Emergency Operating Procedures - Revision 1 Update 1
Emergency Operating Procedures - Revision 1 Update 1
VPO "Союзатомэнерго"
Chernobyl Nuclear Power Plant named after V.I.Lenin
APPROVED
Head of VPO "Союзатомэнерго"
G.A. Veretennikov
"25" XI 1983Г.
1983
Contents
TG-5 TRIP .....................................................................................................................................3
TG-6 TRIP .....................................................................................................................................4
TRANSFORMER FAILURE ..............................................................................................................5
TG-5 TRIP
Expected Operator Actions
Re-establish power to 5PA and 5PB by,
- Check that the PWA-3 Transformer is connected. There will be a green light illuminated
above the switch if the PWA-3 transformer is connected.
- Start and connect the Emergency Diesel Generators (refer to the “remaster manual” pdf for starting
and connecting instructions)
If TG-5 is damaged (2 illuminated bearing vibration lights or more) due to an Emergency Unloading,
Note: During an unexpected TG-5 Trip, a Reactor Trip will occur due to the
loss of power to the 5PB relay.
TG-6 TRIP
Expected Operator Actions
- Check that the PWB-3 Transformer is connected. There will be a green light illuminated
above the switch if the PWB-3 transformer is connected.
- Start and connect the Emergency Diesel Generators (refer to the “remaster manual” pdf for starting
and connecting instructions).
If TG-6 is damaged (2 illuminated bearing vibration lights or more) due to an Emergency Unloading,
Note: During an unexpected TG-6 Trip, a Reactor Power Excursion may occur
due to loss of core flow.
Note: An Automatic Reactor Trip may occur as a result of the Reactor Power
Excursion.
STARTUP TRANSFORMER FAILURE
Expected Operator Actions
If TG-5 and TG-6 are not connected to the relays,
If TG-5 and TG-6 are providing power to the relays, no operator action is
required.
The transformer failure must be waited out, there is nothing operators can do
to manually fix it.
Even during a transformer failure, it is possible to start the reactor after it is tripped. To achieve this,
- Ensure core flow is greater than 10,000 m3/h on each loop by starting SAOR injection.
- Pull rods as normal.
- Stabilize reactor power at 1000mw.
- Run up turbines as normal, 2000RPM or more is required.
- Ensure both AUX buses are on.
- Power 5PA/B 6PA/B relays as normal.