAST ONCE EVERY THREE (3) YEARS. CANADIAN INSTALLATION
TAMPER CONTACTS

MUST BE DONE WITH A 7 / 15


NUMBER. MUST BE LISTED FOR
6139/6160, BUT NEED NOT 8 / 16
ZONE 10 USE IN CANADA
REMAIN IN THE SYSTEM
2k 2k
(SET TO ADDRESS 16). 6.2k
ZONE 3 ZONE 4
TYPICAL WIRING FOR TYPICAL WIRING FOR
DOUBLE BALANCED ZONE ZONE DOUBLING
(VISTA-20P ONLY) (VISTA-20P ONLY)

ADEMCO VISTA-20P / VISTA-20PSIA SERIES / VISTA-15P / VISTA-15PSIA SERIES


SUMMARY OF CONNECTIONS V20P_V15P-SOC-V8

7-5
WARRANTY INFORMATION
For the latest warranty information, please go to:
www.honeywell.com/security/hsc/resources/wa

2 Corporate Center Drive, Suite 100


P.O. Box 9040, Melville, NY 11747
Copyright © 2004 Honeywell International Inc.

www.honeywell.com/security

ÊK5305-1V7/Š
K5305-1V7 10/08 Rev. B

You might also like